Professional Documents
Culture Documents
1. ACKNWLEDGEMENT
2. INTRODUCTION
3. ELECTRICITY
4. GENERATION
5. ENTRY IN THE BUILDING
6. DOMESTIC SUPPLY
7. EARTHING SYSTEM
8. DISTRIBUTION CIRCUITS
9. BASIC WIRING SYSTEM
10. DUCTS FOR ELECTRICAL DISTRIBUTION
11. CONDUCTOR
12. INSULATION
13. EXTERNAL PROTECTION
14. ELECTRICAL APPLIANCES
15. ELECTRICAL INSTALLATIONS
16. EXECUTION
17. SUB-STATION
ACKNOWLEDGEMENT
Since the end of the nineteenth century virtually all buildings are
provided with electric lightings installation for use at night. With the
advent of fluorescent lamp that is compatible with daylight, cheap to
run and not emitting heat gain in buildings, it made possible to install
electric lighting supplementing day light and in extreme cases
provide the only source of light in a windowless environment.
The power generation in India in 1947-48 was only 4.1 billion and
today we generate more than 600 billion KW.
ELECTRICITY
Electricity is generated from the stored energy of water that makes turbine
run and generate electricity. The other method includes fuels (Coal, diesel or
gas) to fire boilers and pass stream and generate electricity through
generators. Transformer step up several Thousands or even hundreds of
thousands of volts before it is supplied to the transmission lines or cable. By
transmitting electricity at high voltages less power is lost in the cables. At the
receiving end of voltage is stepped down by transforms in local sub-stations to
consumers at 240 volts.
GENERATION
SYNCHRONOUS GENERATOR OR ALTERNATOR:
The synchronous machine consist essentially of two parts namely the armature
(or stator) and the field magnet system (or rotor).
The field system of the alternator is rotated within the armature ring and is
known as rotor. The exciting current is supplied to the rotor through two slip
rings and brushes. The polarities of the field produced in alternately north (N)
and south (S). The power rating of the exciter is ordinarily 0.5% to 10% of
power rating of synchronous generator. The voltage rating of the exciter is
usually between125 to 250 volt.
When the rotor is rotated by means of some prime mover, the armature
conductors cut the magnetic-flux; therefore, an EMF is induced in the
armature conductor, due to electro-magnetic induction effect.
ENTRY IN THE BUILDINGS
In Urban areas electrical cables are usually underground and are brought up to
entry point at ground level or into basement service cable cannot be bent to
small radii and this should be borne in mind when considering point of entry.
In small buildings the cable run is kept as short as possible, terminating in a
distribution board at the first convenient position. In these buildings the
distribution board will be fitted with a seal box to prevent moisture from
entering the insulation of the service cable, a main fuse for the premises in a
box sealed by the supply authority and the consumer unit or other switch and
fuse gear belonging to the building. The position chosen for the distribution
board should be readily accessible both for meter reading and for replacing
fuses. In some cases special glasses are provided so that meter can be read
without entering the premises.
DOMESTIC SUPPLY
In three phases, four wires bring 420/ 240 volts, 50 cycles per second. The
voltage between any two of the phases wires is 415 Volts. And between any
phase wire and the neutral is 240 volts. The balancing of load is then achieved
by serving different areas of the building by different phases. Electric motors
are usually designed for three phase operation.
Regulations for earthing system vary considerably among countries and among
different parts of electric systems. Most low voltage systems connect one
supply conductor to the earth (ground).
To protect a structure from lightning stroke directing the lightning through the
earthing system and into the ground rod rather than passing through the
structure.
The most common ground plane for large monopole antenna and some other
kinds of radio antenna.
Applications Of Earthing:
• Provide low resistance and safe path for lightning and fault current
• LV System Earth
FUNCTIONS OF EARTHING
Equipment Earth : Path for fault current, lower touch voltage, protection
against electric shock
Lighting Earth : Low resistance path to diverse the current under lightning
attack.
Class II protection –
• System Earth
• Lightning Earth
• Generator Earth
• Shielding Earth
The sub circuit which gives supply to lighting load points is called lighting load
sub circuit. This circuit includes lamps, fans, tubes etc. As per Indian Electricity
Rules. The following rating should be assumed
• Filament lamp 20 W
• Fluorescent tube 40 W
There are several wiring system in use. Each system of wiring has its own
particular advantage. No one system is suitable for all installations. Great care
must, therefore, be taken in the section of the system which depends upon the
following:
a) Working voltages.
b) Atmosphere.
c) Class of building or size of installation.
The energy is usually supplied by the electric supply co., which brings the
service main to the building in the energy meter.
System of wiring:
a) Tree system
b) Distribution system
Tree system: In this system branch circuit are tapped from the circuit main at
convenient places. There are many joints and often fault occurs which is very
difficult to locate. This system is not used for installation purpose.
There is wide choice of wiring; however one must keep in mind the safety of
men & material. The various types of wiring used are discussed below
Cleat Wiring:
In this system of wiring, V.I.R or PVC Insulated wires are held to the walls and
ceiling by means of porcelain cleats which are fixed at distance of 0.5 m
horizontally and 0.75 m vertically above the walls The cleat are made on two
halves, one is known as base and the other is known as cap. The wirings are
drawn in groves and finally tightened. This wiring is cheapest and requires little
skill and can be quickly installed.
Conduit Wiring:
In this type of wiring system VIR or PVC are carried through steel or PVC tubes
as conduit in case of surface conduit wiring, the conduit is fitted on the surface
of the walls by means of saddles and in case of concealed conduit wiring the
conduit to facilitate the drawing of wires
DUCTS FOR ELECTRICAL DISTRIBUTION
In addition to the wiring systems there are a number of ducts available
specially designed to contain electric cables in particular building stations
Skirting trucking: It is very usual to run cable trunking in or above the skirting
round the perimeter walls. This system is mostly employed in office buildings.
Floor Trucking: System is employed in large offices where desks are placed
remote from walls. Useful where there are comparatively few points, the
positions of which are known, and where flexibility for future re-planning must
be achieved.
Overhead distribution
Overhead distribution systems are clearly more economical and more flexible
than under floor ones. They are mainly used in industrial units when pendants
connection to apparatus is not considered unsightly.
CONDUCTOR
A cable is a length of single conductor, usually having several wires stranded
to-gather, or of two or more conductors, each provide with its own insulation
and laid up to-gather. The insulated conductor (s) may or may not be provided
with an overall protective covering. The conductor with its insulation but
without mechanical protection is called core of the cable. Thus a, cable consists
of three parts:
a) Conductor,
b) Insulation
c) External Protection
There are four best conductors which can be used for conducting electrical
energy. They are:
On the basis of insulations, the cables maybe classified as follows: (i) Paper
Insulated cables. In these cables paper is wound on the conductor in successive
layer to archive required dielectric strength. Such cables are manufactured in
various sizes from 5 mm2 to 500 mm2 cross-section conductors and voltage
rating sup to 33 KV
(ii)PVC cables
Abrupt bending in cables is not desirable; the bending radius ranges from 12
to 30, times the diameter.
There are four main ways in which electricity can be converted into light
It can flow through a wire, so that it glows (lamps), modern filament lamps use
coil of tungsten wire which gives a much whiter light than carbon, and the bulb
contains nitrogen and argon. Most household bulbs are 25 to 150 watt of
electric power, but some large tungsten lamps used in search lights a in
television studios use as much as 30 KW.
Discharge lamps are long tubes containing a gas or vapour. When electricity
passes through a pure gas at low pressure, energy is transferred to the gas
atoms, causing them to emit radiations. The wavelength of this radiation,
which determines color, depends on the gas e.g., sodium vapor and neon emit
visible radiation. Sodium produces an efficient yellow light, mercury produces
a bluish white light and some ultra-violet radiations, and neon gives off a
strong red light.
FLUORESCENT LAMPS
• Testing of Installations
EXECUTION
The execution of entire electrical Installation should be carried out under the
guidance and supervision of competent electrical engineer/through licensed
electrical contractor; in accordance to the design and specification provided in
the tender and strictly as per rules and regulations of electrical supply.
The electrical contractor should get approval for all materials including fitting
and fixtures to be used from the architect before commencement of work.
The end of work the electrical contractor should check and test the entire
electrical installation work and get it approved from the electrical supply
company.
The electrical contractor should submit his test report and completion
certificate in required forms for consumer meter and permanent electric
supply connections to the buildings.
Electric Services for Multi-storied Buildings
• The electrical distribution cables wiring should be laid in a separate duct.
The duct should be sealed at every alternate floor with non-combustible
materials having the same fire resistance as that of the duct.
• Water mains, telephone lines, intercom lines, gas pipe lines should be
laid in the duct of cables
• Separate circuits for water pumps, lifts, staircase and corridor lighting
and blower for the pressurize system should be provided from the main
switch gear panel.
• The inspection panel doors and any other openings in the shaft should
be provided with air tight fire doors having a fire resistance of not less
than two hours.
• Medium and low voltage wiring running in shafts, and within false
ceilings, should run in metal conduits.
The generator should be capable of taking starting current offal machines and
circuit s stated above simultaneously. If the stand-by pump is driven by diesel
engine. The generator supply needs not to be connected to the standby pump.
DISTRIBUTION BOARD
Types of Transformers
SUB-STATION
Substation is a part of an electrical generation, transmission,
and distribution system, where voltage is transformed from high to low, or
low to high, or many other important functions.
The objectives of the act are to consolidate the laws relating to generation,
distribution trading and use of electricity and generally for taking measures
conductive to development of electricity to all areas, nationalization of
electricity tariff, ensuring transparent policies regarding subsidies, promotion
of efficient and environmentally benign policies, constitution of Central
Electricity Authority, Regulatory Commissions and established of Appeallate
Tribunal and for matter connected thereafter or incidental thereto”.