HINDUSTAN ZINC LTD

Doc Ref.No.
1 X 80MW, ZAWAR CPP
ZAWAR MINES, RAJASTHAN 3VYN591602

ABB LIMITED SIZING CALCULATION FOR UPS


Sheet 1 of 3

SIZING CALCULATION FOR UPS

OWNER: HINDUSTAN ZINC LIMITED.


ZAWAR MINES, RAJASTHAN.

TATA PROJECTS LTD.


HYDERABAD.
MAIN
CONTRACTOR

e-BOP ABB LIMITED.


CONTRACTOR: FARIDABAD.

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
© ABB eBoP.
HINDUSTAN ZINC LTD
Doc Ref.No.
1 X 80MW, ZAWAR CPP
ZAWAR MINES, RAJASTHAN 3VYN591602

ABB LIMITED SIZING CALCULATION FOR UPS


Sheet 2 of 3

REVISION STATUS SHEET

REV. NO. DATE DESCRIPTION

10.07.2007 FOR REFERENCE ONLY


R0

Rev. No. Date KK AB For Reference

R0 10.07.2007 Prepared by Reviewed by Remarks

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
© ABB eBoP.
HINDUSTAN ZINC LTD
Doc Ref.No.
1 X 80MW, ZAWAR CPP
ZAWAR MINES, RAJASTHAN 3VYN591602

ABB LIMITED SIZING CALCULATION FOR UPS


Sheet 3 of 3

LOAD IN
S.No. FEEDER/LOAD DESCRIPITION REMARKS
kVA
A BTG LOADS
1 SG/TG DCS 12 Reference has been taken from
UPS sizing calculation of HZL,
Phase-I, Unit-1. Vide Doc. No:
TCE.4221A-EL-CAL-580-01, R1,
Dated 08-09-2004
2 BOP DCS 6.5

3 HMI & MAXNET FOR UNIT # 1 10

4 6.5 Feeder Description not enlisted in


the TPL document. However, load
has been retained.
5 MAX DNA – BMS PANELS (SOLENOIDS) 4.0

6 LEVEL SWITCH 1.0

7 VMS 0.75

8 EWLI 1.20

9 COAL FLOW DETECTOR 0.60

10 ESP IOS 2.0

11 LIGHT OIL FLOW METER PD TYPE 0.2

12 SPARE FEEDERS 1.5

13 CONTROL PANEL (FOR TRANSDUCERS & 0.55


RECORDERS)
14 TSI MONITORING SYSTEM 0.25

15 VMS SYSTEM WORK STN & PRINTER 1.5

B BOP LOADS

1 SWAS & GAS ANALYSERS 2.00

C TOTAL KVA 50.55

LOADING FACTOR OF 25% AS PER CON- 63.18


TRACT
UPS RATING (STANDARD RATING) 65 KVA As per the standard rating.

CONCLUSION

Selected UPS Rating : 65 kVA


Voltage Rating : 110V AC
No. of UPS per Unit : 1 No., parallel redundant type
in line with HZL, phase-1 & 2.