Professional Documents
Culture Documents
net/publication/280625386
Blast Buildings
CITATIONS READS
0 517
1 author:
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Morteza Asgharpour Hassan Kiadeh on 03 August 2015.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
Table of Content
I. Overview ..................................................................................................................... 2
II. Definitions .................................................................................................................... 2
III. Chapter 1: Blast Buildings ............................................................................................ 3
1. Purpose ....................................................................................................................... 3
2. Concepts ..................................................................................................................... 3
2.1 Objectives of hazard analysis ........................................................................................... 3
2.2 Hazard area ................................................................................................................... 3
3. Blast resistance structure (Explosion and fire) ...................................................................... 4
3.1 ARE .............................................................................................................................. 4
3.2 BSE .............................................................................................................................. 7
3.3 BMS .............................................................................................................................. 7
3.4 BEE .............................................................................................................................. 9
4. Toxic Material ............................................................................................................. 10
4.1 ARE ............................................................................................................................ 10
4.2 BMS ............................................................................................................................ 10
IV. Chapter 2: Bunkers and Safe rooms ............................................................................. 11
1. Purpose ..................................................................................................................... 11
2. Concepts ................................................................................................................... 11
3. Bunker ...................................................................................................................... 11
3.1 ARE ............................................................................................................................ 11
3.2 BSE ............................................................................................................................ 15
3.3 BMS ............................................................................................................................ 15
3.4 BEE ............................................................................................................................ 18
4. Safe Room ................................................................................................................. 20
4.1 ARE ............................................................................................................................ 20
4.2 BSE ............................................................................................................................ 21
4.3 BMS ............................................................................................................................ 21
4.4 BEE ............................................................................................................................ 21
V. Reference ............................................................................................................... 22
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
I. Overview
This document is collection and combination of existence data and information including related
standards of different countries, related books, experience of others and us.
Following diagram is a help for following this specification's subjects
Chapter 1 Chapter 2
Blast Buildings Bunkers and
(Above ground) safe room
Explosion/ Fire/Toxic
II.Definitions
• Building
A rigid, enclosed structure (As API 752 Definition)
• Shall and should
The word "Shall" is to be understood as mandatory and the word "Should" as
strongly recommended complying with the requirements.
• ARE
Architectural Part
• BSE
Structural Part
• BMS
Mechanical Part
• BEE
Electrical Part
• Donor System
Amount, type and location of the potentially detonating explosive
• Acceptor System
Personnel, equipment, or explosives that require protection
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
2. Concepts
The chosen concept of this charter is defined based on combination of regular standards
of oil and gas companies also Sazeh Company specially API and ASCE.
The primary objectives for providing blast resistant design for buildings are:
A building is occupied if
• Occupied >400 hours per week,
• Peak occupancy > 40 persons for one hour,
• Must be occupied during incident for safe shutdown of the facility,
• Designated as an emergency response shelter;
Building which is objective of hazard analysis (in each above category) will be checked by
API 752 in three (3) primary hazard scenarios of explosion, fire and toxic material release.
If the analysis results clarify that the building is in hazard area this document is available 1.
a) Explosion: Vapor cloud explosions are typically the dominant explosion scenario for refineries and
petrochemical plants.
For example, the Free Field Overpressure commonly referred to the blast intensity and the blast
duration, are blast characteristics that are provided by the sitting analysis and determine the
structural design and integrity of a particular building system.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
The best solution is relocated buildings in a unified zone and substituted the zone out of
VCE.
1.3. ARE
1.1.1. Doors
♦ External doors shall be blast resistant.
♦ Blast "doors need to be designed for the required blast load (for more see clause
3.2.9).
b) Fire: Fire hazards are potential threats either in or of themselves through the inherent flammable
and combustible products in refineries and petrochemical plants, or as a result of an explosion.
Fires in process areas can be pool fires, jet fires, flash fires, or fireballs and modeling is typically
used to predict the effects and duration. So engineering Team will be given design parameters
such as a 1, 2 or 3-Hour fire wall and/or ceiling requirement.
For example, when designing for specific thermal protection, architects could specify wall/ ceiling/
flooring materials with low heat transfer properties. For moderate to extreme temperatures
varying thicknesses of mineral wool insulation are used to provide a high resistance to a heat
transfer flux such as experienced in many fire related scenarios. In extreme conditions, an
intumescing coating can be applied to the exterior of a building.
c) Toxic material release: When mitigating potential flammable vapors involves the ingress of
flammable vapor concentrations into the building which can then ignite with the occupants inside
For example, NFPA 496 addresses this concern and allows for internal building pressurization to
eliminate infiltration into the building. HVAC systems should be designed to protect the building in
hazard situation.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
1.1.2. Windows
♦ Windows should be considered for manned part of building. These windows shall
be Blast resistance and support blast load required for building.
♦ Windows shall be remaining gastight to protect entrancing gas, fire, smoke and
heat after explosion.
♦ Normal glass with a minimum thickness of 3 mm could be used for internal
windows, since the overpressure inside the building without outer windows or with
only a few small windows will be low enough during an explosion to prevent
fragmented glass flying (Shell company, 1990, p19).
1.1.3. Accessibility & Location
♦ Using posts, bollards or any elements in buildings site shall not blocked emergency
vehicle access.
♦ The distance between control building and equipment containing flammable
substance shall be at least 15m. Depending on size, pressure and contents of this
equipment, the minimum distance can be up to 30m (Shell company, 1990, p7).
1.1.4. Building form
♦ Orient buildings horizontally rather than vertically to reduce the building's profile
and exposure (FEMA 426, 2003, p3-3).
♦ The shape of building shall be rectangular, with no protruding canopies, etc., no
equipment on the roof except for the air intake and exhaust facilities (Shell company,
1990, p14). Air-cooled condensers shall be located next to the building at grade and
not on top of the roof (Shell company, 1990, p24).
♦ Items such as re-entrance corners and set back doors can experience loadings
that are considerably higher than the peak reflected overpressures and should be
avoided(ASCE, 2010, p134).
♦ The building design should not contribute to the likelihood of flying debris.
Canopies and vestibules should be avoided since they frequently become
dislodged and could block. (ASCE, 2010, p134).
♦ The overall height of building and the flat span of the roof of that building shall be
to a minimum to limit the effects of an explosion (Shell company, 1990, p14).
1.1.5. Plan
♦ Building should be as compact of possible (Shell company, 1990, p 8).
♦ Eliminate hiding places within the building (FEMA 426, 2003,p3-6).
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
1.1.6. Finishing
♦ Blast waves may have internal effects on non-structural partitions that can cause
substantial injury if failure occurs. These shall be designed and installed to
resistance about the effects.
♦ Suspended ceiling components particularly are susceptible to being dislodged
during the blast. Ceiling lighting fixtures, diffusers, etc should be supported
independently of the suspended ceiling (ASCE, 2010, p133).
♦ There should not be installed any heavy suspended mechanical units in suspended
ceiling provided that structural requirements have been considered.
♦ The roof shall be well insulated, but shall not be covered with gravel or loose
concrete tiles as these will fly in the event of an explosion (Shell company, 1990,
p14).
♦ External finishing on walls increases their vulnerability in explosion Exposed
concrete is the best finishing. Cement rendering is better than bricks façade
(17ﺹ،1391،) ﺩﻓﺗﺭ ﻣﻘﺭﺭﺍﺕ ﻣﻠﯽ ﺳﺎﺧﺗﻣﺎﻥ.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
1.4. BSE
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
1.1.18. Doors
Doors in external blast resistant walls shall be kept to a minimum. They shall be
fabricated from mild steel and shall open outwards and butt on all four edges against
steel frames cast into the concrete. According to ASCE, external doors for main
personnel access shall conform to Category I. External doors for others (e.g. equipment
access) doors shall conform to Category II. Mid-Range level of blast pressure shall be
considered for both categorizes.
1.1.19. Blast Load
Blast resistant buildings will be designed to withstand a high pressure-short duration
external explosion which generates peak side-on overpressure of 69 kPa with duration
of 20 milliseconds. This is roughly equivalent to the overpressure created by a free-air
explosion of one US ton of TNT at 30 m with a margin of safety of 2.5 against collapse
considering moderate structural damage. Moreover, the structure shall withstand low
pressure-long duration side-on over pressure of 21 kPa with duration of 100
milliseconds, too. The intent is that personnel are kept safe and facilities remain
operable in such an event.
Where:
K 0 = coefficient of lateral earth pressure at rest
Where:
C r = Reflected Coefficient
The reflected coefficient depends on the peak overpressure and the angle of incidence.
For angle of incidence equal to 0°, C r is calculated as follow:
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
1.5. BMS
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
There are four basic strategies for protecting a building and its occupants from CBR
attack:
1) Physical security. This strategy involves measures that limit or prevent access to a
building or deter potential attackers. This includes the application of physical
barriers, surveillance, and access-control procedures as preventive measures.
2) Air purification. This strategy involves high-efficiency filtration, neutralization, or
disinfection of the air in or entering the building. It typically involves mechanical
filtration of aerosols and adsorption of chemical vapors/gases, but it may also
involve the use of ultraviolet light or other non-mechanical air purification, mainly
for biological agents.
3) Unventilated sheltering. This strategy, commonly referred to as sheltering in place,
involves temporarily reducing the air-exchange rate of the building or safe room,
before contaminated air reaches it, and increasing the air-exchange rate after the
hazardous condition passes.
4) Individual protection. This strategy involves building occupants' use of individual
protection equipment, primarily respirators capable of filtering aerosols, vapors,
and gases at very high efficiency.
Each of these strategies has limitations; that is, none is comprehensive in its
effectiveness. For this reason, achieving complete protection requires a combination
of strategies and involves several protective measures- architectural, mechanical,
electrical, and operational-to reduce the vulnerability of a building and its occupants
to airborne hazards. These measures vary in cost as well as effectiveness.
Each strategy involves a combination of two or more protective measures. For
example, unventilated sheltering in an office building is most effective when
combined with the use of a single-switch HVAC system control, to quickly deactivate
all fans in the building, and a public address system, to move people into a
protective posture rapidly. Employed against a potential terrorist attack, sheltering
also requires external surveillance, a detection system, or a community warning sys-
tem. On the other hand, the full effectiveness of air purification can be achieved only
when the building or the spaces selected for protection are pressurized.
Pressurization is most economically achieved by tightening the building envelope
with sealing measures during construction.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
• Buildings should be avoided as little as possible from the use of high leakage
risk or refrigeration systems with direct coil. If the system likely to high leakage
risk or refrigeration systems with direct coil to be applied, the refrigerant gas
should be driven out, through drain valves, when the risk is high.
• Plumbing and ducting in the HVAC systems should be equipped with
expansion components and flexible joints in the equipment installation place
and also interface between the pipe and duct with walls to reduce the damages
of explosion.
• Supports and braces should not be completely rigid to have some flexibility.
• HVAC room should be built in safe place to continue activity after damage
building.
• Pumps and water tanks should be installed horizontal in the HVAC room to
prevention of reversal against the explosion.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
• Natural gas usage throughout the building should be reviewed to enable the
gas supply to be maintained throughout the period it is used.
Automatic emergency shut-off valves triggered by excessive flow rates
should be installed at the bottom of vertical risers.
Where leaks or damage can occur vents should be installed to prevent the
gas concentration from reaching its lower explosive limit.
Current building codes require that natural gas utility piping exit the ground
prior to entering a building, which allows venting of underground leaks to
the atmosphere and protects the building from leakage that can cause
e x p l o s i o n .
If, during sheltering, the temperature at the location of the equipment or supplies is
0°C or above, the equipment or supplies shall function properly at a temperature of
between 0°C and +40°C.
1.1.24. Doors, hatches, shut-off devices, wall sleeves and the air intake duct of the civil
defense shelter
1.1.1.6. General
1) The equipment for closing the doors, the hatches and the gastight shut-off devices
shall be equipped with markings showing the ‘open' and ‘closed' positions. If
necessary, they shall be equipped with sensors indicating the ‘open' and ‘closed'
positions. The closing time of the doors, the hatches and the gastight shut-off devices
may not be more than 1 minute.
2) It shall also be possible to disassemble the parts keeping the door and hatch in place
from inside the shelter with manual tools when the door or hatch has been
permanently deformed.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
1.1.25. Pressure, Safety, Supply Air and Exhaust Air Valves, Sewer Shut-off Valves and
Overpressure Meters
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
4) The characteristic curve of the relief valve shall be continuously rising. The combined
flow resistance of the valve and a 300-mm-long straight wall sleeve duct may not
exceed 95 Pa when the air flow is 54dm3/s. When the air flow is 65dm3/s, the flow
resistance may not exceed 115 Pa. When the air flow corresponding to the rising part
of the characteristic curve is at most 70dm3/s, the effect of the hysteresis phenomenon
may not exceed 20dm3/s.
5) It shall be possible to attach the relief valve to the flange of a wall sleeve duct with a
nominal size of 160mm the measurements of which are given in Table 8 of Appendix
3. The protrusion of the relief valve from the wall surface may not be more than 150
mm and its horizontal protrusion may not be more than 130mm from the centre line of
the wall sleeve duct.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
1.6. BEE
This specification is especially for electrical design in blast buildings. So the other
requirements shall be considered based on general standard.
1.1.30. General
• Two separate lighting systems shall be supplied, one normal lighting system and
one essential lighting system. As a minimum, 30% of the lighting shall be
essential, fed from the emergency generators.
Vital lighting fixture shall be provided over all exit doors and in corridors to
indicate direction of exits. In addition to ‘exit' lights, 10% of (minimum one)
indoor lighting shall be vital lighting.
Vital lighting shall normally be supplied from the emergency distribution board
system.
• All panels shall be protected by minimum over current and over voltage relays.
1.1.33. Fire Alarm
• The alarms and actions generated by the activation of each detector shall be
detailed in Fire and Gas Causes and Effects Charts during design stage of the
project.
• Fire resistant cable shall be used between fire alarm panel and
detectors/sounder/manual call point.
1.1.34. Public Address and General Alarm System
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
• Telephone system shall be designed for calling in case of normal and emergency
time.
• Sufficient space shall remain for outgoing cable trench/tray. Cable entries to
building shall be sealed with compound which shall maintain the floor/wall fire
ratings.
• Transit cable route shall be suitably sealed when passing through fire wall.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
4. Purpose
This chapter is prepared to use as a handbook for designer of bunkers and safe rooms
which usually are used in military attacks.
5. Concepts
Bunkers or self shelter is utilized for keeping persons safe during hazardous conditions.
Numerous forms of bunkers are used specially during the wars. Different items are used for
categorizing these buildings like:
• Type of threats (bombs, biological and chemical, Radon),
• Protection level,
• Capacity,
• Length of stay.
In process plants the bunkers could be used in non-industrial zone where the personnel of
the site are convened. Due to non-industrial buildings zone is out of hazardous area of
plant (if not the occupant buildings should be designed as safe shelter and there is no need
for separated bunker), these buildings are designed for armory attack.
Considering mentioned functional concerns, two forms of bunker will be specified to give
details in this specification:
• Threats are armory attacks of explosive tools and chemical threats(specially chemical
pollution arising from plant material),
• High level of protection with slight loss of building and peoples,
• The maximum capacity of bunker considers as 150 persons,
• The length of stay considers as maximum 24 hours.
6. Bunker
Bunker is separated building to save people from defined hazardous situations with
defined level of protection. In this specification bunker is considered as underground
building.
1.7. ARE
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
Location
• The building should be located far from dangerous source like chemical
storage or gas stations.
• Access way should not be blocked by other buildings' debris after bursting
event.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
Toilets: 1 toilet per each 25 men and Min. 1 toilet for women should be considered,
U U
Normal toilets are preferred but dry toilets could be considered too,
1 square meters is needed for each dry toilet area,
They usually are located near entrance and air exit channel.
Storage requirement
U
• Waste container
• Tank of water
• Drawer for flashlights, radio, gas masks
• Storage of food for 24 hours
Others
U
the bunker.
• Control room:
It should be checked by related expert but for preliminary design about 7
Square meters should be considered for installation related equipment for
controlling and checking outside condition.
• Mechanical room:
It should be checked by related expert but for preliminary design 2 square
meters for ventilation equipment and 1.5 for filters should be considered.
• For resting of people some beds could be considered in the rooms. Folded
beds could be installed to use as chairs in normal situations.
• Sharp edges should be avoided.
• Hanging facilities like chandelier should be avoided. The others should be
fixed or designed to tolerate the blast wave's vibration.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
• Virtual windows could be used to calm and improve the interior environment.
Some examples of bunkers in different countries:
• Swiss - for 123 people with area of 140 square meter
(316 ﺹ،1390 ،)ﻫﺎﺷﻣﯽ
• United state- for 100 people with area of 160 square meter
(336 ﺹ،1390 ،)ﻫﺎﺷﻣﯽ
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
1.8. BSE
• Shallow-buried structures
• Surface-flush structures
For purpose of defining loads, shallow-buried structures have a depth of buried (DOB)
over the roof or crown, such that:
In which:
L=the clear span between supporting walls of a roof slab or the horizontal
diameter of an arch or cylindrical structure.
A large surface explosion can result in the formation of a crater that can extend deep
into the ground and cause substantial damage to the portion of the roof and exterior
walls of a buried structure within the crater.
UFC 3-340 suggest using a "Burster Slab" with minimum thickness of 1400mm, to
prevent a weapon from penetrating through the soil and detonating adjacent to the
structure (See Figure 3-1).
In case of using, the burster slab must extend far enough beyond the edge of the
building to form at least a 45 degree angle with the bottom edge of the building. It may
have to be extended further, though, if it is possible for a bomb to penetrate at a very
shallow angle, travel beneath the burster slab and detonate adjacent to the structure
(See Figure 3-1).
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
Figure 3-1: Depth of buried over the roof with burster slab
Sand is used as backfill because materials with high volume of air-filled voids and low
relative densities are poor transmitters of ground shock. In addition, sand resists
penetration better than soil.
This burster slab is not mandatory, but if it is not used the structure will have to be
buried much deeper.
1.1.38. Bunker Configuration
Rectangular, arch and cylindrical structures are used for underground bunkers.
1.1.39. Design Load
Bunkers shall be design to resist the effects of an attack with conventional weapons.
The magnitude of the ground surface overpressure (P SO ) is affected by:
− The size of the explosive charge (the weight of TNT charge in the bomb, W) and
its distance from the structure (r)
− The mechanical properties of the soil, rock, and/or concrete between the
detonation point and the structure
− The depth of penetration at the time of detonation
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
In which:
a: factor relating the length of a structure to its span length
b: factor relating depth of burial to span length
Underground structures are subject to significant lateral soil pressures and possibly
hydrostatic pressures if these are partially or fully submerged in ground water.
It should be noted that some part of the soil overburden will influence the period of
structure. For design purposes it is assumed that the mass of soil overburden that is
directly over the arch but has a thickness no longer greater than the radius of the arch
influences the period.
1.1.40. Types of Construction
Reinforced concrete shall be considered as construction material for underground
bunkers.
1.1.41. Material
According to chapter 1, clause 3.2.2.
1.1.42. Doors
All the exit doors shall conform to Category I of ASCE. High-Range level of blast
pressure shall be considered for this category.
1.9. BMS
• For heating, cooling and hot water system in the shelters, electric-type
recommended.
• Each shelter should be equipped with emergency power for lighting, air change,
heating, cooling and hot water.
• Gas lines should not be use in the shelters.
• Safe shelter should be pressurized to prevent possible contamination.
• The equipments of HVAC should be withstood against of weapons such as
pressure, shock wave, vibration and debris.
• Smoke, dust should not penetrate into the shelter.
• In case of power failure, Fresh air / ventilation equipment should be worked with
manpower.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
1.10. BEE
This specification is especially for electrical design in blast buildings. So the other
requirements shall be considered based on general standard.
1.1.43. General
• A reliable lighting system will help calm shelter occupants during a disaster.
Failing to provide proper illumination in a shelter may make it difficult for shelter
owners/operators to minimize the agitation and stress of the shelter occupants
during the event.
• All lighting fixtures in bunker rooms, escape route shall be supplied from battery
backup system.
• Vital lighting shall be supplied by individual UPS system installed inside building
and designed for min 8 hour without supplying normal power
• The alarms and actions generated by the activation of each detector shall be
detailed in Fire and Gas Causes and Effects Charts during design stage of the
project.
• Fire resistant cable shall be used between fire alarm panel and
detectors/sounder/manual call point.
1.1.47. Public Address and General Alarm System
• A public address system was installed in the building so that voice messages
could be broadcast throughout the building to notify people at any location of an
emergency
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
• If possible, generator shall be installed inside building and located in safe area
with separated space inaccessible to public.
• Fire and gas detection devices shall be installed throughout the plant to detect
hazardous Conditions resulting from gas leakage or fire and to initiate
appropriate alarms and actions.
• The alarms and actions generated by the activation of each detector shall be
detailed in Fire and Gas Causes and Effects Charts during the detailed design
stage of the project
• Toxic gas detector shall be installed at air intakes to building and fresh Air Inlets
of all HVAC building When detector active by toxic gas detector,
8.8.8. Emergency system
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
• Consideration of generator with sufficient fuel inside building for duration of used
bunker is essential.
• Backup power source for lighting is essential during a disaster because the main
power source is often disrupted.
• If the backup power supply system for the lighting system is not contained within
the building, it should be protected with a structure designed to the same criteria
as the shelter itself
7. Safe Room
Whether the independent bunker is not propounded in project planning, safe room could
be used in main buildings. Safe room is a room in a building which is equipped to be
used as a bunker in hazardous situations.
Following requirements are requested for this room although other related requirements
of bunker (mentioned above) should be met too.
1.11. ARE
• The room which will be chosen as safe room should be analyzed for
♦ If internal access ways are the shortest to access for all residents,
♦ If it could have independent structure,
♦ If its location is proper by service areas,
♦ If Minimum needed area could be supported by the room.
Conference rooms in basement and underground floors are two best choices in this
regard.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
1.12. BSE
1.13. BMS
A CBR safe room protects its occupants from contaminated air outside it by providing
clean, breathable air in two ways:
a) Unventilated Safe Room
By trapping air inside the room and minimizing the air exchange.
Unventilated safe rooms that are tightly sealed cannot be occupied for long periods
without the risk of high carbon dioxide levels.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
In an unventilated Class 2 Safe Room, air is drawn from inside the safe room, filtered,
and discharged inside it.
In a ventilated Class 2 Safe Room, air is drawn from outside but at a flow rate too
small to create a measurable differential pressure.
Class 1 Safe Room
The Class 1 Safe Room, which involves a more complex application of a filter unit,
In a Class 1 Safe Room, air is drawn from outside the room, filtered, and discharged
inside the room at a rate sufficient to produce an internal pressure. The safe room is
thus ventilated with filtered air, eliminating the constraints related to carbon dioxide
accumulation. The internal pressure produced with filtered air prevents infiltration of
outside air through leakage paths.
Table 3-1: Comparison of the Three General Classes of Toxic-agent Safe Rooms
Class 1
Protection has no time limits, but it provides no
Ventilated and High High protection against some toxic chemicals of high
pressurized with vapor pressure.
filtered air
Class 2
Unventilated Class 2 is protective against all gases,
Filtration with little Medium Medium but protection diminishes with duration of exposure
or no (And against non-filterable gases).
pressurization
To protect against the many gases, vapors, and aerosols that could be released in an
accident or terrorist act requires three different filtering processes.
• Mechanical filtration is most commonly used for aerosols;
• Physical adsorption, for chemical agents of low vapor pressure;
• Chemisorptions, for chemical agents of high vapor pressure.
These three processes can be provided by a combination of two types of filters: the
HEPA filter to remove aerosols and a high-efficiency gas absorber with impregnated
carbon to remove vapors and gases. A filter system for a safe room must contain at least
one HEPA and one gas absorber in series, with the HEPA normally placed first in the
flow stream.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
HEPA adequately removes all toxic aerosols, including sub-micron size biological
agents. A gas absorber works for most, but not all gases/vapors. Several of the common
industrial gases, such as ammonia, are not removed by the best broad-spectrum
impregnated carbon available.
To protect against highly toxic chemicals, a Class 1 system requires ultra high-efficiency
filtration, at least 99.999 percent removal in a single pass. HEPA filters, which are
defined as having at least 99.97 percent efficiency against the most penetrating particle
size (about 0.3 micron), have efficiencies greater than 99.999 percent against aerosols
of 1- to 10-micron size, the most likely size range for biological-agent aerosols.
With a filtration system drawing outside air, the level of protection the safe room provides
is a function of the filter efficiency.
With an unventilated Class 2 system, the level of protection is not affected as greatly by
changes in filter efficiency. For example, increasing filter efficiency from 99 percent to
99.999 percent in an unventilated Class 2 system improves the protection factor by
about 1 percent. The same change in a Class 1 system yields a protection factor 1,000
times higher.
1.1.9. Safe Room Criteria
1) HVAC System
The safe room must be isolated or capable of being isolated quickly from the HVAC
system of the building.
If the selected room is served by supply and return ducts, modifications or
preparations must include a means of temporarily closing the ducts to the safe room.
In the simplest form, this involves placing duct tape or contact paper over the supply,
return, and exhaust grilles and turning off fans and air handling units. If there is a
window-type or through-the-wall air conditioner in the selected room, plastic sheeting
and tape must be available to place over the inside of the window and/or air
conditioner, which must be turned off when sheltering in the safe room.
1) Ventilation
For Class 1 Safe Rooms, 15cfm per person is the desired ventilation rate; however,
the minimum ventilation rate is 5cfm per person if that rate is adequate for
pressurization. Class 3 and unventilated Class 2 Safe Rooms are suitable only for
short-duration use, not only because the low Ventilation rate when occupied can
cause carbon dioxide levels to rise, but also because protection diminishes as the
time of exposure to the hazard increases.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
safe room can be used in a toxic-materials emergency unless the HVAC system for
the safe room is designed to safely operate in the protective mode (as described
below).
• Supply and return ducts
• Exhaust fan
• Door louvers
• Window-type air conditioner or unit ventilator
• Door undercut
It is neither practical nor advisable to seal these openings beforehand if the room is
one that has normal day-to-day use, in which case plans and preparations should be
made for sealing them temporarily during rapid transition to the protective mode. The
sealing capability can be either permanent or expedient.
1.1.10. Design and Installation of a Toxic agent Safe Room
Design details for the three classes of safe rooms are presented below.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
through the safe room boundary wall is for a conduit for refrigerant tubing, suction
tubing, condensate drain, and power cable.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
• The adsorber must have at least 1 pound of activated carbon for each 20cfm of
flow rate. For example, a 200-cfm unit requires at least 10 pounds of carbon
adsorbent.
• The particulate filter must have an efficiency of at least 99 percent against 1-micron
particles.
• The unit(s) must provide a total clean-air delivery rate of at least 1 cfm per square
foot of floor area.
• The adsorber must have the capability for chemisorptions (i.e., for removal of
gases that are not removed by physical adsorption).
There are also ventilated Class 2 Safe Rooms and essentially these are ones for
which the filter unit has inadequate capacity to produce a measurable overpressure
with the size of the selected safe room.
Generally, if a filter unit capacity in cfm is less than one-fourth the area (in square
feet) of the selected safe room, depending on the type of construction, it will not
produce a measurable overpressure.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
• Bypass at the seals between the adsorber and its housing must not exceed 0.1
percent.
• For installation of the filter unit outside the safe room, the fan must be upstream of
the filters (blow-through configuration).For installation inside with a duct from the
wall to the filter unit; the fan must be downstream of the filters (draw-through
configuration).
• If a flexible duct is used outside the shelter to convey air from the filter unit to the
safe room, it must be made of a material resistant to the penetration of toxic
chemicals.
• If chemical manufacturing and storage facilities in the community present a special
risk for release of toxic materials, special sorbents or sorbent layers may be
required. In some cases, the chemicals produced/stored may not be filterable with
a broad-spectrum impregnated carbon. For example, a nearby ammonia plant
requires a special absorber for protection against ammonia.
Very tight: 26 -inch thick concrete walls and roof with no windows 0.04
Tight: 12 -inch thick concrete or block walls and roof with tight
0.20
windows and multiple, sealed penetrations
Typical: 12 -inch thick concrete or block walls with gypsum wall
board ceilings or composition roof and multiple, sealed 0.50
penetrations
Loose: Wood-frame construction without special sealing measures 1.00
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
Control System
An interlocking system should be considered for closing automatic dampers turning
off air-handling units, exhaust fans, and ventilation fans serving the building's
unprotected spaces while the safe room is in the protective mode. This increases the
level of protection the safe room provides against an outdoor release of agent.
Pressure Gauge
For Class 1 Safe Rooms, the pressure gauge is the indicator that the system is
operating properly. This gauge displays the pressure in the safe room relative to
outdoors or outside the safe room indoors. If the reference pressure is measured
indoors, the readings can be subject to variations caused by fan pressures unless
other building heating, ventilation, and air conditioning (HVAC) fans are turned off
when the safe room is in use. Reading the reference pressure outdoors can be
subject to positive and negative variations caused by air flows over and around the
building. If the pressure sensor is outdoors, it should be shielded from the wind.
Indoors is the best location if the building HVAC fans are turned off when the safe
room is in use.
1.1.11. Operations and Maintenance
For a shelter to be successful, it is critical to have an understanding and dedication to
operations and maintenance. Depending on the shelter type, specific operations
instructions and` maintenance are needed.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
Status Indicators
For safe rooms that require multiple automatic dampers to isolate the safe room
from the HVAC ducts in the protective mode, status lights and/or visual indicators
should be used to show the position of each damper. Indicators can also be used
to show door position, if there are multiple boundary doors in the safe room. Each
status light should be marked with a reference number corresponding to a diagram
so an operator can easily determine the location of any damper/door and conduct
troubleshooting if problems occur. The indicator lights should have push-to-test
capability for the light bulbs of the status lights.
Public-Address System
For safe rooms in large buildings, a public address system is the most efficient
means of instructing building occupants to proceed to a safe room in an
emergency. Telephone or audible alarm systems can also be used, but they are
less efficient than a broadcast voice system. Communications systems telephone,
alarm, and mass notification systems) should be tied to emergency phone systems.
Non-verbal warning systems are generally less effective because they require
training on the meaning of different types of alarm sounds.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
absorber and HEPA filter, should be stored in a sealed bag in the safe room along
with instructions and any tools needed for changing the filter quickly in an
emergency. Other supplies to be checked on a regular basis are the same as listed
for the Class 3 Safe Room above.
System Pressure
The system pressure is indicated by a gauge typically mounted on the control
panel, with the correct operating range marked on the gauge. If the pressure is
outside this range while the system operates, troubleshooting should be initiated.
Isolation Dampers
Correct damper positioning is indicated by damper status lights on the control
panel. Troubleshooting should be initiated if the status lights indicate a damper is
not properly positioned.
It should be visually inspected while the system is operating. A properly functioning
relief damper should be open when the safe room is pressurized, and it should
close immediately when a door is opened into the safe room, releasing pressure.
Cooling System
If the safe room supply air is cooled and heated, the temperature of the air flowing
from the supply register should be checked with a thermometer during
serviceability checks. In warm weather, this should be approximately 55 degrees if
the cooling system is operating properly.
Door Latches. All doors into the safe room should be adjusted to latch
automatically with the force of the door closer. For safe rooms with multiple doors,
leakage past unlatched doors can cause internal pressure to fall below the
specified operating range.
Weather Stripping
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
The weather stripping on each door on the boundary of the safe room should be
visually inspected to ensure it has not been removed or damaged through wear
and tear. For wipe seals at the bottom of the door, the alignment and height of the
seal above the floor should be inspected and adjusted as necessary.
Filters
Routine maintenance includes replacing filters. If a canister-type filter is used, it is
replaced as a unit at its expiration date. For other types of filter units, three types of
filters are replaced: the pre-filter, HEPA filter, and carbon absorber. Ideally, with
only intermittent operation, all three types of filters should be replaced at the same
time, every 3 to 4 years. This period is defined mainly by the service life of the
absorber.
Each time the CBR filters are replaced, in-place leakage testing should be
performed, except in the case of canister filters (see Figure 3-4), to ensure the
critical seals between the filters and/or between the mounting frame and the filters
are established properly (i.e., there is no leakage past the filters' peripheral seals).
To test the seals of the HEPA filter, the unit is challenged with an aerosol; poly-
alpha olefin (PAO) is the industry standard. To test the seals of the absorbers
requires a chemical that is loosely adsorbed in the filter bed. Halide gases are
typically used for this purpose. For the adsorber, the criterion is that the leak must
be less than 0.1 percent of the upstream concentration. For the HEPA filter, the
criterion is 0.03 percent. Procedures for both tests are described in American
National Standards Institute/American Society of Mechanical Engineers
(ANSI/ASME) N510, Testing of Nuclear Air Treatment Systems.
1.14. BEE
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
V. Reference
Below table is the list of documents which are applied for preparation of the Document.
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
Latest Available
Code & Standard Code or Standard Title
Version
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.
Buildings of Hazard Areas
Page 1
All drawings and documents prepared by the CONSULTANT and submitted to EMPLOYER in accordance with the provisions of CONTRACT shall be
the property of the EMPLOYER.