Deep Sea Electronics: DSE60xx Series PC Configuration Suite
Deep Sea Electronics: DSE60xx Series PC Configuration Suite
E-mail : sales@Deepseaplc.com
Website : www.deepseaplc.com
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.
Amendments List
Issue Comments
1 Initial release
1.1 Correction to the power save mode enable description
2 Added information on fast loading and changes to flexible sender alarms.
3 Power features added to Scada. (Watts,VA,VAr,Power Factor and Accumulated Power.)
Typeface : The typeface used in this document is Arial. Care should be taken not to mistake the upper case
letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.
2
DSE6000 Series configuration suite
TABLE OF CONTENTS
1 BIBLIOGRAPHY .......................................................................................... 4
1.1 INSTALLATION INSTRUCTIONS ...................................................................................................... 4
1.2 MANUALS........................................................................................................................................... 4
1.3 OTHER ................................................................................................................................................ 4
2 DESCRIPTION ............................................................................................. 4
2.1 SOFTWARE INSTALLATION INSTRUCTIONS................................................................................. 5
2.1.1 TROUBLESHOOTING SOFTWARE INSTALLATION ................................................................ 8
3 HARDWARE INSTALLATION ...................................................................... 9
3.1 TROUBLESHOOTING HARDWARE INSTALLATION ...................................................................... 9
4 USING THE CONFIGURATION SUITE ....................................................... 10
5 MENUS AND TOOLBAR ............................................................................ 11
5.1 FILE MENU ....................................................................................................................................... 11
5.2 TOOLS MENU................................................................................................................................... 12
5.2.1 OPTIONS .................................................................................................................................. 12
5.2.2 ACCESS PERMISSIONS .......................................................................................................... 12
5.2.3 UPDATE FIRMWARE ............................................................................................................... 14
5.3 HELP MENU ..................................................................................................................................... 16
5.4 TOOLBAR ......................................................................................................................................... 16
6 EDIT CONFIG............................................................................................. 17
6.1 SCREEN LAYOUT............................................................................................................................ 17
6.2 MODULE ........................................................................................................................................... 18
6.2.1 MODULE ................................................................................................................................... 19
6.3 APPLICATION .................................................................................................................................. 20
6.3.1 CAN OPTION MODULE ............................................................................................................ 20
6.3.2 MAGNETIC PICKUP OPTION MODULE .................................................................................. 20
6.4 INPUTS ............................................................................................................................................. 21
6.4.1 ANALOGUE INPUTS ................................................................................................................ 21
6.4.2 INPUT A - OIL PRESSURE SENSOR ...................................................................................... 22
6.4.3 INPUT B - ENGINE TEMPERATURE SENSOR ....................................................................... 23
6.4.4 INPUT C - FLEXIBLE SENSOR ................................................................................................ 24
6.4.5 EDITING THE SENSOR CURVE .............................................................................................. 25
6.4.7 DIGITAL INPUTS ...................................................................................................................... 26
6.4.8 INPUT FUNCTIONS .................................................................................................................. 27
6.5 OUTPUTS ......................................................................................................................................... 29
6.5.1 DIGITAL OUTPUTS .................................................................................................................. 29
6.5.2 OUTPUT SOURCES ................................................................................................................. 30
6.6 TIMERS ............................................................................................................................................. 32
6.6.1 START TIMERS ........................................................................................................................ 32
6.6.2 LOAD / STOPPING TIMERS..................................................................................................... 33
6.6.3 MODULE TIMERS..................................................................................................................... 33
6.7 GENERATOR.................................................................................................................................... 34
6.7.1 GENERATOR OPTIONS........................................................................................................... 34
6.7.2 GENERATOR VOLTAGE ALARMS .......................................................................................... 35
6.7.3 GENERATOR FREQUENCY ALARMS .................................................................................... 36
6.7.4 GENERATOR CURRENT ......................................................................................................... 36
6.8 MAINS ............................................................................................................................................... 37
6.8.1 MAINS OPTIONS ...................................................................................................................... 37
6.8.2 MAINS ALARMS ....................................................................................................................... 38
6.9 ENGINE ............................................................................................................................................. 39
6.9.1 ENGINE OPTIONS.................................................................................................................... 39
6.9.2 CRANK DISCONNECT ............................................................................................................. 41
6.9.3 SPEED ALARMS....................................................................................................................... 42
6.9.4 PLANT BATTERY ..................................................................................................................... 43
6.10 SCHEDULER .................................................................................................................................... 44
6.11 ALTERNATIVE CONFIGURATIONS................................................................................................ 45
6.11.1 ALTERNATIVE CONFIGURATION OPTIONS.......................................................................... 45
6.11.2 ALTERNATIVE CONFIGURATIONS EDITOR .......................................................................... 46
7 SCADA....................................................................................................... 47
7.2 MIMIC ................................................................................................................................................ 48
7.3 DIGITAL INPUTS .............................................................................................................................. 49
7.4 DIGITAL OUTPUTS .......................................................................................................................... 50
7.5 MAINS ............................................................................................................................................... 51
7.6 GENERATOR.................................................................................................................................... 51
3
DSE60xx Series configuration suite
1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which can be obtained from the
DSE website www.deepseaplc.com:
1.2 MANUALS
1.3 OTHER
The following third party documents are also referred to:
ISBN DESCRIPTION
1-55937-879-4 IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device Function Numbers
and Contact Designations. Published by Institute of Electrical and Electronics Engineers
Inc
2 DESCRIPTION
The DSE6000 Series configuration suite allows the 6000 family of modules to be connected to a PC via
USB ‘A –USB B’ cable. Once connected the various operating parameters within the module can be viewed or
edited as required by the engineer. This software allows easy controlled access to these values.
The configuration suite should only be used by competent, qualified personnel, as changes to the operation of
the module may have safety implications on the panel / generating set to which it is fitted. Access to critical
operational sequences and settings for use by qualified engineers, may be barred by a security code set by
the generator provider.
The information contained in this manual should be read in conjunction with the information contained in the
appropriate module documentation. This manual only details which settings are available and how they may
be used.
A separate manual deals with the operation of the individual module (See section entitled Bibliography
elsewhere in this document).
4
DSE6000 Series configuration suite
Operating System Windows Vista, Windows XP or Windows 2000 with Microsoft™ .Net® 2.0 framework
Monitor 17 inch recommended (1024 x 768 resolution)
Communications USB required o configure the module.
NOTE: - As 6000 Series configuration software for Windows™ is a 32-Bit application requiring
Microsoft .net 2 framework, it will not operate on Windows 2.0, 3.0, 3.1,3.11, 95, 98 or Me.
NOTE: - Exit all other programs before installing the software. It is recommended that any earlier
releases of the software be uninstalled prior to installing this version.
NOTE: - Please register online at www.deepseaplc.com – Once registered you will be able to
download updates to the software to ensure that you always have access to the latest features.
Insert the Software CD into the CD-ROM drive on the PC. The CD will then Auto-run if this feature is enabled
on your PC.
Alternatively:
5
DSE60xx Series configuration suite
Select Disk Cost to view remaining disk space, Click Next to continue.
6
DSE6000 Series configuration suite
7
DSE60xx Series configuration suite
2.1.1.1 WINDOWS 7
• A Windows 7 compatible version of Configuration Suite will be available soon. In the meantime, use
the Windows 7 ‘Troubleshoot Compatibility’ wizard to configure the software for operation on
Windows 7. This operation cannot be guaranteed!
2.1.1.4 WINDOWS XP
• Ensure the operating system is logged onto using an Administrator Account. Failure to do this results
in installation failure due to incorrect user permissions disallowing registration of some parts of the
Configuration Suite Software.
• Ensure the operating system is fully up to date using the Microsoft Windows Update facility.
• Ensure that Windows Installer is fully up to date using the Microsoft Windows Update facility.
• Ensure the operating system has Microsoft .net 2 Framework redistributable (for x86) installed and is
fully up to date. This is available from Microsoft’s website.
8
DSE6000 Series configuration suite
3 HARDWARE INSTALLATION
Ensure the Configuration Suite Software is installed on the PC as described above.
The installation of the PC software also installs the DSE Controller USB Driver automatically.
Connect the USB cable to the module and to the PC as shown below.
You are now ready to configure or monitor the module using the Configuration Suite Software.
Occasionally USB devices are disabled by the Windows operating system, the following procedure will re-enable the
device in these instances.
• Disconnect the Deep Sea Electronics Controller from the USB port. Wait a moment, then reconnect and try
again. If you still encounter problems then :
• Power cycle the DSE controller If you still encounter problems then :
• Try another USB cable. If you don’t have one, it’s the same type of cable as usually used between a PC
and a USB printer. If you still encounter problems then :
• Disconnect the Deep Sea Electronics Controller. Shutdown, then restart the PC. Reconnect the interface,
and then try again. If you continue to experience problems then :
• Check the USB port with another device (for instance a mouse, printer or digital camera).
9
DSE60xx Series configuration suite
Then select ‘All Programs’ - ‘Deep Sea Electronics PLC’ – “DSE Configuration Suite” – “DSE Configuration
Suite”
After a short delay to load the application, the splash screen is shown, after which the screen will
display:-
This is the initial start-up screen and can be disabled by checking the box Hide this screen at start-up.
The screen prompts the user to select between the three main uses for the software:
• Creating a new configuration. Select the module type under Create new configuration. This allows
you to create a configuration for the ‘latest’ module version. Use File | Convert to... to convert the
configuration to suit an earlier module version or use Tools | Update firmware to update an ‘earlier’
module to the latest firmware version.
• Editing a configuration previously saved to disk or flash memory device. Select the configuration file
either from the Open recent configuration area or by clicking Open a configuration file and browsing
to the file.
• Reading and changing the configuration of a connected module. Click Read configuration from a
module. The file is read from a currently connected 6000 Series controller and is available for editing
in the Configuration Suite.
Alternatively you can ignore this screen and continue to use the program in the background. Once you make a
connection or load/create a configuration, the start-up screen will disappear.
10
DSE6000 Series configuration suite
11
DSE60xx Series configuration suite
12
DSE6000 Series configuration suite
13
DSE60xx Series configuration suite
14
DSE6000 Series configuration suite
Click OK to continue.
15
DSE60xx Series configuration suite
5.4 TOOLBAR
The toolbar contains the most used commands from the menus and is often a quicker way of accessing these
commands.
Create a new configuration file
Open an existing file from disk or flash memory device
Save the currently open file to the location it was loaded from previously. If this is
a new file, you are prompted to enter a filename.
Print the currently open configuration file
Preview what the configuration file will look like on the page after printing.
Send the currently open configuration settings to the controller
Read the settings out of the connected controller for viewing / editing
Shows the version number of the configuration suite
Voltages are shown as phase to phase voltages in the configuration editor
Voltages are shown as phase to neutral voltages in the configuration editor
Select the communication method. The choices present are dependent upon your
PC’s configuration.
USB To connect via USB directly to the controller, select USB :
16
DSE6000 Series configuration suite
6 EDIT CONFIG
This menu allows module configuration, to change the function of Inputs, Outputs and LED’s, system timers
and level settings to suit a particular application.
Move to the
The type of Previous or Next
configuration configuration page
file being edited
The coloured
shading shows
Close this
the currently
configuration file
selected page.
Click + or – to
show or hide
the sub settings
within each
sections.
Click to return
Step forward or to this page at
backward through any time
previously viewed
pages
Click to select
the subsection
to view / edit
17
DSE60xx Series configuration suite
6.2 MODULE
The module page is subdivided into smaller sections.
Select the required section with the mouse.
This section allows the user to change the options related to the module itself.
18
DSE6000 Series configuration suite
6.2.1 MODULE
Miscellaneous Options
Lamp Test At Power = Feature disabled
Up = The LEDs on the module’s fascia will all illuminate when the DC power is
applied as a ‘lamp test’ feature.
Power Save Mode =Normal operation
Enable = Module goes into power save (low current) mode after 1m of inactivity in STOP
mode. Press any button to ‘wake’ the module.
Power Up in Auto =The module enters STOP mode when DC power is applied.
= The module enters AUTO mode when DC power is applied.
Display SPN Strings =The module displays CAN messages in manufacturer numerical code.
(CAN only) = The module displays CAN messages in ENGLISH text alongside the
manufacturer numerical code.
Event log in Hours Run = The engine run hours is added to the recorded event in the event log
Enable Fast Loading = Normal Operation, the safety on timer will be observed in full. This feature is
useful if the module is to be used with some small engines where pre-mature
termination of the delay timer can lead to overspeed alarms on start up.
= The module will terminate the safety on timer once all monitored parameters
have reached their normal settings. This feature is useful if the module is to be used
as a standby controller as it allows the generator to start and go on load in the
shortest possible time.
19
DSE60xx Series configuration suite
6.3 APPLICATION
NOTE: - CAN options only available with the CAN version of the 6000 controller.
NOTE: - Magnetic Pickup options only available with the MPU version of the 6000 controller.
20
DSE6000 Series configuration suite
6.4 INPUTS
The inputs page is subdivided into smaller sections, depending upon the variant in use.
Select the required section with the mouse.
21
DSE60xx Series configuration suite
MPU Version module - Analogue input A is selectable as either digital input, or as analogue oil pressure
sensor.
Enable or disable
the alarms. The
relevant values
below will appear
greyed out if the
alarm is disabled.
22
DSE6000 Series configuration suite
MPU Version module - Analogue input B is selectable as either digital input, or as analogue engine
temperature sensor.
23
DSE60xx Series configuration suite
24
DSE6000 Series configuration suite
25
DSE60xx Series configuration suite
Configures when
the input is active:
Never, always, Example of a user configured
active from input
starting, active
from the end of the
safety timer Close or open to activate
26
DSE6000 Series configuration suite
Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor
devices and software programs. Where the DSE input functions can be represented by IEEE 37.2, the
function number is listed below.
27
DSE60xx Series configuration suite
Function Description
Generator Load Inhibit This input is used to prevent the 6000 from loading the generator. If the
IEEE 37.2 - 52 AC circuit breaker generator is already on load, activating this input will cause the 6000 to
unload the generator. Removing the input will allow the generator to be
loaded again.
28
DSE6000 Series configuration suite
6.5 OUTPUTS
6.5.1 DIGITAL OUTPUTS
These labels
match the
typical wiring
diagram
29
DSE60xx Series configuration suite
Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor
devices and software programs. Where the DSE output functions can be represented by IEEE 37.2, the
function number is listed below.
Battery Low Voltage This output indicates that a Battery Under Inactive when battery voltage is not Low
IEEE 37.2 – 27DC undervoltage relay Voltage alarm has occurred.
CAN Data Fail Becomes active when no CAN data is Inactive when:
received from the ECU after the safety • CAN data is being received
delay timer has expired • The set is at rest
• During the starting sequence before
the safety delay timer has expired
CAN ECU WARNING Becomes active when a ‘Yellow lamp’ – Warning alarm is signalled by the CAN ECU
CAN ECU SHUTDOWN Becomes active when a ‘Red lamp’ – Shutdown alarm is signalled by the CAN ECU
CAN ECU Power Used to switch an external relay to power the CAN ECU. Exact timing of this output is
dependent upon the type of the engine ECU
CAN ECU Stop Active when the DSE controller is requesting that the CAN ECU stops the engine.
Charge alternator Active when the charge alternator alarm is active
warning/shutdown
Close Gen Output Used to control the load switching device. Inactive whenever the generator is not
IEEE 37.2 – 52 ac circuit breaker Whenever the 6000 module selects the required to be on load
generator to be on load this control source
will be active.
Close Gen Output Pulse Used to control the load switching device. Whenever the 6000 module selects the
IEEE 37.2 – 52 ac circuit breaker generator to be on load this control source will be active for the duration of the Breaker
Close Pulse timer, after which it will become inactive again.
Close Mains Output Used to control the load switching device. The output is inactive whenever
IEEE 37.2 – 52 ac circuit breaker Whenever the 6000 module selects the mains to the mains is not required to be on
be on load this control source will be active. load
Close Mains Output Pulse Used to control the load switching device. Whenever the 6000 module selects the mains
IEEE 37.2 – 52 ac circuit breaker to be on load this control source will be active for the duration of the Breaker Close
Pulse timer, after which it will become inactive again.
Combined Mains Failure Active when the mains supply is out of limits OR the input for Auxiliary Mains Failure is
active
Common Alarm Active when one or more alarms (of any type) are The output is inactive when no
active alarms are present
Common Electrical Trip Active when one or more Electrical Trip alarms The output is inactive when no
are active shutdown alarms are present
Common Shutdown Active when one or more Shutdo wn alarms are The output is inactive when no
active shutdown alarms are present
Common Warning Active when one or more Warning alarms are The output is inactive when no
active warning alarms are present
30
DSE6000 Series configuration suite
Preheat during preheat timer Becomes active when the preheat timer Inactive when :
begins. • The set is stopped
Normally used to control the engine • The preheat timer has expired
preheat glow-plugs.
Preheat until end of crank Becomes active when the preheat timer Inactive when :
begins. • The set is stopped
Normally used to control the engine • The set has reached crank
preheat glow-plugs. disconnect conditions
Preheat until end of safety timer Becomes active when the preheat timer Inactive when :
begins. • The set is stopped
Normally used to control the engine • The set has reached the end of the
preheat glow-plugs. safety delay timer
Preheat until end of warming timer Becomes active when the preheat timer Inactive when :
begins. • The set is stopped
Normally used to control the engine • The set has reached the end of the
preheat glow-plugs. warming timer
Smoke Limiting Becomes active when the controller Becomes inactive when the controller
requests that the engine runs at idle requests that the engine runs at rated
speed. speed.
As an output, this can be used to give a
signal to the Idle input of an engine speed
governor (if available)
Start Relay Active when the controller requires the cranking of the engine.
IEEE 37.2 – 54 turning gear engaging
device
Waiting for Manual Restore Becomes active when the generator is on load and the mains supply is healthy but an
input configured to Manual Restore is active.
This can be used to signal to an operator that action is required before the set can
transfer back to the mains supply.
31
DSE60xx Series configuration suite
6.6 TIMERS
Many timers are associated with alarms. Where this occurs, the timer for the alarm is located on the same
page as the alarm setting. Timers not associated with an alarm are located on the timers page.
The timers page is subdivided into smaller sections. Select the required section with the mouse.
32
DSE6000 Series configuration suite
Breaker close pulse The amount of time that Breaker Close Pulse signals will be present when the request to
close a breaker is given.
Breaker Trip pulse The amount of time that Breaker Open Pulse signals will be present when the request to open
a breaker is given.
Return delay A delay, used in auto mode only, that allows for short term removal of the request to stop the
set before action is taken. This is usually used to ensure the set remains on load before
accepting that the start request has been removed.
Cooling time The amount of time that the set will be made to run OFF LOAD before being stopped. This is
to allow the set to cool down and is particularly important for engines with turbo chargers.
ETS Solenoid hold The amount of time the Energise to stop solenoid will be kept energised after the engine has
come to rest. This is used to ensure the set has fully stopped before removal of the stop
solenoid control signal.
Fail to stop delay If the set is called to stop and is still running after the fail to stop delay, a Fail to Stop alarm is
generated.
Generator transient Used to delay the generator under/over volts/frequency alarms. Typically this is used to
delay prevent spurious shutdown alarms caused by large changes in load levels.
Timer Description
Power Save Mode If the module is left unattended in STOP mode for the duration of the Power Save Mode Delay
Delay (fixed timer) it will enter low power consumption mode (Power Save Mode).
33
DSE60xx Series configuration suite
6.7 GENERATOR
The generator page is subdivided into smaller sections.
Select the required section with the mouse.
Click to enable or
disable alternator
functions.
Parameter Description
Alternator fitted = There is no alternator in the system, it is an engine only application
= An alternator is fitted to the engine, it is a generator application.
AC System Allows a number of AC systems to be catered for.
Selecting the AC system shows the connections required for that particular system,
along with the relevant connection numbers on the controller.
34
DSE6000 Series configuration suite
Click to enable or
disable the alarms.
6.7.2 GENERATOR VOLTAGE ALARMS The relevant values
below will appear
greyed out if the
alarm is disabled.
35
DSE60xx Series configuration suite
Click to enable or
6.7.3 GENERATOR FREQUENCY ALARMS disable the alarms.
The relevant values
below will appear
greyed out if the
alarm is disabled.
Overfrequency Shutdo wn
can only be disabled if
another method of speed
protection is available (ie
CAN or Magnetic Pickup).
Hence the checkbox is
greyed out
36
DSE6000 Series configuration suite
6.8 MAINS
Timer Description
Mains failure = The module will ignore the status of the mains supply.
detection = The module will monitor the mains supply and use this status for automatically starting
and stopping the set in auto mode.
Immediate = Upon mains failure, the mains load switch will be kept closed until the generator is up
Mains Dropout to speed and volts.
= Upon mains failure, the mains load switch will be opened immediately, subject to the
setting of the mains transient timer.
AC System These settings are used to detail the type of AC system to which the module is connected:
3 phase 4 wire, 1 phase 2 wire, 2 phase 3 wire – L1-L2, 2 phase 3 wire – L1-L3, 3 phase 3
wire, 3 phase 4 wire delta
This list is not exhaustive. DSE reserve the right to add to this list as part of our policy of
continual development
37
DSE60xx Series configuration suite
Click to enable or
6.8.2 MAINS ALARMS disable the alarms.
The relevant values
below will appear
greyed out if the
alarm is disabled.
38
DSE6000 Series configuration suite
6.9 ENGINE
The engine page is subdivided into smaller sections.
Select the required section with the mouse.
Click to enable or
disable the option. The
relevant values below
will appear greyed out
if the alarm is disabled.
39
DSE60xx Series configuration suite
40
DSE6000 Series configuration suite
Having more than one crank disconnect source allows for a much faster crank disconnect response leading to
less wear on the engine and starter components, and provides added safety in case one source is lost, by a
blown or tripped fuse for example.
41
DSE60xx Series configuration suite
Click to enable or
disable the option.
The relevant values
below will appear
greyed out if the
alarm is disabled.
42
DSE6000 Series configuration suite
Start Delay Start delay timer for the Start on Low Battery function.
43
DSE60xx Series configuration suite
6.10 SCHEDULER
The scheduler is used to automatically start the set at on a configured day and time and run for the set
duration.
The generator is made to run on load or off load depending upon the configuration :
44
DSE6000 Series configuration suite
An Alternative Configuration is provided to allow the system designer to cater for different AC requirements
utilising the same generator system. Typically this feature is used by Rental Set Manufacturers where the set
is capable of being operated at (for instance) 120V 50Hz and 240V 50Hz using a selector switch, or by taking
advantage of the “auto voltage sensing” option of the DSE6000 Series.
Click to enable or
disable the option.
The relevant values
6.11.1 ALTERNATIVE CONFIGURATION OPTIONS below will appear
greyed out if the
alarm is disabled.
45
DSE60xx Series configuration suite
Alternative configuration options contain a subset of the main configuration. The adjustable parameters are
not discussed here as they are identical to the main configuration options :
46
DSE6000 Series configuration suite
7 SCADA
SCADA stands for Supervisory Control And Data Acquisition and is provided both as a service tool and also
as a means of monitoring / controlling the generator set.
As a service tool, the SCADA pages are to check the operation of the controller’s inputs and outputs as well
as checking the generators operating parameters.
The Module’s
firmware revision
number
47
DSE60xx Series configuration suite
7.2 MIMIC
This screen provides a mimic of the control module and allows the operator to change the control mode of the
module.
48
DSE6000 Series configuration suite
49
DSE60xx Series configuration suite
State of the
output
(open or closed)
50
DSE6000 Series configuration suite
7.5 MAINS
7.6 GENERATOR
51
DSE60xx Series configuration suite
7.6.2 POWER
Shows the modules measurements of the generator supply power.
52
DSE6000 Series configuration suite
7.7 ENGINE
Shows the modules measurements of the engine parameters.
7.9 ALARMS
Shows any present alarm conditions.
53
DSE60xx Series configuration suite
7.10 STATUS
Shows the module’s current status.
54
DSE6000 Series configuration suite
If the module is connected to a compatible electronic engine, the following information is read from the ECU (if
supported by the engine ECU).
55
DSE60xx Series configuration suite
7.13 MAINTENANCE
The Maintenance section is subdivided into smaller sections.
Select the required section with the mouse.
56