You are on page 1of 39

<< Back Home Next >>

OISD - RP - 149
First Edition
February, 1996
Amended Edition, September
2001

FOR RESTRICTED
CIRCULATION ONLY

DESIGN ASPECTS FOR SAFETY


IN
ELECTRICAL SYSTEM

Prepared by:
COMMITTEE ON “DESIGN ASPECTS FOR ELECTRICAL SAFETY”

OIL INDUSTRY SAFETY DIRECTORATE


7TH FLOOR, NEW DELHI HOUSE
27, BARAKHAMBA ROAD
NEW DELHI – 110 001
NOTE
OISD publications are prepared for use in the oil and gas industry
under Ministry of Petroleum and Natural Gas. These are the property of
Ministry of Petroleum and Natural Gas and shall not be reproduced or
copied and loaned or exhibited to others without written consent from
OISD.

Though every effort has been made to assure the accuracy and
reliability of the data contained in these documents, OISD hereby
expressly disclaims any liability or responsibility for loss or damage
resulting from their use.

These documents are intended to supplement rather than


replace the prevailing statutory requirements.

Note 3 in superscript indicates the


modification/changes/addition based on the
amendments approved in the 19th Safety Council
meeting held in September, 2001July, 1999
FOREWORD

Oil Industry in India is nearly 100 years old. Due to various collaboration
agreements a variety of international codes, standards and practices are in vogue,
Standardisation in design philosophies, operating and maintenance practices at a national
level was hardly in existence. This lack of uniformity coupled with feedback from some
serious accidents that occurred in the recent past in India and abroad, emphasised the
need for the industry to review the existing state of art in designing, operating and
maintaining oil and gas installations.

With this in view, the Ministry of Petroleum and Natural Gas in 1986 constituted a
Safety Council assisted by the Oil Industry Safety Directorate (OISD) staffed from within
the industry in formulating and implementing a series of self-regulatory measures aimed
at removing obsolescence, standardising and upgrading the existing standards to ensure
safer operations. Accordingly OISD constituted a number of functional committees
comprising of experts nominated from the industry to draw up standards and guidelines
on various subjects.

The present document on “Design Aspects for Safety in Electrical System” was
prepared by the Functional committee on “Design Aspects for Electrical Safety”. This
document is based on the accumulated knowledge and experience of industry members
and the various national and international codes and practices.

It is hoped that provisions of this document if implemented objectively, may go a


long way to improve the safety to reduce accidents in Oil and Gas Industry. Users are
cautioned that no document can be a substitute for the judgement of responsible and
experienced engineer.

Suggestions are invited from the users after it is put into practice to improve the
document further. Suggestions for amendments, if any, to this standard should be
addressed to :

The Co-ordinator
Committee on “Design Aspects for Electrical Safety”
OIL INDUSTRY SAFETY DIRECTORATE
th
7 Floor, ‘New Delhi House’
27, Barakhamba Road
New Delhi – 110 001

This document in no way supersedes the statutory regulations of Chief Controller


of Explosives (CCE), Factory Inspectorate or any other statutory body which must be
followed as applicable.
COMMITTEE
ON
DESIGN ASPECTS FOR ELECTRICAL SAFETY
---------------------------------------------------------------------------------------------------------------------------------
NAME ORGANISATION
---------------------------------------------------------------------------------------------------------------------------------
LEADER

Shri V. P. Sharma Engineers India Limited

MEMBERS

Shri R. Sankaran Madras Refineries Limited

Shri U. P. Singh Indian Oil Corporation Limited

Shri Narendra Kumar Gas Authority of India Limited

Shri R. Raghupathy Engineers India Limited

MEMBER CO-ORDINATORS

Shri N. V. Mani Oil Industry Safety Directorate

Shri J. K. Jha Oil Industry Safety Directorate


---------------------------------------------------------------------------------------------------------------------------------
In addition to the above, several other experts from Industry contributed in the preparation,
review and finalisation of this document.
DESIGN ASPECTS FOR SAFETY IN ELECTRICAL SYSTEM

CONTENTS
-------------------------------------------------------------------------------------------------------
SECTION DESCRIPTION PAGE NO.
---------------------------------------------------------------------------------------------------------------------------------
1.0 INTRODUCTION

2.0 SCOPE

3.0 DEFINITIONS

4.0 POWER SYSTEM DESIGN

4.1 Capacity of Electrical Plant

4.2 Neutral Earthing

4.3 Short Circuit Capacities

4.4 Insulation Coordination

4.5 Protection and Metering

4.6 Emergency Power Supply

4.7 Critical Power Supply Systems

5.0 ELECTRICAL EQUIPMENT FOR CLASSIFIED


AREA

6.0 SUB-STATION LOCATION/LAYOUT

7.0 ELECTRICAL EQUIPMENT

7.1 Characteristics

7.2 Equipment Features

7.2.1 Transformers

7.2.2 H.V/M.V Switchboards

7.2.3 Motors (H.V & M.V)

7.2.4 Battery Charger and Distribution Board

7.2.5 Batteries and Battery Accessories

7.2.6 Equipment for Uninterrupted Power Supply


System

7.2.7 Capacitor Banks

7.2.8 Emergency Generator

---------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------
SECTION DESCRIPTION PAGE NO.
---------------------------------------------------------------------------------------------------------------------------------

7.2.9 Cables

7.2.10 Control Station

7.2.11 Convenience Receptacles

7.2.12 Actuators for Motor Operated Valves

8.0 PLANT CABLING

9.0 Plant Lighting

10.0 Plant Earthing

11.0 PLANT SAFETY AND SECURITY SYSTEMS

11.1 Plant Fire Detection and Alarm System

11.2 Communication System

11.2.1 Telephone System

11.2.2 Public Address System

11.2.3 Emergency Communication System


(Hot Line System)

11.2.4 Radio Communication System

a) Portable Walkie-Talkie System


b) VHF System

11.2.5 Telex System

12.0 MOBILE EQUIPMENT FOR HAZARDOUS


AREAS

12.1 Portable Hand Lamps

12.2 Diesel Engines

12.3 Storage Batteries

12.4 Testing Equipment

12.5 Miscellaneous Requirements

12.6 Vehicles

13.0 REFERENCES

=====================================================================
DESIGN ASPECTS FOR SAFETY IN ELECTRICAL SYSTEM

1.0 INTRODUCTION A connection to the general mass of earth


by means of an earth electrode. An object
Safety in electrical system draws is said to be ‘earthed’ when it is
maximum attention especially in the electrically connected to an earth
hydrocarbon industry, where classified electrode; and a conductor is said to be
hazardous atmosphere may be ‘solidly earthed’ when it is electrically
encountered and electricity may connected to earth electrode without a
constitute one of the sources of ignition fuse, switch, circuit-breaker, resistance or
for fire accidents and explosions. Besides impedance in the earth connection.
equipment damage and property loss,
electrical hazards may lead to injuries and ii) Earth Continuity Conductor -
fatalities to personnel due to electric
shock and burns. The electrical system The conductor, including any clamp,
designer, hence, faces a challenge to connecting to the earthing lead or to each
provide a safe and reliable electrical other of those parts of an installation
system. which are required to be earthed.

It is therefore imperative that safety iii) Earth Electrode -


aspects are built into the electrical system
right from the design and engineering A metal plate, pipe or other conductor
stage with the main objective of embedded in the soil that makes a direct
minimising equipment/system failure to contact to the general mass of the earth.
prevent injury to personnel and damage
to system components. iv) Earthing Lead -

Following the guidelines and adhering to The final conductor by which the
the safe practices given in this standard, connection to the earth electrode is made.
would ensure adequate levels of safety in
the electrical facilities of Oil Industry. v) Voltage, Low - (LV)

2.0 SCOPE The voltage which does not normally


exceed 250 volts.
This document recommends minimum
requirements in the design and vi) Voltage, Medium - (MV)
engineering of electrical installations in
the petroleum oil and gas sector. The voltage which normally exceeds 250
However, this standard does not cover volts but does not exceed 650 volts.
offshore installations. It also excludes
drilling rigs and well head installations. vii) Voltage High - (HV)
This standard is not intended for use as a
comprehensive design manual for The voltage which normally exceeds 650
electrical power system design. The volts but does not exceed 33 KV
standard in no way supersedes the
statutory regulations of the Chief viii) Voltage, Extra-High-(EHV)
Electrical Inspectorate, Factory
inspectorate, Chief Controller of The voltage which exceeds 33 KV under
Explosives, Director General Mines normal conditions.
Safety, Central Electricity Authority or ix) Impulse -
other Government bodies, which shall be
followed as applicable. Usually a periodic transient voltage or
current which rises rapidly to a peak value
and then falls, generally more slowly, to
zero.
3.0 DEFINITIONS
x) Earth Fault -]
I) Earth Connection -
Accidental connection of a conductor to A general term covering switching
earth. When the impedance is negligible, devices and their combinations with
the connection is called a dead earth-fault. associated control, measuring,
protective and regulating equipment;
xi) Earth Leakage Current - also assemblies of such devices and
equipment with associated inter-
The current following to earth on account connections, accessories, enclosures
of imperfect insulation. and supporting structures intended in
principle for use in connection with
xii) Insulation Fault - generation, transmission, distribution
and conversion of electrical energy.
An abnormal decrease in insulation Controlgear are switching devices
resistance. intended in principle for the control of
electrical energy consuming equipment.
xiii) Overload -
xx) Flame Arrestor -
Operating conditions in an electrically
undamaged circuit which cause an A device for releasing gas from an
overcurrent. enclosure in such a way that in case of
an internal explosion there is no
xiv) Short-Circuit - appreciable increase in internal pressure
and the released gas will not ignite the
The intentional or accidental connection of surrounding flammable atmosphere.
two points of a circuit. The term is often
applied to the group of phenomena which xxi) Nominal Voltage (of an Installation)
accompany a short circuit between points
at different potentials. Voltage for which an installation or part
of an installation is designated.
xv) Symmetrical breaking current
xxii) Highest System Voltage
The symmetrical breaking current, during
opening of a circuit breaker in the event of The highest R.M.S. phase to phase
a short circuit, is the r.m.s. value of the voltage, which occurs under normal
symmetrical short circuit current flowing operating conditions at any time and at
through the first phase to open at the any point in the system. It excludes
instant of contact separation. voltage transients (such as those due to
system switching) and temporary voltage
xvi) Peak short circuit current variation due to abnormal system
conditions (such as those due to fault
This is the highest instantaneous value of conditions on sudden disconnection of
current after the occurrence of short large loads).
circuit. It is given as a peak value. Its
magnitude depends on the instant of the xxiii) Lightning Protective System -
cycle at which the short circuit occurs.
The whole system of interconnected
xvii) Redundancy conductors used to protect a structure
from the effects of lightning.
Duplication of elements in a system or
installation, for the purpose of enhancing xxiv) Portable Equipment -
the reliability or continuity of operation of
the system or installation. Equipment which can be moved even
while in operation or which can easily
xviii) Electrical Equipment - be moved from one place to another
while connected to the electric supply.
The electrical machines, apparatus and
circuits forming part of an electrical xxv) Hand-Held Equipment -
installation or a power system.
Portable equipment intended to be
xix) Switchgear and Controlgear- held in the hand during normal use in
which the motor, if any, forms an
integral part of the equipment.
capable of ignition is likely to be
xxvi) Stationary Equipment - present;

Either fixed equipment or equipment b) Petroleum or any flammable liquid


not provided with a carrying handle having flash point above 65°C is
and having such a mass that it cannot likely to be refined, blended,
easily be moved. handled or stored at or above its
flash point.
xxvii) Fixed Equipment -
Zone 0 An area in which a flammable
Equipment fastened to a support or atmosphere is present
otherwise secured in a specific continuously, or is present for long
location. periods.

xxviii) Self Powered Vehicle - Zone 1 An area in which a flammable


atmosphere is likely to be present
A vehicle used for the conveyance of periodically or occasionally during
stationary equipment (e.g. normal operation.
compressors), personnel or goods in
which petroleum or storage battery is Zone 2 An area in which a flammable
used to generate the motive power. atmosphere is not likely to occur in
normal operation and if it does
xxix) Flammable Material - occur, it will exist for a short time
only.
A flammable material is a gas, vapour,
liquid, and/or mist which can react xxxiv) Non-hazardous (Safe) Area -
continuously with atmospheric oxygen
and which may therefore, sustain a fire An area, no part of which is within a
or explosion when such reaction is hazardous area.
initiated by a suitable spark, flame or
hot surface. xxxv) Electrical Apparatus for Hazardous
Areas
xxx) Flammable Mixture -
Electrical apparatus which will not
A mixture of flammable gas, vapour, or ignite the surrounding flammable
mist with air under atmospheric atmosphere in which it is used.
conditions, in which after ignition,
combustion spreads throughout the xxxvi) Intrinsic Safety (Ex-i) (Ref : IS : 5780)
unconsumed mixture.
A circuit or part of a circuit is
xxxi) Hazard - intrinsically safe when any spark or
thermal effect produced normally (that
The presence, or the risk of presence, is, by breaking or closing the circuit) or
of a flammable mixture. accidentally (for example by short-
circuit or earth fault) is incapable,
xxxii) Hazardous (Flammable) Atmosphere - under prescribed test conditions, of
causing ignition of a prescribed gas or
In accordance with the Petroleum vapour.
Rules, an atmosphere containing any
flammable gas or vapour in a An intrinsically safe apparatus is one in
concentration capable of ignition. which all electrical circuits are
intrinsically safe. It is placed in one of
xxxiii) Hazardous Area - the following categories:

In accordance with the petroleum


rules, an area shall be deemed to be a
hazardous area, where:
a) Category (Ex-ia)
a) Petroleum having flash point
below 65°C or any flammable gas Apparatus in this category is
or vapour in a concentration incapable of causing ignition in
normal operation, or with a single an explosive gas mixture that may be
fault, or with any combination of present above the surface of the oil,
two faults applied with a specified and all live parts on which areas do not
safety factor for current and/or occur in normal service are either
voltage. immersed in oil or protected by some
other recognised techniques.
b) Category (Ex-ib)
xxxxi) Non-sparking Apparatus (Ex-n) (Ref :
Apparatus in this category is IS 8289) -
incapable of causing ignition in
normal operation, or with any Apparatus which in normal operation is
single fault applied, with a not capable of igniting a surrounding
specified safety factor for current explosive atmosphere, and in which a
and/or voltage. fault capable of causing ignition is not
likely to occur.
xxxvii) Flameproof Enclosure (Ex-d)-(Ref : IS
: 2148) xxxxii) Increased Safety (Ex-e) (Ref : IS :
6381)
An enclosure for electrical apparatus
that will withstand, when the covers or A method of protection in which
other access doors are properly measures additional to those adopted
secured, an internal explosion of the in ordinary industrial practice are
flammable gas or vapour which may applied, so as to give increased
enter it or which may originate inside security against the possibility of
the enclosure, without suffering excessive temperatures and the
damage and without communicating occurrence of arcs or sparks in
the internal flammation to the external electrical apparatus which does not
flammable gas or vapour for which it is produce arcs or sparks in normal
designed, through any joints or service.
structural openings in the enclosure.
xxxxiii) Special Protection ‘S’ -
xxxviii) Pressurised Enclosure (Ex-p) (see IS :
7389 (part 1) - A kind of protection which does not fall
into any of the recognised techniques,
An enclosure for electrical apparatus but which may be demonstrated to
in which the entry of flammable gas or afford equivalent levels of protection to
vapour is prevented by maintaining the equipment intended for use in
air (or other non-flammable gas) within classified hazardous areas. This is to
the enclosure at a pressure above that develop new ideas before standard
of the external atmosphere. specifications are available.

xxxix) Sand-filled apparatus (Ex-q) (Ref : IS : The certificate will normally describe
7724)- the techniques and conditions of use.

Electrical apparatus which has all its


live parts entirely embedded in a mass 4.0 Power System Design
of powdery material, in such a way that
under the conditions of use for which i) The design of electrical installation
the apparatus has been designed, no shall ensure provision of a safe and
arc occurs within the outer explosive reliable supply of electricity at all times.
atmosphere either by the transmission Safe conditions shall be ensured
of flame or by the overheating of the under all operating conditions including
walls of the enclosure. those associated with start-up and
shut down of plant, as well as those
xxxx) Oil Immersed Apparatus - (Ex-o) (Ref : arising out of failure of electrical
IS : 7693) - equipment. The isolation of a part of
system of electrical equipment due to
Electrical apparatus in which all parts either maintenance or shutdown shall
on which are may occur in normal not compromise safety. Power
service are immersed in oil to a distribution system shall constitute
sufficient depth to prevent ignition of
sub-stations located near load centres
as far as practical. iii) Required redundancy (based on specific
process/operating needs) shall be built in
ii) The design shall be broadly based the substation which feeds power supply to
upon the following factors: the process units/important facilities so
that in case of tripping of one feeder, the
- Safety to personnel and equipment unit/facility may not be adversely affected.
during operation and maintenance,
iv) The power system design shall ensure
- Reliability of service, system reliability. This assumes particular
significance where inplant generation
- Ease of maintenance, supplements the external power supply.
For this, quick isolation of inplant system
- Convenience of operation, from faulty grid, inplant load shedding etc.
may need detailed consideration.
- Maximum interchangeability of
equipment, v) Before carrying out system design, it is
recommended that the following minimum
- Elimination of fire risk, information/data be obtained, from the
power supply authorities:
- Facility for ready addition of future
loads. a) Incoming grid voltage and frequency,
actual variation limits, guaranteed
- Suitability for applicable power availability.
environmental factors.
b) Existing fault level of feeding bus and
iii) Special attention is drawn to Chapter X system expansion factor for fault level.
of IE rules which includes requirements
for design of electrical system as c) Location of feeding substation and
applicable to oil mines. routing of supply lines/feeder and the
reliability of power supply.
4.1 Capacity of Electrical Plant
d) Size of conductor and current carrying
capacity.
i) All the components of the electrical
system shall be sized to suit the e) Supply system neutral earthing.
maximum load, under the most severe
operating conditions. The amount of f) Details of protection relays and their
electrical power consumed by each settings at sending end breaker side.
process unit shall be calculated for its
operation at the design capacity. g) Required metering arrangements at
Accordingly, the maximum receiving end.
simultaneous consumption of power,
required by continuously operating vi) When capacitors are added to the system
loads shall be considered and for power factor improvement, necessary
additional margin shall be taken into system study may be carried out to
account for intermittent service loads, if decide measures for avoiding problems
any. due to hormonics, system resonance,
oscillatory torques in rotating equipment,
ii) While carrying out load analysis, loads in rush current, increase in voltage across
shall be characterised under different capacitors due to use of series reactor,
heads as under: harmonic loading of capacitor, etc. The
above assumes particular significance
- Normal loads where there is captive generation.
(continuous/intermittent loads)
4.2 Neutral Earthing
- Essential loads (Emergency loads)
4.2.1 Earthed System
- Critical loads (e.g. computer, fire
water pumps, communication, i) Power system neutral shall be earthed:
instrumentation controls etc.)
a) To limit the difference of electric potential currents arising due to distributed
between all uninsulated conducting capacitance of the entire network. The
objects in a local area. system shall also include alarm/tripping
provision using unbalance voltage sensing
b) To provide for isolation of faulty equipment through open delta potential transformers
and circuits when a fault occurs. (PTs) under earth fault conditions. Besides
it is recommended that provision of ‘on line
c) To limit overvoltages appearing on the insulation monitoring facilities’ may be
system under various conditions. considered.

ii) The neutral earthing system employs one 4.3 Short Circuit Capacities
of the following methods:
i) Each short-circuit interrupting device shall
a) Solid earthing for low, medium voltage have fault duty higher than the maximum
system (upto 650V) and for high value of short circuit current calculated at its
voltage above 11 K.V. location. The related switchgear and bus
ducts shall withstand the above maximum
b) Resistance earthing for 3.3 KV to 11KV fault current (mechanical and thermal
system. stresses) for a minimum duration of one
second.)
iii) The values of neutral earthing resistors
normally applied in industrial power system ii) The sizing of high voltage cables shall be
are selected to meet the governing criteria based on the short circuit withstand
for limiting transient over-voltages, i.e. capacity for a minimum time period as
earth fault current should not be less than dictated by the protection system in addition
the system charging current. Besides, the to the maximum anticipated load current
value of neutral earthing resistor selected carrying capacity.
shall limit the earth fault current to a value,
which shall be sufficient for selective and iii) It is to be noted that in the case of
reliable operation of earth fault protection generators, whose excitation power is
system. terminal dependent, short circuit in the
system will result in drop of the terminal
However, where an earthing transformer is voltage and consequently the over-current
used for obtaining the system neutral, the protective devices may not get adequate
zero sequence reactance limit (i.e. RO > 2 current for operation. To avoid such a
X0) should also be considered. (R0 - zero situation, necessary excitation support shall
sequence resistance of the circuit be provided unless & otherwise required.
including neutral resistor and X0 zero
sequence inductive reactance of the iv) While sizing, the system necessary
circuit). consideration shall be given to restrict the
system voltage drop within permissible
iv) The neutral earthing resistor shall be able to limits during starting of large rated motor
carry at least 10% of its rated current or group of motors. At the same time, the
continuously, unless otherwise required, short circuit current shall be kept within
and full rated current (100%) for a minimum limits keeping in view of the market
duration of 10 seconds. availability of switchgears. Reduced
voltage starting (soft start feature) for
4.2.2 Unearthed System motors may be considered as per system
requirements.
i) It is recommended that use of unearthed
system may be avoided since arcing ground 4.4 Insulation coordination
faults can result in severe over voltages.
i) The insulation of electrical facilities shall
ii) Where unavoidable (such as expansion be designed considering the system
projects where existing systems have voltage, the system neutral earthing, and
unearthed system) unearthed system shall the over-voltages resulting due to system
have provision for detecting earth fault and fault, switching or lightning surges. The
for isolation of faulty section through the insulation co-ordination between the
use of core balance current transformers. electrical equipment and the protective
The current transformers (CTS) shall be devices shall be done in line with IS: 3716
sized in relation to the system capacitive and IS: 2165.
earthed, restricted earth fault protection
ii) Insulation coordination is a correlation of may be provided for transformer
insulation of equipment and circuit with the secondary.
characteristic of protective devices such
that the insulation is protected from over iv) Particular care should be taken in the
voltages. selection of protective devices for
machines and equipment operating in
iii) The rated insulation level of Switchgears hazardous areas, so as to isolate the faulty
shall refer to the power frequency section in the shortest time possible. For
withstand voltage and impulse voltage high voltage system, protective relays shall
withstand values which characterise the be used. For medium voltage systems,
insulation. In respect of systems with direct acting releases and/or protective
nominal voltage of 132 KV and above, full relays may be employed.
insulation values shall be considered for
non-effectively earthed system, and In general, quick acting relays (with time
reduced insulation values may be used for delays if necessary) shall be used and all
effectively earthed system. fault tripping shall be done through high
speed tripping relays.
4.5 Protection and Metering
v) The supply of Energy to every electrical
i) The protective system shall be selected installation other than low voltage
and coordinated to ensure the following: installations below 5 KW and those low
voltage installations which do not attract
a. Protection of equipment against damage provisions of Section 30 of the Indian
which can occur due to internal or Electricity Act, 1910, shall be controlled by
external short circuits, overloading, an earth leakage protective device so as to
abnormal operating conditions, disconnect the supply instantly on the
switching, lightning surges, etc. occurrence of earth fault or leakage of
current (IE Rule 61A).
b. The continuity of operation of those parts
of the system not affected by the fault, is Provided that the above shall not apply to
maintained. overhead supply lines having protective
devices which are effectively bonded to the
c. Personnel and plant safety. neutral of supply transformers and
conforming to Rule 91 of I.E. Rules, 1956.
ii) Accordingly, relays and protective devices
shall be suitably selected and coordinated. vi) Metering instruments shall be provided on
As a minimum, differential protection shall plant Main Switch Board to monitor the
be provided for the following: power consumption and supervision of all
concerned parameters like current,
a. Transformers rated 5 MVA and above, voltage, power, frequency, power factor
etc. Ammeters in the field for monitoring
b. Induction and synchronous motors motor current may be provided as per
rated 1500 KW and above, process requirements. Metering and
protection current transformers shall be
c. Generators rated 2 MVA and above. preferably kept separate. In the case of
contactor controlled feeders having long
d. Bus differential shall be provided for all length of control cables (more than 800
H.T. switchgear having direct Mts. or so) due consideration shall be
connection with the inplant generators given to the effect of capacitance on
and other vital H.T. switchgear. ON/OFF operations of contactor.

iii) Longitudinal differential protection shall be vii) Recommended relay protections for
provided for important plant feeders in Transformers, motors and feeders which
general, and plant feeders connected to a are generally encountered in distributing
captive power plant bus in particular. network are given below :
Wherever the system is resistance
---------------------------------------------------------------------------------------------------------------------------------
RELAY TRANSFORMER MOTOR OUTGOING INCOMER
REF :ANSI/IEEE POWER DIST HV HV MVPCCC HV MVPCC
(IEEC 37.2)
--------------------------------------------------------------------------------------------------------------------------------
A. 51 IDMTL O.C. YES YES - YES YES YES YES
(4) (4)

B. 51(N) IDMTL E.F. YES NO - YES YES YES YES


(7) 4) (4)

C. 5IN BACK UP E.F. YES YES - NO NO NO NO


(SECONDARY SIDE
NEUTRAL)

D. MOTOR PROTECTION NO NO YES NO NO NO NO


RELAY WITH LOCKED
ROTOR FEATURE
(50, 51, 50N, 46, 49, 50L/R)

E. 50N INST REST EF YES NO - NO NO NO NO


(SECONDARY SIDE)

F. 50 INST.O.C YES YES - NO NO NO NO

G. 50N INST.EF (R) YES YES - NO NO NO NO


(6)

H. 87 DIFF.PROT. YES NO YES YES NO NO NO


(1) (2) (3)

I. 86 TRIPPING RELAY YES YES YES YES YES YES YES

J. 95 TRIP CKT SUP. YES YES YES YES NO YES NO

K. 63TX AUX RLYTRAFO YES YES - NO NO NO NO

L. 27,2 UNDERVOLTAGE - - YES - - YES YES


WITH TIMER (5) (5)
--------------------------------------------------------------------------------------------------------------------------------

(1) For transformers rated 5 MVA and above


(2) For motors rated 1500 KW and above
(3) For critical/long feeders.
(4) These relay functions can be substituted by inherent releases.
(5) Wherever Autotransfer feature is provided.
(6) Provide INST E/F 50N for transformers with primary delta.
(7) Provide IDMTL E/F 51N for transformer with primary star
viii) Medium Voltage Motor Protection: ii) Overall generator unit transformer
differential protection.
The minimum protection requirement shall
include fuses and thermal overload relay - In installations where generator is
suitably co-ordinated with contactor operating in parallel with the grid,
characteristics as per applicable Indian special protection such as out of
Standards (BIS). However M.V. Motors step relay may be required.
controlled by circuit breakers may have
either releases or relay for Motor - It is recommended that
Protection. synchorising check relay for bus
coupler may be provided on those
- Large MV Motors which are contactor switchboards having grid as well as
fed (90 KW and above) may have core in plant supply with manual transfer
balance earth fault protection in addition & momentary paralleling feature.
to bimetal and fuse combination or
composite motor protection relay. In addition to electrical protection
relays, rotating machines may also
- Bimetal relays shall be preferably with require tripping/alarm for excessive
inherent protection against single vibration, high winding temperature and
phasing. high bearing temperature.

ix) Generator Protection : x) Capacitor Protection

The Protecting generally used for The protective requirements of capacitors


generators are as under. However the provided for power factor correction will
actual protective requirements will vary vary depending upon the rating and the
from case to case, depending upon the system configuration.
rating, excitation system, operation, type of
prime mover etc. The recommended protections include:

- Differential protection (87 G) i) IDMTL over-current with high set


element for protection against short
- Stator earth fault (51 N) circuits.

- Rotor earth fault (61) ii) Instantaneous earth fault

- Voltage controlled overcurrent (51V) iii) Neutral phase displacement

- Reverse power (32) iv) Under voltage

- Field failure (40) v) Over voltage

- Unbalanced loading protection (46) vi) Each element of basic capacitor unit
may have its own built in fuse, which
(Negative sequence current protection) shall isolate the faulty capacitor.

- Stator winding temperature protection The capacitor bank feeders shall generally
(49 T) be tripped on bus under/over voltage
conditions and necessary interlock shall be
- Under frequency protection (81) provided for re-switching to take care of
capacitor residual voltage.
When generator with unit transformers
is employed besides individual M.V capacitors of smaller ratings may be
equipment protection, the following controlled with switch fuse units.
additional protections are
recommended: The continuous current rating of fuses and
switching devices for capacitors should be
i) Transformer over fluxing protection 30% higher than the normal full load
current.
4.6 Emergency Power Supply continuity of supply to critical loads (e.g.
process control, communication, fire alarm
i) This is an independent back-up source of systems etc.) in the event of
electric energy that upon failure or outage normal/emergency supply failure.
of normal source, automatically provides
reliable electric power within specified time 4.7.1 Un-interrupted Power Supply (UPS)
to critical devices and equipment whose
failure to operate satisfactorily may i) An un-interrupted power supply shall be
jeopardise the health and safety of provided, as required for meeting critical
personnel or result in damage to property. loads that cannot withstand a momentary
interruption/other A.C. mains disturbance
ii) The emergency power supply system shall in supply voltage. A separate battery shall
feed the following loads to enable be provided for UPS system.
continuity of supply in the event of failure
of MAIN SUPPLY. ii) Following loads shall be connected to the
UPS system:
- Electrical loads essential for the
safe shutdown of the plant. - Critical instrumentation and process
control,
- Emergency lighting, security
lighting, obstruction lights. - Critical communication equipment,

- Process plant instruments as - Microprocessor based distributed


required digital control system.

- Communication equipment, Fire UPS system shall be fed from the


Alarm control panels. emergency system, wherever provided.

- D.C. Supply system, UPS system iii) In case of total power failure, un-
interrupted power supply shall be available
- Auxiliaries of emergency set as for at least 30 minutes or as determined by
applicable the process considerations.

- Fire fighting equipment excluding iv) Each branch circuit of the UPS distribution
main fire water pumps system shall have a fused disconnect
switch. The fuse shall be fast clearing type
- Essential ventilation loads, and and the fuse rating shall be coordinated
with the rating of the UPS system.
- Loads critical for process, plant and
personnel safety. 4.7.2 DC Power Supply

iii) Emergency power supply shall be i) Unless otherwise specified, independent


available as per process/equipment DC power supply systems shall be
requirements, but within a period not provided for the following:
exceeding 30 seconds from the instant of
failure of normal supply. - Plant shut-down system and DC
instrumentation.
iv) Unless otherwise required, the emergency
generator in general may not run - Electrical switchgear controls and
continuously in parallel with the normal critical (escape) lighting, critical
power supply system. However, to D.C. drives viz. LUBE OIL PUMPS
facilitate periodic testing and maintenance etc.
it is preferable to include synchronising
facilities for short time parallel operation of ii) Each DC power supply system shall
D.G. set unless objected to by electrical include charger-cum-rectifier, battery and
supply authorities. DC distribution board. DC link in the UPS
system shall generally not be tapped for
4.7 Critical Power Supply Systems DC instrumentation power supply except
in rare circumstances.
i) These systems shall have inherent
independent battery backup to maintain
iii) Fire alarm system shall have a dedicated and equipment for areas where
24 V DC battery backup system. flammable gas or vapour risks may arise:

iv) It is recommended that D.C. supply for a) Area classification, i.e. Zone 0, 1 or 2
electrical controls, instrumentation, UPS
etc. shall have separate independent b) Gas group classification, i.e. the gas
battery banks. group.

4.7.3 Battery Sizing c) Temperature classification

i) Electrical Switchgear and Controls d) Environmental conditions in which


apparatus is to be installed.
Battery shall normally be sized for a load
cycle having a minimum duration of one Where practicable, electrical
hour. While deciding the load cycle, apparatus in general and switch and
consideration shall be given on specific control apparatus in particular shall
operating/safety requirements of plant & be installed in safe area. Substation
equipment e.g. lube oil pump of STG for and control room shall be located in
bearing oil flushing. The duration for safe area. While deciding the route of
battery sizing hence shall vary accordingly overhead power lines, necessary
as per specific operational requirements. considerations shall be given to avoid
overhead lines passing through
ii) DC Instrumentation Shutdown System hazardous areas.

This shall in general be sized for 30 Electrical equipment intended for


minutes, unless otherwise required. service in hazardous area shall be
selected in accordance with IS : 5571
iii) Fire Alarm System and these shall be approved by
recognised testing and certifying
The battery shall be sized for the authorities i.e. CCE or DGMS or
duration and load in line with the DGFASLI as applicable.
guidelines given in IS 2189.
For details on hazardous area
iv) EPABX (Telephone System) classification, enclosure protection
etc. OISD standard 113, NEC 1985,
This will have an independent battery back IS 5571, 5572, IS 13408 Petroleum
up system. Rules and Oil Mines Regulations
shall be referred.
4.7.4 Annunciation
iii) General guidelines for type of protection
Sensitive earth fault detectors shall be for electrical equipment in hazardous
provided in D.C. system to annunciate areas are enumerated in Table-I.
earth faults.
TABLE-I
5.0 Electrical Equipment for Classified TYPES OF PROTECTION
Areas -----------------------------------------------------------
Area Description Symbol
i) All the areas within the Battery limits shall Classif-
be classified for degree and extent of ication
hazard from flammable materials. The -----------------------------------------------------------
basis for hazardous area classification Zone 0
recognises the differing degrees of - Intrinsic safety category ‘ia’ ‘ia’
probability with which flammable
atmosphere may arise in the installation, Other electrical apparatus, ‘s’
in terms of the frequency of occurrence specifically designed for
and the probable duration of existence on Zone 0. (See Note 1)
each occasion.
Zone 1
ii) Following factors shall be considered for - Any type of protection
proper selection of electrical apparatus adequate for Zone 0.
- Flame proof enclosure ‘d’ Note 5 Name plate details of equipment
intended for use in hazardous area
- Instrinsic safety category ‘ib ‘ib’ shall include relevant marking of
hazardous protection as per applicable
- Pressurisation (See Table II) ‘p’ IS codes.

- Sand filling ‘q’ Note 6 Flameproof enclosures are covered


under compulsory certification.
- Other electrical apparatus ‘s’
specifically designed for Zone 1 TABLE-II
MINIMUM ACTIONS ON FAILURE OF
Zone 2
PROTECTIVE GAS FOR TYPE OF
- Any type of protection ade- PROTECTION ‘P’
quate for Zone 0 or Zone 1 -----------------------------------------------
Area Classification Enclosure s Enclosure
- Increased safety (See Note 2) ‘e’ does not contain
contain ignition-
ignition- capable
- Non-sparking apparatus capable apparatus
(See Note 2) ‘n’ apparatus
-----------------------------------------------------------
- Pressurisation (See table II) ‘p’ Zone 1 Alarm Alarm
and
- Oil Immersion (see note 4) ‘o’ switch off

Note 1 It may be noted that as per petroleum Zone 2 No action Alarm


rules the use of intrinsically safe required
electricity apparatus in zone ‘0’ area is -----------------------------------------------------------
permitted only when the use of such 6.0 SUBSTATION LOCATION / LAYOUT
apparatus cannot be completely
excluded, whereas the Oil Mines The sub-station shall be located in a safe
regulations prohibit use of any area. Consideration shall be given to
electrical equipment in zone ‘0’ areas. cooling tower sprays, vapours
contributing to insulation break down,
Note 2 The apparatus with type of protection vehicular traffic accessibility for
‘e’ and type of protection ‘n’ when installation of equipment or any other
installed outdoors shall have factor that might affect the safe
enclosures providing at least the IS operation of the sub-station. (Refer
4691/2147. also OISD Standard 118 ‘Layout for Oil
and Gas Installations’)
a. IP 55 where there are uninsulated
conducting parts internally, and i) In large plants, the main sub-station floor
shall be raised above grade level and the
b. IP 44 for insulated parts. space below the sub-station floor shall be
utilised for installation of cable trays. The
Note 3 Presently there are apprehensions on substation cellar shall have preferably a
the suitability of use of high voltage clear height of 2 meters. The switchgear
Type ‘e’ and Type ‘n’ motors in Zone-2 rooms shall preferably be pressurised to
areas. Since the research work is still prevent ingress of dust. Large substation
inconclusive, the existing standards for shall have three entries, one for equipment
Ex ‘e’ and Ex ‘n’ motors have not been entry, second for normal entry and the
revised. Advice of the concerned third emergency exit. Where as required
statutory authority should be sought normal and equipment entries can be
while selecting Ex ‘e’ or Ex ‘n’ high combined.
voltage motors in Zone-2 areas.
Pressurised sub station shall have
Note 4 Oil-immersed apparatus may be used necessary Airlock lobby for the normal
only in case its security will not be entry.
impaired by tilting or vibration of the
apparatus.
Small and medium size substations shall foundation of such D.G. sets shall be
have one equipment cum normal entry and structurally delinked from the slab or floor
the second for emergency exit. Emergency of the rest of the substation building.
exit door in substation shall open Exhaust of Diesel Engine shall be kept
outwards. The main entry for operating away from Process/Hydrocarbon area.
personnel shall be preferably provided with
double door system. Operator cabin may vii) Transformer yard/bay shall be provided
be separately located to avoid repeated with fencing and gate and shall have fire
opening of doors and dust entry to isolation walls for individual transformers.
substation. Pressurised substation building Oil immersed equipment involving use of
shall have fixed glazing with minimum large quantity of oil shall have oil soak pit
number of openable windows. All openings and drain arrangement as per Indian
shall be kept properly closed to maintain Electricity Rules and regulations. *Fire
sufficient pressure inside to prevent dust fighting equipment, first-aid boxes, etc.
entry. shall also be provided as required. (Further
guidelines on this can be had from OISD
ii) Non pressurised remote switch standard 116 - ‘Fire Protection facilities for
room/offsite substation shall have fixed Petroleum Refineries and Oil/Gas
glazing with suitable exhaust fans with Processing Plants’ and OISD standard 117
louvers to meet the ventilation ‘Fire Protection Facilities for Petroleum
requirements. Proper maintenance and Depots and Terminals.)
care shall be taken to keep the room free
from dust. viii) The substation equipment layout and the
clearances between different equipment
iii) The building shall sized to take care of shall be planned to ensure ease of
present/future needs and to maintain operation and maintenance and meet all
adequate clearances between equipment, requirements from the point of view of
and equipment and wall for ease of safety of the operating personnel.
operation and maintenance. Small sub-
stations shall suitably elevated by ix) Clearance between various equipment
compacting the soil so that the bottom of shall also satisfy respective equipment
the cable trench within substation is above manufacturer’s requirements and Indian
the surrounding grade level. Electricity Rules. Where these are not
specified the following minimum
iv) Normally transformers, reactors, neutral clearances are recommended as general
earthing resistors etc. shall be installed guidelines.
outdoor. Equipment like UPS system and
frequency stablisers shall be installed in a a) At the rear of H.V.
separate air-conditioned room. The battery Swbd : 1500mm
banks shall be located in a separate, freely
ventilated room in the sub-station building b) At the front HV
alongwith the necessary exhaust system Swbd : 2000mm
and water connection. Floor of the battery
room and the walls upto height of one c) At the side of
metre shall have acid resisting various boards
material/coating/be painted with acid/alkali from wall 1000mm
resistive paint or otherwise protected.
d) At the front
v) Necessary space to keep equipment under of various boards 1500mm
repair such as breakers, switch control between front to -2000 mm
gear items, spares/consumables like fuses front of two boards
etc. shall also be identified in building (say DRAWOUT
layout. MCCS) facing
each other.
vi) It may be preferable to locate DG sets in a
separate house/shed away from Sub e) At the rear of MV 1000mm
station in a safe area to reduce noise level Switchboards
in substation. If required DG set of smaller requiring rear access
rating may be located in substation
building provided the substation is located f) Rear clearance in
in a safe area. However in such cases, the other cases More than
750mm Electrical equipment shall be suitable with
otherwise respect to the maximum steady voltage
less than (rms value for AC) likely to be applied, as
200mm. well as overvoltages likely to occur.

g) Transformers with Note: For certain equipment, it may be


wall on one side As per IS necessary to take account of the lowest
Tansformers with 100028 voltage likely to occur.
wall on three sides.
Considerations shall also be given to the
h) Clear height of protective measures inherent in the
busduct 2000mm systems and the method of neutral
from finished earthing viz. earthed or unearthed
floor level system.

I) Clear space betw- ii) Current


een Switch Board 1000mm
top and beam soffit All electrical equipment shall be selected
with respect to the maximum steady state
(Note : The maximum length of switchgear current (rms value for AC) which it has to
lineup may preferably be limited carry in normal service, and with respect to
to 15-20 metres considering the currents (prospective, short circuit
operation and maintenance currents) likely to be carried under
requirements. abnormal conditions and the period (for
example, operating time of protective
x) It is recommended that battery room, devices, if any) during which it may be
UPS room, charger room, operator’s expected to flow.
room of large sub stations, located close
to process units should have blast proof iii) Frequency
walls. This is to protect vital control power
sources from any external damage, thus Electrical equipment shall be suitable for
ensuring availability of control power for continuous operation with respect to the
safe shutdown in disastrous conditions system rated frequency with variation limits
suitable for indoor use. likely to occur.

7.0 ELECTRICAL EQUIPMENT iv) Power

Electrical equipment shall be selected, All electrical equipment to be selected on


sized and installed so as to ensure the basis of their power characteristics
adequacy of performance, safety and shall be suitable for the duty demanded
reliability. The equipment in general shall from the equipment, taking into account
conform to relevant Indian Standards the load factor and the service conditions.
and shall be suitable for installation and Each equipment shall be able to deliver its
satisfactory operation in the service rated power for specified supply and site
conditions envisaged. Specific attention conditions with temperature rise remaining
is drawn to IS:9676 for deciding the well within the design limits as per
design ambient temperature of electrical applicable IS codes.
equipment.
v) System earthing
7.1 CHARACTERISTICS
All electrical equipment shall be selected
Every item of electrical equipment considering the system neutral earthing
selected shall have suitable particularly in high voltage systems where
characteristics appropriate to the values resistance earthing is commonly
and conditions on which the design of the employed.
electrical installation is based and shall in
particular, fulfil the requirements given in vi) Conditions of Installation
Clause i) to vii) below.
a) All the electrical equipment selected
I) Voltage shall have proper protection against
corrosive and solvent agents, water
ingress, thermal and mechanical a) All electrical equipment shall be
stresses as determined by the selected so that it will not cause
environmental factors. If, however, an harmful effects on other equipment or
item of equipment does not have by impair the supply during normal
design, the properties corresponding service including switchgear
to its location, it may be used on operations. In this context, the factors
condition that adequate additional which may have an influence include:
protection is provided as part of the
completed electrical installation. In * Power factor
addition to the above, noise level and
cooling/ventilation shall also be * Inrush current
considered.
* Asymmentrical load
PAINTING
* Harmonics
a) Rotating Machinery
* transient voltage
Internal and external parts of the dips/overshoots.
casing and all metal parts likely to
come in contact with the surrounding b) Energised parts shall be sufficiently
air shall be protected with anti-acid/anti enclosed or isolated so as not to
alkali epoxy paint that will resist expose personnel to explosion, fire,
corrosion under the particular arcing, or shock hazards. Adequate
atmospheric conditions. safety features shall be incorporated in
equipment design for the safety of
b) Switchgear panels and operating personnel.
service boards
7.2 EQUIPMENTS FEATURES
All metal surfaces shall be thoroughly
cleaned and degreased to move mill Certain essential safety features in
scale, rust, grease and dirt. Fabricated design to be considered in specifying
structures shall be pickled and then and sizing of commonly encountered
rinsed to remove any trace of acid. equipment such as Transformer,
The under surface shall be prepared Switchgear, Motors, Cables, Battery
by applying a coat of phosphate paint, charger Battery, and U.P.S. etc. are
and a coat of yellow zinc chromate enumerated below.
promer. The under surface shall be
made free from all imperfections 7.2.1 Transformers
before undertaking the finishing coat.
i) The KVA rating shall depend upon the
After preparation of the under surface, maximum simultaneous continuous load
the switchboard shall be spray painted and probable system expansion loads. In
with two coats of final paint. Colour general, the rating and the percentage
shade of final paint shall generally be impedance of each transformer shall be
light admiralty grey shade No. 631 as selected to limit the continuous current
per IS:5, unless otherwise required. rating and short circuit current to values
The finished panels shall be dried in within the ratings of available switchgear.
stovings ovens in dust-free The transformer impedances shall
atmosphere. Panel finish shall be free generally be as per Indian standards
from imperfections like pinholes, unless otherwise required. The rating and
orange peels, runoff paint, etc. the percentage impedance of transformer
shall be compatible to permit start of
All unpainted steel parts shall be highest rated motor while the transformer
cadmium plated or suitably treated to is preloaded with maximum operating base
prevent rust corrosion. load.

If these parts are moving elements, ii) Transformers connected to Grid supply
then these shall be greased. may have ON LOAD TAP CHANGERS for
inplant control of secondary voltage. Plant
vii) Prevention of Harmful effects distribution transformers may have OFF
CIRCUIT TAP changers.
trucks of the same rating shall be
iii) In addition to standard accessories, the interchangeable.
transformer shall be provided with auxiliary
devices/protective devices such as vi) Suitable interlocks shall be provided to
Buchholz relay, oil level and oil temp. prevent faulty operation such as:
indicator with alarm trip output contacts
and current transformers for the secondary - ‘Pluging in’ or ‘drawing out’ of a closed
side neutral for Protection. Transformers breaker.
of rating above 2000 KVA may be
preferably have winding temperature - ‘Pluging in’ a breaker with earthing
indicators with Alarm/Trip provisions. isolator closed.

7.2.2 High Voltage (H.V)/Medium Voltage - ‘Closing’ of earthing isolator with the
(M.V) Switchboards breaker ‘Plugged in’.

i) These shall be designed to ensure - Pulling out of auxiliary circuit plug with
maximum safety during operation, breaker in service position.
inspection, connection of cables and
maintenance with Switchboards energised. - Pushing in breaker to service position
with auxiliary circuit plug not in
ii) The switchboard shall be totally enclosed, position.
dust and vermin proof.
- Opening of compartment door with
iii) Each unit of the switchgear shall have isolating switch in ON position and
necessary internal sheet metal barrier to vice-versa for Motor Control Centres.
form separate compartments for buses
instruments/relays/cable connections etc. The maximum height of operating
Compartment for cable connection shall handle/switches shall not exceed 1800
allow cable pulling, termination and mm and the minimum height not below
connection work with switchgear 300 mm.
energised. Suitable arc propagation
barriers shall also be provided. - It shall not be possible to operate the
Independent pressure release flaps shall circuit-breaker unless it is fully in
preferably be provided for each different service or Test or isolated position.
compartment of H.V. Switchboards.
Terminal strip for outgoing control cable vii) Suitable eye bolts for lifting of panels shall
connections should be accessible to be provided. On removing the eye bolts,
facilitate working and testing with breaker no holes offering access to panel shall be
in test/service condition and while the permitted.
switchboard is energised.
viii) Different sections, viz. busbar,
iv) Barriers shall be provided to permit switchgear, cable, relays and meters etc.
personnel to work safely within an empty shall be compartmentalised. Busbars and
compartment with the bus bars energised. supports shall withstand specified short
The minimum clearance and creepage circuit level without permanent
distance of bus bars shall conform to IS deformation. Busbars shall be preferably
4237. sleeved and joints shall be
taped/shrouded. Minimum clearances
v) The drawout carriage on the switchboard between live parts, between live parts to
shall have three positions viz., ‘Service’, Earth and Neutral shall conform to
‘Test’ and ‘drawn out’. Automatic safety applicable IS code (IS 4237)
shutters shall be provided to ensure the Switchboards shall have additional safety
inaccessibility of all live parts after the features such as falling tool shrouds for
breaker is drawn out. It shall not be trapping of free fall of maintenance tools
possible to drawout the carriage or rack it on live parts. Busbar supports shall be of
in with circuit breaker closed. The synthetic material with high tracking
breaker/contractor feeder trolley shall index. The switchboard shall have earth
remain inside the cubicle even in the test busbar of adequate size. The switchgear
position. There shall be distinct overall drawout trolley (in case of drawout
door for the breaker compartment and it design) shall have suitable scraping earth
should be lockable. All circuit breaker connection. Feeder tag plates shall be
provided at both front and rear side of suitable for starting under specified load
panels. Where required, busbar routing conditions with 75% of the rated voltage at
shall be clearly marked on the back side the terminals.
of the H.V. Switch board panels for easy
identification during maintenance. iv) The permissible noise level shall not
exceed the stipulations laid down in IEC 34-
ix) All non-current carry metallic parts of 9.
mounted equipment/components shall be
bonded to the earth bus. v) Motor vibrations shall be within the limits of
IS-4729 unless otherwise specified for the
x) Surge absorbers to limit the switching driven equipment. Motors with sleeve
surges shall be provided as dictated by bearings may require proximity probes to
the type of arc quenching media and measure shaft vibration adjacent & relative
switching device. to the bearings.

xi) Starting of motors from substation shall i) Motors shall be required for continuous,
not be allowed and switch boards shall satisfactory operation at rated output under
not have close push button at the following conditions :
switchboard for motor starting.
a) The terminal voltage differing from its
xii) In specific cases, motors requiring rated value by not more than ± 6%.
frequent start/stop, (e.g. product, loading
pumps etc.) shall be controlled by b) The frequency differing from its rated
contractor feeder appropriate to its rating. value by not more than ± 3%

xiii) Switch Boards shall have anti c) Any combination of (a) and (b).
condensation heaters.
vii) Motor ratings and torque characteristics
7.2.3 MOTORS HIGH VOLTAGE (H.V.) shall be adequate to accelerate the load
from zero to rated speed under starting
& MEDIUM VOLTAGE (M.V)
requirements as stipulated by process
operating conditions. Normally, the starting
7.2.3.1 General
time shall be less than the hot withstand
time of the motor.
(1) Motors shall be totally enclosed,
fan cooled type as far as
viii) M.V. Motors in general and H.V. Motors
practicable. As a minimum, all
where required shall be suitable for
H.V. motors shall have anti
restarting under full load after a
condensation heaters. The
momentary loss of voltage with the
minimum degree of enclosure
possibility of application of 100 percent of
protection for motor shall be
the rated voltage, when the residual
preferably IP 44 for indoor use and
voltage has dropped down to 50 percent
IP 55 for outdoor duty motors.
and is in phase opposition to the applied
voltage.
ii) Generally Motors upto and including 160
KW shall be rated for medium voltage and
ix) Motor bearings shall be selected to give a
motors of rating above 160 kw shall be
minimum L-10 life rating of 5 years (40,000
rated for high voltage. If required, the rating
hours) at rated operating condition (the L-
of medium voltage motors may be extended
10 rating life is the number of hours at
upto and including 200 KW. Sleeve or anti
constant speed that 90% of a group of
friction type bearings shall be used. Vertical
identical bearings will complete or exceed
motors shall have thrust bearings suitable
before the first evidence of failure). The
for the load imposed by the driven
bearings shall be adequate to absorb axial
machinery. Unless otherwise specified, all
thrust in either direction produced by the
motors shall be designed for ‘Direct ON
motor itself or due to shaft expansion. On
line’ starting.
line greasing facility should be provided on
motor for all grease lubricated bearings
iii) High voltage motors shall be suitable for
(anti friction bearings). Wherever
starting under specified load conditions with
spaceheaters are provided for motors, a
80% of the rated voltage at the terminals
separate terminal box should be provided
and medium voltage motors shall be
for termination of spaceheater cables, as
far as practicable. Polarisation index of H.V. stator winding
shall have a value of at least 2. If the
7.2.3.2 H. V. Motors insulation value of the motor exceeds a
value of 120 (Un+1) (where Un is rated line
i) Winding insulation shall be class F and - line voltage (KV) mega ohm, a minimum
temperature rise limited to that specified in polarisation index of 1.5 is acceptable.
the applicable IS for class B insulation.
7.2.3.3 M. V. Motors
ii) Motors shall be designed to allow minimum
number of consecutive hot starts as i) Motors shall be designed to allow three
dictated by process operating requirements. consecutive starts from cold condition, two
Number of uniformly spaced startups in an consecutive starts from hot condition and
hour shall be a minimum of three. four uniformly distributed starts in one hour.

iii) The main power Terminal Box shall be ii) Motors shall be provided with minimum
phase segregated and suitable to withstand class ‘B’ insulation or class ‘F’ insulation
the specified fault level for a minimum may be considered for special applications
duration of 0.2 sec. (Commensurate with and permissible temperature rise above the
instantaneous short circuit protection). specified ambient temperature shall be
Winding ends shall be preferably brought limited to the values applicable for class ‘B’
out and star point made in a separate insulation. The windings shall be
terminal box. Neutral terminal box shall tropicalised and adequately braced. The
have necessary space provision to mount ends of the windings shall be brought out in
differential CTs for motors of rating 1500 a terminal box with six terminals with
KW & above. suitable links to connect them in Delta.
However, motors rated upto 2.2 KW may be
iv) Motors of rating above 1000 kw shall be connected in star with three terminals.
provided with RTDs, BTDs. Separate
terminal boxes shall be provided for space iii) The terminal box of motor controlled by air
heater and RTDs, BTDs. circuit breaker shall be capable of
withstanding the full internal short circuit
v) Induced voltage at the shaft of the motor conditions, with the specified system fault
having uninsulated bearing system shall not level for a minimum duration of 0.2 second
exceed 250 mV r.m.s. for roller and ball (Commensurate with instantaneous short
bearings and 400 mV r.m.s. for sleeve circuit protection). Where motor control is
bearings with the motor running at no load. through contactor and MCCB, or back up
Alternatively, the non driving end bearing fuse, the terminal box shall be able to
shall be insulated from the motor frame to withstand the let-through energy of
avoid circulating current. protective devices corresponding to
maximum system fault level.
vi) The insulated bearing end shield or
pedestal shall bear a prominent warning iv) The terminal box shall be of sturdy
and manufacturer shall provide detailed construction and large enough to facilitate
drawing showing insulation arrangement. easy connection of required number of
cable runs and size. (specifically Aluminium
vii) Motors shall be designed to withstand Conductor Cables). Additional trifurcating
impulse voltage of at least (4Un+5) KV with boxes may be considered for motors
a wave front raise time of 1.2 microsecond requiring termination of two or more parallel
and decay time of 50 microsecond to half runs of power cables.
the peak voltage.
7.2.4 Battery Charger and D.C.
viii)The interturn insulation of H.V. motors shall Distribution Board
be able to withstand a peak voltage of at
least 0.5 (4Un+5) KV with a wave front rise Charger and D.B. shall be floor mounted,
time between 0.5 & 1.5 microsecond and a free standing, metal enclosed and vermin
decay time to half the peak voltage of proof type having front access hinged door
between 3 & 10 (microsecond). and suitable for indoor use.
Un = rated line to line voltage.
This shall consist of battery
ix) Polarisation index charger/rectifier, which shall feed the load
and keep the batteries under fully charged be instantaneously transferred to the by-
condition. Provision shall also be made for pass line through the static switch. Normally
necessary boost charging/initial charging of the inverter shall be operated in
battery. synchronised mode with the by-pass line,
and manual forward transfer or manual
7.2.5 Batteries and Battery Accessories reverse transfer shall be effected without
any break.
i) This shall be indoor stationary type (lead
acid/Ni-Cd etc.) with adequate capacity to Automatic forward transfer, in case of
meet the backup requirements as inverter malfunction, shall be effected with a
envisaged in the duty cycle. Accessories break not exceeding 5 ms.
shall generally be as follows :
7.2.7 Capacitor Banks
- Battery stand made of treated first
class teakwood assembled without the i) The capacitor shall conform to IS 2834
use of any metal fastenings.
- specifications for shunt capacitor for power
- Intercell, inter ro and inter bank system.
connectors and end take offs.
ii) H. V. capacitor shall comprise appropriate
- Porcelain cell insulators, stand nos. of basic single phase units (minimum 4
insulators. nos. basic units in parallel per phase) which
shall be connected in star formation.
- Hydrometers suitable for specific
gravity readings. iii) Capacitor banks shall be with necessary

- Cell number plates and fixing pins as 7.2.7 Capacitor Banks


required.
i) The capacitor shall conform to IS 2834 -
- Thermometer with specific gravity specifications for shunt capacitor for power
correction scale Nos. system.

- Cell testing voltmeter (3V-0-3V) ii) H. V. capacitor shall comprise appropriate


complete with leads 1 Metre. nos. of basic single phase units (minimum 4
nos. basic units in parallel per phase) which
- Rubber gloves shall be connected in star formation.
- Rubber aprons
- Spanner Set. iii) Capacitor banks shall be with necessary
discharge resistors to reduce the terminal
ii) While sizing the battery following factors voltage of each unit to a value equal to or
shall be taken in to consideration, in less than 50V in 5 minutes.
addition to envisaged duty cycle :
iv) Steel rack assembly suitable for outdoor
- Temperature correction factor. installations (where outdoor location is
- Ageing factor as applicable. required) to accommodate the basic
capacitor units with necessary post
7.2.6 Equipment for Uninterrupted insulators. Panel assembly (where indoor
Power Supply System location is required) to accommodate the
basic capacitor units, interconnecting
i) This shall be of free-standing, floor busbars, insulators etc. The panel shall
mounted, metal enclosed and vermin proof have minimum IP-51 protection and shall
type having hinged door for front access be constructed with sheet steel of minimum
and suitable for indoor use. thickness 2.0 mm.

ii) Under normal conditions, the rectifier-cum- v) Necessary series reactor to limit in rush
charger shall feed the inverter and charge current and suppress harmonics (where
the battery set. In case of mains failure, the required)
battery shall supply the necessary power to
the inverter. The inverter in turn feeds the vi) The impregnant in the capacitors shall be
load through the static switch. If the inverter non-toxic.
malfunctions or is overloaded, the load shall
7.2.8 Emergency Generator
i) In order to avoid spread of fire due to
i) The emergency generating sets shall form cables, it is recommended that the outer
a complete package and shall be designed PVC sheath of all cables used in industry
to start automatically on power failure and shall be flame retardant type conforming to
feed the selected loads. It shall be capable category AF as per IS: 10810. The cable
of taking care of the load variations (e.g. the shall have a low smoke property. The
Note 3
starting of largest rated motors on a minimum Oxygen Index shall be 29 .
preloaded system). The unit shall be
complete with necessary starting ii) High voltage cables may be
equipment, associated control panel and Aluminium/Copper Conductor XLPE
shall be suitable for remote starting. insulated PVC sheathed, armored type.

ii) The regulation of generator voltage shall be The conductor screen, XLPE insulation
automatic and necessary instruments for screen shall all be extruded in one
metering viz. Ammeter, Voltmeter, operation by ‘Triple Extrusion’ process.
Frequency meter, KWH meter, Power
Factor, Hour run counter etc. shall be iii) 1.1 K.V. grade cables may be
included in control panel. Aluminium/Copper Conductor PVC
insulated, PVC sheathed, armored type.
iii) Warning of abnormal conditions shall be
incorporated prior to automatic trip to iv) All power and control cables shall preferably
prevent unnecessary shutdown. have extruded inner and outer sheaths.

All the six stator winding ends shall be v) Where single core cables are armored and
brought out to an externally mounted are meant for use on A.C circuits,
terminal box and shall be connected in star. armouring with non-magnetic material (e.g.
Necessary temperature detectors shall be Aluminium) shall be given.
provided for the stator winding. The terminal
box shall have sufficient space to receive The communication cables shall conform to
the cables of specified size. ITD specification. For fire alarm systems,
PVC insulated, armoured and overall PVC
iv) Emergency D.G. set shall have Auto sheathed cable with 1.5 mm2 copper
starting arrangement but only with manual conductors may be used.
switching off features. The rating (Ampere
Hours) of battery, for cranking the engine vi) The power and control cables shall have
shall be adequate to make three attempts the following minimum cross sectional
with an interval of 5 to 10 seconds, if areas :
required. In case the engine fails to start
2
‘FAIL TO START’ annunciation shall be a) Medium voltage 4mm
provided in substation or in control room. powercable Aluminium or
2
2.5 mm Copper
v) The generator set shall be provided with
2
complete protection against overloads, b) Control cables 2.5 mm (Copper)
short circuits, ground faults, excitation (See Note 1 below)
failure, prime mover failure and shall
include other connected instrumentation c) Lighting 2.5 mm2 (Copper)/
interlocks. 4mm2 (Aluminium)
(See Note 2 below).
vi) The load shall be switched on to the
generator only after the requisite voltage Note 1 In case of difficulty in connecting the
build-up. cables to instrument relay Annuciation
terminals, the minimum cross section
vii) Diesel Engine installation, do not call for may be reduced to 1.5 mm2 copper.
Area Classification, provided the D.G. room
is properly ventilated. Normally the Note 2 For lighting inside the building copper
ventilation provided to remove heat from the conductor cables shall be used.
radiator is adequate to take care of hazard Where conduit wiring is adopted,
aspect. minimum 1.5 mm2 copper conductor
PVC insulated wire may be used.
7.2.9 Cables
Note 3 Conductor size for wiring inside the - Start/stop push button/close, neutral,
panel for electronic Trip Switch
circuits/components shall be as per
manufacturer’s standard. - Ammeter,

vii) Cables shall be properly sized to carry - Local/Remote Selector Switch


without undue temperature rise the load
current under site derated conditions. The - Auto/Manual selector switch and
derating shall take into account ambient air cable glands.
temperature, ground/duct temperature,
grouping and proximity of cables with each iv) Stop push button shall generally have stay
other, thermal resistivity of soil etc. Cables put feature except in the case of critical
protected by fuses shall be able to drives such as lube oil pump etc.
withstand the maximum I2 t let through
energy of fuse. v) Control station shall have suitable locking
facility.
In other cases, cable shall be able to
withstand the fault current for a duration as 7.2.11 Convenience Receptacles
dictated by protective disconnecting device.
i) These shall have the necessary
viii) The type of cable selected and the mechanical interlocks and earthing
insulation shall be compatible with various facilities. The enclosure shall have suitable
chemicals encountered in the plant and protection for site conditions specified
other environment conditions such as such as flameproof, weather-proof, dust-
dampness highly corrosive atmosphere, proof, corrosion resistant, etc.
high/low temperature, radiation etc., bearing
in mind that certain chemicals (e.g. ii) Welding receptacles shall be provided at
Benzene, Ethylene chloride) are known to suitable locations to ensure accessibility
be detrimental to PVC. with a 50 meters length of trailing cable to
any point in the process area. These shall
ix)The selection of voltage rating of H.V. be rated for 60 A suitable for 415 V, 3-
cables shall take into account the system phase system with a scraping earth
voltage, system earthing arrangements and connection.
type of earth fault protection schemes.
(Guidelines on this can be had from IEC iii) Adequate number of sockets for lamps
183). and portable tools shall be provided at
suitable locations to ensure accessibility
x) When feeders comprising of parallel runs of with a 15 meters length of cable to any
cables are envisaged, the size and type of point in the process area. These shall be
individual cable shall be identical. rated for 15 A single phase supplied at 240
V. Hand lamps and portable tools shall be
earthed through flexible cords. The flexible
7.2.10 Control Station cable shall have 3 cores of multistrand
copper conductor of minimum size
i) Each Motor shall be provided with a control equivalent to 1.5 Sq mm, with PVC
station in the field. Motors installed at insulation and metal braiding. In hazardous
elevated platforms (such as cooling tower areas, handlamps shall be rated for 24
fan, air fin cooler etc.) shall be provided with Volts. Accordingly 240/24 V transformers
one stop push button at ground level in shall be provided either in the plug or in
addition to one near motor. separate flameproof enclosure.

ii) The control station enclosure shall have 7.2.12 Actuators for Motor Operated
suitable protection for site conditions such Valves
as flameproof, weather-proof, dust-proof,
corrosion resistant, etc.). i) Valves with electrical actuators shall
generally be provided with integral starters.
iii) The control station shall include the
following equipment as per individual ii) The necessary local/remote selector
requirements : switch, start/stop control switches or push
button, torque limit switches etc. shall be
provided on actuator for local/remote
control depending on mode of selection. In High voltage, medium voltage and other
case of failure of torque limit switches, the control cables shall be separated from each
mechanical design shall be adequate to other by required spacing or running
stall and trip the motor without damage. through independant pipes, trenches or
cable trays as applicable. Cable trenches
iii) The control circuits shall AC operated for inside substations shall be filled with sand,
short distance or DC operated for pebbles or similar non-flammable materials
extended distance. The actuator shall be or covered with incombustible slabs. If a
provided with an anti condensation heater. significant number of cables are taken on
racks/supports provided on the side wall of
8.0 Plant Cabling trench.

i) Cables below ground may be laid in iv) RCC covers of trenches shall be effectively
concrete trench/tunnel or directly buried. sealed to avoid ingress of chemicals and
Cables above ground shall be laid in cable oils.
trays/cable racks.
v) In unpaved areas, cables may be directly
However cabling for fire water system shall buried in ground. Where underground
as far as possible be taken in exclusive cables cross roadways or pipe sleepers at
route through underground trench. grade etc., they shall be protected by being
drawn through sleeves/ducts to provide a
ii) While designing layout with single core permanent crossing. Sleeves/ducts ends
cable installations following factors shall be shall be effectively sealed thereafter.
considered :
vi) Concrete lined trenches shall have suitable
a) Cables are laid as a general practice in drainage arrangement to avoid water
trefoil formation touching each other. collection. Concrete lined cable trenches
shall be sealed against ingress of liquid and
or gases wherever the trenches leave a
hazardous area or enter control room or
b) flat formation with spacing as per substation. Pipes laid for mechanical
requirement. protection shall be sealed at both ends.

- When cables are laid in a flat vii) Above ground cables shall be well
formation, the individual cable fixing supported suitably at every 2 to 2.5 metres
clamps, and spacers shall be of non interval and protected against mechanical
magnetic material. damage. Routing shall be decided to avoid
proximity to hot sources, place subject to
- As a general practice, the sheath of undue fire risk, gas, water, steam oil drains,
single core cables shall earthed to piping, air conditioning duct etc. Cable
keep sheath at earth potential. trays, racks and trenches shall sized to
However depending on the current allow for 10 to 20% future cables reserve.
the cable has to carry, the feeder Each cable tray tier shall accommodate the
length and permissible sheath cables preferably in single layer.
potential, various methods of sheath
bonding are employed, viz. single Instrument and communication cables shall
point bonding, bonding at middle, not be laid in the same trench/tray along
sectionalised bonding etc., for which with electrical cables. The overall cable
cable manufacturers layouts shall be designed for minimum
recommendations shall be followed. interference between signal and power
cables.
- It should be noted here that the
current rating of cables will vary viii) Cable cellars and important cable
depending upon laying formation, tunnels shall be provided with fire detection
method of sheath bonding etc., apart and monitoring devices.
from other derating factors normally
considered. (Ambient temp., depth ix) Trailing cables for equipment such as
of laying etc.) cranes and excavators shall have one
additional core for earthing and the cable
iii) All trenches shall be sized depending upon shall be well protected against mechanical
the number of cables, and its voltage grade. damage.
critical lighting will be either on 220V or
x) Cable straight through joints in power & 110V DC.
control cables shall be avoided as far as
possible. ii) Sufficient lighting shall be provided so as to
enable plant operators to move safely within
xi) Only type tested and approved make the accessible areas of plant and to perform
termination kits shall be used. While routine operations. In the event of normal
selecting the type of cable kit, necessary power failure, emergency lighting may be
consideration may be given to the additional provided.
safety measures needed for carrying out
termination with kits of type such as heat iii) Lighting requirements provided during the
shrinkable type (particularly in hazardous failure of power supply for Normal lighting
areas). are intended broadly,

xii) Cable route markers shall be installed at a. to facilitate carrying out of specified
every 30 metres intervals all along the cable operations, for safe shutdown of the
routes and also at cable joints and locations plant.
where the direction of cable trench
changes. Cable route markers shall extend b. to gain access and permit ready
600 mm above ground. identification of fire fighting facilities such
as fire water pumps, fire alarm stations
xiii) Cable installations shall provide for etc.
minimum cable bending redii as
recommended by manufacturer. c. Escape route for safe evacuation of
operating personnel.
xiv) Cable trenches in hazardous area
shall be filled with sand and covered with iv) The recommended areas for critical
RCC slabs to prevent accumulation of lighting (D.C.) include :
flammable gas/vapour inside the trench.
- Control rooms (Process & utility)
xv)Cables shall be identified close to their
termination point by cable tag numbers as - Main substations
per cable schedule. Cable tag numbers
shall be punched on aluminium strap 2mm - D. G. Shed
thick flat or circular, securely fastened to
the cable. - Central Fire Station

xvi) Besides each underground cable shall - Fire water pump house (for startup
be provided with identify tags of lead of Diesel driven F.W. pump)
securely fastened at every 30 metres of
underground length with at least one tag at - First Aid Centre
each end before the cable enters the
ground. - Emergency escape route

For further details, on installation practices v) The recommended areas for A.C.
and requirements refer OISD Standard 147 emergency lighting includes :
on ‘Inspection and Safe Practices during
Electrical Installations’. - Control rooms (Process & utility)

9.0 Plant Lighting - Fire water pump house, Fire stations

This can be broadly classified as under : - Main sub stations

i. Normal lighting - Foot of stairs and ladder

ii. Emergency lighting - Platforms with ladders changing


direction
iii. Critical lighting
- Other changes of floor level, that
i) Normal and emergency lighting system may constitute a hazard.
shall be on 415/240V AC supply, whereas
- Strategic locations in Process, utility Depending on the nature of job activities to
areas where specific safety be carried out the suggested minimum
operations are to be carried out such illumination levels for various areas are as
as : under :
--------------------------------------------------------
* Areas near heat exchangers, Areas Illumination
condensers in Lux
--------------------------------------------------------
* Barring gears of steam turbine - Main roads (along process 7 - 10
units, power houses,
* Some portions of roads workshops, etc.)
interconnecting substations and
process plants. - Secondary roads (along 3 - 5
storage tanks settling
vi) As a good engineering practice the A.C. basins etc.)
emergency load is generally considered as
20-25% of Normal Lighting load. However - Tank farm 10
for small plants, where A.C. emergency
load is not substantial/where there is no - Pump houses, sheds 100
separate standby D.G. set, D.C. critical
lighting system may take care of entire - Main operation platforms 60
emergency lighting. & access stairs

vii) The following operational philosophy is - Ordinary platforms 20


recommended. Under normal operation,
both emergency and normal lighting shall - Process areas, pipe 60
be fed by Normal power source. On failure racks, heat exchanger,
of normal supply, emergency lighting load heater, separators, cooling
will be transferred to emergency source tower, columns, pig
after the start of D.G. set within 15 seconds. launching/receiving loading
Critical lighting (D.C. supply based) will be area, flare etc.
normally kept ‘ON’ and during
Normal/emergency power failure, battery - Switchgear bldg. 150-200
will provide power.
- Transformer bay 100
viii) Besides, adequate number of self
contained portable hand lamps and Battery - Battery room 150
emergency lighting units shall be provided
for immediate use in emergency at remote - Control room bldg./laboratory 400
stations and at other strategic places (safe
areas), wherever required, for personnel - Boiler house 150
safety.
- Charger/UPS rooms 150-200
ix) HPMV/MLL lamps shall generally be used
for outdoor plant lighting. Keeping in view - Cooling tower 60
the restrike time lag and to avoid complete
darkness in case of a voltage dip/brown out - Switchyard (i) operating area 100
conditions, necessary incandescent lamps
may be judiciously distributed throughout (ii) other areas 50
the plant area. Incandescent lamps may be
considered for emergency lighting to - Warehouse 100
achieve this objective, Fluorescent lamps
may be used for indoor lighting in non- - Office 300
process buildings and control rooms. Safe
area street lighting and yard lighting may - Compressor area 200
employ sodium vapour lamps. Low
pressure sodium vapour lamps shall not be - Watchroom 100
installed in hazardous areas.
- Stairs 50
x) The illumination levels in different areas
shall be as per good engineering practice. - Corridors/lifts 70
may break only live poles, the neutral being
- Tube well, gate & watchman isolated by a removable link.
booth 100
xvi)For details on installation practices refer
- Fire house, garage 100-150 OISD standard 147.
-----------------------------------------------------------
10.0 Plant Earthing
However, lighting levels in all areas shall
take into consideration the requirements i) Earthing system in general, shall cover the
from point of view of safety, easy operation following :
and maintenance.
- Equipment earthing for personnel
xi) The illumination level requirements (during safety,
normal lighting source failure) depends on
the nature of activities to be carried out. The - System neutral earthing, and
suggested minimum illumination levels are
as below : - Static and lighting protection.

I) Near to areas where Spot ii) The earthing system envisages an earthing
specific safety operations lighting network with designed number of earth
(visual tasks are to be to be electrodes attached to it. The following shall
carried out (e.g. control provided be earthed :
room)
- System neutral,
ii) Escape Lighting
- Current and potential transformer
a. Escape way (interior) - 5 Lux secondary neutral

b. Areas at exit door and - Metallic non-current carrying parts of all


at points where it is nec- electrical apparatus such as
essary to emphasise transformers, switchgears, motors,
the position of potential lighting/power panels, terminal boxes,
hazard if any. - 30 Lux control stations, lighting fixtures,
receptacles etc.
iii) Other notified general
outdoor areas - 1 Lux - Steel structures, Loading platform etc.

xii) The lighting fixtures on various circuits shall - Cable trays and racks, lighting mast and
be suitably interlaced so that failure of any poles.
one circuit do not result in complete
darkness. - Storage tanks, spheres, vessels, columns
and all other process equipments.
xiii)Taller structures shall have aviation
obstruction lighting as per statutory - Electrical equipment fencing (e.g.
regulations (D.G.C.A.). transformer, yard etc.)

xiv)Battery room shall have fixtures mounted - Cable shields and armour
on wall in order to facilitate easy
replacement of fused lamps. Switches - Flexible earth provision for Wagon,
controlling the lighting fixtures and exhaust Truck
fan shall be installed outside the battery
room. iii) Plant earthing design shall generally be
carried out in accordance with the
xv)Switches of lighting panels installed in requirements of Indian Electricity Rules and
hazardous area, shall have a pole to break code of practice for earthing IS 3043.
the neutral in addition to the poles for
phases. - As far as possible, all earth
connections shall be visible for inspection.
When the means of isolation is located in a
non-hazardous area, the switch shall break iv) All connections shall be carefully made and
all poles including neutral or alternatively adequately locked against loosening.
Normally earthing system shall comprise of
GI strip as main earth grid alongwith - For lightning protection, the value of
suitably located GI disconnecting plates to 5 ohms as earth resistance shall be
provide multiple earth connections between desirable, but in no case it shall be
earth grid and equipment and for more than 10 ohms.
connections between main earth grid and
electrodes. Alternatively, mild steel strip can xi) The main earthing network shall be used for
also be used for earth grid after providing earthing of equipment to protect against
corrosion allowance. static electricity.

v) Connections between GI earth electrode For further details on earthing installation


and the disconnecting plates shall be done practices refer OISD standard 147.
by GI strip. For highly corrosive areas, PVC
insulated A1 cond. cable (unarmoured) may TABLE - III
be used. Connections between the -----------------------------------------------------------
disconnecting plate and various equipment Type of Equipment Bare G.I. Strip/G.I.
shall be done by GI strip, GI wire or GI wire Bare Rope or
rope, size as recommended in Table III. G.I. Wire
-----------------------------------------------------------
vi) In corrosive areas, aluminium disconnecting Motors upto 3.7 KW No. 8 SWG solid
plates alongwith suitably sized PVC wire
insulated aluminium conductor cables, may
be used for earthing grid/connections. Motors 5.5 KW to 10 mm (3/8") Wire 30
KW & welding
vii) All utility, process pipelines and flanges receptacles
shall be earthed on entering or leaving the
hazardous areas, except where conflicting Motors 37 KW and 16 mm (5/8") above
with the requirements of cathodic including HT Wire Rope
protection. In addition, steel pipe racks in Motors
the process units and offsite area shall be
earthed at every 25 meters. Building Columns 40 X 5 Strip

viii) Equipment located remote from main Storage Tank (Vertical 40 X 5 Strip
earth network may be earthed by means of & Horizontal)
individual earth conductors and earth
electrodes. Loading Racks 40 X 5 Strip

ix) Lighting protection shall be provided for the Pipe racks, Vessels 10 mm (3/8") &
equipment, structures and buildings which Heat Exchanvers Wire Rope
are higher than 20 metres or as per the risk
index analysis worked out as per IS 2309. Small Equipment & No. 8 SWG Solid
Self-conducting structures do not require Instruments
lightning protection with aerial rod and down
conductors. They shall be connected to the Lighting, Power & 10 mm (3/8")
earthing system at two points of the base. Instrument Panels Wire Rope
An independent earthing network shall be
provided for lighting protection and this shall Main Earth Bus/LT & As
be bonded with the main earthing network HT SW. Gear Intercon- Calculated
below ground, minimum at two points. nections/Power Trans-
former
x) The resistance value of an earthing system
to the general mass of earth shall be as EHV & HV Sub-Stations As Calculated
follows :
Push Button Stations No. 8 SWG Solid
- For the electrical system and equipment, a Wire
value that ensures the operation of
the protective device in the electrical Street Light Poles 10 mm (3/8")
circuit but not in excess of 5 ohms. Wire Rope
However, for generating stations and
large sub-stations this value shall Lighting Transformer 16 mm (5/8")
not be more than 1 ohm. Wire Rope
----------------------------------------------------------- unmistakable way and indicate the
Note : Lighting fixtures shall be earthed location of fire and initiate operation of
through the extra core provided in the ancillary service such as fire extinguishing
lighting cable. system, etc;

xii) Earth rods and conductors shall be d) remain insensitive to phenomena other
designed to cope with the conditions than those which its function is to detect;
imposed. The earth conductor shall be and
adequately sized to carry the applicable
maximum earth fault current without e) signal immediately and clearly any
undue temperature rise. All joints shall supervised fault that might jeopardies the
be protected against corrosion. correct performance of the system. The
system shall also include a FIRE SIREN
xiii) All the electrical equipment operating of distinguished tone having a range of
above 250 volts shall have two separate about 8 kms. Audio/visual fire alarm may
and distinct connections to earth grid. be required at the following locations in a
large plant:
11.0 Plant Safety and Security systems
- Control room
This shall include the following systems: - Fire station
- First aid centre
11.1 Plant Fire Detection and Alarm System - Security office
- Fire water pump house
i) The purpose of a fire detection and alarm
system is to detect fire at the earliest and iv) Detailed design, selection and installation
to give an alarm so that appropriate of fire detection and alarm system shall
action can be taken (e.g. evacuation of be as per IS-2189.
personnel summoning the fire fighting
organisation, triggering of extinguishing 11.2 Communication system
process etc.). An alarm system may be
activated by automatic detection devices The plant communication system shall
viz. smoke detectors, heat detectors etc. include some or all of the following
or by manual operation of manual call facilities as per individual plant
points i.e. break glass units. requirements:

ii) Manned locations prone to fire hazard - Telephone


shall have manual call points which on
operation shall give audio-visual - Public address system
indication at the control rooms and
actuate the sirens. If there are many - Emergency communication
manual call point, these may be system
conveniently grouped together to form
various zones and zone panels may be - Radio communication system
installed in convenient places other than
unit control rooms. Operation of each - Telex system.
zone panel may be indicated by audio-
visual indication in the main control panel Certain requirements for each facility are
in the unit control room as well as in the given below as general recommendation.
other zone panels with distinct colour
indicating the zone number. 11.2.1 Telephone System

iii) A fire detection and alarm system shall: i) A private automatic branch exchange
(PABX) system shall be provided. Trunk
a) operate quickly enough to fulfil its lines connecting with the external telephone
intended functions; network shall be provided and number of
trunk lines shall be decided based on plant
b) reliably transmit the detection signal; size and requirement.

c) Translate this signal into a clear alarm ii) Selective telephone service control shall be
indication that will attract the attention of arranged for all the extensions of the PABX
the user in an immediate and
to have one or more of the following service ambient level for effective recognition of
functions: speaker’s voice signals.

- All phones shall have direct inter- Also the field stations shall be capable of
communication between all the extensions operating in areas of high noise levels
of this exchange and all the extensions without any interference.
shall be able to accept any external calls
handled by the exchange operators. 11.2.3 Emergency Communication System

- Non executive phones shall operate with i) The ‘Hot line system’ shall be designed to
operator assistance for connection to provide a dependable communication link
external lines for both local and long between predesignated points of operation.
distance telephone service. This system shall be completely isolated
from the telephone system.
- Executive phone service shall include direct
unassisted (operator bypass) ii) The emergency communication system
communication to external lines for both shall include a ‘Direct phone to phone hot
local and long distance telephone service. line (H.L.) system’ and a ‘Dedicated hot line
(D.H.L.) system’.
iii) In areas with high ambient noise levels,
intensified bell signals may be provided to iii) H. L. System
produce an effective recognition noise level
of 6db above anticipated ambient noise By removing phone from cradle switch, the
levels. corresponding phone at opposite end will
ring till answered or until the phone is
11.2.2 Public Address System returned back to cradle disengaging the
circuit switch.
i) A public address system shall be provided
for communication within the plant area and iv) D.H.L. System
it shall comprise master stations, central
cabinet/exchange equipment (field station A simplified selective dial scheme shall be
modules, amplifiers etc.), field stations, provided to give selective contact between
paging loudspeakers etc. The public all the extensions of this system. All the
address system shall provide, as a telephones used for the emergency
minimum, the following facilities: communication system shall be red in
colour and shall have ringing indication
a) Paging within the plant area over lights.
loudspeaker from the master station
located in process control room. 11.2.4. Radio Communication System

b) Call back from any of the field stations to Portable Walkie - Talkie system.
the master control station.
i) A walkie-talkie system shall be provided for
c) Communication or call from Master Control radio communication within the plant area.
Station to any of the field stations and The system shall operate in the simplex
communication between field stations at the mode on U.H.F. and the exact frequency
discretion of Master Station. shall be decided in consultation with P & T
authorities.
d) Communication between pre-designated
field stations as per process operating ii) The system shall consist of base station,
requirements without interference of the monitoring receivers, portable stations,
operator manning the master station. antennas and associated accessories.
Adequate number of hand stations shall be
e) Operating an alarm call from master control provided.
station over all the loud speakers during an
emergency. iii) The system shall enable communication
between portable station and the base
ii) Paging speakers provided in areas having station or between any of the two portable
high ambient noise levels shall produce a 6 stations. The system shall have a range of
dB paging noise level above anticipated approximately 6 km.
iv) The system shall provide excellent installed diesel engines in Zone-2 area
penetration in all operating areas of the should be avoided wherever possible.
plant with no marginal locations and extend
beyond the boundaries of the plant. The ii) In the event of use of a permanently
system shall operate above the man-made installed diesel engine, being necessary in
noise spectrum to provide clear noise free Zone-2 it is recommended that it should
communication in all areas of high electrical have the following minimum protection to
noise. ensure safety :

11.2.4.1 VHF System a) The starter shall be either of a flameproof


electrical type (usually operated from the
Radio communication (VHF band) may be mains supply or battery) or of the
provided for communication between the following non-electric types :
plant and pre-designated points outside the
plant. The system shall include necessary i) Pneumatic
transmitter/receivers and associated ii) Hydraulic
antenna. The frequency of operation shall iii) Spring recoil
be decided in consultation with statutory iv) Inertia, or
authorities (P&T). v) Hand start

11.2.5 Telex System b) Any other electrical equipment associated


with the engine shall be flameproof.
One telex machine shall be installed in the Electrical equipment shall be effectively
administration building of the plant. earthed and bonded.

c) Cooling fan blades shall be made from non-


metallic materials which do not accumulate
12.0 MOBILE EQUIPMENT FOR electro-static charge.
HAZARDOUS AREAS
d) All belts shall be of anti-static, fire-resistant
12.1 PORTABLE HAND LAMPS type.

i) Hand lamps for use in hazardous area shall e) In order to contain discharge of sparks or
be flameproof with an operating voltage of flames from the exhaust system, a gas
24 V. The hand lamp shall be connected to conditioner box and a flame trap shall be
the source of supply by a flexible 3x1.5 sq. installed. Alternatively, the exhaust should
mm copper conductor PVC insulated metal be designed to discharge to a location
braided cable. within a safe area.

This cable should be protected by f) To prevent flashback through induction


PVC/tough rubber sheath or similar system, wherever possible, air intakes for
covering. The metallic body or any other engines shall be located in safe area.
exposed metal part of the hand lamp shall Alternatively a flame trap should be
be connected to earthing system. installed.

ii) The source of supply shall be located as g) The surface temperature of the engine and
near as possible to the points to be exhaust system shall not exceed 250°C
illuminated. Automatic protection employing when tested under full load conditions. In
earth leakage detection scheme (e.g. using some situations cooling of the exhaust
ELCB with current sensitivity of 30 mA) manifold and piping may be necessary,
shall be provided to disconnect supply on using water jacketing or finned coolers
occurrence of an earth fault. Hand lamps and/or high temperature cut/outs or alarms
with self contained batteries shall have type should be provided.
of protection appropriate to the applicable
hazardous zone. h) However when either the free movement of
air is restricted by thermal or acoustic
12.2 DIESEL ENGINES shielding or the ignition temperature of the
surrounding flammable atmosphere is
i) The use of permanently installed diesel below 200°C, no engine exposed surface
engines in Zone-0 and zone-1 areas is temperature shall exceed the minimum
unacceptable and the use of permanently ignition temperature of the gases involved.
i) To prevent overspeeding of the engine due 12.3 STORAGE BATTERIES
to induction of flammable gases or vapours,
means shall be provided to stop the engine. i) Storage batteries shall not be installed in
It can be either : Zone 1 locations, except those used in
portable lamps where the enclosure
i) a valve to close the air intake, or housing bulb, switch and battery shall be
ii) a system to inject carbon dioxide into flameproof type.
the air intake.
ii) As far as practicable use of storage
j) Alarms of automatic shutdown devices shall batteries in Zone 2 areas shall be avoided.
be provided, actioned by excessive water However where unavoidable, storage
temperature and low lube oil pressure. batteries for use in Zone 2 areas shall be
“Increased Safety” type. These shall meet
k) A system using an alarm or trip device to the following requirements :
protect the engine from excessive vibration
should be considered. a) Celluloid and similar combustibles shall not
be used as constructional materials.
l) An engine having a crank case volume of
over 0.5 m3 shall be provided with relief b) Battery containers as well as fittings and
devices. Relief valves or breathers on insulating parts outside the enclosed cells
engines shall be fitted with flame traps or shall not consist of porous materials e.g.
discharge into the induction system wood or other flammable materials and
downstream of the flame trap, if fitted and shall be resistant to flame and the action of
upstream of the shut-off valve, if fitted. electrolytes.
Dipsticks and/or filler caps should be
screwed or effectively secured by other c) Openings of cells necessary for the escape
means. of the gases given off shall be so
constructed as to prevent splashing of the
m) Intake and exhaust system design shall electrolyte.
meet the following minimum requirements:
d) The exterior of the cells shall be so
i) The length of the flame path through or constructed as to resist impact, and the cell
across any joint shall be not less than 13 cases shall be firmly fixed.
mm.
e) The cells shall be so built into the
ii) Suitable metal-clad or other acceptable containers that connection of the cells
jointing material shall be interposed getting loose in operation is improbable and
between all joint faces to ensure that normally, the discharge voltage exceeding
leakage does not occur. 24 volts should not appear between
adjacent rows of cells.
iii) Where valve spindles pass through the
walls of any component of the induction f) The creepage distance between two poles
system, the diametrical clearance shall not of adjacent cells shall not be less than 35
exceed 0.13 mm, unless end caps are mm. Where the discharge voltage exceeds
fitted. 24 volts, the creepage distance shall be
correspondingly increased by 1mm per 2
iv) No screw, stud or bolt-hole shall pass volts.
through the wall of any component of the
system. g) Where voltage of batteries is not less than
50 volts, either the battery case shall be
n) Decompression systems should not subdivided by partitions or the batteries
normally be provided. However, if they are shall be grouped into containers such that
essential, then the decompression parts in no grouping does a voltage exceeding 50
should be provided with flame traps and volts occur. In these cases, the partitions or
ducted away to safe area. the containers shall have heights of at least
half that of the battery case.
o) The fuel injection pump and governor
where fitted should be so designed that h) The battery case shall be so constructed as
reverse running of the engine is not to ensure sufficient ventilation in order to
possible. prevent accumulation of gases given off
from the battery, and the free space within f) All electrical circuits shall be cut off
the case shall be as small as possible. automatically in the event of :

i) The metallic cover of the battery case shall i) The current in any circuit exceeding
be lined with materials resistant to more than the rated value in any circuit.
electrolyte.
ii) A leakage current to earth/earth fault.
j) The cover of the battery case shall have
special fastenings. 12.6 VEHICLES
k) Exposed live parts of battery contained in a Commercial vehicles such as jeeps, trucks,
case shall be protected with rubber or cars etc. shall not be allowed inside
equivalent insulated materials. However, hazardous area unless these are
the openings for checking voltage may be specifically certified by competent authority
provided. for use hazardous areas.

Note : Charging of storage batteries shall be 13.0 REFERENCES


conducted in non-hazardous locations,
while the cover of the battery The following codes, standards and
enclosure is kept open. publications have either been referred to or
used in the preparation of this document
12.4 TESTING EQUIPMENT and the same shall be read in conjunction
with this document :
a) All testing equipment such as meggers,
continuity tester etc. shall be intrinsically i) National Electrical Code of Bureau of Indian
safe. Standards. (SP-30 : 1984)

b) Terminal connections shall be made by ii) OISD Standards / Recommended Practices


crimp type lugs. such as :

c) Terminals shall be provided with rubber a) OISD - 147 “Inspection, and safe
covers. practices during Electrical Installation”.

d) Enclosure and other constructional features b) OISD - 116 - Fire Protection facilities
shall be suitable as per the area for petroleum refineries and oil/gas
requirement. processing plants.

12.5 MISCELLANEOUS c) OISD - 117 - Fire Protection facilities


REQUIREMENTS for petroleum depots and terminals.

a) The electrical equipment and the system as d) OISD - 118 Layout for Oil and Gas
a part of mobile equipment shall be of Installations
intrinsically safe/flame proof design, if
required to be taken in classified hazardous e) OISD - 113 ‘Electrical Area
areas. Classification’.

b) The mobile apparatus shall be used for f) OISD - 137 “Inspection of Electrical
temporary purpose only under competent Equipment”
supervision.
iii) Indian Electricity Act & Rules 1956 (Ministry
c) No uninsulated current carrying part shall of Irrigation & Power, Govt. of India)
be exposed.
iv) The Petroleum Rules 1976 (Ministry of
d) All components shall be accessible for Industry, Government of India)
maintenance/repairs.
v) Oil Mines Regulations
e) All remote control or interlock circuits
associated with restrained plug and socket vi) C.B.I.P. (Central Board of Irrigation &
coupling should be intrinsically safe. Power) Technical Report No. 3 ‘Manual on
Layout of Substations’.
<< Back Home Next >>

You might also like