You are on page 1of 18

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/223938345

HVAC and indoor thermal conditions in hospital operating rooms

Article  in  Energy and Buildings · April 2007


DOI: 10.1016/j.enbuild.2006.09.004

CITATIONS READS

121 2,013

3 authors:

Constantinos Balaras Elena Dascalaki


National Observatory of Athens National Observatory of Athens
220 PUBLICATIONS   3,771 CITATIONS    121 PUBLICATIONS   1,853 CITATIONS   

SEE PROFILE SEE PROFILE

Athina Gaglia
National Technical University of Athens
39 PUBLICATIONS   1,210 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

CESBA MED View project

Embodied CO2 Emissions in Building Construction Materials of Hellenic Dwellings View project

All content following this page was uploaded by Constantinos Balaras on 23 December 2015.

The user has requested enhancement of the downloaded file.


Energy and Buildings 39 (2007) 454–470
www.elsevier.com/locate/enbuild

HVAC and indoor thermal conditions in hospital operating rooms


Constantinos A. Balaras *, Elena Dascalaki, Athina Gaglia
Group Energy Conservation, Institute for Environmental Research and Sustainable Development, National Observatory of Athens,
Ioannou Metaxa & Vas. Pavlou, GR 152 36 P. Penteli, Greece
Received 31 July 2006; received in revised form 5 September 2006; accepted 6 September 2006

Abstract
Hospital operating rooms (ORs) require efficient HVAC installations to secure the highly demanding indoor environmental conditions for
patients and medical personnel. This paper reviews published standards and guidelines on design, installation, commissioning, operation, and
maintenance of HVAC installations in hospital ORs, indoor thermal conditions, and summarizes measured data from short monitoring of indoor
thermal conditions along with audit results and main characteristics of 20 ORs in 10 major Hellenic hospitals. Measured indoor temperature ranged
from 14 to 29 8C, and relative humidity from 13 to 80%. The number of air changes per hour ranged from 3.2 to 58 ACH. The commonly
encountered problems include insufficient indoor air exchange, poor control on indoor thermal conditions, bad space ergonomics that influence the
ventilation system operation, poor technical installations maintenance and understaffed technical departments. However, there are still
opportunities for energy conservation, without sacrificing comfort, and overall quality of patient care or services.
# 2006 Elsevier B.V. All rights reserved.

Keywords: Hospital operating rooms; Operating theatres; Operating suites; HVAC; Indoor thermal conditions; Audits

1. Introduction order to avoid drafts and swirls that promote the recirculation of
microbes and may disrupt the procedures during an operation.
Hospitals and health care buildings are among the most The ventilation rate is expressed as the volumetric air flow
complex indoor facilities with numerous different end uses of through the space divided by the volume of the space, e.g.
indoor spaces and functions. In particular, the most demanding number of air changes per hour (ACH). The desirable
independent indoor zones are hospital operating theaters conditions can be met by proper design, installation, operation
(suites) that comprise operating rooms (ORs) or surgical and maintenance of the electromechanical equipment, such as
theatres, their interconnecting hallways and ancillary work the HVAC equipment and lighting systems of the space. Due to
areas. The indoor environmental quality (IEQ) in ORs, their demanding indoor conditions, operating theatres con-
including thermal, visual and acoustical comfort and indoor stitute the most expensive sector of the healthcare establish-
air quality, affects the working conditions, well-being, safety ment mandating an efficient management [1], reaching 33% of
and health of the medical personnel who work in these the total cost [2].
environments. About 50% of the total number of doctors work First documented surgical facilities date from 500 BC [3].
in the ORs, as surgeons or with other responsibilities (e.g. New ORs have become high tech, with automatic controls for
anesthesiologists), while about 10% of the total medical staff adjusting indoor thermal and visual environmental conditions,
also work in the OR. Heating, ventilating and air-conditioning indoor air quality (e.g. proper air circulation, clean air supply
(HVAC) installations control indoor air quality and aseptic and exhaust of indoor contaminants), and are even equipped
conditions, and secure healthy, safe and suitable indoor thermal with temperature and humidity displays, and decision-support
(i.e. temperature, humidity, air quality and airflow) conditions tools to alert medical staff. On the other hand, a great number of
for surgeons and medical staff, and of course, the patients. existing ORs face serious problems with ageing HVAC
The air in an OR must be aseptic, at a reasonably constant installations, and sometimes even luck fundamental services.
temperature and humidity and have relatively low velocity in An OR can be considered a clean space with an emphasis on
controlling specific types of contamination rather than the
* Corresponding author. Fax: +30 210 8103236. quantity of particles present. The airborne particulate cleanli-
E-mail address: costas@meteo.noa.gr (C.A. Balaras). ness level is differentiated by referring to class numbers
0378-7788/$ – see front matter # 2006 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2006.09.004
C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470 455

specified by the maximum allowable number of particles per Greece is a prime example of an environmentally conscious
cubic meter of air. According to the International Organization design that includes: naturally shaded exterior spaces to provide
of Standardization (ISO) Classification Air Cleanliness [4] better microclimatic conditions and amenity, use of daylight
there are nine class levels, from Class 1 up to 9. An OR should whenever feasible for better and healthier lighting conditions
be at least ISO Class 7 (formerly Class 10,000 according to the and reduced energy consumption, effective solar control to
U.S. Federal Standard 209E, Airborne particulate Cleanliness reduce direct solar gains and cooling loads while allowing
Classes in Clean Rooms and Clean Zones, 1992), which is an proper daylighting, increased thermal insulation to reduce
atmospheric environment that contains less than 352,000 heating and cooling loads, use of ceiling fans as hybrid cooling
particles 0.5 mm in diameter per cubic meter of air. For ISO systems in various spaces, natural ventilation where applicable
Class 8 (formerly Class 100,000) atmospheric environment and elaborate energy saving systems for the building services
contains less than 3,520,000 particles 0.5 mm/m3. Most [12]. The annual energy consumption of the 600-bed
national standards have been or are currently being amended (70,000 m2) hospital is 156 kWh/m2, which is about 35%
to align with the ISO Standard [5,6]. lower than average Hellenic hospitals.
Hospitals have the highest energy consumption per unit floor This paper focuses on indoor thermal conditions for ORs,
area, in the buildings sector. The high-energy consumption is including temperature, humidity, and ventilation, providing
due to the high space heating, cooling and ventilation loads, general HVAC design guidelines. It also summarizes the
continuous 24 h operation for the majority of the facilities, and findings from an investigation of 20 ORs at 10 Hellenic
the high number of medical equipment. From an energy audit hospitals, which included an audit of the HVAC installations
campaign of Hellenic health care buildings in the early 1990s, along with complementary measurements of indoor thermal
the average annual total energy consumption was reported as conditions in the ORs.
407 kWh/m2 [7]. In another national investigation, the annual
total energy consumption was reported at 371.5 kWh/m2 [8]. 2. General design
More recent data from 10 hospitals in Athens, reported in this
paper, revealed an average annual total energy consumption of Operating theatre design has responded to changes in
about 426 kWh/m2. surgical needs and practice [13]. The size and number of ORs in
Significant variations of energy consumption may occur a hospital depends on the total size of the facility, the number of
between different facilities, mainly due to differences in HVAC beds and the type of medical treatment. Usually, the number of
installations; the majority of Hellenic hospitals are not fully air- ORs in Hellenic hospitals is about 2.5% of the total number of
conditioned (central HVAC is mainly used in new hospitals). hospital beds, although it strongly depends on the hospital
For example, fully air-conditioned hospitals may reach annual functions. The size of Hellenic ORs is at least 25 m2, while for
energy consumption close to 700 kWh/m2. The National Health operations that require the use of several types of medical
Service (NHS) in the U.K. has initiated an effort to reduce equipment, the size of the OR may reach 75 m2; for minor
primary energy consumption by 15% and eliminate the septic operations, the size may be smaller, down to 10 m2 [14].
emission of at least 15 million kg of carbon equivalent during A typical layout of an OR facility includes the main operating
this decade and has published benchmarking values for best room area, a reception patient area, the anesthesia room, the
practice [9]. Accordingly, U.K. healthcare facilities are audited sterile material rooms (clothes, tools, etc.), the scrub room, the
on an annual basis to monitor energy performance. The target is recovery room and auxiliary spaces (e.g. staff locker rooms,
for all existing buildings to improve to a level of 53 GJ/100 m3 storage areas). A corridor separates the septic and aseptic areas.
(or about <445 kWh/m2) for good practice and 66 GJ/100 m3 A proper space layout must isolate the OR from direct
(or about <550 kWh/m2) for typical total energy consumption, communication with the other secondary use spaces (e.g.
while new premises are required to achieve a benchmark of less offices, storage, locker rooms, etc.) in order to secure aseptic
than 55 GJ/100 m3 (or about <459 kWh/m2). conditions and minimize the risk of microbe migration. A well-
Hospital facilities managers are experiencing first hand the designed space layout can minimize functional problems in the
higher energy operating costs and according to a recent survey OR and improve the employees’ performance.
of U.S. hospital facilities managers [10] more than 90% of the Common OR design problems include:
respondents reported higher energy costs over the previous
year, and more than half cited increases in double-digit (a) Space availability: Several ORs are characterized by lack of
percentages. Ninety-three percent of respondents reported that space availability and small dimensions. It is a common
they will be implementing energy-savings initiatives in their practice in existing hospitals that in order to satisfy the need
construction/renovation projects for the next 3 years. to increase the capacity of the ORs, they resort to
While hospitals are increasingly interested in constructing renovations that simply increase the number of ORs by
and maintaining green buildings, only a handful has become reducing their dimensions and space availability. Even new
deeply involved [11]. For example, in the U.S., of a total of facilities sometimes have the minimum dimensions. This
about 450 buildings nationwide that have registered for creates adverse working conditions for the medical staff and
certification from the leadership in energy and environmental constitutes a common employee complaint.
design initiative (LEED), only seven are health care institu- (b) Space function: Some ORs include spaces with improper
tions. The Papageorgiou teaching hospital in Thessaloniki, functions (e.g. sterilization rooms), which could be moved
456 C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470

outside since they may unnecessarily compromise the visual and acoustic conditions. In addition to ensuring proper
indoor air quality with chemical substances, particles, working conditions, which is a concern like in most working
vapors, etc. Accordingly, spaces with this kind of function environments, the other serious problem that may be
should be moved to another part of the hospital, provided encountered are surgical site infections (SSI) that may involve
sufficiently adjacent locations facilitate effective support by both patients and health care professionals who may be at risk
the functions of the OR needs. The freed up space can then due to their long term exposure during their career.
be used to satisfy other needs. Surgical site infection is the leading complication of surgery
(c) Secondary use spaces: The availability of spaces for storing [5]. While surgical methods have improved since modern
medical supplies and sterile equipment and instruments is antiseptic surgery began in the 1860s, each year, some 700,000
crucial for the proper function of the facility. Otherwise, patients in the United States suffer from SSI [16]. Data from the
placing lockers for medical supplies and other equipment U.S. shows that the direct cost of additional health care of these
inside the main OR area reduces the available free space, SSI cases is at least $3.5 billion annually. The full cost
although the OR may have the necessary dimensions. In including time away from work, degraded life style, suffering
addition, these objects may pose a health and safety risk, and death is surely much higher and demands the attention of
since they may constitute a pollution source, especially every profession involved.
when they are aged and not properly maintained. Septic and Altogether, hospital acquired infections contribute to high
aseptic spaces should be located on different floors to operating costs and even loss of human lives [17–19]. They are
minimize pollution risks. now the fourth leading cause of death in the United States,
exceeding 100,000 annual deaths, behind heart disease, cancer
In general, pathogenic microorganisms do not readily adhere and strokes, according to the centers for disease control (CDC).
to walls or ceilings unless the surface becomes moist, sticky, or Most hospital infections may be preventable by appropriate
damaged [15]. Little evidence exists that walls and ceilings are engineering design and maintenance of HVAC installations that
a major potential source of infections. Wall coverings should be could contribute in reducing the risks for medical professionals
fluid resistant and easily cleaned, especially in areas where as well as for patients.
contact with blood or body fluids may occur, like in the case of Infections are influenced by several factors [20,21], including
ORs. Firnishings around plumbing fixtures should be smooth the type of surgery and the environment in which the procedure
and water resistant. In addition, pipe penetrations and joints takes place [22], ventilation or air-conditioning systems [23],
should be tightly sealed. Acoustical tiles should be avoided in asepsis [24], sterile supplies [25] and equipment [26,27], and
high-risk areas because they may support microbial growth even building works in and around hospitals [23,28].
when wet. False ceilings may harbor dust and pests that may
contaminate the environment if disturbed. Accordingly, they 3.1. Temperature
should be avoided unless adequately sealed. Ideally, walls and
ceilings should have a smooth, impervious surface that is easy The indoor air temperature must be maintained within the
to clean with minimal likelihood of dust accumulation. recommended ranges to ensure acceptable conditions. The
indoor air temperature must be uniform within the space. In the
3. Indoor conditions OR, special care must be taken to account for the different
internal loads (e.g. surgical lamp) by proper design of the air-
The ORs are usually the most demanding areas in a hospital conditioned supply and exhaust vents and temperature of the air
for maintaining aseptic conditions and favorable thermal, supply stream.

Table 1
Recommended indoor conditions for operating rooms
Temperaturea (8C) Relative humidity (%) Ventilation Source/references
20–23 30–60 Positive pressurization. Minimum 15 ACH, of which at least 3 ACH American Institute
should be outdoor air. Filter all recirculated and fresh air through of Architects [29]
min 90% efficient filters. In rooms not engineered for horizontal
laminar airflow, introduce air at the ceiling and exhaust air near the floor
17–27 45–55 Positive pressurization. Minimum 25 ACH with minimum 5 ACH of outdoor air ASHRAE [30]
20–24. 30–60 Positive pressurization (at least 2.5 Pa). Primary Supply Diffusers, non-aspirating. ASHRAE [31]
Minimum 20 ACH with minimum 4 ACH of outdoor air
22–26b 50–60 Positive pressurization. The air changes should be 60 m3/m2/h, German Institute
if the room height is 3 m, or else 20 air changes per hour for Standardization [32]
18–24 50–60 Positive pressurization with 15% excess air. Air flow rates Technical Chamber of
70–85 m3/h. Airflow can be reduced down Greece [33,34]
to 30% of the full load conditions during off-use hours Hellenic Health Ministry [35]
a
Use of lower or higher temperature is acceptable when patients’ comfort and/or medical conditions require those conditions, e.g. 17 8C for specialized procedures
such as cardiac surgery.
b
Reference supply airflow rate 0.67 m3/s.
C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470 457

The desirable indoor air temperature is usually 20–24 8C, High humidity levels cause thermal discomfort. The ventilation
according to international regulations and standards (Table 1). requirements influence humidity control. Depending on
Use of lower or higher temperature is acceptable when patients’ climatic conditions, additional ventilation may increase the
comfort and/or medical conditions require those conditions. For dehumidification load more than the sensible cooling, imposing
example, for specialized procedures, such as cardiac surgery, a disproportionate demand on the HVAC equipment. Low
the indoor air temperature may be set as low as 17 8C; on the humidity levels (dry air) favor blood coagulation, which is
other hand, pediatric surgeries usually demand a higher indoor undesirable during a surgery. In addition, moisture can be
air temperature because children are more sensitive to lower absorbed into the duct lining and building materials where it
temperatures. In any event, a high indoor air temperature may may support microbial growth. With the heavy use of electric
cause discomfort and offers more favorable growing conditions equipment in the OR, low humidity levels may cause problems
for bacteria or their mitigation from and to the patient. associated with static electricity on medical equipment and
Practically, it is not possible to provide all occupants with surfaces. In addition, this may even pose a fire hazard, as there
100% acceptable indoor thermal conditions. Similarly, the may be flammable gases present in the environment.
medical staff working in an OR may have a different perception The recommended levels of indoor relative humidity are 30–
of prevailing indoor conditions due to different levels of activity 60%, according to international regulations and standards
and even working positions within the OR. In general, surgeons (Table 1). Most regulations establish that ORs where the use of
tend to feel from ‘‘slightly warm’’ to ‘‘warm’’ [36]. Regulatory in-flammable anesthetic gases is possible, volatile liquids are
sweating is also present very often. Anesthetists and nurses, by used frequently, and in order to prevent the accumulation of
contrast, experience from ‘‘slightly cool to cold’’ thermal static electricity should maintain a humidity of about 60% [32].
sensation. This is especially true for temperatures below 21 8C, Humidification may be necessary to increase low humidity
mainly because of the low cooling insulation. These are in levels, commonly encountered during winter. Special care must
agreement with other studies where preferable thermal comfort be exercised with humidification to assure that there is no
conditions were reported for anesthetics (23–24 8C), for nurses potential for transferring bacteria to the OR through the
(22–24.5 8C) and for surgeons 18–19 8C. For patient’s, the ventilation system, since humidifiers may provide favorable
recommended air temperature ranges between 24 and 26 8C. environment for bacteria growth. Proper maintenance and
Medical clothing will have a direct impact on personnel’s cleaning practices will minimize this kind of risks. Humidifica-
thermal comfort conditions. Surgical scrub garments are tion is best accomplished by supplying dry steam. Cold-water
typically worn by OR personnel to control airborne contam- humidifiers in HVAC systems must be connected to a domestic
ination, although there is no scientific data to support this water source and provided with a drain line to remove the water
practice as a means for preventing transmission of infection [39]. Stand-alone, console-type humidifiers that recirculate
[37]. Heavier gown requirements used by the surgical team for water for humidification should not be used because the water
protective reasons during an operation (i.e. because of AIDS) in these systems becomes contaminated with microorganisms
may require an indoor temperature down to 18 8C or even rapidly and have been linked to outbreaks of Legionnaires’
lower. disease.
Finally, asymmetric thermal radiation from surgical lights
on the surgical staff is a potential source of thermal discomfort 3.3. Ventilation
[36]. Thermal radiation emitted from surgical lights, results to a
radiant asymmetry ranging from 6 to 7 8C over the operating Separate rooms for surgery were recommended in the 18th
table and from 10 to 12 8C over the floor level (at a height of century but this was mainly for teaching and demonstration
1.1 m), regardless of the indoor air temperature. purposes. It was only after the Second World War, and the
experience of dealing with major trauma, that official
3.2. Humidity documents recommended positive-pressure ventilation as a
means to reduce airborne infection [13,40]. Ever since, there
Air humidity must be maintained at acceptable levels have been significant developments in OR ventilation in
because it is closely related to the space hygiene and thermal relation to the design concepts in OR layout, pressurization and
comfort conditions. Humidity control is most often accom- ventilation, particularly the evolvement of ultra-clean ventila-
plished by treating the ventilated air for lowering (dehumidi- tion (UCV) [41,42].
fication) or increasing (humidification) its water content, using Contamination by air was recognized by Pasteur in the mid-
proper equipment and controls. Using a rule of thumb, e.g. 19th century [43]. He soaked wounds and hands in dilute
54 L/(s kW), or a traditional temperature-only design approach carbolic acid solution and subsequently disinfected the air with
often leads to a system that is unable to meet the strict indoor spray. The death rate from sepsis following amputation fell
OR requirements [38]. Accordingly, various HVAC system from 46 to 15%. Carbolic spray was toxic and was subsequently
configurations can achieve the temperature and humidity replaced by aseptic surgical techniques.
targets for an OR by delivering the required supply air Today, proper OR ventilation has an important role on
conditions, without energy waste. occupant safety and health, including airborne contamination
High humidity levels favor the growth and transfer of [44] and infection and control [45,46], although infection rates
bacteria that can be easily become airborne on water molecules. are still unacceptably high [47]. The optimum is complete
458 C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470

asepsis (exclusion of infective agents which might contaminate zones (spaces) with identical indoor conditions then it is
the sterile inside of the body during surgery), but this may not possible to use a single stage AHU. Alternatively, a double
be possible in all cases. stage AHU is used if an AHU serves more than two zones
About 80–90% of bacterial contamination found in a wound (spaces) with different loads and indoor requirements. In this
comes from the ambient air [48]. OR air contains items such as case, there is one main AHU unit and more than two TUs. Each
skin squames or other particles like lint, respiratory droplets, terminal unit serves one zone. A TU includes a reheat coil and a
aerosols [49], and waste medical gases used for anesthesia. The third class absolute filter (S). The supplied air from the main
air may also contain other particles, like lint, dust, respiratory AHU is supplied at the local TU at some specific conditions
droplets and aerosols, and medical gases which may be used for (temperature and humidity). The desirable conditions of the
anesthesia. The primary source of bacteria in the OR are supply air are then adjusted at the TU by using the reheat coil.
squames, or skin scales, which are of the order of 10–20 mm in This way it is possible to meet the different requirements for the
diameter and are shed from exposed regions of skin, both from connected spaces/zones. In practice, the reheat coil is only used
the surgical staff and also by the patient [5,13,30,44,50] or may to make small adjustments on the delivered air temperature (i.e.
even pass through the interstices of the standard cotton fabric a few degrees). Accordingly, if two zones have distinctively
which has a pore size of 80  100 mm or pass from the bottom different loads and desirable indoor air conditions, then there
of theatre garments to mix with the air circulating in the OR should be best served by two independent AHUs.
[20]. It has been calculated that for a procedure lasting
approximately 1 h, the total number of bacteria-carrying 3.3.1. Filters
particles falling on a wound is about 270 cm 2, but the risk The type and number of filters used in an AHU designated to
of infection will depend on how many of these bacteria are serve an OR must meet strict demands similar only to clean
viable at the time of wound closure, the species and virulence of room applications. The main filter groups include: (1) filters for
the bacteria, the precise site of lodgment and the integrity of the removing solid and liquid particles (viscous impingement and
patient’s host defenses [40]. dry screen available in renewable, cleanable and throwaway
The main chemical parameters found in the indoor air of the variations, fibrous, electrostatic and air washers); (2) filters for
operating rooms are anesthetic gases, as well as disinfection removing gases and vapors (e.g. activated carbon and chemical
and sterilizing substances. Adverse health effects and filters); (3) filters for removing bacteria (e.g. ultraviolet or
discomfort have been detected to OR personnel by the germicidal lamps).
occupational exposure to anesthetic gases (e.g. nitrous The control of microbial contaminants concentrations in
protoxide and halogenated agents); thus, personnel exposure ORs is usually accomplished through the use of high efficiency
should be limited [51,52]. Accordingly, anesthetic gases must particulate air (HEPA) filters, ultraviolet germicidal irradiation
be recovered using scavenging equipment. (UVGI), and strict hygiene procedures. However, particular
Prophylactic antibiotics are now used for a variety of attention should also be given to the prevention of microbial
different procedures but are best given for clean prosthetic growth indoors and in the AHU, thus proper maintenance is of
implant procedures and in clean-contaminated operations [40]. great importance.
In contaminated and dirty operations the use of antibiotics is Three stage filters are commonly used. The first stage filter
therapeutic and may need to be continued for longer than the B2, is a prefilter, placed right after the air intake of the AHU,
single dose used for prophylaxis. In Hellenic hospitals, the filtering the outdoor air. The prefilter (30–50% efficiency) can
prevalence of antibiotic use is quite high, reaching 51.4% arrest large dust particles and solid particles (>0.3 mm) and
according to a nationwide investigation, while literature improve the overall filter effectiveness. When properly
reported data indicates significantly lower rates in other maintained, prefilters can reduce the growth of bacteria on
European countries, ranging from 26 to 34% [53]. However, the main filter. The second stage filter C, is a thin filter (95%
antibiotic prophylaxis does not always guarantee proper efficiency) can arrest particles with a diameter less than 0.3 mm.
prophylaxis. According to a study by [54], 87% of those They are placed at the exit of the air from the AHU and may
who developed SSI had received antibiotic prophylaxis. also serve to withhold water vapor (droplets) or microorgan-
Accordingly, proper ventilation remains the primary isms that may become airborne from the cooling coil. The third
objective for securing a safe and healthy indoor OR stage filter S (special filter), has an even higher efficiency of
environment in order to: (1) reduce bacteria, viruses and dust about 99.97%. This type of filters are placed as close as possible
concentration to acceptable levels, so that the indoor air to the OR, in order to clean the air from any particles that may
satisfies the aseptic levels in accordance to health guidelines for have escaped the previous filters or may have been drawn in
the patients and space occupants; (2) remove anesthetic gases from the AHU itself or the ducts. Automatic dampers are placed
and odors released during an operation, which may perma- before the filters to isolate them when the AHU does not operate
nently or temporarily disturb the occupants; (3) provide and to prohibit any backward air flow from the OR to the AHU.
optimum and comfortable working conditions for the occupants Airborne contaminants are usually attached to dust particles
to facilitate their demanding work during an operation. or water molecules. Studies have shown that 99.9% of all
The air handling unit (AHU) used to serve the OR can be one bacteria present in a hospital are removed by 90–95% efficient
(single) or two (double) stage that is without or with a terminal filters [30]. This is because bacteria are typically present in
unit (TU). Accordingly, if the AHU is used to serve one or two colony forming units that are larger than 1 mm. Viruses are
C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470 459

more difficult to control since airborne infective viruses are unidirectional airflow ceiling diffuser area of about 9 m2
much less than 1 mm in size. provides excellent screening effect that is suitable for complex
The use of UVGI to disinfect room air and air streams dates interventions and provide flexibility in order to cover amended
to about 1900 [55]. In current commercial practice, UVGI using requirements for a wide range of surgeries [65], thus increasing
either ventilation duct irradiation or upper-room air irradiation the utilizability of an OR.
(germicidal lamps with a primary wavelength of about 254 nm) The most widely used installation in general purpose ORs is
deactivates viruses, mycoplasma, bacteria, and fungi, and has plenum—conventional ventilation [43]. However, it is difficult
become popular in battling tuberculosis. However, human to identify the best practice for all design applications of the
exposure to ultraviolet C may cause some health side effects ventilation system, since there are advantages and disadvan-
and requires protection of the skin and the eyes of people tages [5,66]. For example, laminar flow systems are recognized
exposed to levels above recommended exposure limits. for providing lower general concentration levels in the OR, but
Enclosing the UVGI sources in the ventilation system, human they are sometimes blamed for higher infection rates than more
exposure is eliminated. Illustrative examples with design, conventional systems since they cause impingement on the
performance and operating guidelines along with representative wound site. However, this probably depends on the use of high
figures to compare the cost of HVAC installations and UVGI laminar flow velocities at supply. On the other hand, vertical
installations that give an equivalent number of air changes laminar flow units are superior to horizontal airflow units
based on equal levels of reduction in airborne microorganisms because clean air is directed over the operative field, while
are available in [43,55–57]. Studies on the effects of UVGI on UCV has been shown to reduce infections after total hip or knee
infection transmission rates show some statistically significant arthroplasty [40]. People, surgical lamps and equipment will
effects, but little practical significance in reduction rates of obstruct the airflow flow and constitute heat sources, even
airborne infectious disease [58]. UVGI theatres have not been resulting to minor air turbulence in vertical flow systems and
adopted in the U.K. but are used in the U.S.A. and Sweden [43]. disrupting the unidirectional air flow of horizontal flow systems
Outdoor pollutants can add to rather than dilute the indoor [5,63,64,67]. A combination of vertical and horizontal flow,
chemicals and pose a significant problem if not properly known as exponential laminar air flow with the form of an
handled by molecular filtration [59]. Concentrations are upside-down trumpet, is also possible.
expressed as parts per billion (ppb) or parts per million For existing facilities, a new method introducing a mobile
(ppm) and since they are in general 1000 to 10,000 times screen supplying ultra-clean exponential LAF has been
smaller than a fine dust particle, they can pass through the finest developed [26]. The system is designed to work independently
particle filters. Depending on the molecule diffusion gradient, as an addition to basic OR ventilation or in situations with
molecules diffuse through the indoor space from a high insufficient ventilation. The system contains a HEPA filter as
concentration to a lower concentration area. Gas-phase air well as enclosed UVC-light for bacterial control.
filtration is possible with filters based on adsorption condensa- The air supply diffusers vary in size and geometry depending
tion or chemisorption processes. on the specific design. Air diffusers must have good throw
performance over a wide range of discharge velocities
3.3.2. Air changes and distribution depending on the function and geometry of the space, to
Laminar airflow (LAF), defined as airflow that is pre- facilitate appropriate indoor air mixing of supply and indoor air,
dominantly unidirectional when not obstructed and commonly and eliminate air drafts. Diffuser sound ratings should also be
attained with an air velocity of 0.45  0.10 m/s, can either be taken into consideration before making a final selection. The
directed vertically (from the ceiling) or horizontally (from the location and number of diffusers depends on the air volume to
wall), with and without fixed or movable walls around the be supplied into the space, the space layout and load
operating table [30]. Laminar airflow systems were introduced distribution, and temperature differential between the indoor
in the 1960s [60]. and supply air. Non-aspirating diffusers are recommended and
Ultra-clean ventilation air (UCV) is produced by using sized to provide a face velocity of 127–178 L/(s m2) in
laminar air flow supplied from the ceiling with low-level accordance with current research recommendations [68].
exhaust outlets at the room periphery [40,61–64]. It is The air return vents also vary in size and geometry
combined with a HEPA filter located directly in the room depending on the function of the space. According to
inside the air intake of the OR, and is usually necessary for ORs regulations, there should be at least two air-exhaust outlets
used for high-risk operations, e.g. orthopedic implant surgery, inside the OR. One position is close to the floor, in order to
and not for general surgery or in the adjacent spaces. Such a remove the various anesthetic gases that may be released in the
unidirectional downward laminar air flow pattern is achievable space and because they are heavier than the air they are most
with an air velocity at 0.46 m/s or below. UCV theatres are likely to be found at floor level. Anesthetic gases must be
scarce due to their high cost, while there are also practical removed because they may cause health problems or
problems in keeping all medical staff and exposed instruments discomfort to the medical team inside the OR. At the same
within the UCV airflow, which is normally in a 2.8 m by 2.8 m time they pose a fire hazard. The second position is high on the
space [62]. Outside the UCV zone the flow is basically wall in order to most effectively remove any bacteria or other
turbulent, depending on the location of the exhaust vents and microorganisms and chemical substances that may become
possible flow obstructions or heat sources. However, a airborne during a surgery. The breakdown of the air exhaust is
460 C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470

Fig. 1. Various examples of obstructing objects placed in front of ventilation air-exhaust outlets. (A) Vent blocked by a closet (pulled to the right to reveal the vent);
(B) vent partially blocked by a cabinet (left) and medical equipment (right); (C) vent partially blocked with oxygen bottles.

about 25% from the ceiling level air outlets and 75% from the In the U.K., clean areas (operating theatre and preparation
floor level outlets. The optimum layout of the air-exhaust room) should have ventilation equivalent to at least 20 ACH
outlets is to have at every corner of the OR, one floor and one [21]. The air change rate in preparation rooms used for laying-
ceiling height mounted exhaust. That makes a total of four floor up sterile instruments should be around 37 ACH; a greater air
and four ceiling mounted exhausts. This layout also contributes change rate than in theatres (the main route of airborne
to a more uniform air circulation inside the space. contamination entering surgical wounds is probably via
However, special care should be exercised to account for instruments). If preparation rooms are used only as sterile
possible obstructions of the airflow, for example, due to regular pack stores, the ventilation rate should be around 11 ACH.
occupancy, possible obstructions by equipment and other Effective air changes will only occur if airflow is turbulent and
furniture that may alter the flow path or even block the vents there is no short-circuiting. These should have been established
(Fig. 1), and thermal buoyancy from medical equipment, by smoke testing.
lighting, staff, or even the patient’s wound. The systems usually require 100% outdoor air. Some
The most commonly recommended number of air changes national regulations and guidelines allow for a limited
per hour is about 20 ACH (Table 1) to maintain the OR at a recirculation under favorable outdoor conditions and for
positive pressure, while the outdoor air requirements for certain types of surgeries, for example, the German [71] and
acceptable indoor air quality must be at least 51 m3/h person Swiss [72] guidelines. The indoor air that is exhausted from the
according to ASHRAE Standard 62 [69]. Special requirements OR must not mix with the fresh outdoor air supply. Outdoor air
and pressure relationships may determine different minimum intakes must be placed away from the system’s exhaust air or
ventilation rates and filter efficiencies. Procedures generating other building’s emission points (e.g. flue stacks and other
specific indoor contaminants may also require higher air change exhaust vents, cooling towers), at a distance of 3–23 m from
rates. contaminant sources, with 7.6 m most common [31] or street
Each air change will, assuming perfect mixing, reduce level emission sources (e.g. automobile exhaust), so that the
airborne contamination to 37% of its former level [20]. Little bottom of the air intake is at least 1.8 m above grade or 0.9 m
further improvement occurs in the bacterial count after 20 above roof level [31]. Prevailing winds, building geometry,
ACH, unless the air is supplied from a high-volume vertical adjacent buildings or other obstructions, must be taken into
supply that negates the effects of turbulence [40]. Turbulence account. Outdoor air intakes must exclude wind-driven
created by staff movement and the heat from operating lamps is precipitation, contain features for draining away precipitation,
overcome by UCV systems that exclude contamination from and be equipped with a bird screen mesh.
outside the ultra-clean area. Few countries have set bacterial The air distribution pattern in an OR is equally important to
threshold limits for conventionally ventilated ORs, for the number of air changes [68]. In some cases, the airflow may
example, the German standard focuses on control of airborne even convey airborne particles towards the wound, given the
bacteria concentrations around the operating table and close proximity of OR staff near the operating table. For
instrumentation under specific limits, while the Chinese example, when the surgeon leans over the wound in such an
standard emphasizes that the operating area is controlled by airflow direct airborne wound contamination increases 27-fold
bacterial concentration and air cleanliness [70]. However, most [44] and is considered as a source equivalent to as many as 1000
national standards and guidelines recommend 20 ACH to airborne particles/min [73]. On the other hand, in convention-
obtain 50–150 colony forming units (cfu)/m3 of air [5]. ally ventilated theatres, around 70% of airborne contaminants
C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470 461

that end up in the wound, do so after first landing on exposed the surrounding indoor or outdoor environment include the
‘‘sterile’’ instruments [62]. following.
The delivery of air from the ceiling, with a downward The OR is maintained at a positive pressure with respect to
movement to several exhaust inlets located on opposite walls corridors and adjacent areas. The minimum pressurization is
[66], is probably the most effective air movement pattern for 2.5 Pa [31,75]. Maintaining a positive pressure minimizes the
maintaining the concentration at an acceptable level [30]. The air from entering into the OR from the more contaminated
air should be supplied at the ceiling and exhausted or returned spaces. Zone pressurization introduces specific control require-
from at least two locations near the floor. Supply diffusers ments that can be accomplished by different methodologies like
should be unidirectional, while high-induction ceiling or flow tracking and differential space pressurization [76]. Each
sidewall diffusers should be avoided. entry door to the OR should be sealed on its top and sides
The indoor air flow patterns in the OR must ensure that the (including astragal vertical joint seal for leaf or double doors)
air masses are directed from the most demanding zones, in and include an adjustable bottom seal. A sliding entry door is
terms of air quality, to the less demanding zones, and that there preferred over a swing door. If swing door is used, it should
are no pockets where the air can be trapped. The main air flow open into the OR.
pattern should not encounter any obstacles, especially in the The air flow patterns are determined by the placement of the
direction towards the main pollution sources around the air supply and exhaust vents in order to effectively collect and
operating table (i.e. medical staff and patient). The air velocity control the dispersion of contaminants, eliminate zones with
must be maintained at low levels to avoid drafts and turbulence trapped air or strong swirls and provide the desirable indoor
that will cause air mixing and the dispersion of bacteria and conditions throughout the conditioned space. Studies have
airborne particles. The primary air supply diffuser array should shown that when surgery is carried out in a substantially
provide a unidirectional airflow, from the top downwards, with downward and outward flow of microbiologically clean air over
an average velocity of the diffusers 0.127–0.178 m/s, in order to an area large enough to encompass the wound and all things that
maintain laminar flow and minimize strong drafts [31]. The come into contact with the wound, sepsis is reduced by at least
diffusers shall be concentrated to provide an airflow pattern 50% [48].
over the patient and surgical team, covering an area that extends Proper air circulation can be accomplished by various
0.3–0.5 m on each side beyond the footprint of the operating arrangements. In general, outlets for air supply should be
table. Additional supply diffusers may be required to provide located on the ceiling, with perimeter or several exhaust inlets
additional OR ventilation to meet the loads and satisfy indoor near the floor [30]. This arrangement provides a downward
thermal comfort conditions. Indoor air quality can improve movement of clean air through the activity zone (i.e. around the
considerably by using scavenging equipment to recover operating table) to the contaminated floor area for exhaust. The
anesthetic gases. OR shall be provided with at least two low sidewall return
Ensuring the appropriate airflow can contribute towards grilles with the bottom of these grilles installed approximately
infection control. The specific surgical procedures must also 15 cm above the floor [31]. In any event, as medical treatments
be taken into account and optimize the air distribution system and other factors change over time for a particular type of
accordingly [74]. Different levels of bacteriological contam- surgery, the relative importance and optimum design char-
ination can be observed in identical ORs, with the same acteristics of the air distribution system might also change [74].
occupancy rate, air-conditioning systems and air distribution Staff movement, especially entering and leaving the OR,
with a definite turbulent pattern, depending on the type of should be kept to a minimum, since the number of
surgeries performed [73]. For example, the bacterial con- microorganisms in the OR is directly proportional to the
centrations over the operating table in the case of dirty number of people in the room, having a direct impact on the
wound operations usually exceed the contamination levels ventilation system and on the concentration of microorganisms
encountered during traumatology surgery (e.g. with clean and particles [20,44,49,60,63,77,78].
wounds). Historically, different ACH have been investigated in an
Previous studies reviewed in [47] have concluded that effort to correlate airflow rates and bacteria in the air and
reducing air contamination in the operating theatre reduces their role in SSI, and assess their impact on OR indoor
wound contamination, ultra-clean air reduces deep infections environmental quality [77]. Recently, given current advances of
after joint replacements, the use of hats and masks decrease the computational fluid dynamics, CFD analysis has become a
bacterial count in laminar flow theatres, wearing of non-woven powerful and efficient tool for the parametric study on room
clothing decreases both the bacterial count in theatre and the airflow and contaminant dispersion of the entire OR space
rate of postoperative wound infection, the passage of bacteria [42,50,66,79,80].
through fabrics used in the operating room has been identified Considering a range of different air change rates, from 15 to
as a source of wound contamination. 150 ACH, and different ventilation system designs, it appears
that laminar flow conditions are the best choice, although some
3.3.3. Design considerations and operation care needs too be taken in their design [50,66]. A face velocity
Several key design considerations that determine the success of around 0.15–0.18 m/s, is sufficient from the laminar diffuser
in maintaining aseptic conditions and avoiding the transfer of array, provided that the size of the diffuser array is appropriate.
bacteria, viruses and other contaminants from or to the OR and The main factor in the design of the ventilation system is the
462 C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470

control of the central region of the OR where the operating not alter or adversely affect pressure differentials maintained in
lights and surgical staff constitute a large heat source. Increased the ORs. Whenever possible, avoid inactivating or shutting
ACH results in excellent removal of particles via ventilation, down the entire HVAC system. In Greece, the airflow can be
but does not necessarily mean that the percentage of particles reduced down to 30% of the full load conditions during off-use
that impinge on the wound site are also decreased. A lower hours [83]. Provided that measures are taken to ensure timely
percentage of particles hit the site with 20 ACH, than with 150 restarting of the ventilation system prior to surgery (at least
ACH. In a system that provides a laminar flow regime, a 30 min before the OR is used), findings suggest that shutting
mixture of exhaust location levels works better than either low down the OR ventilation system during off-duty periods does
or high level locations only. However, the difference is not not result in an unacceptably high particle count or microbial
significant enough that the low- or high-level location systems contamination [63]. The time required for airborne contaminant
are not viable options. removal depends on the number of air changes per hour [81],
Ideally, an AHU should serve only one OR and possibly an for example, for two ACH the minimum time is 138 min (for
additional secondary use space (e.g. scrub room) and should not 99% efficiency) and 207 min (for 99.9% efficiency), for 10
serve more than two ORs. However, this can also be handled by ACH the minimum time is 28 min (99%) and 41 min (99.9%),
other design means but need independent zone control. It is and for 50 ACH it can be reduced to 14 min (99%) and 21 min
recommended to maintain backup ventilation equipment (e.g., (99.9%).
portable units for fans or filters) for emergency ventilation of The air-exhaust outlet should also be located a minimum of
ORs, and take immediate steps to restore the fixed ventilation 3 m above ground level and away from doors, occupied areas
system [81]. When two ORs are served by a common AHU, and operable windows. Preferred location for exhaust outlets is
they must operate with the same time schedule to minimize at roof level projecting upward away from the outdoor air
energy losses. The independent operation of the HVAC intakes [30]. Prevailing winds, adjacent buildings or other
equipment in each OR must provide the means for adjusting obstructions and discharge velocities must be taken into
the indoor conditions, without affecting the performance and account.
the indoor conditions in the other ORs. The AHUs should be
located near the ORs in order to minimize the duct length for 3.4. Controls
the distribution of the supply air. This will reduce pressure drop,
fan energy consumption and energy losses. Controls are essential for optimally controlling and
The ventilation system should operate continuously, during maintaining desirable indoor conditions. Good control systems
surgery and even when the OR is not being used, but possibly at and strategies also improve energy efficiency. There are various
a reduced ventilation rate, in order to maintain continuous strategies, techniques and systems that can be used, each with a
aseptic indoor conditions and stand-by operation. Electro- different complexity, cost and effectiveness.
nically adjusting the fan speed using an inverter, can efficiently Each AHU that serves an OR should be provided with one
meet different ventilation rates according to the load. This way, thermostat and humidistat for temperature and humidity
it is also possible to meet the varying operating conditions regulation, respectively, from each OR. This way the surgeon
according to the pressure drop variations because of the or authorized medical staff can personally set the temperature
different filter conditions. When the ORs are not in use, the air and humidity that is most appropriate for each procedure. The
supply rate should be adjusted to 30% of the full load operating controls usually available on the AHU itself are not
conditions. Similarly, the fan for the exhaust air should also sufficient. They do not allow easy access since only technical
have a minimum of two speeds for adjusting the exhaust rate personnel are authorized or knowledgeable to make such
down to 30% of full capacity. Depending on the ventilation adjustments.
system, implementing a proper control strategy during the off- A humidistat can be connected with the AHU to adjust
use hours can reduce the total air change rate and thus reduce system operating modes, according to actual indoor conditions.
energy consumption [82]. An OR will be usable 15 min after When indoor humidity drops below the desirable levels the
full ventilation has been restored, provided that pressure humidifier in the AHU is activated to spray dry steam and
relativities are maintained during setback [21], while vertical humidify the supply air. When the humidity levels are
laminar flow theatres need only 5 min to replace the full volume excessive, the three-way valve of the chilled water is activated,
of air in the theatre [20]. Control of setback is normally on a to cool the air and condense out the excess water vapor.
timed basis and there should be an override linked to the Desiccant dehumidification offers an alternative for humidity
operating light or a movement detector so that setback does not control, in a more energy conscious manner, especially at low
occur when lists over-run. There must be a setback override to temperature.
allow for unforeseen use of the theatre to occur. Building management systems (BMS) provide the most
In Germany, it is usual to reduce the volume of the circulated comprehensive means to control the OR operating conditions.
air by 15–50% at times when the OR is not in use, while These are more elaborate systems and are justifiable for large size
regulations in Austria allow shutting down the ventilation facilities, especially when combined with other hospital controls.
system [63]. In the U.S.A., according to the CDC [81], HVAC For example, a system can control and monitor all hospital’s
systems serving offices and administrative areas may be shut main heat and cold production plants and HVAC installations,
down for energy conservation purposes, but the shutdown must e.g. chillers, boilers, hot water system, air-handling units,
C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470 463

including the specialized health-care applications like the ORs, Microbial growth in ventilation systems may contaminate
indoor conditions, alarms, medical gases, steam pressure, indoor air and cause a variety of problems [39]. Fungal growth
building pressure, etc. [84,85]. An open protocol system, like is potentially the most problematic for air quality. HEPA filters
BACNet, allows us flexibility for integrating existing and future can be very effective, provided they are tightly installed, and
equipment or other functions. Properly trained personnel are well maintained. Fungus can grow on HEPA filters as well as
needed to take advantage of such elaborate control systems, other ventilation components (e.g. fans and heat exchangers)
although usually graphical interfaces make it relatively easy to and, if unchecked, can actually contribute to the problem.
handle. Traditionally, postoperative fungus infections in the eye have
been related to contaminated air-conditioning ventilation
3.5. Commissioning—maintenance systems [91].
Cleaning is the simplest treatment for controlling fungal
Commissioning must occur before an OR is first used and contamination of HVAC installations, because contaminating
after any major modifications that may affect airflow patterns fungi on the filter can be removed together with dust by vacuum
(as part of a re-commissioning process), including micro- cleaning or by washing with water and detergent [92].
biological assessments [21,46]. For effective monitoring of OR Maintenance personnel should have easy access to all
commissioning and upgrading there should be a close installations and components.
cooperation between the medical staff and the hospital’s Preventive maintenance assures safe and uninterrupted
technical department; the requirement for bacteriological operation. Regular monitoring and air sampling can contribute
monitoring as part of OR commissioning is well documented, to early detection of possible defects and problems, although
with practical guidance on when and how this should be done in regular visual checks of installations and system components
conventionally ventilated and UCV ORs [86]. Some national can also be helpful [93]. For example, water accumulation near
guidelines include requirements for owners to be provided with the AHU may indicate a clogged drain pan that may become a
detailed maintenance and operation information at the pollution source by allowing the growth of bacteria [39]. In
completion of a project [68]. This is necessary information another case, moth flies appearing in the eye operating theatre
for hospital staff to successfully and efficiently operate their in a Finnish central hospital, where traced back to the air-
facilities. conditioning pipes that were found to harbor several dead
While building, expanding or renovating ORs can be pigeons because the outside grid of the system had broken [91].
expensive, proper maintenance can be relatively inexpensive Ventilation grilles may also be clogged with (green) fluff,
and following viable options can even improve existing derived from OR clothing and drapes, and deposited on these
conditions [87]. Never the less, even in countries with good surfaces by electrostatic attraction, air turbulence or gravity
resources for health, hospital administrators may find it difficult [94]. In particular, the air supply diffusers should allow for
to allocate financial resources in order to properly maintain internal cleaning. Sensors and control systems must also be
their hospitals [88]. However, there may be significant regularly inspected instead of randomly checked to ensure that
consequences that could critically influence indoor well-being, they function properly. For example, humidity sensors
health and safety conditions. commonly drift over time and give unreliable readings. They
Performance will drift away from optimum conditions after should be recalibrated on an annual basis. Employees should
long operation hours. For example, sensors and monitoring also be encouraged to report malfunctions or other problems
devices should be maintained and calibrated routinely, as they (e.g. poor indoor conditions, drafts, noise, damages). A
can become ineffective due to lint accumulation [89]; campaign to increase general awareness and encourage
regulators may fail, a humidifier with recirculation could be participation can also help.
annulled, the air intake may be blocked, the screens and Proper HVAC operation can also influence the OR utilization
diffusers may be arbitrarily manipulated both in form and by rate, which should average 90% or 100%, with 97% considered
the personnel [90]. optimal [95]. Current trends in the health care industry place
Regular maintenance can detect potential problems and if hospital administrators under increased pressure to maintain a
resolved in time, can prevent more serious damage, both in high level of activity under normal conditions and to ensure that
terms of safety and cost for equipment repair. Given the strict they provide uninterrupted health care services [96].
requirements for all OR installations, only through regular The maintenance department must be staffed with properly
maintenance for every piece of equipment and system trained technical personnel. New technologies and systems
component is possible to maintain good working conditions, introduce a need for well-trained and qualified personnel, to
minimize the risk of failure and secure the high health standards monitor, operate and maintain them. Thus, keeping up-to-date
in accordance to design conditions. Since accumulated dust and with current advances and new technical information is
moisture constitute good growing conditions for microorgan- essential. In-house training of staff, hiring qualified personnel
isms, all AHU, ductwork and other equipment must be or a contractor, is necessary pre-emptive actions. A service file
accessible for inspection and necessary periodic cleaning. for all equipment and systems should be kept current and
Without routine care, devices intended to solve problems can readily available, including operation, inspection and service
become a problem. For example, a neglected filter can become instructions, records and reports of work performed, operating
a pollution source. data and energy consumption, if possible.
464 C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470

During OR renovation and construction projects outdoor air requirements in areas with high year-round
[18,19,91,97] it is essential to ensure environmental air quality relative humidity and small ambient air temperature
and implement specific infection control measures, for variations. In addition, high ventilation rates reduce the
example, maintaining the integrity of the barrier walls, dehumidification effectiveness of conventional HVAC units
controlling dust and construction traffic, environmental and create problems with humidity control. Desiccants
monitoring. remove moisture from air by sorption. Solid desiccants are
The maintenance and operations staff of the facility should usually impregnated into a lightweight honeycomb-shaped
work as a team to manage the ventilation systems. Infection- matrix that is then formed into a wheel [101]. The rotating
control personnel must convey the importance of ventilation wheel acts as a heat exchanger between the outdoor and
management to assure that resources are available for exhaust air stream that pass through half of the wheel
appropriate maintenance [89]. A multidisciplinary team that surface as it slowly rotates. The angular speed of the wheel
includes infection-control staff should coordinate demolition, is adjusted according to the operating conditions from
construction, and renovation projects and consider proactive 8 rpm (revolutions per minute) down to 1/20 rpm. The
preventive measures at the inception; produce and maintain airflow can range from 800 to 50,000 m3/h, depending on
summary statements of the team’s activities [81]. the dimensions of the wheel. Caution must be exercised to
ensure that the selected desiccant material limits adsorption
3.6. Energy conservation to small particles not larger than the critical diameter of a
water molecule (that is about 2.8 Å or 2.8  10 10 m). To
The operating rooms are among the most demanding areas in a limit the possibility for pollutant transfer carried by the
hospital. They exhibit increased energy consumption needs for exhaust indoor air, it is recommended to use an S-type filter
their proper operation. The installed HVAC systems represent the along the air exhaust flow, before it enters the wheel.
highest installed electric power capacity. Energy conservation
systems and techniques can reduce energy consumption without Overall, energy efficiency must be strongly supported at the
sacrificing comfort or quality of services while improving air highest management levels with the authority and resources
asepsis [98]. Energy savings mean money savings from reduced needed for the initiatives to be effective. Energy conservation is
running costs that can be invested in other priorities (i.e. medical a never-ending battle. Continuous assessment or operating
equipment) and used to improve other medical services. Energy conditions and new technologies, systems and techniques for
efficient design and operation of the mechanical systems can possible incorporation should be kept in consideration. Set
allow for continuous operation of systems in support of ORs reasonable goals and energy targets that should be reached in
without the necessity of shutdowns which risk compromising OR the long run.
integrity in pursuit of generating cost savings.
In addition to the issues addressed in the previous sections, 4. Audit campaign in Hellenic hospitals
some of the potential design concepts for energy efficiency
include: The stock of Hellenic hospitals and clinics exceeds 360
facilities (not including military hospitals) with a total capacity
(1) Variable air volume: Constant volume terminal reheat of 51,788 beds, employing 18,764 doctors and 37,476 staff.
systems increase energy consumption. Alternatively, air Over 30% of the total number of medical facilities is located in
change rates can be reduced, provided proper relative the greater metropolitan area of Athens [102].
pressure relationships are maintained [99]. Properly A good number of the Hellenic hospitals are in over-aged
controlled variable air volume systems can be used to buildings. In terms of ownership, most of the Hellenic hospitals
reduce the supply air change rates during unoccupied-time are public and they serve the great majority of the population, of
of the ORs. which about 80% have public health insurance. The total
(2) Sensible heat recovery: Heat recovery in ventilation number of available ORs in Hellenic hospitals is rather small
systems, from the exhausted air to the fresh air supply, is and space availability is problematic in most cases. At the same
usually accomplished using a plate heat exchanger in the time, the number of patients that undergo surgery is high in
AHU. There is no mixing of the two air streams and thus no comparison to the capacity of the hospitals, imposing an
transmission of any pollutants that may be carried with the additional burden to the hospital and OR operating conditions.
exhausted air from the indoor environment. The fluid flow In most cases, new hospital installations and recently retrofitted
arrangement is usually a cross flow. The heat exchanger facilities meet the desirable indoor conditions for physical
performance for heat recovery can be as high as 90%. health and safety according to standards.
Although thermal energy savings can be significant, the air An investigation of 20 ORs at 10 Hellenic hospitals included
pressure increase as a result of the heat exchanger presence an audit of the HVAC installations along with complementary
must be accounted for and carefully designed for. An air-to- short-term and spot measurements of indoor thermal conditions
air heat pipe is another alternative and can be used for heat in the ORs. The short-term measurements of air temperature
recovery in an OR with a high ACH [100]. and relative humidity were collected during a 2-week period
(3) Energy recovery: A desiccant-based air-conditioning during spring. Five portable data loggers (0–75  0.2 8C, 0–
system is particularly useful for applications with high 95  4% at 20 8C  0.2%/ 8C) were placed throughout the OR,
Table 2
Summary of the main hospital and operating room HVAC characteristics
Hospitals Operating rooms
No. CD O B HVAC No. TS HP CP AHU IEC AS AE SE
C CH NV LHP BMS S F H RC I E POA OM
1 1991 P SA   1 C HWB 2*/3/3 SB 2*/3/3 C 3*/3/3 DS 3* 3S     100** CO BMS CFLD/2 WO/2 
2 C HWB 2*/3/3 SB 2*/3/3 C 3*/3/3 SS 1 3S     100** CO BMS CPP WRD/6 
2 1975 N M    3 O HWB 3/4/8 C 2/2/5 DS 2 2S  100 NO ACM CSD/6 WO/1
4 O HWB 3/4/8 C 1/2/3 DS 2 3S    100 NO ACM CPP WO/4***

C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470


3 1965 N M  5 O HWB 1/1/3 SB 3/3/7 C 1/1/3 DS 3 3S   100 NO NC CRD/4 WO/2***
6 C SB 3/3/7 C 3/1+/2 DS 2 3S   100 SO NC CFLD/1 WO/3***
4 1977 P SA  7 G AWHP 2/3/6 AWHP 2/3/6 DS 2 3S     80** NO AC CPP WRD/3
8 O AWHP 2/1/3 AWHP 2/1/3 DS 3 3S     80** SO AC CPP WRD/3
5 1974 P SA   9 Ge SB 3/4+/11 C 3/4+/11 DS 2 3S   100** NO AC CFLD/1 WO/3 
10 S SB 3/4+/11 C 3/4+/11 DS 3 3S   100** NO AC CFLD/1 WO/3 
6 1967 N M    11 Ge HWB 2/2/5 C 1/1/3 SS 3 3S 100** NO NC CFLD/1 WO/1
12 Ge HWB 2/2/5 C 1/1/3 SS 3 3S 100** NO NC CFLD/1 WO/1
7 1898 N M    13 A Gy AWHP 1/1/1 AWHP 1/1/1 DS 1 3S     100** SO AC CPP WO/8***
14 A Gy AWHP 1/1/1 AWHP 1/1/1 DS 2 3S     100** SO AC CPP WO/8***
8 1960 N M    15 A Ge HWB 3/2/8 LHP C 1/1/5 LHP SS 5 3S 100 NO AC WSD/1 WO/1 
16 A Ge HWB 3/2/8 LHP C 1/1/5 LHP SS 5 3S 100 NO AC WSD/1 WO/1 
9 1958 N M    17 Ge HWB 3/4+/7 C 2/4/7 DS 2 3S   100 NO ACM CPP WO/8***
18 Ge HWB 3/4+/7 C 2/4/7 DS 3 3S   100 NO ACM CPP WO/8***
10 1930 N M    19 Gy Ot HWB 1/0/1 C 1/1/5 DS 5 1S 100 NO NC WSD/3 WO/1 
20 Ge C 1/1/5 DS 5 1S 100 NO NC WSD/2 WO/1 
Hospital—construction date (CD); ownership (O): national (N), private (P); buildings (B): multiple (M); stand-alone-single (SA); heating, ventilating, air-conditioning (HVAC) system; central HVAC (C); central
heating (CH); natural ventilation (NV); local split heat pumps (LHP); building management system (BMS). Operating room (OR)—type of surgery (TS): abdominal (A), cardiac (C), general (Ge), gynecology (Gy),
orthopedics (O), otorhinolaryngology (Ot), specialized (S); heat production (HP): air-water heat pump (AWHP), hot water boiler (HWB), steam boiler (SB), the numerical values correspond to the number of units/
number of AHUs/number of ORs served; cold production (CP): air-water heat pump (AWHP), chillers (C), local split heat pumps (LHP) for emergency use, the numerical values correspond to the number of units/
number of AHU/number of ORs served; air handling unit (AHU); stages (S): double stage (DS) with a terminal unit, single stage (SS) without a terminal unit, the numerical value indicates the number of ORs being
served by the AHU; filtration (F): first stage filter—B2 (1S), two stage filters—B2 and electrostatic (2S), three stage filters—B2, C and S (3S); humidifier (H); reheat coils (RC); inverter (I), economizer (E) for heat
recovery; percentage (%) of outdoor air (POA); operating mode (OM) of AHU: continuous 24-h operation (CO), night turn off (NO) when OR is not in use, suspend operation (SO) when OR is not in use; indoor
environmental controls (IEC): available controls (AC) with individual thermostats and ON/OFF controls in each OR, available controls but malfunctioning (ACM), building management system (BMS), no local
controls in the OR (NC); air supply (AS): ceiling fixed linear diffusers (CFLD), ceiling perforated plate (CPP); ceiling round diffuser (CRD), ceiling square diffuser (CSD), wall square diffuser (WSD), the numerical
value indicates the number of inlets; air exhaust (AE): wall outlets (WO), wall relief dampers (WRD), unless specified otherwise the outlets are located near floor level; scavenging equipment (SE). *: including a stand-
by unit, **: adjustable air flow to account for pressure drop, ***: located at ceiling and floor height. +: units also serve the AHUs for the remaining hospital, : unit mainly used for cooling. Hot water radiators are used
for heating.

465
466 C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470

Fig. 2. Energy consumption of the 10 audited hospitals. Missing data was not Fig. 4. Measured indoor relative humidity in the 20 audited operating rooms,
available. including the minimum (RHmin), maximum (RHmax) and arithmetic mean
(RHmean) relative humidity in each OR.

usually near the four corners of the OR and one near the percentage of missing data reveals the difficulty to collect even
operating table height. Because of practical difficulties to place this basic type of data in some hospitals. It best illustrates that
the data loggers right next to the operating table, they were for some hospitals, the first step should be collect and monitor
located as close as possible to the main activity area. Data was energy consumption by organizing their technical department’s
recorded on 30-min intervals. The spot measurements were activities and implementing basic housekeeping procedures,
performed during the walk-through audit, using a small follow-up by benchmarking to identify specific needs and then
portable multilogger analyzer ( 50 to 150 8C  0.15 8C, 0– consider what follow-up energy saving measures could be
50 m/s  4%). The data collected include supply air tempera- applicable in their case.
ture at the outlet from the AHU, and air velocity at the air The audits carried out during this investigation revealed
supply and exhaust vents. several problems with regard to the function of the ORs, which
A summary of the HVAC installations in the audited are attributed to the space layout and ergonomics of the spaces.
hospitals and ORs are presented in Table 2. Two ORs were Lack of space availability and small OR dimensions were
audited in each hospital. The following results are identified by common, especially in the older facilities. As a result, they are
the hospital number (1–10) or the OR number (1–20). The date forced to place medical cabinets and store other equipment in
given in the first column refers to the hospital’s date of the ORs despite health and safety risks. Another implication of
construction. Oil is the primary heating fuel for heat production bad space ergonomics is the direct impact on proper ventilation
and only one hospital was in the process of replacing it with system operation, since numerous blocked air-exhaust vents
natural gas. were commonly encountered in the audited ORs.
Measured indoor temperature ranged from 13.8 to 28.9 8C
4.1. Findings (Fig. 3), and relative humidity from 13 to 80% (Fig. 4),
averaging in the 20 audited ORs 22 8C and 37%, respectively.
The average annual total energy consumption of the 10 For OR-19 and OR-20 the data refer to free floating conditions
hospitals audited during this investigation was 426 kWh/m2 since the AHU was not in operation, which operates only during
(Fig. 2). Thermal energy consumption for heating averaged summer for cooling. The monitored data corresponds to
269 kWh/m2, while the average electrical energy consumption continuous 24-h measurements and includes periods when the
was 168 kWh/m2. The observed variations are mostly attributed ORs were not in use or the HVAC systems were not in
to differences in the HVAC installations; the majority of the operation. Consequently, there were significant temperature
audited hospitals are not centrally air-conditioned, and other variations, while lack of humidity control in most cases resulted
than the ORs most spaces are equipped with local heat pumps to significant variations and overall very low levels. Similar
and are naturally ventilated (Table 2). The relatively high problems were reported by San Jose-Alonso et al. [103]

Fig. 3. Measured indoor temperature in the 20 audited operating rooms,


including the minimum (Tmin), maximum (Tmax) and arithmetic mean (Tmean) Fig. 5. Number of air changes per hour (ACH) in the 20 audited operating
temperature in each OR. rooms. Missing data was not available.
C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470 467

principally due to lack of humidity control in the installations. uniform indoor temperature. (3) Missing easily accessible room
Problems with indoor thermal regulations have also been thermostats; even central thermostat controls on AHUs, which
reported by Mora et al. [36]. are only accessible by the technical staff, not functioning
The number of air changes per hour ranged from 3.2 to 58 properly as a result of poor maintenance or improper
ACH (Fig. 5), according to AHU specifications and data installation. (4) AHUs not operating during winter. (5) Poorly
provided by the technical departments. For the audited ORs maintained ducts and diffusers. (6) Humidity control is usually
(Table 2), only 10% had a dedicated AHU for the OR, 10% had overlooked primarily because of the mild weather conditions.
a stand-by (backup) AHU, 20% had an indoor thermostat Some old ORs were not equipped with a ventilation system or
control, 40% had scavenging equipment to recover anesthetic in some cases the system was decommissioned because of
gases (an additional 20% were in the process of installing one), problematic operation.
10% operate the AHU continuously, 70% turn off the AHUs at On the other hand, among the most common positive
night and 20% periodically suspend operation when the ORs characteristics for some of the audited ORs, were: (1) frequent
are not in use although 22% of these units were equipped with a and efficient maintenance; (2) use of scavenging equipment; (3)
fan inverter that could be used to lower the airflow for energy use of economizer for heat recovery; (4) thermostats to control
conservation while maintaining continuous operation to secure indoor air conditions.
optimum indoor conditions and stand-by operation. Only 35% Among the most common employee complaints and
of the AHUs had an economizer for heat recovery although problems were: (1) poor or stuffy air, because of inadequate
practically all of them operate with 100% outdoor air. ventilation rates; (2) unsatisfactory indoor air circulation
Consequently, there are direct complications in terms of caused by annoying air drafts; (3) high indoor temperature
overall performance and dependability, indoor environmental during summer and low temperature during winter; (4)
quality, and energy performance. perception of poor HVAC operation and difficult control over
Understaffed technical department was a common problem desirable indoor conditions.
in practically cases. For the audited ORs, the available
manpower of the technical department ranged from a total 5. Conclusions
of 20 employees for all 24-h shifts in a hospital with 240 beds
and a gross area of 19,500 m2, to 45 employees in a hospital Measured data from short monitoring of indoor thermal
with 127 beds and a gross area of 30,800 m2. conditions along with audit results and main characteristics of
The most common problems in all or the majority of the ORs 20 ORs in 10 major Hellenic hospitals, revealed that indoor
identified during the audit campaign of 20 operating rooms in temperature ranged from 13.8 to 28.9 8C, and relative humidity
10 different hospitals, related to the HVAC system operation from 13 to 80%, averaging 22 8C and 37%, respectively. The
and performance, indoor conditions and physical parameters, number of air changes per hour (ACH) ranged from 3.2 to 58
were: (1) insufficient number of air changes, mostly due to ACH. In the majority of the audited ORs the indoor conditions
obsolete AHUs, improper system sizing or poor maintenance did not conform to the strict optimum indoor thermal conditions
(e.g. high pressure drop from poorly maintained filters); (2) mandated or recommended by various international standards,
unsatisfactory indoor air temperature and spatial variations, regulations and guidelines.
mostly due to malfunctions of AHUs that do not deliver the air The commonly encountered problems include insufficient
at the desirable conditions or blocked ventilation air outlets; (3) indoor air exchange, poor control on indoor thermal conditions,
AHUs either not equipped with a humidification and bad space ergonomics that influence the ventilation system
dehumidification system, or equipment decommissioned due operation by blocking air-exhaust vents, poor maintenance of
to operational problems; (4) no backup for AHUs; (5) technical installations and understaffed technical departments.
discontinuous operation of AHUs during the night, when the Related to other indoor environmental parameters, the audit
ORs are out of duty; (6) outdoor air inlets and exhausts very campaign in the Hellenic ORs revealed lack or improper
close to each other and close to other building exhausts; (7) no operation of scavenging equipment, poor indoor lighting, and
air exhaust filters; (8) no odor filters on the outdoor air supply; noise related problems. On a positive note, the majority of the
(9) understaffed technical departments. In addition, related to audited hospitals are already in the planning and implementa-
other indoor environmental parameters, the audit campaign in tion phase of several expansion and renovation programmes or
the Hellenic ORs revealed lack or improper operation of more specific actions, but yet essential, like the installation of
scavenging equipment, poor indoor lighting, and noise related scavenging equipment.
problems [104].
For some ORs, the most common problems were: (1) Acknowledgments
Operable windows in the older buildings, which are still used
for natural ventilation; windows are allowed in operating This work was performed under contract to the Hellenic
theatres, for purposes of natural light, but they should be sealed Ministry of Labor and Social Affairs, Centre for Occupational
[40]. (2) Use of radiators and split unit heat pumps for heating; Health and Safety in the framework of the European project
sometimes the split units are also used for supplementary ‘‘Survey of occupational problems and risks related to indoor
cooling. They constitute a pollution source and cannot maintain conditions in hospitals operating rooms’’ (SOC 97 202362 05
aseptic conditions, while it is difficult to regulate and maintain a F05) of the European Commission, Directorate General V,
468 C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470

Employment, Industrial Relations and Social Affairs, Public contamination in hospital operating rooms and haematological units,
Journal of Hospital Infection 50 (2002) 155–160.
Health and Safety at Work Directorate V/F. The authors are
[24] W. Madsen, Keeping the lid on infection: infection control practices
grateful to the heads and the staff of the 10 hospitals where of a regional Queensland hospital 1930–50, Nursing Inquiry 7 (2000)
fieldwork was undertaken for their cooperation during this 81–90.
study. [25] Y.J. Drabu, T. Miller, Importance of air quality and related factors in the
prevention of infection in orthopaedic implant surgery, Journal of
Hospital Infection 40 (1998) 326.
References [26] B. Friberg, M. Lindgren, C. Karlsson, A. Bergstrom, S. Friberg, Mobile
zoned/exponential LAF screen: a new concept in ultra-clean air technol-
[1] E. Marcon, S. Kharraja, G. Simonnet, The operating theatre planning by ogy for additional operating room ventilation, Journal of Hospital
the follow-up of the risk of no realization, International Journal of Infection 50 (2002) 286–292.
Production Economics 85 (1) (2003) 83–90. [27] S. Friberg, B. Ardnor, R. Lundholm, B. Friberg, The addition of a mobile
[2] A. Macario, T.S. Vitez, B. Dunn, T. McDonald, Where are the costs in ultra-clean exponential laminar airflow screen to conventional operating
perioperative care? Analysis of hospital costs and charges for inpatient room ventilation reduces bacterial contamination to operating box levels,
surgical care, Anesthesiology 83 (1995) 1138–1144. Journal of Hospital Infection 55 (2003) 92–97.
[3] I. Basiliadou-Zioga, H. Christopoulou-Aletra, The organization of a [28] A.J. Streifel, C. Hendrickson, Assessment of health risks related to
surgery room as it is depicted in the Hippocratic Corpus, in: Proceedings construction, Heating/Piping/Air Conditioning Engineering 74 (2002)
of the IHF Pan-regional Conference Towards the ‘Smart’ Hospital, 27–32.
International Hospital Federation, Thessaloniki, Greece, November 4– [29] AIA Guidelines for Design and Construction of Hospital and Health Care
7, 2004. Facilities, The American Institute of Architects Press, Washington, DC,
[4] ISO 14644-1. Cleanrooms and associated controlled environments. Part 2006.
1. Classification of air cleanliness, International Organization for Stan- [30] Health care facilities, in: HVAC Applications Handbook, American
dardization Technical Committee 209, 1999. Society of Heating, Refrigerating and Air-Conditioning Engineers
[5] S. Dharan, D. Pittet, Environmental controls in operating theatres, Inc., Atlanta, GA, 2003 (Chapter 7).
Journal of Hospital Infection 51 (2002) 79–84. [31] ASHRAE Standard 170P, Ventilation of Health Care Facilities, Amer-
[6] B. Belew, Fundamentals of particle counting, Clean Rooms 20 (3) (2006) ican Society for Heating, Refrigerating and Air-Conditioning Engineers
15–20. Inc., Atlanta, GA, 2006.
[7] M. Santamouris, E. Dascalaki, C.A. Balaras, A. Argiriou, A. Gaglia, [32] DIN 1946, Ventilation and Air-Conditioning. Part 4. Ventilation in
Energy performance and energy conservation in health care buildings in Hospitals, vol. 4, Deutsches Institut für Normung e.V., Beuth-Verlag,
Hellas, Energy Conversion & Management 35 (1994) 293–305. Berlin, 1999.
[8] I. Sofronis, G. Markoyannakis, Energy consumption in public hospitals, [33] Technical Directive 2423/86, Building Installations, Air-Conditioning of
in: Proceedings of the Symposium on Energy Conservation in Hospitals, Building Spaces, Technical Chamber of Greece, Athens, 1987.
European Commission, Athens, 1997. [34] Technical Directive 2425/86, Building Installations, Elements of HVAC
[9] P. Aspinall, Benchmarking and best practice—energy management for Load Calculations for Building Spaces, Technical Chamber of Greece,
healthcare in the UK, business briefing: hospitals engineering & facilities Athens, 1987.
management, Touch Briefings (2004) 3 www.touchbriefings.com. [35] Guidelines for Electromechanical Installations in Hospitals, Directo-
[10] D. Carpenter, S. Hoppszallern, In search of efficiency—2006 Hospital rate of Technical Services, Design Department, Health Ministry,
energy survey, Health Facilities Management Magazine (June 2006). Athens, 1997.
[11] K. Sandrick, Using environmentally friendly construction materials, [36] R. Mora, M.J.M. English, A.K. Athienitis, Assessment of thermal
Health Facilities Magazine (February 2003). comfort during surgical operations, ASHRAE Transactions 107 (1)
[12] A.N. Tombazis, Recent works of A.N. Tombazis and Associates Archi- (2001) 52–62.
tects, Renewable Energy 15 (1–4) (1998) 72–77. [37] N.L. Belkin, Use of scrubs and related apparel in health care facilities,
[13] M. Essex-Lopresti, Operating theatre design, Lancet 353 (1999) 1007– American Journal of Infection Control 25 (1997) 401–404.
1010. [38] J. Murphy, Temperature & humidity control in surgery rooms, ASHRAE
[14] S.M. Stavridou, Nursing Techniques in Operating Rooms, 2nd ed., Journal 48 (6) (2006) 18–25.
University Studio Press, Thessaloniki, 1983. [39] OSHA Technical Manual, Section II. Sampling, Measurement Methods
[15] G.A. Noskin, L.R. Peterson, Engineering infection control through and Instruments, Occupational Safety and Health Administration, US
facility design, Emerging Infectious Diseases 7 (2) (2001) 354–357. Department of Labor, Washington, DC, 1999.
[16] C. Lawson, Research considered on OR air, ASHRAE Insights 19 (12) [40] H. Humphreys, E.W. Taylor, Operating theatre ventilation standards and
(2004) 4. the risk of postoperative infection, Journal of Hospital Infection 50
[17] J. Bellchambers, J.M. Harris, P. Cullinan, H. Gaya, J.R. Pepper, A (2002) 85–90.
prospective study of wound infection in coronary artery surgery, Eur- [41] P. Ninomura, J. Bartley, New ventilation guidelines for health-care
opean Journal of Cardio-thoracic Surgery 15 (1999) 45–50. facilities, ASHRAE Journal 43 (2001) 29–33.
[18] T.H. Kuehn, Airborne infection control in health care facilities, Solar [42] T.T. Chow, X.Y. Yang, Ventilation performance in operating theatres
Energy Engineering 125 (3) (2003) 366–371. against airborne infection: review of research activities and practical
[19] B. Drake, Infection control in hospitals, ASHRAE Journal 48 (6) (2006) guidance, Journal of Hospital Infection 56 (2004) 85–92.
12–17. [43] G. Bannister, Prevention of infection in joint replacement, Current
[20] K. Woodhead, E.W. Taylor, G. Bannister, T. Chesworth, P. Hoffman, H. Orthopaedics 16 (2002) 426–433.
Humphreys, Behaviours and rituals in the operating theatre, Journal of [44] M. Persson, J. van der Linden, Wound ventilation with carbon
Hospital Infection 51 (2002) 241–255. dioxide: a simple method to prevent direct airborne contamination
[21] P.N. Hoffman, et al., Microbiological commissioning and monitoring of during cardiac surgery? Journal of Hospital Infection 56 (2004)
operating theatre suites, Journal of Hospital Infection 52 (2002) 1–28. 131–136.
[22] H. Humphreys, A.R. Stacey, E.W. Taylor, Survey of operating theatres [45] N.J. Fox, Space, sterility and surgery: circuits of hygiene in the operating
in Great Britain and Ireland, Journal of Hospital Infection 30 (1995) theatre, Social Science and Medicine 45 (1997) 649–657.
245–252. [46] W. Grondzik (Ed.), HVAC Design Manual for Hospitals and Clinics,
[23] O. Faure, H. Fricker-Hidalgo, B. Lebeau, M.R. Mallaret, P. Ambroise- American Society of Heating, Refrigerating and Air-Conditioning Engi-
Thomas, R. Grillot, Eight-year surveillance of environmental fungal neers Inc., Atlanta, GA, 2003, p. 287.
C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470 469

[47] A.W. Blom, C. Gozzard, J. Heal, K. Bowker, C.M. Estela, Bacterial [70] Z. Xu, J. Shen, Clean operating room control, ASHRAE Transactions
strike-through of re-usable surgical drapes: the effect of different wetting 111 (2) (2005) 646–651.
agents, Journal of Hospital Infection 52 (2002) 52–55. [71] Guideline VDI 2167—Draft, Building services in hospitals—heating,
[48] F.H. Howorth, Prevention of airborne infection during surgery, ASHRAE ventilation and air-conditioning, The Association of German Engineers-
Transactions 91 (1B) (1985) 291–304. VDI, Dósseldorf, Germany, 2004.
[49] M. Whitby (Ed.), Infection Control Guidelines, 2nd ed., Queensland [72] Guideline SWKI 99-3, Heating, Ventilation and Air-conditioning Sys-
Health, November 2001, p. 371. tems in Hospitals (Planning, Construction, Operation), Swiss Society of
[50] F. Memarzadeh, A.P. Manning, Comparison of operating room ventila- Heating & Air Conditioning Engineers, SWKI, Schönbühl, Switzerland,
tion systems in the protection of the surgical site, ASHRAE Transactions 2003.
108 (2) (2002) 3–15. [73] N. Zamuner, Operating room environment with turbulent air flow,
[51] M.K. Panni, S.B. Corn, The use of a uniquely designed anesthetic ASHRAE Transactions 92 (2A) (1986) 343–349.
scavenging hood to reduce operating room anesthetic gas contamination [74] J.R. Lewis, Operating room air distribution effectiveness, ASHRAE
during general anesthesia, Anesthesia and Analgesia 95 (2002) Transactions 99 (2) (1993) 1191–1199.
656–660. [75] B. Wiseman, Room pressure for critical environments, ASHRAE Journal
[52] S. Mierdl, C. Byhahn, U. Abdel-Rahman, G. Matheis, K. Westphal, 45 (2) (2003) 34–39.
Occupational exposure to inhalational anesthetics during cardiac surgery [76] S.A. Anderson, Control techniques for zoned pressurisation, ASHRAE
on cardiopulmonary bypass, The Annals of Thoracic Surgery 75 (2003) Transactions 93 (2) (1987) 1123–1139.
1924–1927. [77] B. Kruppa, H. Rüden, The influence of various air exchange rates on
[53] A. Gikas, et al., Prevalence study of hospital-acquired infections in 14 airborne particles and microorganisms in conventionally ventilated
Greek hospitals: planning from the local to the national surveillance operating rooms, Indoor Air 6 (2) (1996) 93–100.
level, Journal of Hospital Infection 50 (2002) 269–275. [78] A.J. Mangram, T.C. Horan, M.L. Pearson, L.C. Silver, W.R. Jarvis,
[54] H.M. Eriksen, S. Chugulu, S. Kondo, E. Lingaas, Surgical-site infections Guideline for prevention of surgical site infection—1999, Infection
at Kilimanjaro Christian Medical Center, Journal of Hospital Infection 55 Control and Hospital Epidemiology 20 (1999) 247–278.
(2003) 14–20. [79] C.R. Buchanan, D. Dunn-Rankin, Transport of surgically produced
[55] D. VanOsdell, K. Foarde, Defining the effectiveness of UV lamps aerosols in an operating room, American Industrial Hygiene Association
installed in circulating air ductwork, Final Report ARTI-21CR/610- Journal 59 (6) (1998) 393–402.
40030-01, Air-Conditioning and Refrigeration Technology Institute, [80] T.T. Chow, X.Y. Yang, Ventilation performance in the operating theatre
Arlington, Virginia, 2002, p. 49. against airborne infection: numerical study on an ultra-clean system,
[56] M.W. First, E.A. Nardell, W. Chaisson, R. Riley, Guidelines for the Journal of Hospital Infection 59 (2005) 138–147.
application of upper-room ultraviolet germicidal irradiation for prevent- [81] L. Sehulster, R.Y.W. Chinn, Guidelines for environmental infection
ing transmission of airborne contagion. Part II. Design and operation control in health-care facilities: recommendations of CDC and
guidance, ASHRAE Transactions 105 (1999) 877–887. the Healthcare Infection Control Practices Advisory Committee,
[57] P. Xu, J. Peccia, P. Fabian, J.W. Martyny, K.P. Fennelly, M. Hernandez, Morbidity and Mortality Weekly Report MMWR 52 (2003) 48,
S.L. Miller, Efficacy of ultraviolet germicidal irradiation of upper-room No. RR-10.
air in inactivating airborne bacterial spores and mycobacteria in full- [82] J.E. Woods, G.L. Reynolds, G.M. Montag, D.T. Braymen, R.W. Ras-
scale studies, Atmospheric Environment 37 (2003) 405–419. mussen, Ventilation requirements in hospital operating rooms. Part I.
[58] M.M. Hannan, B.S. Azadian, B.G. Gazzard, D.A. Hawkins, P.N. Control of airborne particles, ASHRAE Transactions 92 (2A) (1986)
Hoffman, Hospital infection control in an era of HIV infection and 396–426.
multi-drug resistant tuberculosis, Journal of Hospital Infection 44 [83] Guidelines for Electromechanical Installations in Hospitals, Directorate
(2000) 5–11. of Technical Services, Design Department, Ministry of Health, Athens,
[59] T.J. Robinson, A.E. Ouellet, Filters and filtration, ASHRAE Journal 41 1997.
(1999) 65–70. [84] J. Williamson, BACnet meets hospital needs, ASHRAE Journal 47 (11)
[60] N. Tumia, G.P. Ashcroft, Convection warmers—a possible source of (2005) 12–14.
contamination in laminar airflow operating theatres? Journal of Hospital [85] G. Arcuri, S. Cencetti, C. Conti, G. Pirini, M. Martignon, G. Melotti, M.
Infection 52 (2002) 171–174. Miselli, M. Rambaldi, Flexibility, ergonomy and safety in the operation
[61] O. Chen, Z. Jiang, A. Moser, Control of airborne particle concentra- room, in: Proceedings of the IHF Pan-regional Conference Towards the
tion and draught risk in an operating room, Indoor Air 2 (1992) ‘Smart’ Hospital, International Hospital Federation, Thessaloniki,
154–167. Greece, November 4–7, 2004.
[62] A.P. Fraise, P. Hoffman, D. Burfoot, Ultraclean ventilation in operating [86] J. Holton, G.L. Ridgway, Commissioning operating theatres, Journal of
theatres beyond laminar flow, Journal of Hospital Infection 53 (2002) Hospital Infection 23 (1993) 153–160.
152–153, Letters to the Editor. [87] E. Abreu, D. Potter, Recommendations for renovating an operating
[63] M. Scherrer, Hygiene and room climate in the operating room, Minimally theater at an emergency obstetric care facility, International Journal of
Invasive Therapy & Allied Technologies 12 (2003) 293–299. Gynecology & Obstetrics 75 (2001) 287–294.
[64] T.T. Chow, X.Y. Yang, Performance of ventilation system in a non- [88] J.A. Fortney, Editor’s comment: recommendations for renovating an
standard operating room, Building and Environment 38 (2003) 1401– operating theater at an emergency obstetric care facility, International
1411. Journal of Gynecology & Obstetrics 75 (2001) 295.
[65] A. Brunner, New Guidelines for Hospitals in Switzerland and in Ger- [89] A.J. Streifel, Health-care IAQ: guidance for infection control, Heating/
many, Brunner Haustechnik AG, 2005, p. 11. Piping/Air Conditioning Engineering 72 (10) (2000) 28–36.
[66] F. Memarzadeh, A. Manning, Reducing risks of surgery, ASHRAE [90] J.F. San Jose-Alonso, E. Velasco-Gomez, F.J. Rey-Martýnez, M.
Journal 45 (2) (2003) 28–33. Alvarez-Guerra, C.G. Pelaez, Study on environmental quality of a
[67] H. Chien-Chang, L. Chung-Hsien, Y. Jung-Pin, L. Tsing-Fa, Numerical surgical block, Energy and Buildings 29 (1999) 179–187.
study of thermal buoyancy effect in an operating state of clean rooms, [91] A. Tarkkanen, V. Raivio, V.-J. Anttila, P. Tommila, R. Ralli, L. Mer-
Journal of Aerosol Science 27 (4) (1996), p. 656. enmies, I. Immonen, Fungal endophthalmitis caused by Paecilomyces
[68] P. Ninomura, C. Rousseau, J. Bartley, Design and construction of hospital variotii following cataract surgery: a presumed operating room air-
and health care facilities, ASHRAE Journal 48 (6) (2006) 33–37. conditioning system contamination, Acta Ophthalmologica Scandina-
[69] ASHRAE Standard 62, Ventilation for Acceptable Indoor Air quality, vica 82 (2004) 232–235.
American Society of Heating, Refrigeration and Air-Conditioning Engi- [92] N. Hamada, T. Fujita, Effect of air-conditioner on fungal contamination,
neers, Atlanta, GA, 1999. Atmospheric Environment 36 (2002) 5443–5448.
470 C.A. Balaras et al. / Energy and Buildings 39 (2007) 454–470

[93] C. Fox, A.S. Whyte, Theatre air sampling––once a year is not enough, [100] S.H. Noie-Baghban, G.R. Majideian, Waste heat recovery using heat pipe
Journal of Hospital Infection 32 (1996) 319–320. heat exchanger (HPHE) for surgery rooms in hospitals, Applied Thermal
[94] C. Fox, A. Whyte, Theatre air sampling––ignorance is bliss, Journal of Engineering 20 (14) (2000) 1271–1282.
Hospital Infection 30 (1995) 80–82. [101] L.G. Harriman, M.J. Witte, M. Czachorski, D.R. Kosar, Evaluating active
[95] A.A. Weinbroum, P. Ekstein, T. Ezri, Efficiency of the operating room desiccant systems for ventilating commercial buildings, ASHRAE Jour-
suite, The American Journal of Surgery 185 (2003) 244–250. nal 41 (10) (1999) 28–37.
[96] C.N. Lawson, Commissioning hospitals for compliance, ASHRAE [102] National Statistics Service, Electric Energy Consumption, by Geo-
Transactions 99 (2) (1993) 1183–1190. graphic region and Department and by Category of Use: 1994 and
[97] D.R. Rask, B. Dziekan, W.C. Swincicki, Air quality control during 1995, Table XII:11, Statistical Yearbook, Hellenic Statistical Authority,
renovation in health care facilities, in: D.J. Moschandreas (Ed.), Design, Athens, 1997.
Construction and Operation of Healthy Buildings. Solutions to Global [103] J.F. San Jose-Alonso, E. Velasco-Gomez, F.J. Rey-Martýnez, M.
and Regional Concerns, ASHRAE, Atlanta, GA, 1998, 291–304. Alvarez-Guerra, C. Gallego Pelaez, Study on environmental quality of
[98] G.J. Williams, Air handling system retrofit reduces energy consumption, a surgical block, Energy and Buildings 29 (1999) 179–187.
ASHRAE Journal 34 (3) (1992) 34–38. [104] C.A. Balaras, E. Dascalaki, A. Argiriou, A. Gaglia, HVAC systems and
[99] W.E. Tinsley, Hospital saves energy with VAV system and DDC control, indoor conditions in Hellenic hospital operating rooms, ASHRAE
ASHRAE Journal 33 (3) (1991) 22–24. Transactions 108 (2) (2002) 23–38.

View publication stats

You might also like