You are on page 1of 1

KNOCKOUTS

WIRING DIAGRAM
CONDUIT SIZE DIAMETER
SYMBOL
IN MM IN MM
C 1.00 25 1.38 35
6.20
E 1.50 38 2.00 51
[157]
14.64
A-L
HUB
[372]
TOP ENDWALL
I I
i-------11-- 3. 00
[76]
2.05
F
G
2.00
2.50
51
64
2.50
3.00
64
76

[52] H 3.00 76 3.63 92

t l 5.95
[151]
5.95
[151]
AH150R
J250R AND CJ250NR
NEMA TYPE 3R CIRCUIT
BREAKER
CIRCUIT BREAKER TERMINAL LUG DATA

AMPERE ONDUCTOR
WIRE SIZE
(AWG/KCMIL) TYPE

31.28
--+- 2.93
[74]
CATALOG NO.
PREFIX
RATING PER PHASE
MAX MIN
16.14 [795]
TO MTG HD, HG
[ 41 OJ SURFACE HJ, HL, HR
15-150 #3/0 #14 AL/CU

150-175 #4/0 #4
23.25 JD, JG o--~~---~~~+--~-+-~---<AL/CU
31.28 29.05 JJ, JL, JR
[591] 200-250 350 #3/0
[795]
[738]
27.00 23.25
[591] FIELD INSTALLABLE SOLID NEUTRAL ASSEMBLIES AND GROUND KIT
[686]

_J
WIRE SIZE
MAXIMUM ONDUCTOR
CATALOG NUMBER OF (AWG/KCMIL)
AMPERE PER TYPE
NUMBER TERMINALS
RATING TERMINAL MAX MIN
#1/0 #14 cu
SN1 OOFA 100A 2
#1/0 #12 AL

0
3.75
[95]
3.75
[95] SN400LA 250A 2
2
1
OR 2
#600
#250
#300
:~
#4
AL OR cu
AL OR cu
AL OR cu

• PKOGTJ250 250A 2 #300 #6 AL OR cu


AL OR cu
PKOGTH15 150A 2 #2 #14
FOR 200% NEUTRALS USE SN400LA (AMP RANGE 100 TO 250,
C,E,F,G,H CU WIRE ONLY).
14.33
i--- [364 J-------j FIELD INSTALLABLE CIRCUIT BREAKER DATA
I COVER I UL LISTED INTERRUPTING RATING
= CIRCUIT RMS SYMMETRICAL AMPERES
BREAKER WIRING AMPERE
C,E,F,G,H CATALOG NO DIAG RATING AC VOLTAGE DC VOLTAGE
PREFIX
240 480Y/277 480 600Y/347 600 125 250 500
SEISMIC NOTES:
0
USE (4) 1/4" DIA GRADE 5 STEEL MOUNTING BOLTS @ HOLES AA AHO A,B 15-150 25K 18K 18K 14K 14K 20K 20K
MAX CONFIGURED WEIGHT 38 LB FOR THE PURPOSE OF DETERMINING JD A,B 150-250 25K 18K 18K 14K 14K 20K 20K
14.00 SEISMIC ANCHORAGE REQUIREMENTS. FOR ALL OTHER APPLICATIONS, AHG A,B 15-150 65K 35K 35K 18K 18K 20K 20K
[356] CONTACT SCHNEIDER ELECTRIC. JG A,B 150-250 65K 35K 35K 18K 18K 20K 20K
BOX OUTSIDE
HJ A,B 15-150 100K 65K 65K 25K 25K 20K 20K
JJ A,B 150-250 100K 65K 65K 25K 25K 20K 20K
HL A,B 15-150 125K 65K 65K 25K 25K 20K 20K
NOTES:
JL A,B 150-250 125K 65K 65K 25K 25K 20K 20K
FINISH - NEMA/EEMAC TYPE 3R GRAY BAKED ENAMEL ELECTRODEPOSITED OVER CLEANED PHOSPHATIZED STEEL. DUAL DIMENSIONS: INCHES
cULus LISTED - FILE E-136861 HR A,B 15-150 125K 65K 65K 25K 25K 20K 20K
MILLIMETERS
SUITABLE FOR USE AS SERVICE EQUIPMENT WHEN NEUTRAL ASSEMBLY IS INSTALLED. (CJ250NR IN CANADA). JR A,B 150-250 125K 65K 65K 25K 25K 20K 20K
NEUTRAL - INSULATED GROUNDABLE.
CJ250NR CONTAINS FACTORY INSTALLED AND BONDED SN400LA NEUTRAL AND IS SUITABLE FOR USE AS 111
SERVICE EQUIPMENT IN CANADA.
AH150R SUITABLE ONLY FOR 2 POLE HD OR HG BREAKERS. CIRCUIT BREAKER ENCLOSURES SQUARE E:]
ENCLOSURES ACCEPT STANDARD 80% RATED OR 100% RATED CIRCUIT BREAKERS. WHEN USING 100% RATED CIRCUIT 15-250 AMPERE
by Schnelder Electric
BREAKERS USE ONLY WITH 9o·c (MIN) RATED WIRE SIZED PER AMPACITY OF 75·c RATED CONDUCTOR. NEMA/EEMAC TYPE 3R RAINPROOF ENCLOSURE
DWG#
NO.
3364S
SEPTEMBER 2016 3364