How to upload a pre configured CID/IID file to a MiCOM relay?


Issue
Cannot upload a pre configured CID/IID file to a MiCOM relay.

Product Line
MiCOM Relays

Environment
IEC61850 communications

Cause
MiCOM relays expects a MCL file for IEC61850 configuration settings. 

Resolution
Unfortunately, a CID/IID file cannot be uploaded directly to a MiCOM relay. The CID/IID file needs to be converted into an MCL file
before the configuration settings can be uploaded to the relay. 

This can be done by following the below steps:


1. Depending on the version of IEC61850 edition being used select the appropriate configurator from Tools.

https://www.schneider-electric.com/en/faqs/FA241248/ 1/4
2. Once the configurator is open, go to File--> Import
4/25/2019 How SCL
to upload a pre configured CID/IID file to a MiCOM relay?

3. Select the appropriate SCD/CID/IID file that needs to be converted. 

https://www.schneider-electric.com/en/faqs/FA241248/ 2/4
4/25/2019 How to upload a pre configured CID/IID file to a MiCOM relay?

4. Open the SCD/CID/IID and then go to File--> Save.

https://www.schneider-electric.com/en/faqs/FA241248/ 3/4
4/25/2019 How to upload a pre configured CID/IID file to a MiCOM relay?