Ac Voltage Controller Circuits: Unit-8
Ac Voltage Controller Circuits: Unit-8
com
Unit-8
AC VOLTAGE CONTROLLER CIRCUITS
AC voltage controllers (ac line voltage controllers) are employed to vary the RMS
value of the alternating voltage applied to a load circuit by introducing Thyristors between
the load and a constant voltage ac source. The RMS value of alternating voltage applied to a
load circuit is controlled by controlling the triggering angle of the Thyristors in the ac voltage
controller circuits.
In brief, an ac voltage controller is a type of thyristor power converter which is used
to convert a fixed voltage, fixed frequency ac input supply to obtain a variable voltage ac
output. The RMS value of the ac output voltage and the ac power flow to the load is
controlled by varying (adjusting) the trigger angle ‘α’
V0(RMS)
AC Vs AC Variable AC
Input Voltage RMSO/P Voltage
Voltage fs Controller
fs
fS
Page 215
www.getmyuni.com
There are two different types of thyristor control used in practice to control the ac power
flow
• On-Off control
• Phase control
In phase control the Thyristors are used as switches to connect the load circuit to the
input ac supply, for a part of every input cycle. That is the ac supply voltage is chopped using
Thyristors during a part of each input cycle.
The thyristor switch is turned on for a part of every half cycle, so that input supply
voltage appears across the load and then turned off during the remaining part of input half
cycle to disconnect the ac supply from the load.
By controlling the phase angle or the trigger angle ‘α’ (delay angle), the output RMS
voltage across the load can be controlled.
The trigger delay angle ‘α’ is defined as the phase angle (the value of ωt) at which the
thyristor turns on and the load current begins to flow.
Thyristor ac voltage controllers use ac line commutation or ac phase commutation.
Thyristors in ac voltage controllers are line commutated (phase commutated) since the input
supply is ac. When the input ac voltage reverses and becomes negative during the negative
half cycle the current flowing through the conducting thyristor decreases and falls to zero.
Thus the ON thyristor naturally turns off, when the device current falls to zero.
Phase control Thyristors which are relatively inexpensive, converter grade Thyristors
which are slower than fast switching inverter grade Thyristors are normally used.
For applications upto 400Hz, if Triacs are available to meet the voltage and current
ratings of a particular application, Triacs are more commonly used.
Due to ac line commutation or natural commutation, there is no need of extra
commutation circuitry or components and the circuits for ac voltage controllers are very
simple.
Due to the nature of the output waveforms, the analysis, derivations of expressions for
performance parameters are not simple, especially for the phase controlled ac voltage
controllers with RL load. But however most of the practical loads are of the RL type and
hence RL load should be considered in the analysis and design of ac voltage controller
circuits.
Page 216
www.getmyuni.com
The basic principle of on-off control technique is explained with reference to a single
phase full wave ac voltage controller circuit shown below. The thyristor switches T1 and T2
are turned on by applying appropriate gate trigger pulses to connect the input ac supply to the
load for ‘n’ number of input cycles during the time interval tON . The thyristor switches T1
and T2 are turned off by blocking the gate trigger pulses for ‘m’ number of input cycles
during the time interval tOFF . The ac controller ON time tON usually consists of an integral
number of input cycles.
Page 217
www.getmyuni.com
Vs n m
wt
Vo
io
wt
wt
ig2 Gate pulse of T2
wt
Example
Referring to the waveforms of ON-OFF control technique in the above diagram,
n = Two input cycles. Thyristors are turned ON during tON for two input cycles.
m = One input cycle. Thyristors are turned OFF during tOFF for one input cycle
Thyristors are turned ON precisely at the zero voltage crossings of the input supply.
The thyristor T1 is turned on at the beginning of each positive half cycle by applying the gate
trigger pulses to T1 as shown, during the ON time tON . The load current flows in the positive
direction, which is the downward direction as shown in the circuit diagram when T1 conducts.
Page 218
www.getmyuni.com
The thyristor T2 is turned on at the beginning of each negative half cycle, by applying gating
signal to the gate of T2 , during tON . The load current flows in the reverse direction, which is
the upward direction when T2 conducts. Thus we obtain a bi-directional load current flow
(alternating load current flow) in a ac voltage controller circuit, by triggering the thyristors
alternately.
This type of control is used in applications which have high mechanical inertia and
high thermal time constant (Industrial heating and speed control of ac motors). Due to zero
voltage and zero current switching of Thyristors, the harmonics generated by switching
actions are reduced.
For a sine wave input supply voltage,
vs = Vm sin ω t = 2VS sin ω t
V
VS = RMS value of input ac supply = m = RMS phase supply voltage.
2
If the input ac supply is connected to load for ‘n’ number of input cycles and
disconnected for ‘m’ number of input cycles, then
tON = n × T , tOFF = m × T
1
Where T = = input cycle time (time period) and
f
f = input supply frequency.
tON = controller on time = n × T .
tOFF = controller off time = m × T .
TO = Output time period = ( tON + tOFF ) = ( nT + mT ) .
(i) To derive an expression for the rms value of output voltage, for on-off control
method.
ωt
1 ON 2 2
V Sin ω t.d (ω t )
ωTO ωt∫=0 m
Output RMS voltage VO( RMS ) =
ω tON
Vm 2
VO( RMS ) = ∫ Sin 2ω t.d (ω t )
ωTO 0
1 − Cos 2θ
Substituting for Sin 2θ =
2
Page 219
www.getmyuni.com
ω tON
Vm 2 1 − Cos 2ω t
VO( RMS ) =
ωTO ∫ 2 d (ω t )
0
ωt ω tON
Vm 2 ON
VO( RMS ) = ∫ d (ω t ) − ∫ Cos 2ω t.d (ω t )
2ωTO 0 0
ω tON ω tON
Vm 2 Sin 2ω t
VO( RMS ) = ( ω t ) −
2ωTO 0
2 0
Where T is the input supply time period (T = input cycle time period). Thus we note that
sin 2ω tON = 0
Vm 2 ω tON Vm tON
VO( RMS ) = =
2 ω TO 2 TO
tON t
VO( RMS ) = Vi( RMS ) = VS ON
TO TO
Vm
Where Vi( RMS ) = = VS = RMS value of input supply voltage;
2
tON tON nT n
= = = = k = duty cycle (d).
TO tON + tOFF nT + mT ( n + m )
n
VO( RMS ) = VS =V k
(m + n) S
Page 220
www.getmyuni.com
Vm n
VO( RMS ) = =V k = VS k
2 ( m + n ) i( RMS )
• Duty Cycle
t tON nT
k = ON = =
TO ( tON + tOFF ) ( m + n ) T
n
Where, k = = duty cycle (d).
(m + n)
PO = I O2 ( RMS ) × RL
I O2 ( RMS ) × RL
PF = ; I S = I in( RMS ) = RMS input supply current.
Vi ( RMS ) × I in( RMS )
Hence, RMS supply current = RMS load current; I in( RMS ) = I O( RMS ) .
Page 221
www.getmyuni.com
n
PF = k =
m+n
0 π 2π 3π ωt
π
n
I m sin ω t.d (ω t )
2π ( m + n ) ∫0
IT ( Avg ) =
π
nI m
sin ω t.d (ω t )
2π ( m + n ) ∫0
IT ( Avg ) =
π
nI m
IT ( Avg ) = − cos ω t
2π ( m + n ) 0
nI m
IT ( Avg ) = [ − cos π + cos 0]
2π ( m + n )
nI m
IT ( Avg ) = − ( −1) + 1
2π ( m + n )
n
IT ( Avg ) = [ 2I m ]
2π ( m + n )
Imn k .I
IT ( Avg ) = = m
π (m + n) π
tON n
k = duty cycle = =
( tON + tOFF ) ( n + m )
Page 222
www.getmyuni.com
Imn k .I
IT ( Avg ) = = m,
π (m + n) π
Vm
Where I m = = maximum or peak thyristor current.
RL
1
nI m2 π
2
IT ( RMS ) = ∫ sin 2 ω t.d (ω t )
2π ( n + m ) 0
1
nI m2 π
(1 − cos 2ω t ) d ω t 2
IT ( RMS ) = ∫ ( )
2π ( n + m ) 0 2
1
nI m2 π π
2
1
nI m2 π
sin 2ω t
π
2
IT ( RMS ) = (ω t ) −
4π ( n + m ) 0 2
0
1
nI m2 sin 2π − sin 0
2
IT ( RMS ) = (π − 0 ) −
4π ( n + m ) 2
1
nI m2 2
IT ( RMS ) = {π − 0 − 0}
4π ( n + m )
1 1
nI m2π 2
nI m2 2
IT ( RMS ) = =
4π ( n + m ) 4 ( n + m)
Im n I
IT ( RMS ) = = m k
2 (m + n) 2
Im
IT ( RMS ) = k
2
Problem
Page 223
www.getmyuni.com
1. A single phase full wave ac voltage controller working on ON-OFF control technique
has supply voltage of 230V, RMS 50Hz, load = 50Ω. The controller is ON for 30
cycles and off for 40 cycles. Calculate
• ON & OFF time intervals.
• RMS output voltage.
• Input P.F.
• Average and RMS thyristor currents.
1 1
T= = = 0.02sec , T = 20ms .
f 50 Hz
n 30
Duty cycle k = = = 0.4285
( m + n ) ( 40 + 30 )
RMS output voltage
n
VO( RMS ) = Vi ( RMS ) ×
(m + n)
30 3
VO( RMS ) = 230V × = 230
( 30 + 40 ) 7
Page 224
www.getmyuni.com
n 30
PF = = = 0.4285
( m + n ) 70
PF = 0.654653
Vm 2 × 230 325.269
where Im = = =
RL 50 50
6.505382 3
IT ( Avg ) = ×
π 7
IT ( Avg ) = 0.88745 A
IT ( RMS ) = 2.129386 A
Page 225
www.getmyuni.com
positive half cycle of input supply. When T1 is triggered it conducts and the load current
flows through the thyristor T1 , the load and through the transformer secondary winding.
By assuming T1 as an ideal thyristor switch it can be considered as a closed switch
when it is ON during the period ω t = α to π radians. The output voltage across the load
follows the input supply voltage when the thyristor T1 is turned-on and when it conducts from
ω t = α to π radians. When the input supply voltage decreases to zero at ω t = π , for a
resistive load the load current also falls to zero at ω t = π and hence the thyristor T1 turns off
at ω t = π . Between the time period ω t = π to 2π , when the supply voltage reverses and
becomes negative the diode D1 becomes forward biased and hence turns ON and conducts.
The load current flows in the opposite direction during ω t = π to 2π radians when D1 is ON
and the output voltage follows the negative half cycle of input supply.
vs = Vm sin ω t
Vm
VS = Vin( RMS ) = = RMS value of secondary supply voltage.
2
Page 226
www.getmyuni.com
vo = vL = 0 ; for ω t = 0 to α
vo = vL = Vm sin ω t ; for ω t = α to 2π .
vo Vm sin ω t
io = iL = = ; for ω t = α to 2π .
RL RL
io = iL = 0 ; for ω t = 0 to α .
2π
1
VO( RMS ) = ∫ Vm sin ω t.d (ω t )
2 2
2π α
2π
Vm 2 1 − cos 2ω t
VO( RMS ) = ∫ .d (ω t )
2π α 2
2π
Vm 2
VO( RMS ) = ∫ (1 − cos 2ω t ) .d (ω t )
4π α
Vm 2π 2π
VO( RMS ) = ∫ ( ) ∫ cos 2ω t.dω t
d ω t −
2 π α α
2π 2π
Vm sin 2ω t
VO( RMS ) = (ω t ) −
2 π α 2 α
2π
sin 2ω t
( 2π − α ) −
Vm
VO( RMS ) =
2 π 2 α
sin 4π sin 2α
( 2π − α ) −
Vm
VO( RMS ) = − ;sin 4π = 0
2 π 2 2
Page 227
www.getmyuni.com
Vm sin 2α
VO( RMS ) = ( 2π − α ) +
2 π 2
Vm sin 2α
VO( RMS ) = ( 2π − α ) +
2 2π 2
Vm 1 sin 2α
VO( RMS ) = ( 2π − α ) +
2 2π 2
1 sin 2α
VO( RMS ) = Vi( RMS ) ( 2π − α ) +
2π 2
1 sin 2α
VO( RMS ) = VS ( 2π − α ) +
2π 2
Vm
Where, Vi( RMS ) = VS = = RMS value of input supply voltage (across the
2
transformer secondary winding).
Note: Output RMS voltage across the load is controlled by changing 'α ' as indicated by the
expression for VO ( RMS )
PLOT OF VO ( RMS ) VERSUS TRIGGER ANGLE α FOR A SINGLE PHASE HALF-WAVE
AC VOLTAGE CONTROLLER (UNIDIRECTIONAL CONTROLLER)
Vm 1 sin 2α
VO( RMS ) = ( 2π − α ) +
2 2π 2
1 sin 2α
VO( RMS ) = VS ( 2π − α ) +
2π 2
By using the expression for VO ( RMS ) we can obtain the control characteristics, which is
the plot of RMS output voltage VO ( RMS ) versus the trigger angle α . A typical control
characteristic of single phase half-wave phase controlled ac voltage controller is as shown
below
Page 228
www.getmyuni.com
300 π
6 ( 6)
; 1π 0.992765 VS
600 π ; ( 2π ) 0.949868 VS
3 6
900 π ; ( 3π ) 0.866025 VS
2 6
1200 2π ; ( 4π ) 0.77314 VS
3 6
1500 5π ; ( 5π ) 0.717228 VS
6 6
1800 π ; ( 6π ) 0.707106 VS
6
VO(RMS)
100% VS 70.7% VS
60% VS
20% VS
0 60 120 180
Trigger angle α in degrees
Fig 6.5: Control characteristics of single phase half-wave phase controlled ac voltage controller
Note: We can observe from the control characteristics and the table given above that the
range of RMS output voltage control is from 100% of VS to 70.7% of VS when we vary the
trigger angle α from zero to 180 degrees. Thus the half wave ac controller has the drawback
of limited range RMS output voltage control.
2π
V
VO( dc ) = m
2π ∫ sin ω t.d (ω t )
α
2π
V
VO( dc ) = m − cos ω t
2π α
Vm
VO( dc ) = [ − cos 2π + cos α ] ; cos 2π = 1
2π
Vm
Vdc = [ cos α − 1] ; Vm = 2VS
2π
Page 229
www.getmyuni.com
2VS
Hence Vdc = ( cos α − 1)
2π
−Vm
When 'α ' is varied from 0 to π . Vdc varies from 0 to
π
These drawbacks of single phase half wave ac voltage controller can be over come by
using a single phase full wave ac voltage controller.
Problem
1. A single phase half-wave ac voltage controller has a load resistance R = 50Ω ; input ac
supply voltage is 230V RMS at 50Hz. The input supply transformer has a turn’s ratio
of 1:1. If the thyristor T1 is triggered at α = 600 . Calculate
• RMS output voltage.
• Output power.
• RMS load current and average load current.
• Input power factor.
• Average and RMS thyristor current.
Page 230
www.getmyuni.com
Given,
V p = 230V , RMS primary supply voltage.
f = Input supply frequency = 50Hz.
RL = 50Ω
π
α = 600 = radians.
3
VS = RMS secondary voltage.
Vp Np 1
= = =1
VS NS 1
Therefore V p = VS = 230V
2π
1
VO( RMS ) = ∫V
2
sin 2 ω t.d (ω t )
2π
m
α
1 sin 2α
VO( RMS ) = VS ( 2π − α ) +
2π 2
Page 231
www.getmyuni.com
1 π sin1200
VO( RMS ) = 230 2π − +
2π 3 2
1
VO( RMS ) = 230 [5.669] = 230 × 0.94986
2π
PO = 0.9545799 KW
PO
PF =
VS × I S
954.5799 W
∴ PF = = 0.9498
( 230 × 4.36939 ) W
• Average Output (Load) Voltage
2π
1
VO( dc ) = ∫ Vm sin ω t.d (ω t )
2π α
We have obtained the expression for the average / DC output voltage as,
Page 232
www.getmyuni.com
Vm
VO( dc ) = [ cos α − 1]
2π
2 × 230 325.2691193
VO( dc ) = cos ( 600 ) − 1 = [ 0.5 − 1]
2π 2π
325.2691193
VO( dc ) = [ −0.5] = −25.88409 Volts
2π
VO( dc ) −25.884094
I O ( dc ) = = = −0.51768 Amps
RL 50
iT1
Im
π 2π 3π
α (2π+α) ωt
α
α
I m π
IT ( Avg ) = ∫ sin ω t.d (ω t )
2π α
π
Im
IT ( Avg ) = ( − cos ω t )
2π α
Im
IT ( Avg ) = − cos (π ) + cos α
2π
Page 233
www.getmyuni.com
Im
IT ( Avg ) = [1 + cos α ]
2π
Vm
Where, I m = = Peak thyristor current = Peak load current.
RL
2 × 230
Im =
50
I m = 6.505382 Amps
Vm
IT ( Avg ) = [1 + cos α ]
2π RL
2 × 230
IT ( Avg ) = 1 + cos ( 600 )
2π × 50
2 × 230
IT ( Avg ) = [1 + 0.5]
100π
π
1 2 2
IT ( RMS ) = ∫ I m sin ω t.d (ω t )
2π α
I m2 (1 − cos 2ω t )
π
IT ( RMS ) = ∫ .d (ω t )
2π α 2
π π
I m2
IT ( RMS ) = ∫ d (ω t ) − ∫ cos 2ω t.d (ω t )
4π α α
π π
1 sin 2ω t
IT ( RMS ) = I m (ω t ) −
4π α 2 α
1 sin 2π − sin 2α
IT ( RMS ) = I m (π − α ) −
4π 2
Page 234
www.getmyuni.com
1 sin 2α
IT ( RMS ) = I m (π − α ) +
4π 2
Im 1 sin 2α
IT ( RMS ) = ( π − α ) +
2 2π 2
IT ( RMS ) = π − +
2 2π 3 2
1 2π 0.8660254
IT ( RMS ) = 4.6 +
2π 3 2
6.5 Single Phase Full Wave Ac Voltage Controller (Ac Regulator) or Rms Voltage
Controller with Resistive Load
Single phase full wave ac voltage controller circuit using two SCRs or a single triac is
generally used in most of the ac control applications. The ac power flow to the load can be
controlled in both the half cycles by varying the trigger angle 'α ' .
The RMS value of load voltage can be varied by varying the trigger angle 'α ' . The
input supply current is alternating in the case of a full wave ac voltage controller and due to
the symmetrical nature of the input supply current waveform there is no dc component of
input supply current i.e., the average value of the input supply current is zero.
A single phase full wave ac voltage controller with a resistive load is shown in the
figure below. It is possible to control the ac power flow to the load in both the half cycles by
adjusting the trigger angle 'α ' . Hence the full wave ac voltage controller is also referred to as
to a bi-directional controller.
Page 235
www.getmyuni.com
Fig 6.7: Single phase full wave ac voltage controller (Bi-directional Controller) using SCRs
The thyristor T1 is forward biased during the positive half cycle of the input supply
voltage. The thyristor T1 is triggered at a delay angle of 'α ' ( 0 ≤ α ≤ π radians ) . Considering
the ON thyristor T1 as an ideal closed switch the input supply voltage appears across the load
resistor RL and the output voltage vO = vS during ω t = α to π radians. The load current
flows through the ON thyristor T1 and through the load resistor RL in the downward direction
during the conduction time of T1 from ω t = α to π radians.
At ω t = π , when the input voltage falls to zero the thyristor current (which is flowing
through the load resistor RL ) falls to zero and hence T1 naturally turns off . No current flows
in the circuit during ω t = π to (π + α ) .
The thyristor T2 is forward biased during the negative cycle of input supply and when
thyristor T2 is triggered at a delay angle (π + α ) , the output voltage follows the negative
halfcycle of input from ω t = (π + α ) to 2π . When T2 is ON, the load current flows in the
reverse direction (upward direction) through T2 during ω t = (π + α ) to 2π radians. The time
interval (spacing) between the gate trigger pulses of T1 and T2 is kept at π radians or 1800. At
ω t = 2π the input supply voltage falls to zero and hence the load current also falls to zero and
thyristor T2 turn off naturally.
Instead of using two SCR’s in parallel, a Triac can be used for full wave ac voltage
control.
Fig 6.8: Single phase full wave ac voltage controller (Bi-directional Controller) using TRIAC
Page 236
www.getmyuni.com
Equations
Input supply voltage
vS = Vm sin ω t = 2VS sin ω t ;
(i) To Derive an Expression for the Rms Value of Output (Load) Voltage
The RMS value of output voltage (load voltage) can be found using the expression
2π
1
=V = ∫ v d (ω t ) ;
2 2 2
VO ( RMS ) L ( RMS )
2π
L
0
For a full wave ac voltage controller, we can see that the two half cycles of output
voltage waveforms are symmetrical and the output pulse time period (or output pulse
Page 237
www.getmyuni.com
repetition time) is π radians. Hence we can also calculate the RMS output voltage by using
the expression given below.
π
1
V 2
L ( RMS )
= ∫ Vm 2 sin 2 ω t.dω t
π 0
2π
1
V 2 L( RMS ) = ∫v
2
.d (ω t ) ;
2π
L
0
Hence,
π 2π
1
∫ (Vm sin ω t ) d (ω t ) + ∫ (Vm sin ω t ) d (ω t )
2 2
V 2
L( RMS )
=
2π α π +α
1 2π 2 2π
= m ∫
V sin ω t .d ( ω t ) + Vm ∫ sin ω t .d (ω t )
2 2
2π α π +α
Vm 2 π 1 − cos 2ω t 2π
1 − cos 2ω t
= ∫ d ( ω t ) + ∫ d (ω t )
2π α 2 π +α 2
Vm 2 π π 2π 2π
= ∫ d ( ω t ) − ∫ cos 2ω t .d ( ω t ) + ∫ d ( ω t ) − ∫ cos 2ω t.d (ω t )
2π × 2 α α π +α π +α
π 2π π 2π
Vm 2 sin 2ω t sin 2ω t
= (ω t ) + (ω t ) − −
4π α π +α 2 α 2 π +α
Vm 2
(π − α ) + (π − α ) − ( sin 2π − sin 2α ) − ( sin 4π − sin 2 (π + α ) )
1 1
=
4π 2 2
Vm 2 1 1
=
4π 2 (π − α ) − 2 ( 0 − sin 2α ) − 2 ( 0 − sin 2 (π + α ) )
Vm 2 sin 2α sin 2 (π + α )
= 2 (π − α ) + +
4π 2 2
Vm 2 sin 2α sin ( 2π + 2α )
= 2 (π − α ) + +
4π 2 2
Page 238
www.getmyuni.com
Vm 2 sin 2α 1
=
4π 2 (π − α ) + 2 + 2 ( sin 2π .cos 2α + cos 2π .sin 2α )
Therefore,
Vm 2 sin 2α sin 2α
VL2( RMS ) =
4π 2 (π − α ) + 2 + 2
Vm 2
= 2 (π − α ) + sin 2α
4π
Vm 2
V 2 L( RMS ) = ( 2π − 2α ) + sin 2α
4π
Vm
VL( RMS ) = ( 2π − 2α ) + sin 2α
2 π
Vm
VL( RMS ) = ( 2π − 2α ) + sin 2α
2 2π
Vm 1
VL( RMS ) = ( 2π − 2α ) + sin 2α
2 2π
Vm 1 sin 2α
VL( RMS ) =
2π 2 (π − α ) + 2
2
Vm 1 sin 2α
VL( RMS ) = (π − α ) +
2 π 2
1 sin 2α
VL( RMS ) = Vi( RMS ) (π − α ) +
π 2
1 sin 2α
VL( RMS ) = VS (π − α ) +
π 2
Page 239
www.getmyuni.com
Maximum RMS voltage will be applied to the load when α = 0 , in that case the full
sine wave appears across the load. RMS load voltage will be the same as the RMS supply
V
voltage = m . When α is increased the RMS load voltage decreases.
2
Vm 1 sin 2 × 0
VL( RMS ) = (π − 0 ) +
α =0 2 π 2
1
(π ) +
Vm 0
VL( RMS ) =
α =0 2 π 2
Vm
VL( RMS ) = = Vi ( RMS ) = VS
α =0 2
The output control characteristic for a single phase full wave ac voltage controller
with resistive load can be obtained by plotting the equation for VO( RMS )
The control characteristic is the plot of RMS output voltage VO( RMS ) versus the trigger
angle α ; which can be obtained by using the expression for the RMS output voltage of a full-
wave ac controller with resistive load.
1 sin 2α
VO( RMS ) = VS (π − α ) + ;
π 2
Vm
Where VS = = RMS value of input supply voltage
2
300 π
6 ( 6)
; 1π 0.985477 VS 98.54% VS
Page 240
www.getmyuni.com
1800 π (
; 6π
6 ) 0 VS 0 VS
VO(RMS)
VS
0.6VS
0.2 VS
0 60 120 180
Trigger angle α in degrees
We can notice from the figure, that we obtain a much better output control
characteristic by using a single phase full wave ac voltage controller. The RMS output
voltage can be varied from a maximum of 100% VS at α = 0 to a minimum of ‘0’ at
α = 1800 . Thus we get a full range output voltage control by using a single phase full wave
ac voltage controller.
G1
Gate
Trigger K1
Pulse G2
Generator
K2
Page 241
www.getmyuni.com
6.6 Single Phase Full Wave Ac Voltage Controller (Bidirectional Controller) With RL
Load
In this section we will discuss the operation and performance of a single phase full
wave ac voltage controller with RL load. In practice most of the loads are of RL type. For
example if we consider a single phase full wave ac voltage controller controlling the speed of
a single phase ac induction motor, the load which is the induction motor winding is an RL
type of load, where R represents the motor winding resistance and L represents the motor
winding inductance.
A single phase full wave ac voltage controller circuit (bidirectional controller) with an
RL load using two thyristors T1 and T2 ( T1 and T2 are two SCRs) connected in parallel is
shown in the figure below. In place of two thyristors a single Triac can be used to implement
a full wave ac controller, if a suitable Traic is available for the desired RMS load current and
the RMS output voltage ratings.
Fig 6.11: Single phase full wave ac voltage controller with RL load
The thyristor T1 is forward biased during the positive half cycle of input supply. Let
the load in the downward direction. This load current pulse flowing through T1 can be
considered as the positive current pulse. Due to the inductance in the load, the load current iO
flowing through T1 would not fall to zero at ω t = π , when the input supply voltage starts to
become negative.
The thyristor T1 will continue to conduct the load current until all the inductive energy
stored in the load inductor L is completely utilized and the load current through T1 falls to
ω atβ t =
zero β
, where is referred to as the Extinction angle, (the value of ω t ) at which the
Page 242
www.getmyuni.com
β
load current
β falls to zero. The extinction angle is measured from the point of the beginning
of the positive half cycle of input supply to the point where the load current falls to zero.
φ
The thyristor T1 conducts from ω t = α to . The conduction angle of T1 is
=( − ), which depends on the delay angle α and the load impedance angle . The
waveforms of the input supply voltage, the gate trigger pulses of T1 and T2 , the thyristor
current, the load current and the load voltage waveforms appear as shown in the figure below.
is the extinction angle which depends upon the load inductance value.
Page 243
www.getmyuni.com
Page 244
www.getmyuni.com
α φ
α φ β π α
Waveforms of single phase full wave ac voltage controller with RL load for > .
Discontinuous load current operation occurs for > and <( + );
i.e., ( − )< , conduction angle < π .
Fig 6.14: Waveforms of Input supply voltage, Load Current, Load Voltage and Thyristor Voltage across T1
Note
• The RMS value of the output voltage and the load current may be varied by varying
the trigger angle α .
• This circuit, AC RMS voltage controller can be used to regulate the RMS voltage
across the terminals of an ac motor (induction motor). It can be used to control the
temperature of a furnace by varying the RMS output voltage.
• For very large load inductance ‘L’ the SCR may fail to commutate, after it is triggered
and the load voltage will be a full sine wave (similar to the applied input supply
Page 245
www.getmyuni.com
voltage and the output control will be lost) as long as the gating signals are applied to
the thyristors T1 and T2 . The load current waveform will appear as a full continuous
sine wave and the load current waveform lags behind the output sine wave by the load
power factor angle φ.
(i) To Derive an Expression for the Output (Inductive Load) Current, During
t = to When Thyristor T1 Conducts
Considering sinusoidal input supply voltage we can write the expression for the
supply voltage as
β
Let us assume that the thyristor T1 is triggered by applying the gating signal to T1 at
ω t = α . The load current which flows through the thyristor T1 during ω t = α to can be
found from the equation
di
L O + RiO = Vm sin ω t ;
dt
The solution of the above differential equation gives the general expression for the
output load current which is of the form
τ
−t
Vm
iO = sin (ω t − φ ) + A1e ;
Z
ω
Z = R 2 + ( L ) = Load impedance.
2
ω
L
φ = tan −1 = Load impedance angle (power factor angle of load).
R
τ L
= = Load circuit time constant.
R
Therefore the general expression for the output load current is given by the equation
−R
Vω φ t
iO = m
sin ( t − ) + A1e L ;
Z
Page 246
www.getmyuni.com
The value of the constant A1 can be determined from the initial condition. i.e. initial
value of load current iO = 0 , at ω t = α . Hence from the equation for iO equating iO to zero
φ and substituting ω t = α , we get
−R
V t
iO = 0 = m sin ( − ) + A1e L
Z
α φ
−R
t −Vm
Therefore A1e L
= sin ( − )
Z
α φ
1 −Vm
A1 = −R Z sin ( − )
Lt
e
α φ
+R
−Vm
)
t
A1 = e Z sin ( −
L
α φ
R (ω t )
−Vm
A1 = e ωL
Z sin ( − )
α φ
R (α )
−V
A1 = e ω L m sin ( − )
Z
Substituting the value of constant A1 from the above equation into the expression for iO , we
obtain
ω φ α Rφ(α )
−R
−V
)
V t
iO = m sin ( t − )+e L
e ω L m sin ( − ;
Z Z
ω φ V − R (ω t ) α φ−V
R (α )
iO =m
sin ( t − )+e ωL
e ωL m
Z sin ( − )
Z
ω Vφ −R
α−Vmφ
)
(ω t −α )
iO =
m
sin ( t − ) + eω L Z sin ( −
Z
Therefore we obtain the final expression for the inductive load current of a single
phase full wave ac voltage controller with RL load as
Page 247
www.getmyuni.com
α ω β
Vm −R
(ω t −α )
iO = sin ( ω t − φ ) − sin (α − φ ) e ωL
; Where ≤ t≤ .
Z
ω α β
The above expression also represents the thyristor current iT 1 , during the conduction
β time interval of thyristor T1 from t = to .
β
To Calculate Extinction Angle
The extinction angle , which is the value of ω t at which the load current iO
falls to zero and T1 is turned off can be estimated by using the condition that iO = 0 , at
t=
By using the above expression for the output load current, we can write
Vm −R
( β −α )
iO = 0 = sin ( β − φ ) − sin (α − φ ) e
ωL
Z
Vm
As ≠ 0 we can write
Z
−R
( β −α )
sin ( β − φ ) − sin (α − φ ) e =0
ωL
β α
Therefore we obtain the
ω expression
−R
( − )
sin ( β − φ ) = sin (α − φ ) e L
β
The extinction angle can be determinedβ from this transcendental equation by using
the iterative methodδof solution
β α (trial and error method). After is calculated, we can
Page 248
www.getmyuni.com
π α α φ
vO vO=vS
Vm
π 2π 3π
0 φ ωt
φ φ φ
iO
Im
φ ωt
Page 249
www.getmyuni.com
(ii) To Derive an Expression For rms Output Voltage VO ( RMS ) of a Single Phase Full-Wave Ac
Voltage Controller with RL Load.
When α > O , the load current and load voltage waveforms become discontinuous as
shown in the figure above.
1
β
1 2
VO( RMS ) = ∫ Vm 2 sin 2 ω t.d (ω t )
ω α β π α
1
Vm 2 β (1 − cos 2ω t ) 2
VO( RMS ) = ∫ d ( ω t )
π α 2
1
V 2
β β
2
1
V 2 β
sin 2ω t
β
2
1
1 sin 2α sin 2 β 2
VO( RMS ) = Vm ( β − α ) + −
2π 2 2
1
V 1 sin 2α sin 2 β 2
VO( RMS ) = m ( β − α ) + −
2 π 2 2
The RMS output voltage across the load can be varied by changing the trigger angle
α.
φ
For a purely resistive load L = 0 , therefore load power factor angle = 0.
Page 250
www.getmyuni.com
ωL
φ = tan −1 =0 ;
R
Extinction angle β = π radians = 1800
Vm 1 sin 2α V
• RMS Output Voltage VO( RMS ) = (π − α ) + ; m = VS = RMS input
2 π 2 2
supply voltage.
VO ( RMS )
• I O ( RMS ) = = RMS value of load current.
RL
VO ( RMS ) 1 sin 2α
PF = = (π − α ) +
VS π 2
iT1
Im
π 2π 3π
α (2π+α) ωt
α
α
π π
1 1
∫ iT d (ω t ) = I m sin ω t.d (ω t )
2π α∫
IT ( Avg ) =
2π α
Page 251
www.getmyuni.com
Im π I π
IT ( Avg ) = ∫ sin ω t.d (ω t ) = m − cos ω t
2π α 2π α
Im I
[ − cos π + cos α ] = m [1 + cos α ]
IT ( Avg ) =
2π 2π
• Maximum Average Thyristor Current, for α = 0 ,
I
IT ( Avg ) = m
π
Im 1 sin 2α
IT ( RMS ) = (π − α ) +
2 2π 2
Im
IT ( RMS ) =
2
In the case of a single phase full wave ac voltage controller circuit using a Triac with
resistive load, the average thyristor current IT ( Avg ) = 0 . Because the Triac conducts in both the
half cycles and the thyristor current is alternating and we obtain a symmetrical thyristor
current waveform which gives an average value of zero on integration.
Performance Parameters of A Single Phase Full Wave Ac Voltage Controller with R-L
Load
V −R α ω
(ω t −α )
β
iO = iT1 = m sin ( ω t − φ ) − sin ( α − φ ) e ωL
; for ≤ t≤
Z
Where,
Vm = 2VS = Maximum or peak value of input ac supply voltage.
ω
Z = R 2 + ( L ) = Load impedance.
2
ω
L
φ = tan −1 = Load impedance angle (load power factor angle).
R
δ β α π α φ
Thyristor Conduction Angle =( − )
Maximum thyristor conduction angle =( − )= radians = 1800 for ≤ .
α β
β α
RMS Output Voltage
Vm 1 sin 2 sin 2
VO( RMS ) = ( − )+ −
2 π 2 2
1 β Vm −R
(ω t −α )
IT ( Avg ) = ∫ ( ω − φ ) − (α − φ ) d (ω t )
ωL
sin t sin e
2π α Z
β β
Vm −R
(ω t −α )
IT ( Avg ) = ∫ sin (ω t − φ ) .d (ω t ) − ∫ sin (α − φ )eω L d (ω t )
2π Z α α
1 β
IT ( RMS ) = ∫ iT21 d (ω t )
2π α
When a Triac is used in a single phase full wave ac voltage controller with RL type of
I
load, then IT ( Avg ) = 0 and maximum IT ( RMS ) = m
2
Page 253
www.getmyuni.com
PROBLEMS
1. A single phase full wave ac voltage controller supplies an RL load. The input supply
voltage is 230V, RMS at 50Hz. The load has L = 10mH, R = 10Ω, the delay angle of
π
thyristors T1 and T2 are equal, where α1 = α 2 = . Determine
3
a. Conduction angle of the thyristor T1 .
b. RMS output voltage.
c. The input power factor.
Comment on the type of operation.
Given
π
Vs = 230V , f = 50 Hz , L = 10mH , R = 10Ω , α = 600 , α = α1 = α 2 =
3
radians, .
ω L = ( 2π fL ) = ( 2π × 50 × 10 ×10−3 ) = π = 3.14159Ω
(10 ) + ( 3.14159 )
2 2
Z= = 109.8696 = 10.4818Ω
Vm 2 × 230
Im = = = 31.03179 A
Z 10.4818
ω
L
Load Impedance Angle φ = tan −1
R
π
φ = tan −1 = tan ( 0.314159 ) = 17.44059
−1 0
10
α φ
Trigger Angle > . Hence the type of operation will be discontinuous load current
operation,βwe get
π α
<( + )
β
Therefore the range of is from 180 degrees to 240 degrees. (180 0
< β < 2400 )
β
Extinction Angle is calculated by using the equation
Page 254
www.getmyuni.com
β α
ω
β −R
( − )
sin ( β − φ ) = sin (α − φ ) e L
In the exponential term the value of α and should be substituted in radians. Hence
−R
( β Rad −α Rad ) π
sin ( β − φ ) = sin (α − φ ) e ω L ; α Rad =
3
(α − φ ) = ( 60 − 17.44059 ) = 42.55940
−10
( β −α )
sin ( β − 17.44 ) = sin ( 42.5594 ) e π
0 0
β α
β
π
−3.183 3.3161−
R.H.S: 0.676354 × e 3
= 4.94 ×10−4
Assuming β = 1830 ;
β 0 ×π 1830 × π
β Rad = = = 3.19395
1800 180
π
( β − α ) = 3.19395 − = 2.14675
3
−3.183( 2.14675 )
R.H.S: 0.676354e = 7.2876 ×10−4
Assuming β ≈ 1800
β β 0 ×π π 0 ×π
180
Rad = = =
1800 180
π 2π
( β − α ) = π − =
3 3
L.H.S: sin ( β − φ ) = sin (180 − 17.44 ) = 0.2997
Page 255
www.getmyuni.com
π
−3.183 π −
R.H.S: 0.676354e 3
= 8.6092 ×10−4
Assuming β = 1960
β 0 ×π 1960 × π
β Rad = = = 3.420845
1800 180
Assuming β = 197 0
β 0 ×π 197 0 × π
β Rad = = = 3.43829
1800 180
Assuming β = 197.420
β 0 ×π 197.42 × π
β Rad = 0
= = 3.4456
180 180
Page 256
www.getmyuni.com
PO 3901.716
PF = = = 0.8588
VS × I S 230 × 19.7527
2. A single phase full wave controller has an input voltage of 120 V (RMS) and a load
resistance of 6 ohm. The firing angle of thyristor is π 2 . Find
d. RMS output voltage
e. Power output
f. Input power factor
g. Average and RMS thyristor current.
Solution
π
α= = 900 , VS = 120 V, R = 6Ω
2
1
1 π sin180 2
VO = 120 π − +
π 2 2
VO = 84.85 Volts
VO 84.85
IO = = = 14.14 A
R 6
Load Power
PO = I O2 × R
Page 257
www.getmyuni.com
Therefore
Load Power 1200
Input Power Factor = = = 0.707 ( lag )
Input Volt-Amp 1696.8
π
1
Vm sin ω t.d (ω t )
2π R α∫
IT ( Avg ) =
α
Vm
= (1 + cos ) ; Vm = 2VS
2π R
2 ×120
= [1 + cos 90] = 4.5 A
2π × 6
π
1 Vm2 sin 2 ω t
d (ω t )
2π α∫
IT ( RMS ) =
R2
Vm2
π
(1 − cos 2ω t ) d ω t
= 2 ∫ ( )
2π R α 2
1
V 1 sin 2α 2
= m π −α +
2 R π 2
1
2VS 1 sin 2α 2
= π π − α +
2R 2
1
2 × 120 1 π sin180 2
= π − + = 10 Amps
2 × 6 π 2 2
3. A single phase half wave ac regulator using one SCR in anti-parallel with a diode feeds 1
kW, 230 V heater. Find load power for a firing angle of 450.
Page 258
www.getmyuni.com
Solution
π
α = 450 = , VS = 230 V ; PO = 1KW = 1000W
4
At standard rms supply voltage of 230V, the heater dissipates 1KW of output power
Therefore
VO × VO VO2
PO = VO × I O = =
R R
Resistance of heater
V 2 ( 230 )
2
R= O = = 52.9Ω
PO 1000
RMS value of output voltage
1
1 sin 2α 2
VO = VS 2π − α + ; for firing angle α = 450
2π 2
1
1 π sin 90 2
VO = 230 2π − + = 224.7157 Volts
2π 4 2
4. Find the RMS and average current flowing through the heater shown in figure. The delay
angle of both the SCRs is 450.
SCR1 io
+
Solution
π
α = 450 = , VS = 220 V
4
Resistance of heater
Page 259
www.getmyuni.com
V 2 ( 220 )
2
R= = = 48.4Ω
R 1000
1 π sin 90
VO = 220 π − +
π 4 2
1 π 1
VO = 220 π − + = 209.769 Volts
π 4 2
VO 209.769
RMS current flowing through heater = = = 4.334 Amps
R 48.4
5. A single phase voltage controller is employed for controlling the power flow from 220 V,
50 Hz source into a load circuit consisting of R = 4 Ω and L = 6 mH. Calculate the following
a. Control range of firing angle
b. Maximum value of RMS load current
c. Maximum power and power factor
d. Maximum value of average and RMS thyristor current.
Solution
For control of output power, minimum angle of firing angle α is equal to the load
impedance angle θ
α = θ , load angle
ωL −1 6
θ = tan −1 = tan = 56.3
0
R 4
Maximum value of RMS load current occurs when α = θ = 56.30 . At this value of α the
Maximum value of RMS load current
Page 260
www.getmyuni.com
VS 220
IO = = = 30.5085 Amps
Z 42 + 6 2
PO 3723.077
Power Factor = = = 0.5547
Input VA 6711.87
Average thyristor current will be maximum when α = θ and conduction angle γ = 1800 .
Therefore maximum value of average thyristor current
π +α
1 Vm
IT ( Avg ) = ∫ sin (ω t − θ ) d (ω t )
2π α Z
Vm −R
(ω t −α )
iO = iT1 = sin (ω t − θ ) − sin (α − θ ) e
ωL
Note:
Z
ω α θ= 0 ,
At
V
iT1 = iO = m sin ( t − )
π α Z
Vm +
IT ( Avg ) = − cos (ω t − θ ) α
2π Z
π α θ α θ
V
IT ( Avg ) = m − cos ( + − ) + cos ( − )
2π Z
But α = θ , π
Vm Vm V
IT ( Avg ) = − cos ( ) + cos ( 0 ) = [ 2] = m
2π Z 2π Z πZ
Vm 2 × 220
∴ IT ( Avg ) =
= = 13.7336 Amps
π Z π 42 + 62
γ π
Similarly, maximum RMS value occurs when α = 0 and = .
π +α 2
1 Vm
ITM = ∫ sin (ω t − θ ) d (ω t )
2π α Z
Vm2
π +α
1 − cos ( 2ω t − 2θ )
ITM = ∫ d (ω t )
2π Z 2 α 2
Page 261
www.getmyuni.com
π +α
Vm2 sin ( 2ω t − 2θ )
ITM = ω t −
4π Z 2 2 α
Vm2
ITM = [π + α − α − 0]
4π Z 2
Vm 2 × 220
ITM = = = 21.57277 Amps
2 Z 2 42 + 62
Recommended questions:
1. Discuss the operation of a single phase controller supplying a resistive load, and
controlled by the on-off method of control. Also highlight the advantages and
disadvantages of such a control. Draw the relevant waveforms.
2. What phase angle control is as applied to single phase controllers? Highlight the
advantages and disadvantages of such a method of control. Draw all the wave forms.
3. What are the effects of load inductance on the performance of voltage controllers?
4. Explain the meaning of extinction angle as applied to single phase controllers supplying
inductive load with the help of waveforms.
5. What are unidirectional controllers? Explain the operation of the same with the help of
waveforms and obtain the expression for the RMS value of the output voltage. What are
the advantage and disadvantages of unidirectional controllers?
6. What are bi-directional controllers explain the operation of the same with the help of
waveforms and obtain the expression for the R<S value of the output voltage. RMS value
of thyristor current. What are the advantages of bi-directional controllers?
7. The AC Voltage controller shown below is used for heating a resistive load of 5 Ω and
the input voltage Vs = 120 V (rms). The thyristor switch is on for n=125 cycles and is off
for m = 75 cycles. Determine the RMS output voltage Vo, the input factor and the
average and RMS thyristor current.
8. T1
i. + D +Vo
~ Vs
a. R
b. (load)
ii. -
Page 262
www.getmyuni.com
in the problem above R=4Ω, Vs =208 V (rms) if the desired output power is 3 KW,
determine the duty cycle ‘K’ and the input power factor.
9. The single phases half wave controller shown in the figure above has a resistive load of
R=5Ω and the input voltage Vs=120 V(rms), 50 Hz. The delay angle of the thyristor is .
Determine the RMS voltage, the output Vo input power factor and the average input
current. Also derive the expressions for the same.
10. The single phase unidirectional controller in the above problem, has a resistive load of 5Ω
and the input voltage Vs = 208 V (rms). If the desired output power is 2 KW, calculate
the delay angle α of the thyristor and the input power factor.
Page 263