TS 99

EN 2-5

Free-swing
slide channel
door closer
in Contur design
DORMA TS 99 Free-swing slide channel
door closer

For easy use of fire and smoke Data and features


TS 99 TS 99 TS 99
FL FLR FLR-K
check doors combined with safe Adjustable spring
closing in an emergency. strength setting Size EN 2-5 EN 2-5 EN 2-5
Standard doors ≤ 1250 mm 2 2 2
The DORMA TS 99 FL in the built-in smoke detector
Fire and smoke
Contur design is a hold-open system, is also available in check doors 2 2 2
≤ 1250 mm
device with a free-swing the form of the DORMA
Non-handed 2 2 2
function from a door opening TS 99 FLR or TS 99 FLR-K.
Slide channel 2 2 2
angle of > 0°, which, com- In both systems, the door can
bined with a smoke detector be operated without resis- Closing speed adjustable at valve 2 2 2
system (e.g. DORMA RMZ), tance thanks to their free- Latching action adjustable at valve 2 2 2
can be used as a hold-open swing feature. In the event Cushioned limit stay, mechanical " " "
system for fire doors. of an alarm or power failure,
Free-swing function from
An integrated solution, i.e. however, the door isreliably a door opening angle of > 0° 2 2 2
hold-open device with free- closed by the re-instated Weight in kg 5,2 5,9 5,7
swing function from a door action of the door closer.
Dimensions Length 413 785 413
opening angle of > 0°, plus Certified to ISO 90001. in mm (without Overall depth   52   52   52
slide channel) Height   71   71   71
Door closer compliant with EN 1154 2 2 2
Plus points
Hold-open device compliant
with EN 1155 2 2 2
For the trade 2 Uniform appearance
2 Ideal complement to the matching all products of Hold-open device compliant
under preparation
product range the DORMA Contur design with DIN EN 14637
2 Clear range structure for mark for building products 2 2 2
For the user
easy stock management Functions Smoke detector – 2 2
2 Free-swing function from a
Release device 2 2 2
For the installer/fabricator door opening angle of > 0°
Power supply unit – 2 2
2 Easy and quick to fit 2 Resistance-free opening
Scattered light
2 Flexible application suita- of doors in passive/preven- Smoke
principle – 2 2
bility thanks to standard tive fire protection appli- detection
Optical sensor
leaf or overhead transom cations Connection of other detectors – 2 2
installation 2 Maximum degree of user
Total installed load (max.)
safety – 7,8 7,8
For the architect/specifier for further detectors in W
2 Meets legal requirements LED indicators Alarm – 2 2
for barrier-free building Standby – 2 2
Maintenance due – 2 2
2 Universally suitable for
Contaminated – 2 2
single or double doors
Input voltage 24 V DC 230 V AC 230 V AC
± 15 % + 10 % / – 15 % + 10 % / – 15 %
F Approval certification Output voltage – 24 V DC 24 V DC
TS 99 FL When using the TS 99 FL in Power consumption in W 2 14,8 14,8
The DORMA TS 99 FL is a transom-mounted arrange- Floating change-over contact, 24 V 24 V
approved and certified by ment, a certificate of com- safety extra low voltage (SELV) – AC/DC AC/DC
2A 2A
the MPA NRW, Dortmund, pliance in conjunction with
to EN 1155. the relevant fire and smoke Reset Manual reset – 2 2
check door is mandatory. Connection terminals
– 2 2
for external manual release
TS 99 FLR for use as a hold-open Degree of protection – IP 20 IP 20
The DORMA TS 99 FLR is system. An acceptance 2 Yes – No " Option
approved and certified by inspection is mandatory.
the MPA NRW, Dortmund, Certificate of compliance in
to EN 1155. Approved by conjunction with the fire and Note
the German Institute for smoke check door concerned According to the regulations This switch must be red and
Building Technology, Berlin, is additionally required. governing hold-open systems carry the inscription “Close
issued by the Institute of Door”. The switch must be
TS 99 FLR-K the German Institute for Building Technology (DIBt), located in the immediate
The DORMA TS 99 FLR-K Building Technology, Berlin, Berlin, a manual release vicinity of the door and must
is certified and approved by for use as a hold-open switch (e.g. DORMA HT) not be hidden by the opened
the MPA NRW, Dortmund, system. An acceptance must be provided for free- door.
to EN 1155. Approved by inspection is mandatory. swing door closers.

2 TS 99 FL/FLR, GB
DORMA TS 99 FL
506,5

31 428

23
106

16 11 16

18 18
71
4
52
93 200
64 160

413

DORMA TS 99 FLR
785

52 430 69 131 29 64

16 11 16
18 18
71
106

23

31 428

441

DORMA TS 99 FLR-K
823
40 428
30
115

16 11 16

18 18
71

4
52
93 200

64 160
413

Free-swing function from an opening angle > 0°


As the door is opened, the In the event of a fire or power
free-swing function is activated failure, the door is automati-
from an opening angle of > 0°. cally and safely closed by the
The free-swing function door closer. This system is
enables the door to be opened ideal for ensuring the closure
with ease by reducing the of fire and smoke check
amount of resistance encoun- doors in senior homes, centres
tered by the user. The door for the disabled, hospitals
remains freely operable and and clinics.
is not automatically closed,
facilitating access in both 1 Free-swing range
directions in heavily frequen- 2 Fully controlled closing
ted zones and passageways. action (mechanical)
2 1

TS 99 FL/FLR, GB 3
DORMA TS 99 FL Hold-open device
with free-swing function

Applications and fixing

max. 10 143 441

32 150 428

34
65
42

72
16

120
110

78
175

24 V DC
142 160

DORMA TS 99 FL door closer, standard application (door leaf fixing)


Examples: Anticlockwise-closing (ISO 6/LH) door; mirrored arrangements apply to clockwise-closing (ISO 5/RH) doors

450
171 200 ø 8 24 V DC
78
max. 7
36

42
84
23
41,5

27,5
11

150 428
143 441

175

DORMA TS 99 FL door closer, frame mounted (transom fixing)


Examples: Anticlockwise-closing (ISO 6/LH) door; mirrored arrangements apply to clockwise-closing (ISO 5/RH) doors

4 TS 99 FL/FLR, GB
1 2 3 4 5
DORMA TS 99 FLR Hold-open device
TS 99 FLR with
TSfree-swing
99 FLR-K function TS 99 GSR-EMR TS 93 GSR-EMR/BG RMZ
TS 93 EMR TS 93 GSR-EMR

min.10

min.10
min.10

min.10
min. 10

min.10
504 126,5

171 200 430

78
max. 7

ø 14 (230 V AC) ø 14 (24 V DC)

7
36

84
41,5

23

30
11

150 428

min.10

min.10
min.10

min.10
min. 10

143 441

min.10
175

1 2 3 4 5
S 99 FLR TS 99 FLR-K TS 99 GSR-EMR TS 93 GSR-EMR/BG RMZ
TS 93 EMR TS 93 GSR-EMR

DORMA TS 99 FLR door closer


Examples: Anticlockwise-closing (ISO 6/LH) door; mirrored arrangements apply to clockwise-closing (ISO 5/RH) doors
min.10

min.10
min.10

min.10

min.10

max. 10 ø 12 (230 V AC) 150 428 24 ø 10 (24 V DC)

40 125
5

5
30

43
65
42

72
71

120
110
16

78 4
52
min.10

min.10
min.10

min.10

24 V DC 171 200
142 160
min.10

DORMA TS 99 FLR-K door closer


Examples: Anticlockwise-closing (ISO 6/LH) door; mirrored arrangements apply to clockwise-closing (ISO 5/RH) doors

TS 99 FL/FLR, GB 5
DORMA TS 99 FL Application
on double doors

The modular TS 93 GSR operable and is not automa- The system operates inde-
system also enables the use tically closed, which facili- pendently of the door closer
of the TS 99 FL EN 2-5 on tates access in doors located hydraulics using a push rod
the active leaf of double in heavily frequented areas. clamping arrangement with
doors. As the door is opened, The GSR system ensures protective overload release.
the free-swing function is the closure of double doors The door release/closer
activated from an opening in the correct sequence: activator mechanism is inte-
angle of > 0° at the active first the inactive leaf then grated in the slide channel.
leaf. The door remains freely the active leaf.

DORMA TS 99 FL GSR DORMA TS 99 FL GSR-EMF 1

Door co-ordinator with Door co-ordinator with In the event of an alarm or


free-swinging active leaf free-swinging active leaf and power failure, the hold-open
The GSR system ensures electro-mechanical hold- is released and the door
the closure of double doors open of the inactive leaf co-ordinator ensures that
470
in the correct sequence: The GSR-EMF 1 system the door leaves close in the
34
first the inactive leaf then ensures the closure of correct sequence.
the active leaf. double doors in the correct The release signal is emitted
sequence: first the inactive by external smoke detectors

43
leaf then the active leaf. It (e.g. DORMA RMZ in the

4
also facilitates the combined Contur design).
TS 93 B
hold-open of both door DORMA RM-N units can 84
leaves. The inactive leaf can also be connected as a 142 160
be held at an angle between second and third detector.
80° and 130°, and the With adjustable pull-off
active leaf is held open at force (no tools required),
any angle up to max. 150° the hold-open can also be
by the door co-ordinator. readily released by hand.
Note: The hold-open point
Inactive leaf
of the inactive leaf is always Minimum width 370 mm
located at the maximum in the case of unequal leaves
door opening angle – install
a door stop at this position.

DORMA TS 99 FL GSR-EMR 1

Door coordinator with In the event of an alarm or


free-swinging active leaf, power failure, the hold-open
electro-mechanical hold- is released and the door
open of the inactive leaf and co-ordinator ensures that 470
integral smoke detector the door leaves close in the
The GSR-EMR 1 system. correct sequence. Hold- 34
ensures the closure of open release is initiated by
double doors in the correct the GSR-EMR via a smoke
sequence: first the inactive detector integrated in the
leaf then the active leaf. It door coordinator.
43

also facilitates the combined DORMA RM-N units can


4

hold-open of both door also be connected as a TS 93 B


leaves. The inactive leaf can second and third detector. 84
be held at an angle between With adjustable pull-off 142 160
80° and 130°, and the force (no tools required),
active leaf is held open at the hold-open can also be
any angle up to max. 150° readily released by hand.
by the door co-ordinator. Note: The hold-open point
of the inactive leaf is always
Inactive leaf
located at the maximum
door opening angle – install
a door stop at this position.

6 TS 99 FL/FLR, GB
Ø8 (24 V DC)
115 470
34

120
78

110
TS 99 FL

160 142
24 V DC
1350 – 2500

Active leaf
min.10

444 470

250 34

31 95
2,5

2,5

120
110

TS 99 FL
Ø10 (230 V AC) Ø8 (24 V DC)
78
160 142
24 V DC
1700-2500

Active leaf

TS 99 FL/FLR, GB 7
DORMA TS 99 Application examples
Hold-open system

DORMA TS 99 FL + RMZ + 2x RM-N

RM-N

230 VAC
RM-N
RMZ
2 x 121 KΩ 2 x 121 KΩ

TS 99 FL

1 234 1 234
C C

B - B -
T + T +
HT
- -
A A
12 3 11 10 2 14

DORMA RM-N DORMA RM-N

7 8 9 16 1 4

HT Junction box Fuse


by others by others
B 10 A
TS 99 FL
N PE L
230 V AC
± 10%
121 KΩ
RMZ

Recommended cabling:
I - Y (St) Y 2 x 2 x 0,6

DORMA TS 99 FLR + 2x RM-N

RM-N

230 VAC RM-N

2 x 121 KΩ 2 x 121 KΩ
TS 99 FLR

1 234 1 234
C C

B - B -
HT
T + T +
- -
A A
12 3 11 10 2 14

DORMA RM-N DORMA RM-N

7 8 9 16 1 4

12 4 1

HT Junction box Fuse


by others by others
B 10 A

N PE L 230 V AC
± 10%
121 KΩ TS 99
FLR

Recommended cabling:
I - Y (St) Y 2 x 2 x 0,6

8 TS 99 FL/FLR, GB
DORMA TS 99 FLR-K + 2x RM-N

RM-N

230 VAC
RM-N

2 x 121 KΩ 2 x 121 KΩ

TS 99 FLR-K

1 234 1 234
C C

B - B -
T + T +
HT - -
A A
12 3 11 10 2 14

DORMA RM-N DORMA RM-N

7 8 9 16 1 4

HT Junction box Fuse


by others by others
B 10 A

N PE L 230 V AC
± 10%
121 KΩ TS 99
FLR-K

Recommended cabling:
I - Y (St) Y 2 x 2 x 0,6

DORMA TS 99 FL GSR-EMR 1 + 2x RM-N

RM-N

230 VAC
RM-N
GSR-EMR
2 x 121 KΩ 2 x 121 KΩ
TS 99 FL TS 93

Active leaf Inactive leaf


1 234 1 234
HT C C

B - B -
T + T +
- -
A A
12 3 11 10 2 14

DORMA RM-N DORMA RM-N

7 8 9 16 1 4

Junction box Fuse


HT by others by others
B 10 A

N PE L 230 V AC
± 10%
121 KΩ
TS 93
GSR-EMR

Recommended cabling:
I - Y (St) Y 2 x 2 x 0,6

TS 99 FL/FLR, GB 9
DORMA RMZ Smoke detectors
DORMA RM-N

The DORMA RMZ in the issued by the German Data and features RMZ RM-N
Contur design and DORMA Institute for Building Techno-
Functions Smoke detector 2 2
RM-N smoke detectors pro- logy and ensure perfect
Release device 2 –
vide the ideal complement interaction between all Power supply unit 2 –
to the DORMA TS 99 FL the devices employed for
Smoke Scattered light principle
system for passive/preventive holdingopen fire and smoke detection (optical sensor) 2 2
fire protection. check doors – whatever the
Fixing Lintel or
They are designed in accor- situation.
transom-mounted 2 –
dance with the latest codes Ceiling-mounted – 2
Connection of other detectors 2 –
Total installed load (max.)
for hold-open device and
DORMA RMZ other detectors in W 9,8 –
The DORMA RMZ smoke for both further detectors Power consumption of
detector in the Contur design and for an external manual internal detectors in W 1,2 0,65
provides a 24V DC supply release device are also provi- LED Alarm 2 2
for all the hold-open devices ded. The unit is available in indicators Standby 2 –
connected to it. the RMZ version with a sta- Maintenance due 2 –
Contaminated 2 –
In the event of an alarm or bilised power pack, or in the
power failure, it de-energises RMZ DCW version without a Input voltage 230 V AC 24 V DC
± 10 % +15 %, –10%
the devices (release function). power pack for integration in
Output voltage 24 V DC –
It has an automatic reset building management and
Detector operating voltage 24 V DC 24 V DC
which can be switched to control systems via a DCW +15 %, –10 %
manual mode if required. bus and the DORMA TMS Input current (max.) in mA 75 20
A floating (no-volt) change- door management system. Floating (no-volt) change-over contact 24 V 30 V
over contact and connections Safety extra low voltage (SELV) AC/DC AC/DC
2 A 1A
Reset Automatic 2 2
378 30
Can be changed
to manual reset 2 –
34

357,5
Functional check Smoke detection 2 2
Connection terminals
for external manual release 2 –
Degree of protection IP 30 IP 43
Ambient temperature in °C –20, +40 –10, +60
Weight in kg 0,25 0,15
Dimensions Length 379
in mm Overall depth 34 ø 100
Height 30 44
min.10

Compliant with EN 54 Part 7 2 2


mark for building products 2 2
2 Yes – No

DORMA RM-N
The DORMA RM-N smoke with smoke evolution. It can
detector ensures the early be connected to all DORMA
detection both of smoul- hold-open systems.
dering fires and open fires
F Approval certification
DORMA RMZ in the
Contur design and DORMA
Ø 100
RM-N smoke detectors have
been granted general building
approval by the German
44

Institute for Building


Technology, Berlin;
acceptance inspection
mandatory in Germany.

10 TS 99 FL/FLR, GB
Hold-open systems Regulations/Information

The use of hold-open systems The regulations and instruc- Further information can – General building regula­
is subject to special tions provided below are be found in the following tions pertaining to the
regulations based on offi- intended as an aid, pursuant documents: approval of the hold-open
cial approval requirements. to statutory regulations that – Richtlinien für Feststell­ system concerned
These relate in particular apply e.g. in Germany, to anlagen des Deutsches – EN 1155
to the final inspection ensure that all participants Instituts für Bautechnik, – DIN EN 14637
(acceptance), continuous are properly informed of the Berlin
monitoring and maintenance. most important requirements [Code of practice relating
that relate to the installation to hold-open systems
and operation of hold-open issued by the German
systems. Institute for Building
Technology, Berlin]

1. General
1.1 In the case of fire doors pipes, stored/deposited goods 1.3 Each hold-open device used, a pushbutton must be
(and similar shutters/closures/ or components (e.g. false must also be capable of being provided to facilitate manual
barriers) that are held open by ceilings or other overhead released by hand, without release.
hold-open systems, the sweep items/elements) are reliably adversely affecting the The manual release push­
area necessary for the closing prevented from falling into functional capabilities of the buttons employed for this
operation must be kept the sweep area. automatic release device. purpose must be red and
constantly clear. This area 1.2 Wherever possible, In the case of door closers carry the wording “Close
must be clearly identified smoke detectors should be with electro-magnetic Door” or equivalent. The
by lettering, floor markings used for hold-open systems. hold-open, the manual release pushbutton must be located
or similar. Where necessary, For hold-open systems may be performed by a small in the immediate vicinity of
structural measures must also for fire doors in emergency tug applied to the door leaf. the door and must not be
be implemented to ensure escape routes, smoke If holding electro-magnets or concealed by the door when
that cables, leads, lines, detectors must be used. free-swing door closers are this is held open.

2. Final inspection (acceptance)

2.1 In Germany and countries turers of monitoring and/or in the immediate vicinity of 2.3 The operator is to be
governed by DIN regulations: hold-open devices, skilled the door, a plate supplied by provided with a certificate
Following on-site installation personnel authorized by same, the manufacturer of the detailing the successful
of the operable hold-open or skilled personnel from an hold-open system measuring acceptance inspection; this
system, its functional integrity accredited inspection agency. 105 mm x 52 mm and certificate must be retained
and quality of installation must 2.2 In Germany and countries carrying the inscription by the operator.
be confirmed by an accep- governed by DIN regulations: Hold-open system
tance inspection procedure. Once the acceptance inspec- Inspected by... (company
The acceptance inspection tion has been successfully logo with month and year
may only be performed by completed, the operator shall of acceptance inspection)
skilled personnel of manufac- permanently fix on the wall or equivalent

3. Periodic surveillance

3.1 The hold-open system 3.2 In addition, the operator and to carry out or instigate 3.3 The scope, result and
must be kept by the operator is obliged at least once a adequate maintenance. The time of the periodic
in a constantly good year, or at shorter intervals associated test, inspection inspection are to be
operating condition, and if specified in the approval and the maintenance work recorded. These records
inspected at least once a certificate, to inspect all the may only be performed by must be retained by the
month to ensure that it is devices to ensure that they an expert or an appropriately operator.
functioning properly. are operating and interacting trained person.
properly and without fault,

TS 99 FL/FLR, GB 11
DORMA TS 99 Standard equipment
and accessories

Hold-open device TS 99 FL door closer TS 99 FL door closer


RMZ smoke detector body, Leaf-fixed body, Transom-fixed
Free-swing action Size EN 2-5 Size EN 2-5

Slide channel with


free-swing arm assembly
yY yY
533202xx 533302xx

Slide channel with


free-swing arm assembly

G-SR

64102001
G-SR-EMF 1

64112001
G-SR-EMR 1

64215001

RMZ
smoke detector
# #
648000xx
RM-N
smoke detector
# #
64830000
Manual release pushbutton
HT-UP 35901531
# #
HT-AP 35901532

12 TS 99 FL/FLR, GB
TS 99 FLR TS 99 FLR-K TS 99 FL door closer TS 93 B Cushioned
door closer body door closer body body, Leaf-fixed door closer body limit stay
Size EN 2-5 Size EN 2-5 Size EN 2-5 Size EN 2-5

with free-swing arm


assembly, without slide
channel, for GSR co-ordi- for GSR door co-ordina-
nator fixed to active leaf tor fixed to inactive leaf
y 53380201 y 43020001 35800093

yY
542903xx
#

yY
543001xx
#

1x 1x
y y

Y
1x 1x
y y

Y
1x 1x
y y

# # #1)

# # #

# # #

yY = Closer body complete Colour xx Not necessary in the case


1)

with slide channel Silver 01 of the G-SR-EMR1


assembly White (sim. to RAL 9016) 11
Special colour 09
yy = Closer body separate Stainless steel
“Design” 04
Y = Slide channel separate
TS 99 FLR only available
# = Accessory in 01 and 04

“Design” relates to the surface finish


of the product

TS 99 FL/FLR, GB 13
DORMA TS 99 Specification texts

DORMA TS 99 FL, Size EN 2-5


Slide channel door closer action adjustable. arrangement, a certificate of Colour
compliant with EN 1154, Non-handed. compliance in conjunction Y Silver
with CE mark, in the Contur Operating voltage 24V DC. with the relevant fire and Y White (sim. to RAL 9106)
design, for door widths up to Approved by the German smoke check door is man- Y Stainless steel “Design”
1250 mm, with electro- Institute for Building datory. Y Special colour
hydraulic hold-open, com- Technology, Berlin, for use (sim. to RAL ____)
pliant with EN 1155, with in a hold-open system. Model Make
free-swing action from a Acceptance inspection Y Leaf-fixed/pull side DORMA TS 99 FL
door opening angle of > 0°. mandatory in Germany. Y Transom-fixed/pull side EN 2-5
Closing speed and latching In transom-mounted

DORMA TS 99 FLR, Size EN 2-5


Slide channel door closer action adjustable. Institute for Building Model
compliant with EN 1154, Non-handed. Technology, Berlin, for use Y Transom-fixed/pull side
with CE mark, in the Contur Additional connections as a hold-open system.
design, for door widths up available for further detec- Acceptance inspection Colour
to 1250 mm, with electro- tors, external manual release mandatory in Germany. Y Silver
hydraulic hold-open, com- device and floating (no-volt) Approval certification with Y Stainless steel “Design”
pliant with EN 1155, with alarm contact. the relevant fire and smoke
free-swing action from a door Power supply 230V AC. check door mandatory. Make
opening angle of > 0°. Operating voltage 24V DC. DORMA TS 99 FLR
Closing speed and latching Approved by the German EN 2-5

DORMA TS 99 FLR-K, Size EN 2-5


Slide channel door closer Non-handed. Operating voltage 24V DC. Colour
compliant with EN 1154, Slide channel with integral Approved by the German Y Silver
with CE mark, in the Contur power pack and smoke Institute for Building Y White (sim. to RAL 9106)
design, for door widths up detector, with standby and Technology, Berlin, for use Y Stainless steel “Design”
to 1250 mm, with electro- maintenance due indicators. as a hold-open system. Y Special colour
hydraulic hold-open, com- Overall height 30 mm. Acceptance inspection (sim. to RAL ____)
pliant with EN 1155, with Additional connections availa- mandatory in Germany.
free-swing action from a ble for further detectors, exter- Make
door opening angle of > 0°. nal manual release device and Model DORMA TS 99 FLR-K
Closing speed and latching floating (no-volt) alarm contact. Y Leaf-fixed/pull side EN 2-5
action adjustable. Power supply 230V AC.

DORMA RMZ
Smoke detector in the Contur manual release devices are Model Colour
design, with standby and provided. Y RMZ with integrated Y Silver
maintenance due indicators, Can be switched to manual power pack. Power supply Y White (sim. to RAL 9106)
integral power pack and reset. One-piece cover. 230V AC, operating vol- Y Stainless steel “Design”
optical smoke sensor for Overall height 30 mm. tage 24V DC Y Special colour
transom/lintel fixing. For General building approval Y RMZ DCW. Smoke detec- (sim. to RAL ____)
release activation of DORMA granted by DIBt, Berlin, for tor without power pack for
hold-open devices. A floating use in a hold-open system. connection to DCW bus. Make
(no-volt) alarm contact Acceptance inspection of Y Optional integral alarm mo- DORMA RMZ
and connections for further the system is mandatory in dule adding an audible sig- DORMA RMZ DCW
detectors and external Germany. nal to the visual indicator.

DORMA RM-N
Optical smoke detector, General building approval Colour
24V DC, for ceiling fixing. granted by DIBt, Berlin and Y White (sim. to RAL 9106)
For use as second and third the VdS, Cologne; compliant
triggering detector on all to EN 54, Part 7.
DORMA hold-open systems. Acceptance inspection Make
With floating (no-volt) mandatory in Germany. DORMA RM-N
change-over contact.

14 TS 99 FL/FLR, GB
DORMA TS 99 FL EN 2-5 GSR
Slide channel door closer on Slide channel with integral Approved by the German Model
the active leaf, compliant with mechanical door coordinator, Institute for Building Y Leaf-fixed/pull side
EN 1154, with CE mark, in compliant with EN 1158. Technology, Berlin, for use (TS 99 FL on active leaf,
the Contur design, for door This system operates inde- in a hold-open system. TS 93 on inactive leaf)
widths up to 1250 mm, with pendently of the door closer Acceptance inspection man-
electro-hydraulic hold-open hydraulics using a push datory in Germany. Colour
complaint with EN 1155, and rod clamping system with a Y Silver
with a free-swing function from protective overload release Y White (sim. to RAL 9106)
a door opening angle of > 0°. and one-piece cover. Overall Y Stainless steel “Design”
Closing speed and latching height 30 mm. Y Special colour
action adjustable. Non-handed. (sim. to RAL ____)
Non-handed. Cam-action door closer on the
Operating voltage 24V DC. inactive leaf: TS 93 EN 2-5. Make
DORMA TS 99 FL GSR

DORMA TS 99 FL EN 2-5 GSR-EMF 1


Slide channel door closer on Slide channel with integral Approved by the German Model
the active leaf, compliant with mechanical door coordinator, Institute for Building Y Leaf-fixed/pull side
EN 1154, with CE mark, in compliant with EN 1158. Technology, Berlin, for use (TS 99 FL on active leaf,
the Contur design, for door Electro-mechanical hold-open, in a hold-open system. TS 93 on inactive leaf)
widths up to 1250 mm, with 24V DC, compliant with Acceptance inspection man-
electro-hydraulic hold-open EN 1155. Hold-open point datory in Germany. Colour
complaint with EN 1155, and 80°-130° and pull-off force Y Silver
with a free-swing function from adjustable. Y White (sim. to RAL 9106)
a door opening angle of > 0°. This system operates inde- Y Stainless steel “Design”
Closing speed and latching pendently of the door closer Y Special colour
action adjustable. hydraulics using a push (sim. to RAL ____)
Non-handed. rod clamping system with a
Operating voltage 24V DC. protective overload release Make
and one-piece cover. Overall DORMA TS 99 FL GSR-EMF 1
height 30 mm. Non-handed.
Cam-action door closer on the
inactive leaf: TS 93 EN 2-5.

DORMA TS 99 FL EN 2-5 GSR-EMR 1


Slide channel door closer Additional connections protective overload release Model
on the active leaf, compliant available for further detec- and one-piece cover. Overall Y Leaf-fixed/pull side
with EN 1154, with CE mark, tors, external manual release height 30 mm. Non-handed. (TS 99 FL on active leaf,
in the Contur design, for device and floating (no-volt) Cam-action door closer on the TS 93 on inactive leaf)
door widths up to 1250 mm, alarm contact. inactive leaf: TS 93 EN 2-5.
with electro-hydraulic Power supply 230V AC. Approved by the German Colour
hold-open complaint with Operating voltage 24V DC. Institute for Building Y Silver
EN 1155, and with a free- Slide channel with integral Technology, Berlin, for use Y White (sim. to RAL 9106)
swing function from a door mechanical door coordinator, as a hold-open system. Y Stainless steel “Design”
opening angle of > 0°. compliant with EN 1158. Acceptance inspection man- Y Special colour
Closing speed and latching Electro-mechanical hold- datory in Germany. (sim. to RAL ____)
action adjustable. open, 24V DC, compliant
Non-handed. with EN 1155. Hold-open Make
Operating voltage 24V DC. point 80°-130° and pull-off DORMA TS 99 FL GSR-
Smoke detector with force adjustable. EMR 1
standby and maintenance This system operates inde-
due indicators fully integra- pendently of the door closer
ted in the housing of the hydraulics using a push
door coordinator. rod clamping system with a

TS 99 FL/FLR, GB 15
www.dorma.com

Door Control Division worldwide

Central Europe Gulf


DORMA GmbH + Co. KG DORMA Gulf Door Controls FZE
DORMA Platz 1 Jebel Ali Free Zone South
D-58256 Ennepetal Plot No. S 20135
Phone +49 2333 793-0 Road No. SW 301 G
Fax +49 2333 793-495 P.O. Box 17268
Dubai – United Arab Emirates
Australasia Phone +971 4 8020400
DORMA Door Controls Pty. Ltd. Fax +971 4 8869100 / 8869101
52, Abbott Road
Hallam/Victoria 3803 North America
Australia DORMA Architectural Hardware
Phone +61 3 8795 0666 DORMA Drive, Drawer AC
Fax +61 3 8795 0280 Reamstown, PA 17567-0411
Phone +1 800 5238483
China/Hong Kong Fax +1 800 2749724
DORMA Door Controls
(Suzhou) Co. Ltd. Scanbalt
Door Control No. 9, Hong Feng Road DORMA Danmark A/S
Suzhou Singapore Industrial Park Sindalvej 6–8
techniques
notice

Suzhou, 215021 DK-2610 Rødovre


P.R. of China Phone +45 44 543000
Phone +86 512 67612481
to change without

Fax +45 44 543001


Fax +86 512 67614582
de modifications

South America
DORMA Door Controls Pte. Ltd. DORMA Sistemas de Controles
Room 701, Technology Plaza para Portas Ltda.
651 King’s Road Av. Piracema, 1400
North Point
· Subject

Centro Empresarial Tambore


Automatic Hong Kong
Sous réserve

CEP 06400-933 Barueri/


Phone +852 25034632 São Paulo, Brasil
Fax +852 28875370 Phone +55 11 46899280
x. XX.· xx/10

Fax +55 11 46899215


Emerging Markets
DORMA GmbH + Co. KG South-East Europe
GB,xx/09

DORMA Platz 1 DORMA AUSTRIA GmbH


D-58256 Ennepetal Pebering Strass 22
F, x. XX.

Phone +49 2333 793-0 A-5301 Eugendorf


FL/FLR,

Fax +49 2333 793-495 Phone +43 6225 284880


Fax +43 6225 28491
85,

DORMA Door Controls (Pty.) Ltd.


RTS99

Glass fittings Kings Court South Europe


07/09, TS

and Accessories 4A Mineral Crescent DORMA Italiana S.r.l.


917 51532, 12/10,

ZA-2000 Crown/Gauteng Via. Canova 44/46


South Africa I-20035 Lissone (MI)
Phone +27 11 8300280 Phone +39 039 244031
Fax +27 11 8300291 Fax +39 039 24403310
050 811

Far East DORMA Ibérica, S.A.


WN 053

DORMA Far East Pte. Ltd. Camino San Martin de la Vega, 4


No. 31 Gul Lane E-28500 Arganda del Rey
Singapore 629425 (Madrid)
Security Time Phone +65 6268 7633 Phone +34 91 8757850
and Access (STA) Fax +65 6265 7995 Fax +34 91 8757881
021226 290675
839522

France UK/Ireland
DORMA France S.A.S. DORMA UK Ltd.
Zone Europarc Wilbury Way
Immeuble Mega 42 Hitchin
44 021226

42, Rue Eugène Dupuis GB-Hertfordshire SG4 0AB


F-94046 Créteil Cedex Great Britain
Phone +33 1 41942400 Phone +44 1462 477600
Fax +33 1 41942401 Fax +44 1462 477601
Movable Walls

You might also like