POWER [Pump DS Values required]

Input
Fluid flow rate, Q = 849 gpm
Rated Total Diff. Head, TDH = 132.5 f
Specific gravity of the fluid, sg = 1
Calculate
Fuid power, P = Q*H*sg / 3960
= 28.4 hp [Hydraulic (Water) HP @ 100% Eff]

Pump shaft power, Ps = Hydraulic power, hp / Pump efficiency ηpump


Input
Hydraulic power, hp = 28.4 hp
Pump efficiency, ηpump = 78.0 %
Calculate
Pump shaft power, Ps = 36.42 hp

Motor power, Pm = Pump shaft power, Ps / Motor efficiency, ηm


Input
Pump shaf power, Ps = 36.42 hp
Motor efficiency, ηm = 89.5 %
Calculate
40.69 hp

Motor Synchronous speed = 2*60*f/p


Input
Supply frequency, f = 60 Hz
Number of poles, P = 4
Motor Synchronous speed , Ms = Calculate
1800 RPM