Professional Documents
Culture Documents
I. DESCRIPTION
The INS DME LDB – 102 is a dual 1-kW, enroute, ground based navigational aid which provides
slant-range distance information between aircraft and ground station. Signals transmitted
between an aircraft and a DME ground beacon enables the aircraft to accurately determine its
distance from the beacon.
The DME consists of three subsections namely, Transponder Subsystem, Control & Test
Subsystem, and Power Supply Subsystem. The Remote Control and Monitoring System (RCMS)
feature of the system allows operator at the remote site to monitor the detailed performance
and provides basic control of the equipment.
II. SPECIFICATION
The performance parameters of the major system function are given in Table 1.
CHARACTERISTIC PARAMETER
Frequency and Pulse Characteristics
Operating Channel Channel 81X
Pulse Spacing
Transmit 12.0 ± 0.1 μs
Decode 12.0 ± 1.0 μs
Transmitter
Operating frequency 1168 MHz
Frequency accuracy ±0.002%
Peak output power 1 kW
Transmission rate
Minimum 945 pp/s
Maximum 2 800 pp/s
Pulse Shape
Width 3.5 ± 0.5 μs
Rise Time 2.25 ± 0.75 μs
Fall Time 2.5 ± 1.0 μs
Ident
Rate 1350 ± 25 pp/s
Repeat Interval 40 sec nominal
Receiver
Operating frequency 1105 MHz
Frequency stability 0.002%
Sensitivity (70% reply) -91dBm (at cabinet connector)
Adjacent channel rejection 80dB min
IF Rejection 80dB min
Spurious Rejection 80dB min
System time delay 50 μs
System
Transponder capacity 100 interrogators
Monitoring Alarm Limits
Reply Delay Adjustable to ± 1 µsec, in 0.1 µsec steps
Pulse spacing Adjustable to ± 1 µsec, in 0.1 µsec steps
Reply efficiency 60%
Power Adjustable from -1 to -6 dB decrease
Transmitter pulse rate Below 833 pp/s or exceeds 3000 pp/s
Identification Absence of 40 to 120 seconds, adjustable
Pulse width ±0.5 µsec, adjustable
Pulse rise & fall times Exceed 3.5 µsec, adjustable
Antenna (omni-directional type)
Polarization Vertical
Gain (mean) 8dBi
VSWR 2:1 maximum
Pattern circularity ± 0.5 dB
Input Power
Primary supply 200 to 260 V AC, 50/60Hz 350VA
Standby Power 21 V to 28V DC (24V DC nominal)
Current 12A maximum (1kW DME, max traffic)
Environmental
Indoor equipment
Temperature -10°C to +60°C
Humidity 95% (to 45°C); 50% (45°C to 60°C)
Antenna
Temperature -40°C to +70°C
Humidity 100%
Switching On Procedure
A. Local Operation.
1. Set the Front Panel controls as shown in the table below prior to placing the Beacon into
operation.
AC PWR NORM
BATT CHG1
BATT CHG2
LOCAL (press LOCAL pushbutton if the indicator is of)
SELECT MAIN, OFF/RESET (press OFF/RESET pushbutton if the indicator is of)
Check that the following CTU front panel indicators are of:
TEST section:
MODULES
ANT RELAY
POWER section:
BATT LOW
STATUS section:
NO1 ON
NO2 ON
NORMAL
TRANSFER
SHUTDOWN
MAINTENANCE
3. On the CTU, press the SELECT MAIN, NO1 or NO2 pushbutton. This activates the rack in its
normal operating mode. The following indications should result:
a. SELECT MAIN, NO1 or NO2 indicator on.
b. NO1 ON or NO2 ON status indicator on.
c. NORMAL status indicator on, after the selected POWER ON inhibit time. This
indicates that the monitor is powered, and no faults are detected.
d. All the ALARM REGISTER indicators of immediately, and stay of unless a fault is
present.
4. Check that no unit or module has a red indicator on. A red indicator on indicates that a test
switch is not in the NORMAL position, or a fault is present. Note: A monitor module self test
occurs every 15 seconds (±2 sec), and will produce a momentary PRIMARY fault display on
the monitor module. This is normal operation.
B. Remote Operation.
1. At the DME site, refer to Switching On Procedure Local Operation steps 1 & 2.
2. On the CTU, press the SOURCE, REMOTE pushbutton.
3. At the remote site run the CMT program and open the CONTROL menu to open the Control
Equipment Dialog Box (refer to Use of Standby/Reserve Equipment Remote Operation section
for complete steps).
4. When the Control Equipment dialog box opens, select Connect. After a few seconds, the
equipment status will be displayed in the Equipment Status window.
5. Select NO 1 or NO 2 to the right of Select Main to select the system to be used as main. Then
click Close.
6. The following indications should result:
e. SELECT MAIN, NO1 or NO2 indicator on.
f. NO1 ON or NO2 ON status indicator on.
g. NORMAL status indicator on, after the selected POWER ON inhibit time. This
indicates that the monitor is powered, and no faults are detected.
All the ALARM REGISTER indicators of immediately, and stay of unless a fault is present.
7. Check that no unit or module has a red indicator on. A red indicator on indicates that a test
switch is not in the NORMAL position, or a fault is present. Note: A monitor module self test
occurs every 15 seconds (±2 sec), and will produce a momentary PRIMARY fault display on
the monitor module. This is normal operation.
B. Remote Operation
1. With the Control Equipment Dialog Box opened, select Connect, then OFF to switch the
navaid of. The indicators in the STATUS section should go of, after a short delay. The OFF/RESET
indicator should be on, and the SELECT MAIN, NO1 and NO2 indicators should be of.
2. The Power Distribution Panel circuit breakers should be switched of followed by AC Power
Supplies switches.
MAIN/STANDBY OPERATION
Proper coordination with ATMO on duty must be observed prior to making changes on
equipment controls.
System interchange should be done every month (during conduct of DME Monthly PMI) and with
the procedures strictly followed.
Local Operation:
1. On the CTU, press the LOCAL control source pushbutton.
2. On the CTU, press the SELECT MAIN, NO 1 or NO 2 pushbutton (depending on which system
will be utilized).
3. The following indicators should result:
a. SELECT MAIN, NO 1 or NO 2 indicator on.
b. NO 1 or NO 2 ON status indicator on.
c. NORMAL status indicator on, after the selected Power On inhibit time. This indicates
that the Monitor is powered, & no faults are detected.
d. All Alarm Register indicators of immediately, & stay of unless a fault is present.
e. Check that no unit or module has a red indicator on.
Remote Operation
1. On the CTU, make sure that the SOURCE, REMOTE indicator should be on.
2. At the remote site (DME RCMS Workstation), check if the CMT software is loaded. If not, double-
click the CMT icon on the RCMS desktop. Note: If the CMT software is already running and an
Operator already logged in, proceed to No. 5.
3. The Operator Dialog Box will open over the CMT window. The operator must be logged in to
access the CMT menus. Select the Operator’s name from the operator’s list. After which, select
LOG-IN. The Password Dialog Box will then open.
4. Type in the operator’s password, remembering that the password is case sensitive. Then select
OK. Then click CLOSE to return to the CMT Window.
5. Select the Navaid Site by double-clicking the site icon, labeled as CATICLAN. Select the required
equipment 1kW DME and then select CONTROL menu to open the Control Equipment Dialog
Box.
6. When the Control Equipment dialog box opens, select Connect to establish a communications
link with the selected Navaid Site. The message, Executing Command – Please Wait… will be
displayed at the bottom of the dialog box until the connection is established. Following
successful connection, the equipment status will automatically be requested and the message at
the bottom of the dialog box will change to Retrieving Status – Please Wait…
7. After a few seconds, the equipment status will be displayed in the Equipment Status window of
the dialog box and the message at the bottom of the dialog box will change to Operation
Successful. Once communications have been established with the site, the various control
options will be enabled. Note: If reliable communications cannot be established, a message,
Failure will be displayed at the bottom of the dialog box.
8. Select OFF, then NO 1 or NO 2 to the right of Select Main to switch the navaid of or select the
unit to be used as main. Whenever a Select Main button is selected, the message, Executing
Command – Please wait… will be displayed at the bottom of the dialog box until the command is
executed. Following a successful execution of the command, the message will change to
Settlement Delay – Please Wait while the equipment is allowed to settle before status is
requested. The equipment status will then automatically be requested and the message at the
bottom of the dialog box will change to Retrieving Status – Please wait… After a few seconds,
the equipment status will be displayed in the Equipment Status window of the dialog box and the
message at the bottom of the dialog box will change to Operation Successful.
Note: If a navaid cannot action the command (for example, requesting NO 2 while NO 1 is still ON
in a dual), the message Command Rejected will be displayed at the bottom of the dialog box.
9. Click DISCONNECT, and then CLOSE.
10. At the DME site, ensure that the following indicators should take efect:
a. SELECT MAIN, NO 1 or NO 2 indicator On.
b. NO 1 or NO 2 ON status indicator On.
c. NORMAL status indicator On, after the selected Power On inhibit time. This indicates
that the Monitor is powered, & no faults are detected.
d. All Alarm Register indicators of immediately, & stay of unless a fault is present.
e. Check that no unit or module has a red indicator on.
ADJUSTMENT PROCEDURES
For Procedural Requirements prior to the specific adjustments, refer to Section 3.2.4.3 of the 1kW
DME Station LDB – 102 Technical Handbook, Vol. 2.
The table below summarizes the adjustment and its corresponding section on the Vol. 2 of the
Handbook.
Table 3 – Alignment and Adjustment of DME LDB – 102
ADJUSTMENT SECTION
Test Interrogator Alignment
RF Generator 3.2.4.4.1
RF Generator at Nominal Interrogation Frequency 3.2.4.4.2
Receiver Video Alignment 3.2.4.7
Transmitter Driver RF Output Alignment 3.2.4.8
1kW RF Power Amplifier Alignment
Output Pulse Alignment 3.2.4.9.1
Automatic Level Control 3.2.4.9.2
Transmitter Pulse Parameters
Output Pulse Peak Power Calibration 3.2.4.10.5
Receiver On-channel Threshold Adjustment 3.2.4.11.1
Internal Ident Adjustment 3.2.4.14.1
Monitor Fault Limits Adjustments 3.2.4.15
Control System Adjustment
HV Shutdown Adjust 3.2.4.16.10
LV Alarm Adjust 3.2.4.16.11
LV Shutdown Adjust 3.2.4.16.12
V. CORRECTIVE MAINTENANCE