Professional Documents
Culture Documents
S.No Parameters Alarm Value Triping Value
S.No Parameters Alarm Value Triping Value
2 (pr switch)
S.NO PARAMETERS ALARM VALUE TRIPING VALUE
1 Fuel feeding SA Pr. 250mmwc 200mmwc
2 Drum Level low 30% 18%
3 Drum Level HH 90% 98%
4 Furnrnce Draft HH 20 75
5 Furnrnce Draft LL -20 -75
6 D/A level LOW 40% 30%
7 FEED Tank Level LL 80% 18%
8 Fan Winding Temp. 95.C 120.C
9 Fan bearing Temp 70% 90%
10 BFP Suctiom Pr.LOW 1kg/cm2 .60kg/cm2
11 BFP Suctiom Pr.HIGH 5kg/cm2 6kg/cm2
12 BFP winding Temp 90.C 110.C
13 BFP Bearing Temp 70.C 90.C
14 Interlocking
ANY UPDATE
baggase feeder Trip
Boiler Trip
turbine trip
mmwc (Boiler Trip
mmwc(boiler trip)
BFP Trip
FTP Trip
when Two Winding Temp same time