You are on page 1of 7

Specifying Steam

Surface Condensers
cooling water entering the condenser
by Elliot Spencer and the quantity of water available.
Graham Mfg.Co., Inc., Great Neck, Long Island, N.Y. The steam condensing temperature
can get down to as low as 5F above
Factors affecting condenser design and selection. the entering cooling water temperature,
A typical air conditioning surface condenser specification is included. but in most air conditioning
installations the differential is 20F,
sometimes 10F, but seldom smaller, as
from the turbine manufacturer. the closer approach would require a
costly amount of condenser surface.
THE FORMULA for determining the Generally speaking, on systems where In practice, cooling tower water is first
amount of surface required in a surface the motive steam pressure is used in the refrigerant condenser,
condenser is as follows: approximately 150 lb and the turbine is where it rises about 10F and is then
Q = UA (LMTD) (1) discharging to a vacuum of 26.inches available for steam condensing. The
where of mercury (4 in. Hg absolute) , a steam great bulk of steam-driven cen-trifugal
Q = Heat to be absorbed, Btuh = rate of 14-16 lb per hr per bhp is refrigeration systems operate with a
pounds per hour of steam times 950 economically feasible. Although steam condenser vacuum of
Btu per pound; greater efficiency is available at approximately 4 in. Hg abs., which is
U = Overall heat transfer rate, Btu per increased cost, utility costs for this equivalent to a condensing
(hr) (sq ft) (F); type of installation seldom justify temperature of 125.4F. Thus, referring
A = Surface required, sq ft; reducing the steam consumption by to Fig 1 and presuming that 85F
LMTD = Loge mean temperature means of higher ef-ficiency turbines or cooling water is supplied to the system
difference between condensing lower condensing pressures. When from the cooling towers, water
temperature and cooling water. special conditions are present, the temperature into the steam condenser
No attempt will be made to go through specifying engineer may consider is approximately 95F. Assuming a
a formal condenser selection. The either of the above modifications to turbine steam rate of 14-16 lb per hr per
procedure for condenser rating is improve performance. bhp (bhp per ton of refrigeration is
amply covered in the publication of approximately 1) and a condensing
Heat Exchange Institute entitled, Condenser Vacuum water circulation rate of 3 gpm per ton
"Standards for Steam Surface The vacuum produced in a steam of refrigeration, water rise on the steam
Condensers."* Rather we shall attempt condenser is that pressure condenser is also about 10F. Thus, the
to discuss qualitatively the factors corresponding to the temperature at leaving water temperature approach is
affecting selections and their effects which the steam condenses. This 20F(125F minus 105F).
on size and price. steam condensing temperature, in turn,
is dependent upon the temperature of
Turbine Steam Rate
Turbine steam rate is usually
expressed in pounds per hour of
steam per brake horsepower and is
commonly called the water rate. This
water rate is a function of motive steam
pressure and temperature, condensing
temperature, or equivalent vacuum,
and turbine efficiency. Specific
information for a given turbine
application can be obtained
_____________________________
_
This Standard is currently out of print, but a
new edition is in preparation and will be
available in the future from Heat Exchange
Institute, 122 E. 42nd St., 'New York, N.Y.
10017.
If, on the other hand, we designed the be specified. This temperature is accessory items have built-in excess
steam condenser for 3 in. Hg. abs., determined by the water source and capacity), no statement of excess
which is equivalent to a condensing varies with the location of the capacity need be made.
temperature of 115F for the same installation. Water flow rate to the
approximate water temperature rise, the condenser is usually determined by Water Pressure Drop
approach would be 10F (115F minus the refrigeration manufacturer and is Water side pressure drop is a function
105F). Thus from Eq (1), because the generally set at approximately 3 gpm of tube velocity, condenser length and
log mean temperature difference is per ton of refrigeration when cooling the number of passes the water has to
greater, we see that the condenser towers are used. However, when river make in a given condenser. Air
designed for 4 in. Hg abs. requires less water or water at relatively low conditioning practice permits
surface than the one designed for 3 in temperature is available, water flow velocities as high as 10 fps in the tube
Hg abs. rate varies and specifications should side of refrigerant condensers and, in
The foregoing example is an take these variations into account. recent years, this has been extended to
oversimplification. In practice, the A recent trend in large multi-story apply to steam surface condensers for
steam rate of a turbine discharging at 4 office buildings has been to use 2 gpm air conditioning installations.
in. Hg. abs. is somewhat higher than per ton of refrigeration. Although this It has been common practice to limit
one discharging at 3 in. Hg. abs. affects condenser, and turbine water pressure drop to 10 ft. However,
Choice of a lower absolute pressure adversely due to higher condensing if this limitation is rigidly enforced,
might permit using a turbine with one temperatures, there is a saving in velocities must be reduced to comply
less wheel, which would result in condenser water piping. with this pressure drop requirement,
reduced turbine cost. This reduced Too often, specifications state that the resulting in lower heat transfer rates
turbine cost might or might not be surface condenser shall be capable of and higher condenser costs. Generally,
offset by the increased condenser handling turbine exhaust while water pressure drops of approximately
cost. (See "Is There a Steam Turbine in maintaining the desired vacuum with a 15 ft can be attained in most single-
Your Future," ACHV, April, 1968, pp 5% increase in normal steam load. pass condensers operating at 4 in. Hg
43-47.) Similarly, condenser cost could Compliance with this requirement is abs. Most two-pass condensers,
be reduced if the condenser were almost impossible. Specifications usually those running at 3 in. Hg abs.,
operated at 5 in. Hg. abs. (133.8F seldom provide the 5% greater water require pressure drops as high as 20-30
condensing). However, turbine cost quantity needed to balance this 5% ft.
might increase more rapidly if the loading factor. Further, usually no Specification of water velocity and
steam rate had to be held to a provision is made for the extra load on materials of construction for tubes and
previously set value, which, as the cooling tower and the change in tube sheets where river water or
indicated, is generally in the range of steam rate of the turbine when brackish water is involved must be
14-16 lb per hr per bhp. overload hand valves are used. carefully evaluated. Information
Thus, the specification should simply Furthermore, the refrigeration machine should be obtained on the experience
state the number of pounds per hour is operating at a different point on its of other users in the area having
of steam to be used and the maximum curve and may be rejecting more heat similar design conditions before a
temperature and quantity of available which, in turn, means hotter water to specific material is selected. Generally
cooling water, omitting the precise the steam condenser. The net result speaking, for brackish water
operating vacuum to be maintained by under the 5% excess load condition is applications, velocities in excess of 6.5
the surface condenser. This permits that the steam condenser receives fps can seriously reduce tube life, but
the manufacturer to offer the best cooling water that is more than 5% for cooling tower applications a 10 fps
combination of condenser, turbine and above the initial design temperature velocity is acceptable.
refrigeration unit to comply with the and the resulting excess heat imparted
limitations on steam consumption to the water overloads the cooling
Fouling Factor
specified. tower, further aggravating the
Most surface condensers for air
Other considerations, such as length situation.
conditioning and power plant
limitations and turbine vapor exhaust If it has been decided that the surface
applications are designed with a
size, very often have a determining condenser should have additional
cleanliness factor of 85%. This means
affect on condenser cost. surface in it, the most practical
that the heat transfer rate used in
approach would be to state that the
designing the condenser is 85% of the
Water Temperature unit shall have 5% excess surface or
clean heat transfer coefficient. For
As cooling water temperature 10% or whatever is needed. In general,
those installations where cooling water
determines the vacuum that can be a surface condenser will handle the
sources produce rapid fouling of
produced, it is imperative that the entire excess load at a slight increase
maximum anticipated water temperature in back pressure. If this is permissible
(and it must happen unless all
the tubes, a higher factor must be field for proper vapor velocities within leakage quantities based on various
used. This holds true for both the the shell. team quantities entering the
refrigerant condenser and the steam Calculation of condenser heat load is condenser. Specification that the
condenser. based on the fact that steam entering ejector shall be designed for the
For most applications using clean the condenser has a value of quantities of air leakage as designated
cooling tower water, refrigeration approximately 950 Btu per lb. More in HEI Standards is sufficient.
condensers should be specified with a precise calculations can be made if the
fouling factor of 0.0005 and steam specific turbine characteristics are Codes
surface condensers designed for an available, but this figure is sufficiently
85% clean tube coefficient. If the accurate for the sizing of the cooling Steam surface condensers operate
refrigerant fouling factor is increased, tower and condenser. under a vacuum and are, therefore, not
the surface condenser cleanliness considered pressure vessels. The
factor should be increased by the same Space Limitations ASME Code is a pressure vessel code
percentage. Thus, if the refrigerant and is not, strictly speaking, applicable
condenser is specified as 0.001 vs. Space considerations often influence to surface condensers operating under
0.0005, the corresponding cleanliness the cost of a condenser. For example, if a vacuum. However, the tube side of a
factor for the surface condenser is 70% the surface condenser is limited in tube surface condenser is considered a
clean vs. 85 % clean. length, a multipass design may be pressure vessel, as it is subjected to
required in place of a single-pass the full water pressure. When
Steam Inlet Velocity design. This results in a short, stubby necessary, this side of the condenser
unit, which is generally more expensive can be designed and constructed to
Velocity at the exhaust of the steam than a long, thin unit. ASME Code requirements. Most
turbine is limited by National Electrical Specifications of head room limitations surface condensers are designed and
Manufacturers Association to 450 fps. and permissible condenser tube length constructed in accordance with HEI
Should the exhaust line from turbine to should take into consideration the Standards. They can be built to ASME
condenser be long, there can be distance beyond the tube sheets of the Code requirements and so stamped by
excessive pressure drop in the vacuum condenser required to allow removing a qualified inspector. This type of
line, which means that pressure at the tubes for replacement. Condensers construction, which requires specific
condenser inlet is penalized by the must be mounted so that liquid level methods of welding, specially qualified
pressure drop between turbine and on the hotwell is sufficiently high to welders and keeping of material
condenser. Condenser manufacturers permit removal by condensate pumps. records with certified copies of these
usually guarantee to maintain the For air conditioning installations, the records to be supplied, results in a
specified vacuum at the inlet to the liquid level should be at least 5 ft more expensive surface condenser.
steam condenser. However, pressure above the inlet to the condensate However, if the unit is to be built to
drop between turbine exhaust and pump and preferably 1 or 2 ft higher. ASME Code requirements, it should be
steam condenser must be calculated This permits an economical pump stated that both the shell and tube
by the design engineer and selection. sides, or simply the tube side, shall be
compensated for by specifying that designed, constructed and stamped in
the condenser shall maintain a vacuum Air Leakage accordance with ASME Code and shall
slightly below the vacuum at the be accompanied by certifications
exhaust of the turbine. A specification As both the exhaust of the steam signed by a qualified insurance
that calls upon the supplier to supply a turbine and the condenser are inspector. Do not be mislead by the
specified steam consumption obviates operating under a substantial vacuum, statement, "Condenser is constructed
this problem. Where a given velocity is air is bound to leak into the system. in accordance with applicable ASME
used to determine the pressure drop, This leakage occurs through the gland Codes." It is common for some
this should be stated in the seals on the steam turbine and through manufacturers to indicate that, as
specification so that it is not exceeded. minute holes in the piping connections ASME is a pressure vessel code, it is
In any event, velocities in excess of associated with the surface condenser not applicable to vacuum condensers
450 fps should not be permitted. itself. Over a period of years, Heat and therefore their equipment complies
Impingement plates should be Exchange Institute has determined the with applicable ASME Codes.
provided below the condenser steam normal quantity of air that should leak
inlet to protect tubes from the effect of through properly designed turbines
locally high inlet velocities and and piping systems, and these are
impingement of condensate. Steam specified in their "Standards for
inlet velocities should not exceed 400 Surface Condensers." Manufacturers
fps and provision should be made have similarly standardized their
based upon design experience in this ejector sets so that several standard
sizes are available for specific air
Materials of Construction which are the only moving parts in a
surface condenser system should be
Materials used in construction of supplied in duplicate. Power plant
steam surface condensers are given in practice usually requires twin air
Table 1. ejector sets, one a standby, but for air
Use of copper alloy tube sheets in conditioning installations, a single set
steam surface condensers with the is sufficient.
accompanying requirement that tube
sheets be bolted to the shell by means Ejectors
of collar bolts, is a carryover from
marine practice. There is no reason For condensing pressures of 5 in. Hg
why a steel tube sheet cannot be used, abs. (25 in. of vacuum) and lower, a
in view of the fact that the refrigeration two-stage ejector system is
condenser just upstream of the steam recommended because, as the
condenser uses this type of condenser water temperature drops,
construction. When a steel tube sheet the two-stage ejector permits operating
is used, the specification should at reduced condenser pressure that, in
indicate that it may be welded to the turn, reduces overall steam
shell. consumption of the turbine. Also, as
these systems are designed on the
Specification Considerations basis of maximum summer
temperatures, a two-stage ejector
When tube alloys that differ from the provides operating economies during
standard admiralty material are used, those days when maximum water
ratings must conform to HEI temperature levels are not reached.
Standards. These standards reduce the It is important in specifying steam
heat transfer rate to conform with the ejectors that the minimum anticipated
characteristic performance of various steam pressure be stated. Allowance
alloys. Similarly, when tube gages should be made for pressure drop
must be increased above the normal 18 between the source of steam and the
BWG, heat transfer rates should be point at which steam enters the
corrected in accordance with HEI ejectors. If an ejector is designed for
Standards to compensate for increased 100 lb steam and lower pressure steam
tube wall resistance. is delivered, the ejector may not
function properly; if the pressure is It is therefore recommended that
It is not uncommon in power plant condensate be used as a cooling
practice to use a divided water box more than 10% below design level it
will fail to operate altogether. medium for the inter and
construction on surface condensers, aftercondensers, as condensate is
but this type of construction is Specifications should state that design
air leakage for the ejector system be in practically pure water and contains
unusual in air conditioning practice, as little or no solids. A typical schematic
air conditioning equipment is seldom accordance with HEI Standards. When
more than one turbine discharges into control diagram using condensate over
critical. However, where cooling water the inter and aftercondensers is shown
is particularly dirty, fouling of the a common condenser, the ejector must
be designed for 1 1/2 times the normal in Fig. 2.
tubes may be rapid and, under these Condensate from the intercondenser
circumstances, a divided water box air leakage for the total steam quantity.
For more than two turbines, other must be drained back to the hotwell, as
condenser might have some the intercondenser is under a vacuum.
advantage. correction factors are applicable.
The cooling medium for the inter and This can be done by means of a
Corrosive effects on water boxes condensate trap or, where headroom
should be compensated for by use of aftercondensers of the two-stage
ejector system can be cooling water permits, by means of a loop seal, which
alloy cladding, fiber glass reinforced must be at least 8 ft high. Condensate
polyester lining or similar procedure. from the cooling tower or condensate
from the hotwell of the surface from the aftercondenser can be drained
back to the hotwell through a trap or
Auxiliary Equipment condenser. As intercondenser
may simply be drained to an open
condensing temperature is about 145F
and aftercondenser condensing sight drain. The writer prefers the
Selection of auxiliary equipment to be second method
temperature is about 212F, fouling of
used in conjunction with the surface
the inter and aftercondensers will be
condenser can be very important.
more rapid than that of the main
Failure of the ejector set or condensate
condenser.
pump is critical to the operation of the
entire system. The condensate pumps,
possible. The greater the available overflow to drop into an open sight
NPSH, the easier job the pump has and drain. Thus, as long as there is an
because it eliminates the possibility of the less danger there is of cavitation. overflow, we know that the valve is
a malfunction of this trap, which could Condensate pumps are generally of the supplied with water.
bleed air back to the hotwell. horizontal close coupled type, 3450 rph
and with open drip-proof motors. Liquid Level Control
Pumps The method of control used depends
Condensate pumps for air conditioning Relief Valves upon whether or not condensate is
are customarily of the horizontal type, Surface condensers most commonly used as the cooling medium for the
designed for approximately 4 1/2 - 5 ft use atmospheric relief valves of the inter and aftercondensers of the
net positive suction head (NPSH) and water-sealed or O-ring type, although ejectors. When condensate is used as
total dynamic heads of from 80-150 ft. bursting discs are occasionally the cooling medium, a scheme such as
Actual NPSH available for these applied. Size and rating characteristics that shown in Fig. 2 should be used. If
pumps depends upon the physical for these valves are given in HEI condensate is simply dumped
location of the condenser. The Standards. In operation, a small overboard, then a simple mechanically
discharge head is affected by where amount of water is kept above the operated level control on the discharge
the condensate is pumped after it relief disc to prevent the inleakage air. of the condensate pump is sufficient.
leaves the condensate pump; that is, Water in the valve must be The arrangement shown in Fig. 2
to an open condensate tank or back to supplemented periodically, as a certain requires that all of the condensate be
the cooling tower, etc. The importance amount will evaporate. A sight glass is pumped over the inter and
of providing sufficient NPSH for provided, but because relief valves are aftercondensers before diverting a
proper operation of the condensate usually located at a considerable portion back to the hotwell, or
pumps cannot be overemphasized. The height and the sight glasses are overboard, depending upon load
condenser should be located frequently obscured by sediment, they conditions.
sufficiently high off the floor to put as are difficult to read. This author prefers
much head on the inlet of the to supply a small constant drip of
condensate pumps as is physically water to the valve, permitting the
Minimum Simplified Specification for
Steam Surface Condensers in
Air Conditioning Practice

Vacuum at inlet to steam condenser__________________ Cleanliness factor________________________________


Steam flow to condenser, lb per hr___________________ (85% clean for cooling tower applications)
Condenser water inlet temperature, F_________________ Waterbox design pressure__________________________
Condenser water gpm_____________________________ Water test pressure________________________________
Permissible condenser water pressure drop, ft__________ (1.5 times design pressure except for cast iron
Number of water passes___________________________ which is 5 Lb above design pressure)___________
(Single-pass for 26 in. of vacuum and two-pass Shell side design pressure ___________________________
for .27 in. Should be left up to supplier) . (Full vacuum test to 20 Lb)
Maximum water velocity, fps_______________________ Steam pressure and temperature at ejector inlet___________
10 fps for cooling tower applications) Condensate pump capacity, gpm ______________________
Tube diameter and gage___________________________ Condensate pump net positive suction head______________
(3/4 in. X 18 BWG) Condensate pump discharge
head______________________
(Add pressure drop through inter- and
aftercondensers and overboard valve to total
system loss.)
Electrical characteristics of pump motors ________________

1. The steam condenser shall be of the shell and tube type, single or multipass, designed and constructed in accordance with
Heat Exchange Institute (HEI) Standards, except as noted herein, and shall be suitable for the design conditions noted above.
Condenser manufacturer shall demonstrate successful installations of similar equipment that has been in operation for at
least__________(5 or 10) years.

2. Condenser shall have cast iron or steel waterboxes, steel tube sheets, steel tube supports, admiralty tubes and a steel hotwell
complete with screen, strainer and hand-hole clean-out. Hotwell shall be of the vertical tank type, suitable for one-minute
storage capacity.

3. Provision for tube expansion shall be made either by means of bowed tubes or shell side expansion joint. Covers of the
waterboxes shall be removable without disturbing water piping. Connections shall be provided in the hotwell for ejector drain,
condensate outlet, liquid level control bypass, fresh water startup, gage glass and high level water alarm. Connections shall also
be supplied in the condenser shell for pump vent, vacuum gage, pressure gages to be located on waterboxes, an atmospheric
relief valve and steam inlet from the turbine drive. Waterboxes shall be supplied with a plugged vent and drain and shall have
flanged water connections. All vapor side flanges shall be 125 lb FF. Water side flanges shall be______________ lb (raised or
flat face, depending upon pressure).

4. A single-element, two-stage ejector assembly, complete with internal interconnecting water and steam piping with surface
inter- and after-condenser shall be provided. Ejector shall be cast iron. Ejector motive steam nozzles shall be stainless steel. The
two-stage ejector shall be a self-contained package, complete with steam valves, interconnecting steam piping, steam strainer
and interconnecting vapor piping, and shall be provided with mounting bracket so that ejector can be mounted directly on the
surface condenser.

5. Condensate pumps shall be supplied in accordance with design conditions and shall be close coupled, single suction,
enclosed impeller type with cast iron casings, bronze or cast iron impellers, stainless steel shafts, shaft seals suitable for the
service, grease lubricated bearings and open drip-proof motors. Pump motor starters will be provided by others. Electrical
characteristics will be as specified under _____________herein.

6. A hotwell gage glass shall be provided.

7. A steam inlet expansion joint shall be provided, sized to conform with the diameter of the turbine exhaust with corrugations.
Expansion joint shall have copper or stainless steel bellows and shall be provided with a liner if steam velocity exceeds 300 fps.

8. An atmospheric relief valve shall be furnished, sized for protection in accordance with HEI Standards.
head beyond the overboard control
valve. Expansion Joint
Gages and Thermometers A single or multi-corrugation
A combination pressure and expansion joint should be placed
vacuum gage of the dial type should between the exhaust of the turbine
be supplied to give a rough and the inlet to the surface
indication of condenser vacuum. condenser. These expansion joints
Exact vacuum can be properly usually have copper or stainless
determined only by use of a mercury steel bellows and a steel flange.
manometer, which can be specified. However, as the cost of copper
Pressure gages should be installed increases, stainless steel joints are
on the inlet and outlet water boxes. replacing them. The number of
It is also common practice to install corrugations is determined by the
pressure gages at the condensate amount of expansion that must be
pump discharge, as well as at the accommodated by the joint and
inlet to the condensate pump, so the should be determined by the
When condensate quantity exceeds
operating engineer can easily check engineer prior to completing the
that required by the inter and
the performance of pump and specification. When the number of
aftercondensers, a suitable bypass
condenser. In addition, corrugations is not stated, a single-
should be supplied.
thermometers should be placed so corrugation joint is supplied, which
Selection of air-operated level
that inlet and outlet water may or may not be sufficient for the
control valves is dependent upon
temperatures, as well as temperature job.
information supplied by the
of the condensate in the hotwell of When steam velocities through the
consulting engineer; namely, the
the surface condenser, may be read. expansion joint exceed 300 fps, it is
discharge head beyond the
Air Leakage Meter advisable to install a stainless steel
overboard level control valve and
Most operating engineers of air liner to prevent noise and excess
the total dynamic head the pump
conditioning installations judge vibration of the joint.
must develop. Specifications should
excessive air leakage by the amount It is possible to obtain reduced
indicate whether the total dynamic
of steam and droplets of condensate steam consumption simply by
head stated for the pump has taken
issuing from the aftercondenser designing the surface condenser for
into account the condensate
vent. However, an air leakage meter a higher vacuum. Relative costs of
pressure drop through the inter and
placed on the vent of the condensers designed for 26 and 27
aftercondensers and the overboard
aftercondenser is more reliable and, in. of vacuum are given in Fig. 3.
valve. Generally, pressure drop
as it represents an investment of
through the inter and
approximately $150, is well worth the
aftercondensers is less than 15 ft
expense.
and that on the overboard valve is
10-30% of the available discharge

You might also like