Galaxy VM Modular Battery Cabinet Runtimes in Minutes: Europe Middle East Africa
Galaxy VM Modular Battery Cabinet Runtimes in Minutes: Europe Middle East Africa
Typical battery runtimes in minutes for systems with modular battery cabinets
NOTE: Battery runtimes are intended as an estimate at 0.9 power factor.
(2) GVMMODBCWS
x30 30 22.5
(1) GVMMODBCNS
(3) GVMMODBCWS
x42 46 34.5
(1) GVMMODBCNS
(4) GVMMODBCWS
x54 62.5 47.5
(1) GVMMODBCNS
(5) GVMMODBCWS
x66 79.5 60.5
(1) GVMMODBCNS
(6) GVMMODBCWS
x78 97.5 74
(1) GVMMODBCNS
(7) GVMMODBCWS
x90 115 88
(1) GVMMODBCNS
Example:
160 kVA and 30 minutes runtime then the SKUs to be ordered are:
GVMMODBCWS = 2
+
GVMMODBCNS = 1
+
GVMMBTU = 30
Galaxy VM Classical Battery Cabinet Runtimes in Minutes
NOTE: Battery runtimes are intended as an estimate at 0.9 power factor.
Europe Applicable for Galaxy VM 200 kVA UPS: GVMSB200KHS and GVMPB200KHS
Africa Contains
1
x
2
x
2
x
2
x
3
x
3
x
40 40 40 40 40 40
% load kW of load XP12V2500 XP12V1800 XP12V2500 XP12V3000 XP12V2500 XP12V3000
At ambient temperature @ 25 °C
All runtimes are given in minutes at 0.9 PF of load
Example:
Requirement is to obtain 20.4 minutes backup time for
connecting a 200 kVA UPS (assume 80% load),the SKUs
to be ordered for the backup time are:
GVMCBC2WED = 1
Classical Battery Cabinet Runtime in Minutes
NOTE: Battery runtimes are intended as an estimate at 0.9 power factor.
Europe Applicable for Galaxy VM 160 kVA UPS: GVMSB160KHS and GVMPB160KHS
Africa Contains
1
x
2
x
2
x
2
x
3
x
3
x
40 40 40 40 40 40
XP12V2500
% load kW of load XP12V2500 XP12V1800 XP12V2500 XP12V3000 XP12V3000
At ambient temperature @ 25 °C
All runtimes are given in minutes at 0.9 PF of load
Modular Battery Cabinet Runtime in Minutes
NOTE: Battery runtimes are intended as an estimate at 0.8 power factor.
China Modular Battery Modular Battery Number of Battery 160 kVA 200 kVA
Cabinets Cabinet Quantity Modules — GVMMBTU UPS UPS
GVMMODBCWS 1 x10 8.1 N/A
GVMMODBCWS 1 x11 9.3 N/A
GVMMODBCWS 1 x12 10.5 N/A
GVMMODBCWS 1
x13 11.5 8.5
GVMMODBCNS 1
GVMMODBCWS 1
x14 13 9.5
GVMMODBCNS 1
GVMMODBCWS 1
x15 14 10.5
GVMMODBCNS 1
GVMMODBCWS 1
x16 15.5 11.5
GVMMODBCNS 1
GVMMODBCWS 1
x17 17 12.5
GVMMODBCNS 1
GVMMODBCWS 1
x18 18 13.5
GVMMODBCNS 1
GVMMODBCWS 2 x19 19.5 14.5
GVMMODBCWS 2 x20 21 15.5
GVMMODBCWS 2 x21 22.5 16.5
GVMMODBCWS 2 x22 23.5 17.5
GVMMODBCWS 2 x23 25 18.5
GVMMODBCWS 2 x24 26.5 19.5
GVMMODBCWS 2
x25 28 21
GVMMODBCNS 1
GVMMODBCWS 2
x26 29.5 22
GVMMODBCNS 1
Modular Battery Cabinet Runtimes in Minutes
NOTE: Battery runtimes are intended as an estimate at 0.9 power factor.
(2) GVMMODBCWS
x30 30 22.5
(1) GVMMODBCNS
(3) GVMMODBCWS
x42 46 34.5
(1) GVMMODBCNS
(4) GVMMODBCWS
x54 62.5 47.5
(1) GVMMODBCNS
(5) GVMMODBCWS
x66 79.5 60.5
(1) GVMMODBCNS
(6) GVMMODBCWS
x78 97.5 74
(1) GVMMODBCNS
(7) GVMMODBCWS
x90 115 88
(1) GVMMODBCNS