You are on page 1of 44

TRANSTECH ELECTRONIC CONTROLS Electronic Transient Surge Protection

From
Mains Power Supply to Low Volts & Communications
www.transtech.com.au

Transtech Electronic Controls Pty Ltd


ABN 21 070 629 499
Perth - Melbourne
Perth Tel: (08) 9302-2044
Melbourne Tel: (03) 9330-3624
Also in Melbourne - Sydney – Brisbane – Adelaide
Info@transtech.com.au
TRANSTECH
TLP Transient Lightning Protection
This is a TLP overview - contact sales for the full range of TLP protectors

Process - Industrial - Mining - Commercial - Government - Factories - Research

MAINS PROTECTORS
CAT C, 20kV AND 20 kA - use TLP-80-3P, TLP-120-3P, TLP-160-3P

CAT B, 6kV and 3kA - use TLP-8-1P/240 OR TLP-150-3P/CATB,


FIG 1 FIG 2 FIG 3 FIG 4 FIG 5
PEAK DISCHARGE
VOLTAGE Nominal MAX “LET-THRU”
CURRENT INDICATION DIMENSIONS
AS 1768 IEEE C62 compliant MODELS (Vrms) VOLTAGE FIGURE No
Per Mode 8/20usec Visual/Remote in mm
Maximum (Vrms) Volts/Modes
(kA)
kA W H D
Low Cost DIN 1 PH (Cat A) TLP-8-1P/120V 120 / 150 8.5 390 / 2 N/N Ref HO 12.5 75 53
TLP-8-1P/240V 240 / 275 8.5 600 / 2 N/N Ref HO 12.5 75 53
High Spec DIN 1 PH (Cat C) TLP-40-1P 240 / 275 40 <600 / 3 Y/Y FIG 1 80 110 85
TLP-80-1P 240 / 275 80 <600 / 3 Y/Y FIG 1 80 110 85
TLP-120-1P 240 / 275 120 <600 / 3 Y/Y FIG 1 80 110 85
High Spec DIN 3 PH (Cat C) TLP-P40-3DRI 240 / 275 40 <810 / 3 Y / Y + FIG9 FIG 1 105 120 75
Compact series DIN profile TLP-P80-3DRI 240 / 275 80 <810 / 3 Y / Y + FIG9 FIG 1 105 120 75
Remote status/Indication capable TLP-P120-3DRI 240 / 275 120 <810 / 3 Y / Y + FIG9 FIG 1 105 120 75
High E-N Fault DIN 3 PH (Cat C) TLP-80-3P/NEM 415 / 475 80 <810 / 3 Y / Y + NEM FIG 3 150 110 85
With unique N to E monitoring feature = NEM TLP-120-3P/NEM 415 / 475 120 <810 / 3 Y / Y + NEM FIG 3 150 110 85
TLP-160-3P/NEM 415 / 475 160 <810 / 3 Y / Y + NEM FIG 3 150 110 85
TLP-200-3P/NEM 415 / 475 200 <810 / 3 Y / Y + NEM FIG 3 150 110 85
Compact Series DIN PROFILE (Cat A or B) TLP-150-3P/CAT B 415 / 475 40 <710 / 3 Y/Y FIG 4 150 110 85
No neutral required for this model TLP-415P-E-DIN 415 / 475 40 <810 / 1 Y/N FIG 4 43 110 85

SERIES FILTERS UP TO 40 AMPS


CAT B & A, 6kV @ 20 Amps.
FIG 6 FIG 7 FIG 8 FIG 9 FIG 10
VOLTAGE Nominal PEAK DISCHARGE MAX “LET-THRU”
INDICATION DIMENSIONS
AS 1768, IEEE C62 compliant MODELS (Vrms)/ CURRENT VOLTAGE FIGURE No
Visual/Remote in mm
Maximum (Vrms) With 8/20usec (kA) Volts/Modes

kA W H D
Industrial (Cat B) TLP-GPO-10A 240/275 20 710 / 2 N/N 1 x 10A GPO ith 2mtr lead
Integral 20Amp series filter TLP-SF20SL-120V (DIN style) 120 / 275 48 385 / 3 Y/N FIG 6 23 115 85
Integral 20Amp series filter TLP-SF20SL-240V (DIN style) 240 / 275 48 600 / 3 Y/N FIG 6 23 115 85
Integral 20Amp series filter + Relay TLP-SF20RI-120 240 / 275 48 600 / 3 Y/Y FIG 8 23 115 85
Integral 20Amp series filter + Relay TLP-SF20RI-240 240 / 275 48 600 / 3 Y/Y FIG 8 23 115 85
Integral 40Amp series filter TLP-SF40T-P120 185 / 210 48 810 / 3 Y/N FIG 10 95 115 85
Integral 40Amp series filter TLP-SF40T-P240 255/275 48 810 / 3 Y/N FIG 10 95 115 85
Series OR Parallel Cat B TLP-SP20SL 30V 30 / 40 54 600 / 3 Y/ N FIG 7 23 115 85
Up to 20 amps series connected TLP-SP20SL 50V 50 / 60 72 690 / 3 Y/N FIG 7 23 115 85
unlimited in parallell connected TLP-SP20SL 150V 150 / 170 72 690 / 3 Y/N FIG 7 23 115 85
TLP-SP20SL 275V 240 / 275 72 690 / 3 Y/ N FIG 7 23 115 85

LOW VOLTAGE PROTECTORS, INSTRUMENTATION


AND COMMUNICATIONS (Cat A & B)
FIG 11 FIG 12 FIG 13 FIG 14 FIG 15
VOLTAGE Nominal PEAK DISCHARGE MAX “LET-THRU”
INDICATION DIMENSIONS
AS 1768, IEEE C62 compliant MODELS (Vrms) CURRENT VOLTAGE FIGURE No
Visual/Remote in mm
Maximum (Vrms) With 8/20usec (kA) Volts/Modes

kA W H D
Signals (either Analog or Digital) TLP-15L TO TLP-60L 15 /18 - 60 / 70 8 18 / 3 N/ N FIG 14 17.5 75 65.5
transmitters or switches TLP-SL62-xxD (2 ch 6.2mm wide) 15 /18 - 60 / 70 8 21 / 3 N/ N FIG 13 6.2 90 100
TLP-SL62-xxD (2 ch 6.2mm wide) 16 /18 - 60 / 70 8 43 / 3 N/ N FIG 13 6.2 90 100
* Other voltages TLP-SL62-xxD (2 ch 6.2mm wide) 17 /18 - 60 / 70 8 75 / 3 N/ N FIG 13 6.2 90 100
upon request TLP-SL62-xxD (2 ch 6.2mm wide) 18 /18 - 60 / 70 8 90 / 3 N/ N FIG 13 6.2 90 100
Protects 24v loop M20 entry TLP-48HM/M20 24 / 48 10 28 / 3 N/ N FIG 15 - 172 25 hex
Protects 24v loop NPT entry TLP-48HM/NPT 24 / 48 10 28 / 3 N/ N FIG 15 - 172 25 hex
Protects 24v supply as well as loop M20 entry TLP-48HM-4W/M24 24 / 48 10 28 / 3 N/ N FIG 15 - 172 25 hex
Protects 230v supply as well as loop M20 entry TLP-48HM-4W/M240 240/24/48 10 28 / 3 N/ N FIG 15 - 172 25 hex
Bus Protectors TLP-RS232 ±15 / ±18 400W PPPD 19 / 2 N/ N FIG 14 17.5 75 65.5
* Other types upon request TLP-RS485 ±12 / ±15 Vdc 400W PPPD 19 / 2 N/ N FIG 14 17.5 75 65.5
TLP-RS485/MB ±12 / ±15 Vdc 400W PPPD 19 / 2 N/ N FIG 14 17.5 75 65.5
TLP-RS485/PB ±12 / ±15 Vdc 400W PPPD 19 / 2 N/ N .FIG 14 17.5 75 65.5
TLP-DNET 24 / 31 400W PPPD 19 / 2 N/ N FIG 14 30 75 65.5
TLP-48/RJ45H-4 24 / 31 400W PPPD 19 / 2 N/ N FIG 12 25 85 55
Coaxial RF Protectors TLP-N/FF 70V 20 700 / 1kV/Ms N/ N FIG 11 TNC FEM/FEM Bulkhead
* Other types upon request TLP-F/MF 90V 20 700 / 1Kv/Ms N/ N FIG 11 F FEM/MALE
TLP-F/FF 90V 20 701 / 1Kv/Ms N/ N FIG 11 F FEM/FEM

Notes and Standards: AS 1768-2005, IEC61643-1, BS 6651-1992, IEEE C62. 41-1991, BS 2914-1972 Compliance: N2909

Perth - Melbourne - Sydney - Brisbane - Adelaide


TransTech Electronic Controls Pty Ltd
Perth H.O Design/Manufacturing
Contact: Dale Tunbridge or John King or Mark Van Schalm (Melbourne)
MOB: 0439 911-883 or 0419-502-660 or 0409 697-156
Unit 2 / 48 Dellamarta Road
WANGARA W.A. 6065
dale@transtech.com.au or john@transtech.com.au or mark@transtech.com.au
\\server\i\Shared\Price Lists & data sheets\Transtech\Flyers\TLP_Listing.xlsx
Transient Protection Presentation

5. Transient Standards Categories and Definitions.

According to AS 1768:2005 the installation of transient over-voltage protectors can


be broken down into five (5) categories.

Such categories are shown below from highest risk (E) to lowest risk (A):

CAT E 6kV / 70kA


The Point of entry to “very exposed or
critically important site.

Example: Telecom tower on hill.

CAT D 6kV / 30kA CAT E – very high risk

The point of entry to an exposed rural


site.

Example: Pump station a Country Area

CAT C 6kV / 15 - 20kA


The point of entry to a site in the City or
built up area.

Example: Most common building or site

CAT B 6kV / 3kA


Within a building immediately after the
point of entry or Main Board.

Example: Sub-boards.
C B B

CAT A 6kV / 500Amp


Within a building and fed from a sub-board
being CAT B location.

Example: GPO,s
C B A A

- 10 –
I:\Shared\Price Lists & data sheets\Transtech\Application Notes\TLP Presentation_new.docx
TRANSTECH
DATA SHEET Subject to change without notice

MODEL :- TLP-80-1P
Transtech Lightning Protector - 240V Single Phase, 3 Modes
For CAT C or less

TECHNICAL DATA

Normal Working voltage 240VAC rms


Minimum Working voltage 220VAC rms
Maximum Working voltage 275VAC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 800V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 80kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES 80(W) x 80(H) x 115(L)


Relay Output Phase loss or Neutral
Disconnected the relay
de-energizes.
GENERAL DESCRIPTION
LED’s (2) Power On / Unit Healthy, The TLP-80-1P is a “new series” lightning and transient
(LED ON = healthy) protector which provides protection for electrical / electronic
equipment connected to three phase distribution systems.
GENERAL SPECIFICATION
The TLP-80-1P is a true 3 mode parallel connected
Operating Temp -40 to +70 Deg C protection device offering 3 levels of kA rating in all 3
Terminals 2
16mm solid max / 10mm flex max
2 modes.
2
Remote Terminals Plug in 2.5mm
The TLP-80-1P offers a DIN style housing to suit most MCB
Indicators Red LED’s profiles.
Housing Material Mild Steel(Powder coated)
Dimensions 80 (H) x 80 (H) x 115 (L) For mains supply of greater than 100A adequate HRC fuse
Weight 850 grams or MCB protection must be installed prior to the TLP-xx 1P.
Mounting DIN 43880 Standard DIN Rail
FEATURES
REMOTE RELAY OUT
♦ Low “let thru” voltage
♦ Designed and manufactured to ISO 9001
3 2 1 ♦ Neutral to Earth Monitor
Model No

Remote Alarm

TLP-80-1P
1 = N/O | 2 = COMM | 3 = N/C
Internally protected – automatic reset

TRANSTECH

UNIT
HEALTHY
POWER Local status indication by LED’s

ON
SINGLE PHASE
(Replace if OFF)

TRANSIENT PROTECTOR
CAT C
V = 240V
Remote status indication c/o relay

In = 40kA

L1 N E
Imax = 120kA
High Energy designed pcb’s
♦ CE Marking / C-tick N 2909
♦ Full 3 mode protection
SUPPLY LOAD ♦ DIN 43880 compliant
L1
♦ Designed to pass IEC 61643-1:2005 and
AS/NZS 1768:2003
N
E NOTE: This device must be installed by a
CONNECTION Qualified Electrician
(CABLES 16sq/mm AS SHORT AS POSSIBLE)

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-80-1P new.docx 05/02/2011


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-120-1P
Transtech Lightning Protector - 240V Single Phase, 3 Modes
For CAT C or less

TECHNICAL DATA

Normal Working voltage 240VAC rms


Minimum Working voltage 220VAC rms
Maximum Working voltage 275VAC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 800V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 120kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES 80(W) x 80(H) x 115(L)


Relay Output Phase loss or Neutral
Disconnected the relay
de-energizes. GENERAL DESCRIPTION
LED’s (2) Power On / Unit Healthy,
(LED ON = healthy) The TLP-120-1P is a “new series” lightning and transient
protector which provides protection for electrical / electronic
equipment connected to three phase distribution systems.
GENERAL SPECIFICATION
The TLP-120-1P is a true 3 mode parallel connected
Operating Temp -40 to +70 Deg C protection device offering 3 levels of kA rating in all 3
Terminals 2
16mm solid max / 10mm flex max
2 modes.
2
Remote Terminals Plug in 2.5mm
The TLP-120-1P offers a DIN style housing to suit most
Indicators Red LED’s MCB profiles.
Housing Material Mild Steel(Powder coated)
Dimensions 80 (H) x 80 (H) x 115 (L) For mains supply of greater than 100A adequate HRC fuse
Weight 850 grams or MCB protection must be installed prior to the TLP 1P.
Mounting DIN 43880 Standard DIN Rail
FEATURES
REMOTE RELAY OUT
♦ Low “let thru” voltage
♦ Designed and manufactured to ISO 9001
3 2 1 ♦ Neutral to Earth Monitor
Model No

Remote Alarm

TLP-120-1P
1 = N/O | 2 = COMM | 3 = N/C
Internally protected – automatic reset

TRANSTECH

UNIT
HEALTHY
POWER Local status indication by LED’s

ON
SINGLE PHASE
(Replace if OFF)

TRANSIENT PROTECTOR
CAT C
V = 240V
Remote status indication c/o relay

In = 40kA

L1 N E
Imax = 120kA
High Energy designed motherboard
♦ CE Marking / C-tick N 2909
♦ Full 3 mode protection
SUPPLY LOAD ♦ DIN 43880 compliant
L1
♦ Designed to pass IEC 61643-1:2005 and
AS/NZS 1768:2003
N
E NOTE: This device must be installed by a
CONNECTION Qualified Electrician
(CABLES 16sq/mm AS SHORT AS POSSIBLE)

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-120-1P new.docx 05/02/2011


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-P80-3DRI
Transtech Lightning Protector - 415V Three Phase, 3 Mode
For CAT C
TECHNICAL DATA

Normal Working voltage 415VAC rms


Minimum Working voltage 328VAC rms
Maximum Working voltage 476VAC rms
Working Freq. 40 - 60Hz
Peak let thru volts Less than 810V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
In 36kA
Imax 80kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output Phase loss disconnected
the relay de-energizes. GENERAL DESCRIPTION
LED’s (dual colour) L1, L2, L3,
(LED ON = healthy) The TLP-P80-3DRI is a “new series” lightning and transient
(LED AMBR = replace) protector which provides protection for electrical / electronic
equipment connected to three phase distribution systems.
GENERAL SPECIFICATION The TLP-P80-3DRI is a true 3 mode (L-L / L-N / N-E) parallel
connected surge protection device offering protection for all 3
Operating Temp -40 to +70 Deg C phases, it also introduces a unique feature, by being connected to
2 2
Terminals 16mm solid max / 10mm flex max a TLP-DSI which will indicate the status of each phase remotely.
2
Remote Terminals Plug in 2.5mm
Indicators Red / Amber LED’s The TLP-P80-3DRI is powered by all 3 phases and does not lose
Housing Material Mild Steel(Powder coated) indication until all 3 phases have failed. This is a distinct
advantage over units where indicators are powered from a single
Dimensions 105 (W) x 120 (H) x 75 (D)
phase.
Weight 700 grams
Mounting DIN 43880 Standard DIN Rail For mains supply of greater than 100A adequate HRC fuse or
MCB protection must be installed prior to the TLP-xx-3P.
RELAY
OUT
FEATURES
REMOTE IND
OUT
♦ Low “let thru” voltage

LE D’s L1 -L2-L3
TLP-P80-3DRI
TRANSTECH RED = OK
AMBE R = DECRE ASE D
Designed and manufactured to ISO 9001
3PH + E
OFF = REP LACE TLP
♦ Internally protected – automatic reset
SURGE PROTECTION
♦ Local status indication by dual colour LED’s
L1 L1 L1 N E ♦ Remote panel indicator
♦ Alarm status indication via in-built c/o relay
LOAD SIDE

SUPPLY SIDE
High Energy designed pcb’s
FUSE/MCB PROTECT ION ♦ CE Marking / C-tick N 2909
L1 L1 ♦ Full 3 mode protection
L2 L2 ♦ DIN 43880 compliant
L3 L3 ♦ Designed to pass IEC 61643-1:2005 and AS/NZS
N N 1768:2003
E E

CONNECTION DIAGRAM NOTE: This device must be installed by a Qualified


Electrician

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-P80-3DRI new.docx 30 Jan 2010


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-80-3P/NEM
Transtech Lightning Protector - 415V Three Phase, 3 Mode with Neutral to Earth Monitoring
For CAT C or less
TECHNICAL DATA

Normal Working voltage 415VAC rms


Minimum Working voltage 328VAC rms
Maximum Working voltage 476VAC rms
Working Freq. 40 - 60Hz
Peak let thru volts Less than 810V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 80kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output Phase loss or Neutral & 155(W) x 105(D) x 85(H)
Earth both disconnected
the relay de-energizes.
LED’s (4) L1, L2, L3, N-E GENERAL DESCRIPTION
(LED ON = healthy)
The TLP-80-3P/NEM is a “new series” lightning and transient
protector which provides protection for electrical / electronic
equipment connected to three phase distribution systems.
GENERAL SPECIFICATION
The TLP-80-3P/NEM is a true 3 mode parallel connected
Operating Temp -40 to +70 Deg C protection device offering 3 levels of kA rating in all 3 modes.
2 2
Terminals 16mm solid max / 10mm flex max
2 The TLP-80-3P/NEM now offers a Neutral to Earth protection
Remote Terminals Plug in 2.5mm
monitoring circuit (NEMON) which until now has not been
Indicators Red LED’s available. The NEMON circuit ensures that all 3 modes of
Housing Material Mild Steel(Powder coated) protection are active and offers a fully monitored and reliable
Dimensions 155 (W ) x 105(D) x 85 (H) protection device.
Weight 850 grams
Mounting DIN 43880 Standard DIN Rail For mains supply of greater than 100A adequate HRC fuse or
MCB protection must be installed prior to the TLP-xx-3P/NEM.
REMOTE RELAY OUT

RELAY OUT
1 = N/O
1 2 3 FEATURES
2 = COMM
3 = N/C

♦ Low “let thru” voltage


TLP-80-3P/NEM ♦ Designed and manufactured to ISO 9001
♦ Neutral to Earth Monitor
THREE PHASE TRANSIENT PROTECTOR WITH NEUTRAL/EARTH MONITOR
♦ Internally protected – automatic reset
L1 L2 L3 NE ♦ Local status indication by LED’s
♦ Remote status indication c/o relay
♦ High Energy designed pcb’s
SUPPLY LOAD ♦ CE Marking / C-tick N 2909
L1 ♦ Full 3 mode protection
L2 ♦ DIN 43880 compliant
L3 ♦ Designed to pass IEC 61643-1:2005 and AS/NZS
N 1768:2003
E NOTE: This device must be installed by a Qualified
CONNECTION Electrician
(CABLES 16sq/mm AS SHORT AS POSSIBLE)

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-80-3P_NEM new.docx 30 Jan 2010


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-P130-3DRI
Transtech Lightning Protector - 415V Three Phase, 3 Mode
For CAT C
TECHNICAL DATA

Normal Working voltage 415VAC rms


Minimum Working voltage 328VAC rms
Maximum Working voltage 476VAC rms
Working Freq. 40 - 60Hz
Peak let thru volts Less than 810V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
In 43kA (10 Impulses)
Imax 130kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output Phase loss disconnected
the relay de-energizes. GENERAL DESCRIPTION
LED’s (dual colour) L1, L2, L3,
(LED RED = healthy) The TLP-P130-3DRI is a “new series” lightning and transient
(LED AMBER = replace) protector which provides protection for electrical / electronic
equipment connected to three phase distribution systems.
GENERAL SPECIFICATION The TLP-P130-3DRI is a true 3 mode (L-L / L-N / N-E) parallel
connected surge protection device offering protection for all 3
Operating Temp -40 to +70 Deg C phases, it also introduces a unique feature, by being connected to
2 2
Terminals 16mm solid max / 10mm flex max a TLP-DSI which will indicate the status of each phase remotely.
2
Remote Terminals Plug in 2.5mm
Indicators Red / Amber LED’s The TLP-P130-3DRI is powered by all 3 phases and does not
Housing Material Mild Steel(Powder coated) lose indication until all 3 phases have failed. This is a distinct
advantage over units where indicators are powered from a single
Dimensions 105 (W) x 120 (H) x 75 (D)
phase.
Weight 700 grams
Mounting DIN 43880 Standard DIN Rail For mains supply of greater than 100A adequate HRC fuse or
MCB protection must be installed prior to the TLP-xx-3P.

RELAY
OUT
FEATURES
REMOTE IND
OUT
♦ Low “let thru” voltage
TRANSTECH
TLP-P130-3DRI LE D’s L1 -L2-L3
RED = OK
♦ Designed and manufactured to ISO 9001

AMBE R = DECRE ASE D

3PH + E
OFF = REP LACE TLP Internally protected – automatic reset
SURGE PROTECTION
♦ Local status indication by dual colour LED’s
L1 L1 L1 N E ♦ Remote panel indicator
SUPPLY SIDE LOAD SIDE
♦ Alarm status indication via in-built c/o relay
♦ High Energy designed pcb’s
FUSE/MCB PROTECT ION
♦ CE Marking / C-tick N 2909
L1 L1
♦ Full 3 mode protection

L2 L2
L3 L3
DIN 43880 compliant
N N
♦ Designed to pass IEC 61643-1:2005 and AS/NZS
E E 1768:2003
CONNECTION DIAGRAM

NOTE: This device must be installed by a Qualified


Electrician

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-P130-3DRI new.docx 24 April 2013


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-120-3P/NEM
Transtech Lightning Protector - 415V Three Phase, 3 Mode with Neutral Earth Monitoring
CAT C or less
TECHNICAL DATA

Normal Working voltage 415VAC rms


Minimum Working voltage 328VAC rms
Maximum Working voltage 476VAC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 810V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 120kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output Phase loss or Neutral & 155(W) x 105(D) x 85(H)
Earth both disconnected
the relay de-energizes. GENERAL DESCRIPTION
LED’s (4) L1, L2, L3, N-E
(LED ON = healthy) The TLP 120-3P/NEM is a “new series” lightning and transient
protector which provides protection for electrical / electronic
equipment connected to three phase distribution systems.

GENERAL SPECIFICATION The TLP120-3P/NEM is a true 3 mode parallel connected


protection device offering 3 levels of kA rating in all 3 modes.
Operating Temp -40 to +70 Deg C
Terminals 2
16mm solid max / 10mm flex max
2 The TLP-120-3P/NEM now offers a Neutral to Earth protection
2 monitoring circuit (NEMON) which until now has not been
Remote Terminals Plug in 2.5mm
available. The NEMON circuit ensures that all 3 modes of
Indicators Red LED’s protection are active and offers a fully monitored and reliable
Housing Material Mild Steel (Powder coated) protection device.
Dimensions 155 (W) x 105 (D) x 85 (H)
Weight 850 grams For mains supply of greater than 100A adequate HRC fuse or
Mounting DIN 43880 Standard DIN Rail MCB protection must be installed prior to the TLP 3P/NEM.

FEATURES
REMOTE RELAY OUT

RELAY OUT
1 2 3
♦ Low “let thru” voltage

1 = N/O
2 = COMM
3 = N/C
Designed and manufactured to ISO 9001
♦ Neutral to Earth Monitor
TLP-120-3P/NEM ♦ Internally protected – automatic reset
♦ Local status indication by LED’s
THREE PHASE TRANSIENT PROTECTOR WITH NEUTRAL/EARTH MONITOR ♦ Remote status indication c/o relay
L1 L2 L3 NE ♦ High Energy designed pcb’s
♦ CE Marking / C-tick N 2909
♦ Full 3 mode protection
SUPPLY LOAD ♦ DIN 43880 compliant
L1
♦ Designed to pass IEC 61643-1:2005 and
L2
L3 AS/NZS 1768:2003
N NOTE: This device must be installed by a Qualified
E Electrician.
CONNECTION
(CABLES 16sq/mm AS SHORT AS POSSIBLE)

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-120-3P_NEM new.docx 12 January 2010


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-160-3P
Transtech Lightning Protector - 415V Three Phase, 3 Mode
CAT C or less
TECHNICAL DATA

Normal Working voltage 415VAC rms


Minimum Working voltage 328VAC rms
Maximum Working voltage 476VAC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 810V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 160kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output Phase loss or MOV failed
the relay de-energizes.
LED’s (4) L1, L2, L3, N-E GENERAL DESCRIPTION
(LED ON = healthy)
The TLP 160-3P is a “new series” lightning and transient
protector which provides protection for electrical / electronic
equipment connected to three phase distribution systems.

GENERAL SPECIFICATION The TLP160-3P is a true 3 mode parallel connected


protection device offering 3 levels of kA rating in all 3 modes.
Operating Temp -40 to +70 Deg C
2 2
Terminals 16mm solid max / 10mm flex max
2 For mains supply of greater than 100A adequate HRC fuse or
Remote Terminals Plug in 2.5mm
MCB protection must be installed prior to the TLP-xxx- 3P
Indicators Red LED’s
Housing Material Mild Steel (Powder coated)
Dimensions 155 (W) x 105 (H) x 85 (D)
Weight 850 grams
Mounting DIN 43880 Standard DIN Rail FEATURES

♦ Low “let thru” voltage


REMOTE RELAY OUT
♦ Designed and manufactured to ISO 9001
RELAY OUT
3 2 1
♦ Internally protected – automatic reset

1 = N/O
2 = COMM
3 = N/C
Local status indication by LED’s
♦ Remote status indication c/o relay
TLP-120-3P
♦ High Energy designed pcb’s
♦ CE Marking / C-tick N 2909
THREE PHASE TRANSIENT PROTECTOR ♦ Full 3 mode protection
L1 L2 L3 NE ♦ DIN 43880 compliant
♦ Designed to pass IEC 61643-1:2005 and
SUPPLY LOAD
AS/NZS 1768:2003
L1
L2
L3 NOTE: This device must be installed by a Qualified
N Electrician.
E
CONNECTION
(CABLES 16sq/mm AS SHORT AS POSSIBLE)

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-160-3P new.docx 27 June 2011


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-160-3P/NEM
Transtech Lightning Protector - 415V Three Phase, 3 Mode with Neutral Earth Monitoring
CAT C or less
TECHNICAL DATA

Normal Working voltage 415VAC rms


Minimum Working voltage 328VAC rms
Maximum Working voltage 476VAC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 810V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 160kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES 155(W) x 105(D) x 85(H)


Relay Output Phase loss or Neutral &
Earth both disconnected
the relay de-energizes. GENERAL DESCRIPTION
LED’s (4) L1, L2, L3, N-E
(LED ON = healthy) The TLP 160-3P/NEM is a “new series” lightning and transient
protector which provides protection for electrical / electronic
equipment connected to three phase distribution systems.

GENERAL SPECIFICATION The TLP160-3P/NEM is a true 3 mode parallel connected


protection device offering 3 levels of kA rating in all 3 modes.
Operating Temp -40 to +70 Deg C
Terminals 2
16mm solid max / 10mm flex max
2 The TLP-160-3P/NEM now offers a Neutral to Earth
2 protection monitoring circuit (NEMON) which until now has not
Remote Terminals Plug in 2.5mm
been available. The NEMON circuit ensures that all 3 modes
Indicators Red LED’s of protection are active and offers a fully monitored and
Housing Material Mild Steel (Powder coated) reliable protection device.
Dimensions 155 (W) x 105 (D) x 85 (H)
Weight 850 grams For mains supply of greater than 100A adequate HRC fuse or
Mounting DIN 43880 Standard DIN Rail MCB protection must be installed prior to the TLP 3P/NEM.

FEATURES
REMOTE RELAY OUT

RELAY OUT
1 2 3
♦ Low “let thru” voltage

1 = N/O
2 = COMM
3 = N/C
Designed and manufactured to ISO 9001
♦ Neutral to Earth Monitor
TLP-160-3P/NEM ♦ Internally protected – automatic reset
♦ Local status indication by LED’s
THREE PHASE TRANSIENT PROTECTOR WITH NEUTRAL/EARTH MONITOR ♦ Remote status indication c/o relay
L1 L2 L3 NE ♦ High Energy designed pcb’s
♦ CE Marking / C-tick N 2909
♦ Full 3 mode protection
SUPPLY LOAD ♦ DIN 43880 compliant
L1
♦ Designed to pass IEC 61643-1:2005 and
L2
L3 AS/NZS 1768:2003
N NOTE: This device must be installed by a Qualified
E Electrician.
CONNECTION
(CABLES 16sq/mm AS SHORT AS POSSIBLE)

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-160-3P_NEM new.docx 12 January 2010


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-240-3P
Transtech Lightning Protector - 415V Three Phase, 3 Mode
CAT C or less
TECHNICAL DATA

Normal Working voltage 415VAC rms


Minimum Working voltage 328VAC rms
Maximum Working voltage 476VAC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 810V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 240kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output Phase loss or MOV failed
the relay de-energizes.
LED’s (4) L1, L2, L3, GENERAL DESCRIPTION
(LED ON = healthy)
The TLP 240-3P is a “new series” lightning and transient
protector which provides protection for electrical / electronic
equipment connected to three phase distribution systems.

GENERAL SPECIFICATION The TLP 240-3P is a true 3 mode parallel connected


protection device offering 3 levels of kA rating in all 3 modes.
Operating Temp -40 to +70 Deg C
2 2
Terminals 16mm solid max / 10mm flex max
2 For mains supply of greater than 100A adequate HRC fuse or
Remote Terminals Plug in 2.5mm
MCB protection must be installed prior to the TLP-xxx- 3P
Indicators Red LED’s
Housing Material Mild Steel (Powder coated)
Dimensions 155 (W) x 105 (H) x 85 (D)
Weight 850 grams
Mounting DIN 43880 Standard DIN Rail FEATURES

♦ Low “let thru” voltage


REMOTE RELAY OUT
♦ Designed and manufactured to ISO 9001
RELAY OUT
3 2 1
♦ Internally protected – automatic reset

1 = N/O
2 = COMM
3 = N/C
Local status indication by LED’s
♦ Remote status indication c/o relay
TLP-240-3P
♦ High Energy designed pcb’s
♦ CE Marking / C-tick N 2909
THREE PHASE TRANSIENT PROTECTOR ♦ Full 3 mode protection
L1 L2 L3 NE ♦ DIN 43880 compliant
♦ Designed to pass IEC 61643-1:2005 and
SUPPLY LOAD
AS/NZS 1768:2005
L1
L2
L3 NOTE: This device must be installed by a Qualified
N Electrician.
E
CONNECTION
(CABLES 16sq/mm AS SHORT AS POSSIBLE)

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-240-3P new.docx 27 June 2011


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL: TLP-150-3M/CAT B
Transtech Lightning Protector - 415V Three Phase, 3 Mode

TECHNICAL DATA

Normal working voltage 415VAC rms


Minimum working voltage 328VAC rms
Maximum working voltage 476VAC rms
Working Freq. 40 - 60Hz
Peak let thru volts <800V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over 100A Mains
Category AS/NZS 1768 Cat B
In (Crest current) 60kA (8/20uS)
Imax (Max discharge current) 150kA (8/20uS)
Response time Less than 25nS
Surge Reset Automatic

SPECIAL FEATURES
LED Indication LED’s ON = TLP healthy
LED OFF = TLP repair
Relay Output Changeover volt-free GENERAL DESCRIPTION
The TLP-150-3M/CAT B is a lightning and transient protector
GENERAL SPECIFICATION which provides protection for electrical / electronic equipment
connected to three phase distribution systems. The mains borne
transient voltages may occur as a result of lightning strikes or the
Operating Temp -40 to +70 Deg C
2 2 switching of large inductive / capacitive loads.
Terminals 16mm solid max / 10mm flex max The TLP-150-3M/CAT B is a parallel device for Cat B applications
Remote Terminals N/A and should be installed as close as possible to the supply being
Indicators Green LED’s protected. It is recommended that connecting cables be kept
Housing Material Aluminium (Powder coated) shorter than 300mm.
Dimensions 95.5(W) x 72(H) x 108(L) The TLP-150-3M/CAT B is a true 3 mode protection device with
Weight 700 grams an Imax rating of 150kA for Cat B applications.
Mounting DIN 43880 Standard DIN Rail
For mains supply of greater than 100A adequate HRC fuse or
MCB protection must be installed prior to the TLP 150-3M.

FEATURES
PROTECTION
FUSE/MCB

TLP-XXX-3M/CATB ♦ Low “let thru” voltage


3PH 415V PROTECTION ♦ Designed and manufactured to ISO 9001
CAT B ♦ Certified for BER Projects
♦ Internally protected – automatic reset
L1 L2 L3 N E
♦ LED status indication for power loss or fault
SUPPLY LOAD ♦ Designed to pass IEC 616431-1:2005 and AS/NZS
SIDE 1768:2003
L1 SIDE L1
♦ Long lifetime, fully lacquered PCB’s
L2 L2
♦ CE Marking / C-tick N 2909
L3 L3
♦ Full 3 mode protection
N N
♦ DIN 43880 compliant
E E
CONNECTION DIAGRAM

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

th
I:/Docs/word/DataSheets/TLP-150-3M/CATB 14 October 2009 PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET
d
Subject to change without notice

MODEL TLP-DSI
Direct Status Indicator

TECHNICAL DATA

The TLP-DSI is powered directly from the Remote


Indicator (RI) output of Transtech TLP any High
Energy TLP unit which incorporates the unique
Remote Indicator circuitry.

Status LEDs 3 x RED

GENERAL SPECIFICATION
GENERAL DESCRIPTION

The TLP-DSI is a self-powered remotely mounting


Operating Temp. -25 to 70 degrees C
status indicator which mirrors the status LEDs on
Connection 3 way 2.5mm2 plug-off
Transtech’s High Energy TLP’s which have a unique
Housing Material ABS.
remote Indicator (RI) output fitted.
Dimensions 48 x 48 x 60 mm
Weight 25gm nominal
The LEDs of the TLP-DSI match their respective
Mounting Through panel mount
status LED on the monitored TLP unit. A unique circuit
design means that only 3 wires are required to display
the status of any one of the monitored TLP LEDs.
TRANST ECH

TLP-DSI
The length of the 3 core cable between the TLP-xxx
and its TLP-DSI should be no more than a maximum
of 5 meters.
Max 5 mtr 3 core cable 0.5 sqmm
REMOTE STATUS OUT REMOTE RELAY OUT

FEATURES
3 2 1


Model No Rem ote Alarm

TRANSTECH
TLP-40-3P
1 = N/O | 2 = COMM | 3 = N/C

Designed and manufactured to ISO 9001


UNIT
HEALTHY
(Repl ace if OFF)
POWER
ON ♦ Small size 48mm x 48mm panel mount unit

THREE PHASE CAT C

TRANSIENT PROTECTOR
V = 240V
In = 40kA
Im ax = 120kA
3 bright, easy to read LEDs
L1 L2 L3 N E
♦ Status LEDs match those of the TLP LEDs
♦ Easy to connect - only 3 wires
L1
LOAD
♦ Plug-off terminals
L2 ♦ No setup required.
L3
N
E
CONNECTION

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
PAGE Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-DSI.doc

Confidential Page 1 March 12, 2013


DATA SHEET
d
Subject to change without notice

MODEL TLP-PSI
Powered Remote Status Indictaor

TECHNICAL DATA

Power Supply: 120, 220/240 +/- 15%


VA Rating : Typically 1.3VA

Status LEDs:
Power BLUE
Healthy RED
Fault YELLOW

Output: Relay volt free contact

GENERAL SPECIFICATION
GENERAL DESCRIPTION
Operating Temp. -25 to +70 degrees C
2
Power Terminals Plug in 1.5mm The TLP-PSI is a 48mm x 48mm AC powered, status
2
Sense Terminals Plug in 1.5mm indicator which may be connected to any TLP product
2
Relay Output Term. Plug off 2.5mm which incorporates a status output relay. The TLP-PSI
Indicators Blue, Red, Yellow LEDs can be mounted in a convenient location at some
Housing Material ABS distance from the associated transient protection
Dimensions 48 x 48 x 60 device.
Weight 50gm nominal
Mounting Through panel mount
The TLP-PSI uses a transformer isolated 24V DC to
monitor the TLP status (fault) relay, it has three status
LEDs;
TRANST ECH
BLUE = Power OK
TLP-PSI/240V
RED = Healthy
YELLOW = Faulty (replace)

Supply
REMOTE RELAY OUT Neutral
120Vac or 240Vac
Line

REMOTE RELAY OUT

FEATURES
3 2 1
♦ Designed and manufactured to ISO 9001
Model No

Rem ote Alarm

TLP-40-3P
1 = N/O | 2 = COMM | 3 = N/C
Small size 48mm x 48mm panel mount unit

TRANSTECH
UNIT
HEALTHY
POWER
ON
3 bright, easy to read LEDs

(Repl ace if OFF)
THREE PHASE
TRANSIENT PROTECTOR
CAT C
V = 240V
In = 40kA
Easy to connect

Im ax = 120kA

L1 L2 L3 N E Plug-off terminals
♦ Boxed (shrouded) AC connector
SUPPLY LOAD
♦ No setup required.
L1
L2
L3
N
E

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
PAGE Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-PSI.docx

Confidential Page 1 March 7, 2013


DATA SHEET Subject to change without notice

MODEL :-TLP-415P/E-DIN
Transtech Lightning Protector (no Neutral) - CAT B

TECHNICAL DATA

Voltage rating Normal working voltage


415V
Max. working volts 480V RMS
Working Freq. 40 - 60 Hz
Peak let thru volts 710V
Protection Modes Phase -Earth ONLY
Surge Rating 20kA,
Mass Surge Material 60kA 8/20uSecs
Meets Surge Ratings to AS/NZS 1768-1991
IEEE C 62.41, UL 1449
Earth Leakage Approx 500uA
Operating Current N/A in parallel

L x H x W = 112mm x 75mm x 45mm

GENERAL SPECIFICATION GENERAL DESCRIPTION

Operating Temp -20 to 70 Deg C The TLP-415P/E-DIN series is a lightning and power
Storage Temp -55 to 75 Deg C transient arrester which provide voltage surge limitation to
Humidity 0 - 90% RH power electrical devices connected to the mains power
Indication 3 Neon indicators supply.
Terminals Self opening 0.5 - 10mm The TLP-415P/E-DIN provides effective protection by
20 - 6 AWG clamping the over voltage to a safe level. Three (3)
Housing Material KRILEN / AL cover indicators show if the TLP-415P/E-DIN is “healthy” and
Mounting Style DIN or G rail providing protection. Should one(1) indicator go off
Dimensions 112mm x 75mm x 45mm replacement should be done as soon as possible if ALL
Weight 195 grams three indicators are off the device must be replaced
IMMEDIATELY.
The TLP-415P/E-DIN must always be installed on the load
L1 L2 L3 side of a fuse or MCB.
The TLP-415P/E-DIN can be mounted directly on to “G” or
“DIN” rails (DIN 46277-1 and 46277-3)

BENEFITS:-
♦ Low “let thru” voltage
♦ Protection between 3 Phases – Earth
♦ Fast snap on DIN rail mounting
♦ 26kA discharge capacity per line
♦ Location Category B to AS 1768
♦ CE / C-tick marking

*** CAUTION ***
♦ Ensure that the Earth is appropriately terminated at
EARTH
all times. Ensure that the all Phases are at 0V
potential before removing the unit for service.

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-415p e.din new.docx Confidential August 24, 2011
TRANSTECH ELECTRONIC CONTROLS Electronic Transient Surge Protection
20 AMP Series Filter 23mm WIDE

Model: TLP-SF20-SL-240V

Model: TLP-SP20-SL-240V
www.transtech.com.au

UNIQUE FEATURES:

Slimmest 20Amp Model available


3rd Party Tested to IEC 61643-1:2005
(PASSED)
High Fault Rating 54kA Mass
Metal Hosuing
Front LED
Australian Designed and Manufactured
Over 15,000 Installed Australia Wide

Transtech Electronic Controls Pty Ltd


ABN 21 070 629 499
Perth - Melbourne
Perth Tel: (08) 9302-2044
Melbourne Tel: (03) 9330-3624
Also in Melbourne - Sydney – Brisbane – Adelaide
Info@transtech.com.au
TRANSTECH
DATA SHEET
d
Subject to change without notice

MODEL :-TLP-SF20SL-240V
Transtech Lightning Protector/Surge Filter - 20Amp for 240Vac

TECHNICAL DATA
Voltage rating Normal working voltage
240V RMS
Max. Working volts 275V RMS
Working Freq. 40 - 60 Hz
Peak let thru volts 710 V (typical 1 pulse)
Protection Modes Ph-N, Ph-E, N-E
Surge Rating;-
Imax (max discharge current)42kA (8/20msec) @ 75%
Iin (crest current) 24kA
Meets Surge Ratings to AS/NZS 1768:2003
IEEE C 62.41, UL 1449
Tested & Pass to IEC 61643.1:2005
Surge Filter
Inductor Type Common Mode 20A choke
Capacitors X and Y
L x H x W = 112mm x 75mm x 23.5mm nom.
Cut-off Frequency Less than 1kHz (-3dB loss)
Attenuation (60dB) 5MHz
Earth Leakage Approx. 500uA
Operating Current 3mA nominal GENERAL DESCRIPTION
Loss Less than 2Watts
Continuous Current 20 Amps The TLP-SF20SL series are lightning and power surge
transient arrestors with surge filtering. These provide
GENERAL SPECIFICATION voltage limitation and filtering of transients for sensitive
electronic devices connected to the mains power supply.
Operating Temp -35 to 70 Deg C The TLP-SF20SL provides effective protection via a three
Storage Temp -55 to 90 Deg C stage circuit. The input stage limits the over-voltage
Humidity 0 - 90% RH excursion, the second stage series surge filter restricts the
Terminals Self opening 0.5 – 4sq mm rate of rise of voltage (dV/dt) of any transient over-voltage
and the final stage clamps the output voltage to a safe
Housing Material MS cover/ ABS base level.
Mounting Style DIN or G rail The TLP-SF20SL must always be installed on the load
Dimensions (LxHxW) 112mm x 75mm x 23.5mm side of a fuse rated at 20 amps or less.
nom. The TLP-SF20SL can be mounted directly on to “G” or
Weight 175 grams “DIN” rails (DIN 46277-1 and 46277-3)
INPUT
POWER BENEFITS:-
♦ Slim 23mm wide metal housing.

UNIT HEALTHY LINE
LED Low “let thru” voltage
♦ Series inductor to control rate of voltage
CB / FUSE
L N E rise
SYSTEM
♦ Protection between all lines
HEALTHY
RCD DEVICE
♦ System Healthy Indicator - LED
TLP-SF20SL
♦ Fast snap on DIN rail mounting
♦ 24kA discharge capacity per line
L N E TLP-SF
♦ For location Cat B to AS 1768:2003
♦ Tested & Passed to IEC 61643-1:2005
♦ Designed to IEEE C 62.41 (UL1449)
♦ Designed and manufactured in Australia to
LOAD
OUTPUT POWER ISO 9001
CLEAN

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
PAGE Page 1 of 2 ISSUE A / Rev C
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-SF20SL-240V revc.docx

Confidential Page 1 November 2, 2011


DATA SHEET Subject to change without notice

MODEL :-TLP-SF20RI-240V
Transtech Lightning Protector/Filter - 20Amp for 240Vac with Relay

TECHNICAL DATA
Voltage rating Normal working voltage
220 - 250V RMS
Max. working volts 275V RMS
Working Freq. 40 - 60 Hz
Peak let thru volts 710V (single pulse)
Protection Modes Ph-N, Ph-E, N-E
Surge Rating:
Imass 108kA
Imax 72kA
Iin 48kA
Operating Burden Approx 7mA
Meets Surge Ratings to AS/NZS 1768:2003
IEEE C 62.41:2005UL 1449
Filter
Inductor Type Common Mode 20A choke
Capacitors X and Y
Attenuation (60dB) 5MHz
Earth Leakage Approx 500uA
GENERAL DESCRIPTION
Operating Current 20 Amps
Maximum Current 22 Amps The TLP-SF20RI series is a series of lightning and power
transient arrestors with filtering + LED and relay output
which provides voltage surge limitation and filtering to
Other Features
sensitive electronic devices connected to the mains power
Relay Output Form C 5A continuous supply and rated up to 20 amps.
(Relay fails to safe position)
Relay Terminals Plug-in 0.5 – 2.5mm The TLP-SF20RI provides effective protection by clamping
the over voltage and via the series filter reducing the rate of
GENERAL SPECIFICATION
rise of the clamped voltage to a safe level.
If a fault occurs within the TLP-SF20RI the “healthy LED will
Operating Temp -35 to 70 Deg C
extinguish and the relay will de-energize).
Storage Temp -55 to 75 Deg C
Humidity 0 - 90% RH
The TLP-SF20RI must always be installed on the load side
Terminals Self opening 0.5 – 4 sq mm
of a protective device rated at 20 amps or less.
Housing Material Mild Steel – DIN clip feet
Mounting Style DIN rail
The TLP-SF20RI can be mounted directly on to “DIN” rails
Dimensions (HxWxD) 120mm x 52mm x 80mm
(DIN 46277-1)
Weight 195 grams

INPUT SUPPLY
ALARM OUTPUT BENEFITS:-

L N E
Low “let thru” voltage
♦ Series filter to control rate of voltage rise
♦ Protection between all lines (diff & common
INPUT N/O COM N/C
mode)

RELAY
Power
Power “ON” indication
TLP-SF20RI-240
SERIES FILTER SURGE PROTECTOR
♦ Unit “HEALTHY” indication (with relay)
Fault

TRANSTECH
♦ Fast snap on DIN rail mounting

OUTPUT
Designed for MEN Systems
♦ Location Category B to AS 1768:2005
♦ Tested to IEEE C 62.41:2005 & compliant)
L N E
♦ Designed and manufactured to ISO 9001

OUTPUT CLEAN SUPPLY
CE / C-tick marking

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
PAGE Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-SF20RI-240.doc

Confidential Page 1 8/9/2012


DATA SHEET
MODEL :-TLP-SP20SL-275
Transtech SERIES/PARALLEL Lightning Protector - 20Amp for 275V

TECHNICAL DATA

Voltage rating Normal working voltage


240V DC/AC
Max. Working volts 275V DC/AC
Working Freq. DC - 60 Hz
Rated Current 20 Amps for series connect
Unlimited for parallel connect
Peak let thru volts 900 V
Protection Modes Ph-N, Ph-E, N-E
Surge Rating;- Ph-N, 24kA, 8/20μS
Ph-E, 24kA, 8/20μS
N-E, 24kA, 8/20μS
Imax 72kA
Earth Leakage Approx 500uA
Continuous Current 20 Amps
(see above re series/parallel)

GENERAL DESCRIPTION
Meets Surge Ratings to AS/NZS 1768:2003
IEEE C 62.41, UL 1449 The TLP-SP20SL range is either a series or parallel
IEC 61643.1:2005 connected lightning and power transient arrestor. The
range provides voltage surge limitation for sensitive
GENERAL SPECIFICATION electronic devices connected to the mains power supply.
Operating Temp -35 to 70 Deg C The TLP-SP20SL must always be installed on the load
Storage Temp -55 to 90 Deg C side of a fuse rated at 20 amps or less.
Humidity 0 - 90% RH
Terminals Self opening 0.5 – 4sq mm The TLP-SP20SL can be mounted directly on to “G” or
“DIN” rails (DIN 46277-1 and 46277-3)
Housing Material M/Steel cover / ABS base
Mounting Style DIN or G Rail
Dimensions (LxHxW) 112mm x 75mm x 23.5mm
Weight 175 grams

SERIES PARALLEL
INPUT
POWER
INPUT BENEFITS:-
POWER
FUSES OUTPUT


Max 20amps TO LOAD
UNLIMITED amps Slim 23mm wide metal housing.
UNIT HEALTHY ♦ Low “let thru” voltage
FUSES

LED
L N E Max 20amps Protection between all lines
UNIT HEALTHY ♦ System Healthy Indicator

SYSTEM
LED
HEALTHY Fast snap on DIN rail mounting
L N E

TLP-SP20SL
24kA discharge capacity per line
SYSTEM
HEALTHY
♦ For location Cat B to AS 1768:2003
L N E TLP-SP20SL ♦ Tested to IEC 61643-1:2005
♦ Tested to IEEE C 62.41 (UL1449)
♦ Designed and manufactured in Australia to
L N E
OUTPUT ISO 9001
TO LOAD
MAX 20amps

CONNECTION SCHEDULE

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE. PAGE 1 / 1
ISSUE A REV B
TRANSTECH ELECTRONIC CONTROLS
Low Cost Surge Protection
www.transtech.com.au

Transtech Electronic Controls Pty Ltd


ABN 21 070 629 499
Perth - Melbourne
Perth Tel: (08) 9302-2044
Melbourne Tel: (03) 9330-3624
Also in Melbourne - Sydney – Brisbane – Adelaide
Info@transtech.com.au
TRANSTECH
DATA SHEET Subject to change without notice

MODEL :- TLP-V60/275/S
Transtech Lightning Protector - 240V Plug-in Protectors CAT C or less

TECHNICAL DATA

Normal Working voltage 240VAC rms


Minimum Working voltage 185VAC rms
Maximum Working voltage 275AC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 1000V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 60kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output MOV failed the relay
de-energizes.
Indicator L1, L2, L3, flag type
GENERAL DESCRIPTION
The TLP-V60/275S is a “new series” PLUG-IN lightning and
transient protector which provides protection for electrical /
GENERAL SPECIFICATION electronic equipment connected to three phase distribution
systems.
Operating Temp -40 to +80 Deg C The TLP-V60/275S is a single mode parallel connected
2 2
Terminals 35mm solid max / 10mm flex max protection device offering 60kA single mode but for all three
2
Remote Terminals Plug in 2.5mm phases. see “1 Pole N/E” version Fig below.
Indicators Green/Red mechanical flag
Housing Material Thermoplastic UL94-V-O For mains supply of greater than 100A adequate HRC fuse or
Degree Protection IP-20 MCB protection must be installed prior to the TLP-xxx- 3P
Dimensions (module) 18 (W) x 60 (H) x 90 (D)
Weight 850 grams
Mounting DIN 43880 Standard DIN Rail
FEATURES

♦ Designed and manufactured to ISO 9001


LOAD SIDE

SUPPLY SIDE
L1
L2
L1
L2
Local status indication by mechanical flag
L3 L3
♦ Remote status indication by c/o relay
♦ High Energy designed pcb’s
PROTECTION
FUSE/MCB

♦ CE Marking / C-tick N 2909


♦ Available in 1P or 2P or 3P bases
L L N L L L
♦ DIN 43880 compliant
♦ Designed to pass IEC 61643-1:2005 and
TRANSTECH TRANSTECH TRANSTECH

AS/NZS 1768:2005
TRANSTECH TRANSTECH TRANSTECH
TLP-V60 TLP-V60 TLP-V60 TLP-V60 TLP-V60 TLP-V60

N/PE PE PE

NOTE: This device must be installed by a Qualified


N N
Electrician.
E E
1 Pole N/E 1 Pole N+E 3 Pole + E
CONNECTION DIAGRAM

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-v60-275s.docx 01 Feb 2013


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-V60/275/SM
Transtech Lightning Protector - 240V Plug-in Protector Range CAT C or less

TECHNICAL DATA

Normal Working voltage 240VAC rms


Minimum Working voltage 185VAC rms
Maximum Working voltage 275AC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 1000V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 60kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output MOV failed the relay
de-energizes.
Indicator L1, L2, L3, flag type
GENERAL DESCRIPTION
The TLP-Vxx/275/S is a “new series” PLUG-IN lightning and
transient protector which provides protection for electrical /
GENERAL SPECIFICATION electronic equipment connected to three phase distribution
systems.
Operating Temp -40 to +80 Deg C The TLP-V60/275SM is the replacement plug-in module
2 2
Terminals 35mm solid max / 10mm flex max single mode parallel connected 60kA protection device.
2
Remote Terminals Plug in 2.5mm
Indicators Green/Red mechanical flag For mains supply of greater than 100A adequate HRC fuse or
Housing Material Thermoplastic UL94-V-O MCB protection must be installed prior to the TLP-xxx- 3P
Degree Protection IP-20
Dimensions (module) 18 (W) x 60 (H) x 90 (D)
Weight 850 grams
Mounting DIN 43880 Standard DIN Rail FEATURES

♦ Designed and manufactured to ISO 9001


SUPPLY SIDE LOAD SIDE
♦ Local status indication by mechanical flag
L1
L2
L1
L2
♦ Remote status indication by c/o relay
L3 L3
♦ High Energy designed pcb’s
♦ CE Marking / C-tick N 2909
PROTECTION
FUSE/MCB

♦ Available in 1P or 2P or 3P bases
♦ DIN 43880 compliant
L L N L L L
♦ Designed to pass IEC 61643-1:2005 and
TRANSTECH TRANSTECH TRANSTECH TRANSTECH TRANSTECH TRANSTECH
AS/NZS 1768:2005
TLP-V60 TLP-V60 TLP-V60 TLP-V60 TLP-V60 TLP-V60

N/PE PE PE
NOTE: This device must be installed by a Qualified
Electrician.
N N
E E
1 Pole N/E 1 Pole N+E 3 Pole + E
CONNECTION DIAGRAM

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-v60-275sm.docx 01 Feb 2013


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-DS60/275-2V
Transtech Lightning Protector - 240V 1P+N E Protector 60kA CAT C or less

TECHNICAL DATA

Normal Working voltage 240VAC rms


Minimum Working voltage 185VAC rms
Maximum Working voltage 275AC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 1000V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 100kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output MOV failed the relay
de-energizes.
Indicator Flag type
GENERAL DESCRIPTION
The TLP-V60/275S is a “new series” lightning and transient
protector which provides protection for electrical / electronic
GENERAL SPECIFICATION equipment connected to a single phase distribution system.

The TLP-V60/275S is a single mode parallel connected


Operating Temp -40 to +80 Deg C protection device offering 60kA single mode L-N and L-E(PE)
2 2
Terminals 35mm solid max / 10mm flex max (see middle Fig bottom left).
Remote Terminals Plug in 2.5mm2
Indicators Green/Red mechanical flag
Housing Material Thermoplastic UL94-V-O
Degree Protection IP-20 For mains supply of greater than 100A adequate HRC fuse or
Dimensions (module) 36 (W) x 60 (H) x 90 (D) MCB protection must be installed prior to the TLP-xxx- 3P
Weight 850 grams
Mounting DIN 43880 Standard DIN Rail

FEATURES
SUPPLY SIDE LOAD SIDE


L1 L1
L2 L2 Designed and manufactured to ISO 9001

L3 L3
Local status indication by mechanical flag
♦ Remote status indication by c/o relay
PROTECTION
FUSE/MCB

♦ High Energy designed pcb’s


♦ CE Marking / C-tick N 2909
L L N L L L
♦ Available in 1P or 2P or 3P
♦ DIN 43880 compliant

TRANSTECH TRANSTECH TRANSTECH TRANSTECH TRANSTECH TRANSTECH
TLP-V60 TLP-V60 TLP-V60 TLP-V60 TLP-V60 TLP-V60
Designed to pass IEC 61643-1:2005 and
AS/NZS 1768:2005
N/PE PE PE

N N
NOTE: This device must be installed by a Qualified
E E Electrician.
1 Pole N/E 1 Pole N+E 3 Pole + E
CONNECTION DIAGRAM

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-ds60-275-2vs.docx 01 Feb 2013


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-V100/275
Transtech Lightning Protector - 240V 1P Protector 100kA CAT C or less

TECHNICAL DATA

Normal Working voltage 240VAC rms


Minimum Working voltage 185VAC rms
Maximum Working voltage 275AC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 1000V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 100kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output MOV failed the relay
de-energizes.
Indicator L1, L2, L3, flag type
GENERAL DESCRIPTION
The TLP-V100/275S is a “new series” lightning and transient
protector which provides protection for electrical / electronic
GENERAL SPECIFICATION equipment connected to three phase distribution systems.

The TLP-V100/275S is a single mode parallel connected


Operating Temp -40 to +80 Deg C protection device offering 60kA single mode.
2 2
Terminals 35mm solid max / 10mm flex max
2
Remote Terminals Plug in 2.5mm
Indicators Green/Red mechanical flag
Housing Material Thermoplastic UL94-V-O For mains supply of greater than 100A adequate HRC fuse or
Degree Protection IP-20 MCB protection must be installed prior to the TLP-xxx- 3P
Dimensions (module) 36 (W) x 60 (H) x 90 (D)
Weight 850 grams
Mounting DIN 43880 Standard DIN Rail
FEATURES

SUPPLY SIDE LOAD SIDE ♦ Designed and manufactured to ISO 9001



L1 L1
L2
L3
L2
L3
Local status indication by mechanical flag
♦ Remote status indication by c/o relay
♦ High Energy designed pcb’s
PROTECTION
FUSE/MCB

♦ CE Marking / C-tick N 2909


♦ Available in 1P or 2P or 3P
L L
♦ DIN 43880 compliant
TRANSTECH TRANSTECH

TLP-V100 TLP-V100
♦ Designed to pass IEC 61643-1:2005 and
AS/NZS 1768:2005

NOTE: This device must be installed by a Qualified


N
E
N
E
Electrician.
1 Pole N+E
CONNECTION DIAGRAM

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-v100-275.docx 01 Feb 2013


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-DS60/275/3V
Transtech Lightning Protector – 3 x 240V Plug-in Protectors CAT C or less

TECHNICAL DATA

Normal Working voltage 240VAC rms L – E(PE)


Minimum Working voltage 185VAC rms
Maximum Working voltage 275AC rms
Working Freq. 40 - 60Hz
Peak let thru volts less than 1000V
Maximum mains current Unlimited (parallel connected)
Must be fuse protected over
100A Mains
Imax 60kA (8/20uS)
Response time Less than 25nS
Relay Contacts SPCO (1 amp @240Vac)
Surge Reset Automatic

SPECIAL FEATURES
Relay Output MOV failed the relay
de-energizes.
Indicator L1, L2, L3, flag type
GENERAL DESCRIPTION
The TLP-DS60/275 3V is a “new series” lightning and
transient protector which provides protection for electrical /
GENERAL SPECIFICATION electronic equipment connected to three phase distribution
systems.
Operating Temp -40 to +80 Deg C The TLP-DS60/275 3V is a single mode parallel connected
2 2
Terminals 35mm solid max / 10mm flex max protection device offering 60kA single mode for Line 1,2,3 and
2
Remote Terminals Plug in 2.5mm Earth – see “3 Pole PE” version Fig below.
Indicators Green/Red mechanical flag
Housing Material Thermoplastic UL94-V-O For mains supply of greater than 100A adequate HRC fuse or
Degree Protection IP-20 MCB protection must be installed prior to the TLP-xxx- 3P
Dimensions (module) 55 (W) x 60 (H) x 90 (D)
Weight 850 grams
Mounting DIN 43880 Standard DIN Rail
FEATURES

♦ Designed and manufactured to ISO 9001


LOAD SIDE

SUPPLY SIDE
L1
L2
L1
L2
Local status indication by mechanical flag
L3 L3
♦ Remote status indication by c/o relay
♦ High Energy designed pcb’s
PROTECTION
FUSE/MCB

♦ CE Marking / C-tick N 2909


♦ Available in 1P or 2P or 3P bases
L L N L L L
♦ DIN 43880 compliant
♦ Designed to pass IEC 61643-1:2005 and
TRANSTECH TRANSTECH TRANSTECH

AS/NZS 1768:2005
TRANSTECH TRANSTECH TRANSTECH
TLP-V60 TLP-V60 TLP-V60 TLP-V60 TLP-V60 TLP-V60

N/PE PE PE

NOTE: This device must be installed by a Qualified


N N
Electrician.
E E
1 Pole N/E 1 Pole N+E 3 Pole + E
CONNECTION DIAGRAM

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-v60-275s.docx 01 Feb 2013


PAGE 1 / 1 ISSUE A / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-LEC-A
Transtech Surge/ Lightning Counter

TECHNICAL DATA

Normal Working voltage 110 - 240VAC


Minimum Working voltage -
Maximum Working voltage 275AC
Working Freq. 40 - 60Hz
Peak let thru volts -
Maximum mains current 100A
Imax -
Response time -
Relay Contacts -
Surge Reset Automatic

SPECIAL FEATURES
Relay Output -
Indicator 2 digit LCD
Battery 7.2V service life 1 year

GENERAL DESCRIPTION
The TLP-LEC-A is a “new series” lightning and transient
protector COUNTER with sensor for electrical / electronic
GENERAL SPECIFICATION equipment connected to three phase distribution systems.

The TLP-LEC-A has a single current sensor for monitoring any


Operating Temp -40 to +80 Deg C one phase – if three phases require monitoring ins tall
Terminals 2.5mm 3 TLP-LEC-A units.
Remote Terminals -
Indicators 2 Digit LCD
Housing Material Thermoplastic UL94-V-O
Degree Protection IP-20
Dimensions (module) 18 (W) x 60 (H) x 90 (D)
Weight 125 grams
Mounting DIN 43880 Standard DIN Rail FEATURES

♦ Designed and manufactured to ISO 9001


♦ CE Marking / C-tick N 2909
♦ Available in 1P only
CONNECTION DIAGRAM
SUPPLY SIDE LOAD SIDE ♦ DIN 43880 compliant
L1 L1
L2 L2
L3 L3
N N
E E
SUPPLY SENSOR
L N

TLP-LEC-A

99

TRANSTECH
NOTE: This device must be installed by a Qualified
Electrician.

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-lec-a.docx 01 Feb 2013


PAGE 1 / 1 ISSUE A / Rev A
TRANSTECH ELECTRONIC CONTROLS Electronic Transient Surge Protection

LOW VOLTAGE & BUS PROTECTORS – Cat B or A


www.transtech.com.au

NEW

Transtech Electronic Controls Pty Ltd


ABN 21 070 629 499
Perth - Melbourne
Perth Tel: (08) 9302-2044
Melbourne Tel: (03) 9330-3624
Also in Melbourne - Sydney – Brisbane – Adelaide
Info@transtech.com.au
TRANSTECH
DATA SHEET Subject to change without notice

MODEL :- TLP-SL62-30D
Transtech Lightning Protector - Dual Channel

TECHNICAL DATA

Voltage rating (per channel)


Normal working volt 30V D.C. (peak AC)
Max. working volts 37V D.C. (peak AC)
Peak let thru volts 43.5V

Current/Resistance rating (per channel)


End to End resist. 6 ohms nominal
Max Current 500 mA
Discharge Current 2kA per mode or 4kA per
line (8/20usec)
Response rating
Response time: Under 10nsec

93mm x 102.5mm x6.2mm

GENERAL SPECIFICATION GENERAL DESCRIPTION


Operating Temp -10 to 70 Deg C The TLP-SL62 series of lightning and transient arrestors are
Storage Temp -40 to 105 Deg C manufactured in a slim-line 6.2mm housing for those applications
Connections Self-opening 2.5mm/12AWG where a high packing factor is required. The units provide
Housing Material Polyester PBT protection for electronic equipment connected to twisted pair
Mounting Style DIN Rail control and communication signal lines.
Dimensions 93.1(d) x 102.5(h) x 6.2(w)
The TLP-SL62-30D has true three stage protection in all modes.
Weight 52 grams

FEATURES

♦ Dual channel unit


TLP-SL62-xxD ♦ Two independent channels ( common earth)
Transient Barrier
♦ 3 stage protection
CLEAN OUT 2

4 5 ♦ Low “let thru” voltage


INPUT 2

♦ Protection between ALL lines


♦ Designed for 3kV impulse protection
3 6 ♦ Fast snap on DIN rail mounting
♦ Fail to safe
♦ Field proven technology
CLEAN OUT 1

2 7 ♦
INPUT 1

4kA discharge capacity per channel


♦ Designed and manufactured to ISO 9001
8 ♦ 6.2mm Slim Profile
1
♦ 300mm uncommitted earthing cable
CAT B ♦ CE marking / C-tick N2909
Imax = 8kA
Voltage (Uc) = V
Earth
N2909

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-SL62-30D new.doc Confidential August 23, 2011
DATA SHEET Subject to change without notice

MODEL :- TLP-SL12-xx
Transtech Lightning Protector for Low Voltages 05V – 48V

TECHNICAL DATA

Voltage rating
Normal working volt 05,12,15,18,24,48V +/-
Peak let thru volts 10,19,25,29,39,78V resp.

Current/Resistance rating
End to End resist. Less than 6 ohm
Max Current 600 mA
Surge Current Imax 2 kA/mode (8/20uS)

Response rating
Response time Under 10nsec

GENERAL SPECIFICATION GENERAL


GENERAL DESCRIPTION
SPECIFICATION
The TLP-SL12-xx series is a very compact 12mm wide
lightning and transient arrester providing protection for
Operating Temp -10 to 60 Deg C
equipment connected to low voltage instrument loops by
Storage Temp -55 to 75 Deg C
limiting the transient over-voltage to less than twice the
Terminals Self-opening 2.5mm/12AWG
normal working voltage.
Housing Material KRILEN
Mounting Style DIN
The TLP-SL12-xx series provides protection between all
Dimensions 110mm X 52mm X12mm
conductors, line to line and each line to earth. It is mounted
Weight 60 grams
on to “DIN” rail (46277-3) and offers screen termination via
terminals and the earth via a 300 mm earth wire “tail”.

CABLE - CABLE -
INPUT INPUT

3
2

4
1

3
2

4
FEATURES
1 2 1 2
3 4 3 4


INPUT INPUT
LINE LINE
Low “let thru” voltage
♦ Protection between ALL lines
CONNECTION

CONNECTION

TRANSTECH TRANSTECH
PARALLEL

♦ Fast snap on DIN rail mounting


SERIES

TLP-SL12-xx
TLP-SL12-xx

♦ Fail to safe status design


♦ Field proven technology
OUTPUT
LINE
OUTPUT
LINE
♦ Low line losses (volt drop)

5 6 5 6
7 8 7 8 Designed and manufactured to ISO 9001

5 6 5 6

7 8 7 8
High stacking density
CABLE -
♦ C-Tick/ CE Compliant
OUTPUT
♦ IEC 1000-4-2 & EN50082
CONNECTION SCHEDULE

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-SL12-xx.docx Confidential November 6, 2012
DATA SHEET Subject to change without notice

MODEL :- TLP-48HM-4W-240
Transtech Lightning Protector - Process Transmitter
Loop plus 240V Supply Protector
TECHNICAL DATA

Voltage Rating
Current Loop: 22V – 48Vdc (black/black)
Supply: 190-265Vac (blue/brown)

Current/Impedance Rating
End to End Impedance: N/A parallel connection
Max Current: N/A parallel connection
Discharge Power: Imax = 10kA (8-20uS wave)

Response rating
Response time: Less than 10nS
EMC Compliance: EN50082 part 2
C-tick / CE compliant
Field Bus: 31.25kbit/s
25mm Hex x 75mm c/- 250mm leads
GENERAL DESCRIPTION
GENERAL SPECIFICATION
The TLP-48HM-4W-240 lightning/transient protector provides
Operating Temp: -20 to 60 Deg C protection for field mounted transmitters or electronic devices mounted
Storeage Temp: -40 to 80 Deg C in exposed areas. The TLP-48HM-4W-240 consists of a high speed
solid state switching network which protects all signal and supply lines
Humidity: 5% to 95% RH and common earth. The front end protection per line has a gas
(Non-condensing) discharge tube with a 10kA rating.
Termination wires: Flying Leads (250mm 1.0mm2)
The housing material is ANSI 316 stainless steel with a 23mm flat for
(colour coding) Blue & Brown for 240vac supply assisting mechanical mounting. The unit is encapsulated in high
Black for 4-20mA signal temperature casting epoxy. This epoxy offers high impact resistance
Green / Yellow for earth with excellent electrical properties and high temperature stability. The
Housing Material: ANSI 316 Stainless Steel standard male thread is the common 20mm conduit entry (20mm ISO,
o M20 x 1.5), several other thread types are available upon request.
Dielectric Strength: 25 C, 50 kHz, 19kV/mm
Thread: a) 20mm ISO (M20 x 1.5) The TLP-48HM-4W-240 is designed to be added to standard
b) ½” NPT installations. Most field transmitters have two conduit entries, one is
used to connect the data cable, the spare can be used for the TLP-
Weight: 185g 48HM-4W-240 connection. Under most field installations no additional
Dimensions: 75mm (L) x 25mm Hex connection boxes are required. Should no spare entry be available
c/- 250mm coloured leads then a simple conduit tee can be used as close as possible to the field
device.
The TLP-48HM-4W-240 connection is a simple parallel connection for
BOTH supply and signal lines (see connection schedule). Care must be
taken in the earthing of the green/yellow earth wire from the TLP-
48HM-4W-240. This earth wire must be earthed to local
general/structural metal work, all leads to be kept as short as possible
at all times.
FEATURES
♦ ESD Protection
♦ Low “let thru” voltage
♦ Protection between ALL lines (including 240vac supply)
♦ Field proven technology
♦ Simple field mounting
♦ Field Buss compatible (4-20mA loop only)
♦ Parallel Connection (No loop impedance)
♦ Designed and manufactured to ISO 9001
♦ C-Tick/CE compliant
♦ Meets AS/NZS 1768:2003 Class B
♦ Meets IEC 61643.1:2005 Class I & II
♦ Auto resetting
♦ High 10kA discharge

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE.
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-48HM-4W-240rev.doc 1st January 2009 PAGE 1 / 1 ISSUE C / Rev A
DATA SHEET Subject to change without notice

MODEL :- TLP-SL12-RS 485MB


Transtech Lightning Protector - RS-485 (Modbus Compatible)

TECHNICAL DATA

Voltage rating
Normal working volt +/- 12V
Peak let thru volts 19V @ 1p = 1A
Peak let thru volts 24V @ 1p = 10A

Current/Resistance rating
End to End resist. Less than 0.6 ohms
Max Current 1 Amp
Discharge Power 400W PPPD @ (8/20uS)
(Peak Pulse Power Discharge)
Response rating
Response time Under 10nsec

GENERAL SPECIFICATION GENERAL


GENERAL DESCRIPTION
SPECIFICATION
The TLP-SL12-RS 485MB is a very compact 12mm wide
Capacitance @ 1mMz, 75pF
lightning and transient arrester providing protection for
Operating Temp -10 to 60 Deg C
equipment connected to the Modbus RS 485 multi-point or
Storage Temp -55 to 75 Deg C
party line bus by limiting the transient over-voltage to less
Terminals Self-opening
than twice the normal working voltage.
2.5mm/12AWG
Housing Material KRILEN
The TLP-SL12-RS 485MB provides protection between all
Mounting Style DIN
conductors, line to line and each line to earth. It is mounted
Dimensions 110mm X 52mm X12mm
on to “DIN” rail (46277-3) and offers screen termination via
Weight 60 grams
terminals and the earth via a 300 mm earth wire “tail”.

FEATURES
L1 +ve RS-485 BUS
Screen

L2 -ve
♦ Low “let thru” voltage
♦ Protection between ALL lines
♦ Fast snap on DIN rail mounting
1
3
INPUT
LINE
2
4
1
3
INPUT
LINE
2
4
1
3
INPUT
LINE
2
4
1
3
INPUT
LINE
2
4
♦ Fail to safe status design
TRANSTECH TRANSTECH TRANSTECH TRANSTECH

♦ High speed switch technology to prevent


TLP-SL12-RS485

TLP-SL12-RS485
TLP-SL12-RS485

TLP-SL12-RS485

signal attenuation
CLEAN

5
7
LINE
6
8
5
7
CLEAN
LINE
6
8
CLEAN

5
7
LINE
6
8
CLEAN

5
7
LINE
6
8
♦ Low line losses (volt drop)
♦ Designed and manufactured to ISO 9001

END OF LINE R

END OF LINE R

C-Tick/ CE Compliant

30 NODES
IEC 1000-4-2 & EN50082
RS 485 STN RS 485 STN RS 485 STN RS 485 STN

CONNECTION SCHEDULE

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-SL12-RS485MB.docx Confidential November 6, 2012
DATA SHEET Subject to change without notice

MODEL :- TLP-DNET
Transtech Lightning Protector - DeviceNet

TECHNICAL DATA

Voltage Rating Supply


Normal Working voltage 24V D.C.
Max. Working voltage 31V D.C.
Varistors voltage 39V D.C.
Surge current 1000A@(8/20uS)

Current/Resistance Rating
End to End resist. Less than 0.2R
Max Current Thin cable = 4Amp
Thick cable = 8 Amp
Discharge Power 300W PPPD@ (8/20uS
(dissipation per line)

Protection
Protection modes CAN-H to CAN-L, CAN-H to Screen
CAN-L to Screen, Screen to V-Screen to V+, V+ to V-
Line Capacitance 15pF GENERAL DESCRIPTION
Breakdown Voltage 26.7V D.C. minimum
Clamp voltage 43.0V D.C. maximum @ (8/20uS)
The TLP-DNET lightning and transient arrestor provides
protection for equipment connected to the DEVICENET
GENERAL SPECIFICATION INTERFACE NETWORK.

Operating Temp -10 to 70 Deg C The TLP-DNET provides very effective protection by
Storeage Temp -55 to 80 Deg C limiting the transient overvoltage to less than twice the
Terminals Self opening normal voltage on the supply and data lines.
2.5mm/12AWG
Housing Material KRILEN The TLP-DNET provides protection between all
Mounting Style DIN conductors, Power/data line to line and line to earth.
Dimensions 75mm X 45mm X 30mm
Weight 120 grams The TLP-DNET can be mounted on DIN rail and the earth
return in via a 5mm earth stud.

CAN bus FEATURES

♦ ESD Protection > 25kV


♦ Low “let thru” voltage
♦ Protection between ALL lines
1 2 3 4 5
V1 L S H V+
BUS CONNECTION
1 2 3 4 5
V1 L S H V+
BUS CONNECTION
BUS INPUT
1 2 3 4 5
V1 L S H V+
BUS CONNECTION
1 2 3 4 5
V1 L S H V+
BUS CONNECTION ♦ Fast snap on DIN mounting
TRANSTECH

X
TRANSTECH

X
TRANSTECH

X
TRANSTECH

X ♦ Fail to safe status design



TLP-DNET TLP-DNET TLP-DNET TLP-DNET
SUPPLY/CONTROLLER
V1 L S H V+
SUPPLY/CONTROLLER
V1 L S H V+ CLEAN LINES
SUPPLY/CONTROLLER
V1 L S H V+
SUPPLY/CONTROLLER
V1 L S H V+
IEC 1000-4-2 & EN50082

1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5

Ultra low capacitance data line


NODES ♦ Field proven technology
♦ Low line losses (volt drop)

PSU NODE PSU NODE PSU NODE PSU NODE
Designed and manufactured to ISO 9001

DeviceNET DeviceNET DeviceNET DeviceNET
STN STN STN STN
High stacking density
CONNECTION SCHEDULE ♦ C-Tick / CE Compliant

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-DNET new.docx Confidential August 25, 2011
TRANSTECH ELECTRONIC CONTROLS Electronic Transient Surge Protection
COMMUNICATIONS PROTECTORS
www.transtech.com.au

Transtech Electronic Controls Pty Ltd


ABN 21 070 629 499
Perth - Melbourne
Perth Tel: (08) 9302-2044
Melbourne Tel: (03) 9330-3624
Also in Melbourne - Sydney – Brisbane – Adelaide
Info@transtech.com.au
TRANSTECH
DATA SHEET Subject to change without notice

MODEL:- TLP-48/RJ45H-4
Transtech Lightning Protector – Ethernet RJ45

TECHNICAL DATA

Voltage rating
Normal working volt 48Volts
Nominal Current 1 Amp or less
Clamping Volts 90Volts line to screen
Impulse Clamping < 600Volts (1kV/us)
Surge withstand Imax 0.3kA (8/20usec)
Energy Level Less than 100 joules

Characteristics
Transmission Speed 100M bpss
Insertion Loss < 3.0 dB at 100MHz
Pins 1 – 2 and 3 - 6

GENERAL DESCRIPTION

GENERAL SPECIFICATION The TLP-48/RJ45H-4 lightning and transient arrestor


provides protection for Ethernet, Twisted Pair Cat 5 ISDN
and DSL Network Cables
Insulation resistance > 10 Megohm
Connections RJ45 Female / Female
The TLP-48/RJ45H-4 provides very effective protection by
Operating Temp -10 to 70 Deg C
limiting the transient over-voltage between the conductor s
Storage Temp -55 to 80 Deg C
of Netowrk cable pairs and the screen
Mounting Style DIN Rail Female to Female
Dimensions 85mm X 25mm X 40mm
The TLP-48/RJ45H-4 utilizes fast response gas filled
Weight 62 grams
arrestors and Transorbs to provide low let thru voltages for
fast transient rise times. The use of low capacitance gas
filled arrestors ensures reliable operation at high
frequencies with low insertion losses.

FEATURES

♦ Low “let thru” voltage


♦ Two Stage protection
♦ Protection between lines and screen
♦ Suitable for 10BaseT and 100BaseT
♦ Aluminium housing
♦ Field proven technology
♦ Low line losses
♦ Designed and manufactured to ISO 9001
♦ C-Tick/ CE Compliant
♦ Complies with IEC 616431L21-2005

IMPORTED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-48_RJ45H4 new.docx Confidential August 25, 2011
DATA SHEET Subject to change without notice

MODEL:- TLP-N/FF
Transtech Lightning Protector – Coax Bulkhead +Tag

TECHNICAL DATA

Voltage rating
Normal working volt 70Volts
Nominal Current 5 Amps or less
Clamping Volts 90Volts line to screen
Impulse Clamping < 600Volts (1kV/us)
Surge withstand 20kA (8/20usec)
Energy Level 400 joules

RF Characteristics
RF Power 50 Watts
Insertion Loss < 0.2dB at 2GHz
VSWR 1.07 : 1 @ 1GHz
1.10 : 1 @ 2GHz

GENERAL DESCRIPTION

GENERAL SPECIFICATION The TLP-N/FF lightning and transient arrestor provides


protection for coaxial lines for radio transmitters, receivers
or HF party line bus.
Capacitance < 1.5pF
Insulation resistance > 10 Megohm
The TLP-N/FF provides very effective protection by
Operating Temp -10 to 80 Deg C
limiting the transient over-voltage between the inner
Storage Temp -55 to 80 Deg C
conductor of the coaxial cable and the screen
Mounting Style Bulkhead/Type N
Female to Female
The TLP-N/FF utilizes fast response gas filled arrestors to
Dimensions 67mm X 25mm X25mm
provide low let thru voltages for fast transient rise times.
Weight 80 grams
The use of low capacitance gas filled arrestors ensures
reliable operation at high frequencies with low insertion
losses.

FEATURES
TLP-N/FF
♦ Low “let thru” voltage
♦ Protection between line and screen
♦ Bulkhead mounting with additional fixed
12 mm
22 mm
20 mm
25 mm “bolt-thru” earth tag
56 mm ♦ Field proven technology
DIMENSIONS ♦ Low line losses
♦ Designed and manufactured to ISO 9001
♦ C-Tick/ CE Compliant
♦ IEC 1000-4-2 & EN50082
♦ AS 1768-2003

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-N_FF new.doc Confidential August 20, 2011
DATA SHEET Subject to change without notice

MODEL:- TLP-F/FF
Transtech Lightning Protector – Coax Type F Cables

TECHNICAL DATA

Voltage rating
Normal working volt 70Volts
Nominal Current 5 Amps or less
Clamping Volts 90Volts line to screen
Impulse Clamping < 700Volts (1kV/us)
Surge withstand 20kA (8/20usec)
Energy Level 400 joules

RF Characteristics
RF Power 50 Watts
Insertion Loss < 0.5dB at 2GHz
VSWR < 1.3

GENERAL DESCRIPTION

GENERAL SPECIFICATION The TLP-F/FF lightning and transient arrestor provides


protection for coaxial lines for radio transmitters, receivers
or HF party line bus.
Capacitance < 1.5pF
Insulation resistance > 10 Gigohm
The TLP-F/FF provides very effective protection by
Operating Temp -10 to 80 Deg C
limiting the transient over-voltage between the inner
Storage Temp -55 to 80 Deg C
conductor of the coaxial cable and the screen
Mounting Style Type F
Female to Female
The TLP-F/FF utilizes fast response gas filled arrestors to
Dimensions 52mm X 25mm X25mm
provide low let thru voltages for fast transient rise times.
Weight 50 grams
The use of low capacitance gas filled arrestors ensures
reliable operation at high frequencies with low insertion
losses.

FEATURES

♦ Low “let thru” voltage


TLP-F/FF
♦ Protection between line and screen
♦ Field proven technology
♦ Low line losses
12 mm
♦ Designed and manufactured to ISO 9001

21 mm
22 mm 25 mm C-Tick/ CE Compliant
55 mm ♦ IEC616431:21
DIMENSIONS ♦ IEC 1000-4-2 & EN50082
♦ AS 1768-2003

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-F_FF new.doc Confidential August 20, 2011
DATA SHEET Subject to change without notice

MODEL:- TLP-F/MF
Transtech Lightning Protector – Coax Type F Cables

TECHNICAL DATA

Voltage rating
Normal working volt 70Volts
Nominal Current 5 Amps or less
Clamping Volts 90Volts line to screen
Impulse Clamping < 700Volts (1kV/us/V)
Surge withstand 20kA (8/20usec)
Energy Level 400 joules

RF Characteristics
RF Power 50 Watts
Insertion Loss < 0.5dB at 2GHz
VSWR <1.3

GENERAL DESCRIPTION

GENERAL SPECIFICATION The TLP-F/MF lightning and transient arrestor provides


protection for coaxial lines for radio transmitters, receivers
or HF party line bus.
Capacitance < 1.5pF
Insulation resistance > 10 Gigohm
The TLP-F/MF provides very effective protection by
Operating Temp -10 to 80 Deg C
limiting the transient over-voltage between the inner
Storage Temp -55 to 80 Deg C
conductor of the coaxial cable and the screen
Mounting Style Type F
Male to Female
The TLP-F/MF utilizes fast response gas filled arrestors to
Dimensions 52mm X 25mm X25mm
provide low let thru voltages for fast transient rise times.
Weight 50 grams
The use of low capacitance gas filled arrestors ensures
reliable operation at high frequencies with low insertion
losses.

FEATURES
TLP-F/MF ♦ Low “let thru” voltage
♦ Protection between line and screen
♦ Field proven technology
12 mm
♦ Low line losses

20 mm
22 mm 25 mm Designed and manufactured to ISO 9001
56 mm ♦ C-Tick/ CE Compliant
DIMENSIONS ♦ IEC616431:21
♦ IEC 1000-4-2 & EN50082
♦ AS 1768-2003

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499
Design changes may occur in the interests of product performance & development E&OE
Page 1 of 1 ISSUE A / Rev A
I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-F_MF new.doc Confidential August 20, 2011
TransTech Electronic Controls Pty Ltd
ABN 21 070 629 499

A GUIDE
TO SPECIFYING
ELECTRONIC SURGE PROTECTION DEVICES
Preface:

This document is meant as a guide to those involved in specifying, applying and/or approving electronic
transient protection devices. It is by no means a definitive paper on the types of transient surge protection
available nor in any way proposes to set out a particular manufacturer, type or technique.

This guide does not address “structural lightning protection” other than to direct the reader to the
Australian Standard AS NZS 1768:2005 and in particular to the proven techniques for effective structural lightning
design and installation. Good structural protection and earthing/bonding is an essential part of minimizing possible
effects from lightning transients.

The most important consideration for any Engineer specifying electronic transient protection is the “let-
thru” voltage as this is critical to the proper functioning of the electronic/electrical equipment it is intended to
protect following a transient. The critical considerations in specifying electronic transient protectors are:

1. Be compatible with the system it is protecting


2. Survive transients and contain any fault condition arising
3. Have a low “let-thru” voltage for ALL conductor combinations
4. Not fail and leave the installation un-protected
5. Be correctly installed and maintained regularly.

1. Compatibility
The protector should not inhibit the systems normal operation if it operates
2. Survival & housing
Transients from a lightning strike (close proximity) can exceed 200,000 amps, however statistically
the average transient is approx 10,000 amps. The IEC Standard uses 10,000 amps as the accepted
“norm”, however AS1768 has adopted 70,000 amps therefore any protector at a point of entry
should have a rating equal to or exceeding 70,000 amps to meet the current Australian Standard.
It is recommended by the leading MOV suppliers that surge protectors incorporating such devices be
constructed of metal as a safety precaution Clause 7.9.2 of IEC61643-1:2005 addresses this aspect.
3. Let-thru voltage
The magnitude of the transient reaching the electronic/electrical equipment is critical and can cause
anything from data-corruption to flash-over and arcing damage. The suitable protector should
therefore offer a let-thru voltage less than the maximum voltage rating for the equipment (the
current IEC states 2.5kV as the minimum insulation level).
Transients occur between all conductors of a system – that is: Ph-N / Ph-E / N-E and in
instrumentation and data-line circuits both Common Mode and Differential Mode. Protectors need to
offer such levels of protection
4. Indication of failure
In-line protectors such as used for 120/240vac sub-circuit, instrumentation and/or data-lines are
inherently “self-revealing” upon a major transient as the circuit invariably goes open. In Main Board
protection systems it is essential to have an indication to warn of failure or degradation of the
protective devices, such indication should be both local visual and a relay output.
5. Installation
The performance of transient protectors depends upon correct installation as they are required to
manage high frequency waveforms, therefore the length and size of connecting cables must be
considered, as a guide refer to AS4070:1992. As a rule of thumb the larger the cross section and the
shorter the cable the better, 500mm of 6 sq mm cable is recommended as a minimum.

I:\Shared\Price Lists & data sheets\Transtech\Application Notes\surge protection guide.docx Updated: 15/11/2011/
TransTech Electronic Controls Pty Ltd
ABN 21 070 629 499

SUGGESTED SPECIFICATION
1.1 Point-of-Entry Main & Sub Distribution Boards.

Provide lightning/transient surge suppression to the mains supply of the main


switchboard and each sub distribution board. Supply, install and connect a … insert
Manufacturer(s)…., orsimilar product of equivalent function and quality to the satisfaction of the
Engineer. Such rating to be no less than 70kA surge capacity according to IEC 61643.1 and
are to include all 3 phases plus Neutral and offer true 3 mode protection.

The installation shall be strictly in accordance with the Manufacturers recommendations.

1.2 Final Sub Circuits

Where indicated on power circuit schedules a series filter surge protector shall be fitted
to protect individual circuits. The series filters shall be …. Insert manufacturer(s)…...or similar
product equivalent in function, size and quality to the approval of the Engineer. Rating shall be
no less than 24kA according to IEC 61643.1 and offer true 3 mode protection. The surge
device shall be compatible with any RCD protection and protect against high frequency noise
and transient surges in all modes (L-N, L-E, N-E). The series protectors shall be constructed to
meet UL 1449 and be Third Party tested to IEC61643.1.

Where alternatives are offered the tenderer shall provide sufficient data to prove that the
alternative complies with the specification.

All transient/surge protection devices shall be mounted to protrude thru the distribution
board escutcheon plate and shall have visible status indication. Where nominated such series
surge filters shall have in addition an incorporated relay that monitors the health of the
protection device and provides a volt-free changeover contact for monitoring by the Building
Management System (BMS).

I:\Shared\Price Lists & data sheets\Transtech\Application Notes\surge protection guide.docx Updated: 15/11/2011/
TransTech Electronic Controls Pty Ltd
ABN 21 070 629 499

SURGE CURRENT CAPACITY & FUSING


REF: AS/NZS 1768:2005

1. INTRODUCTION

The committees of all International Standards, after years of research have decided that the average
indirect lightning surge is only 10kA, Standards Australia, however, via AS1768:2005 Table F1 states
70kA as a maximum indirect lightning surge value,

Transtech has therefore taken the decision to meet the higher level as detailed by Standards Australia
and as a consequence the main board of the TLP range of Surge Protectors is designed to withstand
multiple transient surges of 70kA and a single surge of 140kA.

NOTE: The fault rating assigned to a Mains Surge Protector is not to be confused with the switchboard
bus bar fault rating. A transient/lightning surge rating is based upon an 8/20micro second waveform
therefore a duration of only 28 microseconds.

2. DESIGN OF TRANSTECH MAINS PROTECTORS

Transtech Electronic Controls Pty Ltd has been designing and manufacturing electronic transient/surge
protectors since 1996 and has supplied some of Australia’s biggest Companies not to mention delivering
over 15,000 pcs of its 20Amp single phase series filters to the BER Project Australia Wide.

Based upon the preceding information, Transtech Electronic Controls Pty Ltd designs its
TLP Mains Surge Protectors with high quality 70micron copper board and accurately calculated track
sizing designs. Surge protectors with ratings above 70kA simply offer extended lifetimes to users.

3. PROTECTING A TLP MAINS PROTECTOR

Protection of a Mains Surge Protector is governed according to AS3000. It is a requirement to protect the
circuit with either an HRC Fuse or a MCB, the HRC Fuse or MCB size is determined firstly by the Fault
Rating of the Switchboard and secondly by the wire size supplying the TLP.

3.1.1. SWITCHBOARD FAULT RATING


This refers to the bus bar fault level, therefore any protection device such as an HRC Fuse or
a MCB must be in accordance with suppliers ratings and application advice (an example
being Schneider Cascading & Enhanced Discrimination tables)

3.1.2. WIRE SIZE


Transtech Electronic Controls Pty Ltd recommends the maximum size wire to connect a TLP
2
Mains Protector – that is 16 mm therefore according to AS3000 Table B2 the HRC Fuse or
MCB shall be 50 amps maximum.

3.1.3. PROTECTION SELECTION (amp rating)


As per preceding comments, either an HRC Fuse or MCB is required to protect and provide
isolation for the Mains Surge Protector. The factors to be considered in the selection of a
suitable primary protection device are as per Clauses 3.1.1 and 3.1.2 above.

The current rating of the HRC or MCB should be between 25 amps and 50 amps.

I:\Shared\Price Lists & data sheets\Transtech\Application Notes\fault rating design and fuse sizes.docx
TransTech Electronic Controls Pty Ltd
ABN 21 070 629 499

SUMMARY.

A. Transtech Electronic Controls Pty Ltd follows AS1768:2005 and all other relevant Standards in its
designs and meets them regarding surge fault ratings.

B. Transtech Electronic Controls Pty Ltd Mains Surge Protectors cover all Category’s E / D / C / B / A

C. Transtech Electronic Controls Pty Ltd manufactures Mains Surge Protectors offering Surge Fault
ratings in excess of 70kA, these simply offer the user extended lifetime.

D. The fault ratings of the TLP Mains Surge Protectors should not be confused with switchboard bus bar
fault ratings.

E. All Transtech Mains Surge Protectors type TLP’s have internal MOV protection fuses suitable to break
100Amps.

F. The fault rating of a TLP Mains Surge Protector is based upon a very short time of 28 microseconds,
not to be confused with a typically 1sec rating as for switchboard Type Tests.

G. Transtech Electronic Controls Pty Ltd has been designing electronic surge protectors for over 16
years and accurately designs the circuit board layout in its TLP series to withstand a 70kA 8/20
microsecond surge.

H. PROTECTION TABLE:

TLP MODEL RECOMMENDED AMPS COMMENT


DEVICE

TLP-SF20SL-240V HRC 25 Single phase series filter


TLP-40-xP HRC 40
TLP-80-xP HRC 50
TLP-120-xP MCB 50 MCB’s not tripped by transient
TLP-160-xP MCB 50 MCB’s not tripped by transient
TLP-200-xP MCB 50 MCB’s not tripped by transient
TLP-240-xP MCB 50 MCB’s not tripped by transient

I:\Shared\Price Lists & data sheets\Transtech\Application Notes\fault rating design and fuse sizes.docx
Transtech Electronic Controls Pty Ltd

Australian Agent for:

HAZARDOUS AREA ENCLOSURES

HIGH SPEED SENSORS & TACHOS

ALARM ANNUCIATORS

ENCODERS AND TECHOS

HAZARDOUS AREA FLOW/TEMP/PRESSURE

PROXIMITY SENSORS & PE CELLS

Transtech Electronic Controls Pty Ltd


ABN 21 070 629 499
Perth - Melbourne
Perth Tel: (08) 9302-2044
Melbourne Tel: 0400 848-064
Also in Sydney – Brisbane – Adelaide Info@transtech.com.au
TRANSTECH