You are on page 1of 2

STEP 1.

CALCULATE FOR POWER TRANSFORMER MVA RATING


Maximum Diversified MW Demand = 11.05 MW

Pf = 0.9

 Power Transformer
𝑀𝑎𝑥. 𝐷𝑖𝑣𝑒𝑟𝑠𝑖𝑓𝑖𝑒𝑑 𝐷𝑒𝑚𝑎𝑛𝑑
𝑇𝑟𝑎𝑛𝑠𝑓𝑜𝑟𝑚𝑒𝑟 𝑀𝑉𝐴 𝑅𝑎𝑡𝑖𝑛𝑔 = ∗ 1.25
𝑝𝑓
11.05 𝑀𝑊
𝑇𝑟𝑎𝑛𝑠𝑓𝑜𝑟𝑚𝑒𝑟 𝑀𝑉𝐴 𝑅𝑎𝑡𝑖𝑛𝑔 = ∗ 1.25 = 𝟏𝟓. 𝟑𝟒𝟕𝟐 𝑴𝑽𝑨
0.9
Closest standard transformer MVA rating available is 20 MVA

Manufacturer WEG
Power rating 20 MVA
High voltage 69 kV +/- 2x2.5%
Low voltage 13.8 kV
Vector group Dyn1
%Z 12.5 %

STEP 2. CALCULATE FOR CONTINUOUS CURRENT


 Transformer Cables:

Maximum Diversified MW Demand = 11.05 MW

Pf = 0.9
Maximum Diversified MW Demand 11.05 𝑀𝑊
𝑀𝑉𝐴 𝐷𝑒𝑚𝑎𝑛𝑑 = = = 𝟏𝟐. 𝟐𝟕𝟖 𝑴𝑽𝑨
𝑝𝑓 0.9
𝑀𝑉𝐴
𝐼𝑐𝑜𝑛𝑡𝑖𝑛𝑢𝑜𝑢𝑠 =
√3 ∗ 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑅𝑎𝑡𝑖𝑛𝑔
For high-side (69 kV):
12.278 𝑀𝑉𝐴
𝐼𝑐𝑜𝑛𝑡𝑖𝑛𝑢𝑜𝑢𝑠_ℎ𝑖 = = 𝟏𝟎𝟐. 𝟕𝟑𝟒𝟖𝟕𝟖𝟑 𝑨
√3 ∗ 69 𝑘𝑉
For low-side (13.8 kV):
12.278 𝑀𝑉𝐴
𝐼𝑐𝑜𝑛𝑡𝑖𝑛𝑢𝑜𝑢𝑠_𝑙𝑜 = = 𝟓𝟏𝟑. 𝟔𝟕𝟒𝟑𝟗𝟏𝟕 𝑨
√3 ∗ 13.8 𝑘𝑉
 Lumped Loads (80% motor, 20% static)

 Lumped load 1:

Lumped load 1 max. demand: 3.5 MW (3.89 MVA)


3.86 𝑀𝑉𝐴
𝐼𝑐𝑜𝑛𝑡𝑖𝑛𝑢𝑜𝑢𝑠_𝐿1 = = 𝟏𝟔𝟐. 𝟕𝟓 𝑨
√3 ∗ 13.8 𝑘𝑉
 Lumped load 2

Lumped load 2 max. MW demand: 2.8 MW (3.11 MVA)


3.86 𝑀𝑉𝐴
𝐼𝑐𝑜𝑛𝑡𝑖𝑛𝑢𝑜𝑢𝑠_𝐿2 = = 𝟏𝟑𝟎. 𝟏𝟏 𝑨
√3 ∗ 13.8 𝑘𝑉
 Lumped load 3

Lumped load 3 max. MW demand: 3.6 MW (4 MVA)


3.86 𝑀𝑉𝐴
𝐼𝑐𝑜𝑛𝑡𝑖𝑛𝑢𝑜𝑢𝑠_𝐿3 = = 𝟏𝟔𝟕. 𝟑𝟓 𝑨
√3 ∗ 13.8 𝑘𝑉
 Lumped load 4

Lumped load 4 max. MW demand: 6.8 MW (7.56 MVA)


3.86 𝑀𝑉𝐴
𝐼𝑐𝑜𝑛𝑡𝑖𝑛𝑢𝑜𝑢𝑠_𝐿4 = = 𝟑𝟏𝟔. 𝟐𝟗 𝑨
√3 ∗ 13.8 𝑘𝑉