You are on page 1of 22

3M''' Cold Shrink QT-lll Silicone Rubber lndoor :

Tubular Termination Kit


W¡th High-K Stress Relief
For Tape Shield, Wire Shield and UniShield@ Cable

7622-T-1 1 0,7622-T-110(L), 7623-T-1 1 0,7624-T-11 0,


7625-T-1 1 0,7625-T-1 10(L), 7626-T-1 10
lnstructions
¡EEE Std. No. ¡t8
Class 1 Termination
15 kV Class
1 10 kv BtL

A OAI'TI§T{
Working around energized systems may cause serious injury or death. lnstalla¡on should
be performed by personnel famil¡ar with good safety practice in handling electrcal
equipment. De-energize and ground all electrical systems before installing product.

i jtil

February 2018
78-811 3-5099-6 Rev G
3 3M'" Gold Shrink 0T-lll Silicone Rubber Indoor Tubular Termination K¡t With High-K Stress Relief

1.0 K¡t Contents


I 3 High-K, Tracking Resistant, Silicone Rubber Terminations

3 Pre-formed Ground Braids


3 Constant Force Springs
3 3M* EMI Copper Foil Shielding Tape l18l Strips, ll2" x 70"
6 Strips Scotch@ Mastic Strip 2230 (black with white release liners, bagged)
1 3M* Cable Cleaning PreparationKitCC-2
I Instruction Sheet

Note: Do not use knives to open plastic bags.

Kit Selection Tables


tlOTE: Final Determination Factor is cable insulation diameter.

For Use With Compression Lugs or Connectors

C¡nducbr Size Range (AWG & kcmil)


Primary lnsulation
Kit Number 0.0. Range Jacket 0.0. Range 5kv 8ku 15 kv

7622-I-110
0.64' - 1.08 0.97', - 1.48" 4/0400 3/0 - 300 2-2t0
(16,3 - 27,4 mm) (24,6-37,7 nm\ (35 - 70 mm')
7623-T-1 1 0
0.72" -1.29" 1.04" - 1.60', 300 - 500 250 - 500 2i0 - 300
(18,3 - 32,8 mm) (26,4 - 40,6 mm) (70 - 150 mm')

7624-r-110
0.83" - 1.53', 1.12" - 1.87', 500 - 750 350 - 700 4/0 - 500
(21,1 - 38,9 mm) (28,4 - 47,5 mm) (120 - 240 mm'?)

7625*T-1 1 0
1.05" - 1.80', 1.39" - 2.40" 700 - 1 500 600 - 1 250 500 - 1 000
(26,7 - 45,7 mm) (35,2 - 61,0 mm) (240 - 500 mm')
'1750
7626-T-1 1 0
1.53" - 2.32', 1.84" - 2.80' - 2000 1 500 - 2000 1 250 - 2000

(38,9 - 58,9 mm) (46,7 - 71,1 mm) (625 - 1000 mnn')

Table 1

For Use With 3MrM Mechanical Shearbolt Lugs 012 Series: Two Hole

Gonductor Size Range 3Mrt Shearbolt lugs


Primary lnsulation (AWG & kcmil) 0[2 Series: Two Hole
Kit Number 0.D. Range Jacket 0.D. Range 15 kV Part Number

7622-r-110(t\
0.69', -
1.22', 0.97 - 1.48 1t0 - 4t0
QL2-A-2-250
(17,5 - 31,0 mm) (24,6-37,7 nn) (60 - 120 mm')

4.72" -1.29" 1.04', - r .60" 210 -250


7623-T-1 1 0 012-A-2-250
(18,3 - 32,8 mm) (26,4 - 40,6 mm) (70 - 150 mm')

7624-f-110
0.83" - 1.53" 1.12" - 1.87' 4/0 - 350 012-A-1 i 0-350
(21,1 - 38,9 mm) (28,4 - 47,5 nn) (120 - 150 mm'z)

'1.80" .r.39"
7625-T-1 1 0
1.05" - - 2.40" 500
012-A+/0-600
t
(26,7
= 45,7 mm\ (35,2 - 61,0 mm) (240 mm')

7625-T-1 1 0
1.05" - 1.80" 1.39" - 2.40" 500 - 750 012-A-350-750
(26,7 - 45,7 nn) (35,2 - 61,0 mm) (240 - 325 mm'?)
1.15', - 1.98" 1.39" - 2.40 ', 750 - 1 000
7625-T-1 1 0(L) QL2-A-500-1 000
(29,2 - 50,3 mm) (35,2 - 61,0 mm) (400 - 500 mm')
'1.84"
I
7626-T-'1 10
1.53" - 2.32" - 2.80' 1250
012-A-1 000-1 250
(38,9 - 58,9 mm) (46,7 - 71,1 mm) (625 mm')
I

Table2
I

78-8113-5099-6 Rev G
3M* Cold Shrink 0T-lll Silicone Rubber lndoor Tubular Termination K¡t W¡th High-K Stress Relief

2.0 lnstructions for Tape Shielded Cable


Prepare Cable
2.1 Check to be sure cable size fits r.-r,ithir.r r . r,-..'.ii :s shown in Table 1. (For Use With Compression Lugs or
Connectors), or Table 2 (For Use \\iith :1,,1 I'i¡¡ranical Shearbolt Lugs QL2 Series: Tr,vo Hole).

2.2 il F : . ; 1 BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG


Prepare cable using dimer.rsions shoun
OR CONNECTOR. Ilnecessary to prer er , ..::r3 shield fiom unrolling, hold dou,n edge with a single u,rap of 3M EMI
Copper Foil Shielding Tape I l8l.

2.3 lf using a Crimp Type (Compression) lus, r':::.ure the depth of the barrel. oi if using a Crin-rp T¡rpe (Cornpression)
connector, measure to the bartel center strrr ::- .r¡Lrnt. and see the NOTE below, and Table 3, concen.ring Aluminum
Lug and Connector growth allorvances. in ,.':,.:'¡rr r-alculate the lnsulation Removai Length. Table 6 (located in the
final pages of this Instruction document) c¡-' ...¡d to assist in calculating the total Jacket Removal Length when using
a compression lLrg or connector.

If using 3M Shearbolt Lugs QL2 Series: Tn o Hole, or 3NI Mechanical Shearbolt Connector QCI Series,
proceed to Step 2.4.

NOTE: Provide additional exposed conductor disrattt'e to uccount fnr growth during crimping of ALUMINL|M lugs or
conneclors as .follows:

Aluminum Lug
and Connector
2-350 400 - 650 750-1 000 1250 - 2000
Growth Allowance
1/4 (6 mm) I2 (13 mm) 3/4" (19 mm) Field determined

¡ Table 3

\-OTE: It is i»tperatire to reiltore all renmants o.f tlte semi-con laye\ even if the semi-con layer comes o.ff as one layer.
There should not be atry rentainittg black oreas, or ptrticles, on tlte cable insulation layen

Jacket Removal Length

lnsulat or ::ixoval Length = Depth 0f Compression Lug or Connector


+ Grow,t¡ j lrvance 0R lnsulationoutback dimension from
Shearboit L-! 0r Connector lnstructions

9' (229 mm)

3" (76 mnl)

1-112" (38 mm) 1'1l2" (38 mm)

'1
Figure

78-tl I I 3-5099-6 Rev G 3


31 3M'" Cold Shrink QT-lll Silicone Rubber lndoor Tubular Termination K¡t W¡th High-K Stress Relief

2.4 If using 3M Mechanical Shearbolt Lugs QL2 Series: Two Hole, or 3M Mechanical Shearbolt Connector QCI Series,
T refer to the lnstructions that are packed with the Shearbolt product for the Insulation Cutback length for the specific
- Shearbolt Lug or Connector being used. Table'/ (located in the final pages of this Instruction document) can used to
assist in calculating the total Jacket Removal Length when using 3M Shearbolt Lugs QL2 Series: Two Hole, or 3M
Shearbolt Connector QCI Senes.

3.0 lnstall Ground Braid


3.1 Select a Scotch'r' Mastic Strip 2230 from kit and remove white release liners. L sing light tensic¡n. apply' a SI-\GLE
WRAP of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure I L Cut t¡fi ercess.

Single Wrap of 3M-" EMI Copper Fol


l/4" (6 mm) < Shield¡ng Tape 81 (if used)
I
11

Tape Shield

I st Scotch@ Mastic StrÍp 2230 - SltlGLE WRAP

Cable Jacket

Figure 2

3.2 Position pre-fomed ground braid with short tail over tape shield directl¡ ad¡acent to cable jacket cut edge. PLEASE
NOTE: The ground braid needs to make full contact with the metallic tape shield. Position long tail of ground braid,
extending over cable jacket with solder biock over mastic strip (Figure 3). Secure ground braid to cable jacket 4-112"
(114 mm) from cable semi-con edge using vinyl tape (see NOTE and Figure 3).

NOTE: Position vinyl tupe with care, it also serves as a marker Jbr positioning the termination.

4-112" (114mm) !
I

t [+óü{
IAA¡\A

I c(xxx)
IAAAA
I\AAA]
. IAAAi\l
I\AAA¿
ñnnnl
IAAA,\

I Semi-Con Edge
Single Wrap sf 3M" EMI CopFr Fo¡l
Tape Shield Shielding Tape 'l 181 (if useCI
Ground Braid
Cable Jacket Edge

Solder Block

lst Scotcho Mastic Strip 2230 - SINGLE WRAP

Vinyl Tape l\ilarker

Figure 3

3.3 Wrap ground braid around cable tape shield one complete rvrap. lrim excess at approximatell a 15 degree angle,
and iine up with the pre-bent 45 degree angie already on the ground braid, to prevent overlap. Secure in place u''ith
constant force spring. Wrap spring in same direction as grolrnd braici (Figure 4). Cinch (tighten) the spring after
wrapping the final winding.

4 78-8113-5099-6 Rev G
3M'" Cold Shrink 0T-lll Silicone Rubber lndoor Tubular Termination Kit W¡th High-K Stress Relief

3.4 Select second Scotch@ Mastic Strip 2230 from kit and remove white release liners. Apply a second SINGLE WRAP
of mastic over solder block on ground braid and previously applied mastic (Figure 4). Cut off excess.

Consiant Force Spring


-

- -. Single Wrap of 3M* EMI Copper Foil Shielding Tape 1181 (¡f used)
r :- ¡ d
:--, .=-'a:

1 s: S: -:::: lv{astic Strip 2230 - SINGLE WRAP

Jl -r :

2nc l:::.^: l/astic Strip 2230 - SINGLE WRAP

GroundBraid tg /

Figure 4

3.5 Wrap two highly stretched half-lapped iayers oi electrical grade vinyl tape around Scotch" Mastic Sfrip 2230,
constant force spring and exposed tape shield t Figure 5).

)-OTE: Take care not to cover exposed semi-cott insulation shield. A minimum of 1- (25 mm) must be exposed.

\OTE: DO NOT completely cover the ground brsid b'ith electrical grade vinyl Íape when applying over the Scofch@
-llastic Strip 2230 per Step 3.5. LEAVE A MII{IML rI OF 1/4" (6 MM) OF EXPOSED GROUND BRAID between the
lintl Tape .lIarker applied in step 3.2 and the start of the two hulf-lapped layers of electrical grade vinyl tape covering
rhe Scotch' .lÍastic Strip 2230 applied in Sfep 3.5.

SPECIAL NOTE FOR CLOTH OR PAPER SEMI-COT INSULATION SHIELD


In cables with cloth or paper semi-conducfive shields, it is recommended the shield be over wrapped with one half-
lapped layer of highly strefched semi-conductive rubber tape, such as Scotch@ Electrical Semi-Conducfing Tape 13.

,- Ground Braid (Must Leave Minimum of 1/4" (6 MM) Exposed. See Note Under Step 3.5.)

Semi-Con (Must Leave Minimum of 1 " (25 mm) Exposed. See Note Under Step 3.5.)

Tape Shield Ground Braid

Constani Force Spring

Two High ; S:'iiched Ha f-Lapped Layers of Electrical Grade Vinyl Tape

Scotcho Mastic Strip 2230

Vinyl Tape Marker

Figure 5

78-8113-5099-6 Rev G
3l 3M'" Cold Shrink QT-lll Silicone Rubber lndoor Tubular Termination K¡t W¡th High-K Súess Relief

T 4.0 Install Lug or Connector


Important Packaging Notice
In order to make sure that you receive an undamaged termination, this 3M Cold Shrink QT-III Silicone Rubber Termination
is packed with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install
the termination. This shipping core can be recycled with other polypropylene waste.

4.1 Check to insure 3M Cold Shrink QT-lll Silicone Rubber Termination assembl¡ fits over the selected lug
or connector BEFORE installing the lug or connector. If lug or connector. (Figure 6) v-ilt not fit through the
termination core, clean the insulation (per Step 5.0) and slide termination on cable before installing lug or connector.
DO NOT REMOVE CORE AT THIS TIME.

Figure 6

4.2 For 3M Compression Lugs and 3M Stem Connectors:


a. Refer to the final pages of this Instruction document for 3M Connector and Lu_s cnmpine inlbrmation.
b. For Aluminum Conductors - Thoroughly wire brush conductor strands ttr rerrtr\ e aluminum oxide 1ayer. lnsert
conductor into lug or connector and then remove conductor. This will transitr sr-rme of the antio\idant paste onto the
conductor. Wire brush the antioxidant paste into the strands. Immediatelr inseñ cr¡nductor into lus or connector barrel
as far as it will go.

I{OTE: Die/crimper hesd rotation between consecutive crimps is RECOIIIIE\DED

c. Position connector or lug and crimp according to manufacturer's direciions. Remove excess oxide inhibitor and
sharp crimp flashings following crimping.

4.3 For 3M Mechanical Shearbolt Lugs QL2 Series: Two Hole or 3M lrlechanical Shearbolt Connector QCI Series;
a. Refer to the Instructions that are packed with the Shearbolt product lor the installation procedures.

5.0 Clean Cable lnsulation and Lug or Connector Barrel Using Standard Practice
5.1 If abrasive must be used:
a. Use on insulation only. DO NOT USE ABRASIVE ON SEMI-CO\ 1\S¿Z-{TIOli SIIIELD!
b. Use only aluminum oxide abrasive; grtt 120 or finer, included in -1\f Cable Cleaning Preparation Kit CC-2.
c. Be careful not to reduce the cable insulation diameter below that ¿ll¡r'* ed br the kit.

5.2 Wipe the cable insulation with one of the solvent saturated pads from ¡he -r\1 Cable Cleaning Preparation Kit CC-2,
or other approved cable cleaner/solvent, AND ALLOW IT TO DR\ BEFORI I\STALLING TERMINATION.
A clean lint-free cloth, or inexpensive paper towel, can be used to dry the ln.uiation surlace if air drying time is of
concern. DO NOTALLOW SOLVENT TO TOUCH SEMI-CO\ I\SLLA.TIO\ SHIELD!

78-8113-5099-6 Rev G
3M* Cold Shrink QT-lll Silicone Rubber lnOoor Tubular Termination K¡t W¡th High-K Stress Relief

6.0 lnstall Termination


6. 1 Slide the termination body onto the c¡:.: :nd remove core. Make sure the termination body (not the core) is butted
up to the edge of the vinyl tape marke:::¿',.trusll applied in Step 3.2 (Figure 7). Pull the core while unwinding,
counterclockwise. starting with the lt.¡t¡!3 ::i rFisure 7). Be sure to alternate the pulling and unwinding actions
(pu11-unwind-pull-unwind-etc.) to help l:e,, ent the core material from binding up as the core is being removed.

NOTE: Once the termination body makes conÍact over the mastic seal area, there is no need to continue supporting the
assembly. DO NOT PaSH OR PULL ON THE TELIII!'¡ATION ASSEMBLY l.l/HILE UNWII{DING THE CORE.

rlltl
llllr
Vinyl Tape Marker NoTE: The mater¡al being removed at this step is mixed polymers
(Applied in Step 3.2) and can be recycled.
l?

Figure 7

6.2 Connect ground braid to system ground according to standard practice.

Correct lnstallation of Termination on Tape Shielded Cable

li ;^-l
{(Jl
-l

Vinyl Tape
Marker
Ridge at End of Cable
lnsulation Shield (Semi-Con)
Bidge at End
of High-K Tube

Semi-Con lnsulation Shield Cable lnsulation Environmental Top


Seal
Stress Controlling Compound

High-K Stress
Relief Tube

78-8113-5099-6 Rev G
3M" Cold Shrink QT-lll Silicone Rubber lndoor Tubular Termination K¡t With High-K Stress Relief

lnstructions for Wire Shielded Gable


7.0 Prepare Cable
7 .1 Check to be sure cable size fits within kit range as shown in Table l. (For Use \\'nh Compression Lugs or
Connectors), or Table 2 (For Use With 3M Mechanical Shearbolt Lugs QL2 Series: Ts o Hole r.

7.2 Prepare cable using dimensions shown in Figure 8 and Figure 9. BE SURE TO ALLO\\ FOR DEPTH OF
TERMINAL LUG OR CONNECTOR.
7.3 If using a Crimp Type (Compression) lug, measure the depth of the banel. or if usirg a Cnmp T]pe rCLrmpression)
connector, measure to the barrel center stop/midpoint, and see the NOTE belo*. and Table J. cr¡ncernine -\luminum
Lug and Connector growth allowances, in order to calculate the Insulation Remor al Len5:.. Ta¡:e 5 rlor-ated in the
final pages of this Instruction document) can used to assist in calculating the total Jacket Rem.rr al Len$h uhen using
a compression lug or connector.

If using 3M Shearbolt Lugs QL2 Series: Two Hole, or 3M Mechanical Shearbolt Connector QCI Series.
proceed to Step 7.4.

NOTE: Provide additional exposed conductor distance to account for growth during crimping of aLL YI\ L'.V lugs or
conneclors as .follows :

Aluminum Lug
2-350 400 - 650 750-1 000 1250 - 2C00
and Gonnector
Growth Allowance
1/4" (6 mm) 1/2" (13 mm) 31 i19 mml Freld 0etermined

Table 4

NOTE: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one lo¡'en
There should not be any remaining black areas, or particles, on the cable insulotion loyen

Jacket Removal Length

lnsulation Removal Length = Depth 0f Compression Lug or Connector +


+ Growth Allowance 0R lnsulat¡on Cutback dimension ftom
Shearbolt Lug or Connector lnstructions

9" (229 mm)

3" (76 mm)

Coflductü
-

Cable Jacket

Figure 8

-\-\ I l-:- jr'q!-Á R¿\ G


3M'" Cold Shrink QT-lll Silicone Rubber lndoor Tubular Termination K¡t W¡th High-K Stress Relief

7.4 lf using 3M Mechanical Shearb,'.: ---, . -l Series: Two Hole, or 3M Mechanical Shearbolt Connector QCI Series,
refer to the Instructions that are 'r: - ,.; - . : ' : S hearbolt product for the Insulation Cutback length for the specific
Shearbolt Lug or Connector bein= ,...- ..: . a iLocated in the finai pages of this Instruction document) can used to
assist in calculating the total Jaci,e. ?.;:- , Length when using 3M Shearbolt Lugs QL2 Series: Two Hole, or 3M
Shearbolt Connector QCI Series

1 .5 Bend leading 1- 1/2" (3 8 mm) of e \po!3 r .' : -.r n ires back upon themselves to jacket edge (Figure 9).

3" (76 mm)

1-112" (38 mm) I -112" (38 mm)

Figure 9

8.0 lnstall Ground Braid


E.1 Select a Scotch! Mastic Strip 2230 fiom kit ani :emove white release liners. Using iight tension apply a SINGLE
\\'RAP of mastic around the cable jackei I 1' L. ::rm) fiom cut edge (Figure 10). Cut ofT excess.

i t- 1/4"(6 mnr)

'lst Scotch@ Mastic Strip 2230 - SINGLE WRAP

'10
Figure

8.2 Position pre-flormed ground braid with short tail or er wire shield directly adjacent to cable jacket cut edge. PLEASE
ITIOTE: The ground braid needs to make full conta.'t rvith the shield wires. Position long tail of ground braid,
extending over cable jacket with solder block or er mastic strip (Figure 1 1). Secure ground braid to cable jacket
4-112" (114 mm) from catrle semi-con edge using vin¡-l tape (see NOTE and Figure ll).

NOTE: Position vinyl tape with care, it ctlso serves as a marker for positioning the termination,

78-8 I I 3-5099-6 Rev G


3M'" Cold Shrink QT-lll Silicone Rubber lndoor Tubular Termination K¡t W¡th High-K Süess Relief

4-1t2" (114 mml- -l

ffil
I

ffit
n${i
nffifl I

Sem¡-Con Edge

Shield Wire

Ground Braid

Cable Jacket Edge

Solder Block

1st Scotch@ Mastic Strip 2230 - SINGIE WRAP

V¡nyl Tape Marker

Figure 11

8.3 Wrap ground braid around cable shield wires one complete wrap, trim e\üess eI approrimatelv a 45 degree angle,
and line up with the pre-bent 45 degree angle already on the ground braid. to pre\ ent overlap. Secure in place with
constant force spring. Wrap spring in same direction as ground braid tFigure 1l l. Cinch (tighten) the spring after
wrapping the final winding.

8.4 Select second Scotch@ Mastic Strip 2230 from kit and remove white release liners. -{pply' a second SINGLE WRAP
of mastic over solder block on ground braid and previously applied mastic tFigure 12). Cut offexcess.

Constant Force Spring

Shield Wires

Ground Braid
'I
st Scotch@ Mastic Strip 2230 - SINGLE I¡JMP

Solder Block

2nd Scotch@ Mastic Sfip 2230 - Slt{GLE WRAP

Ground Braid Leg

Figure 12

l0 78-8113-5099-6 Rev G
3M'" Gold Shrink QT-lll Silicone Rubber lndoor Tubular Termination K¡t W¡th High-K Stress Relief

8.5 Wraptwohighlystretchedhali-la¡:=: j.-:s,-rielectricalgradevinyltapearoundmasticseal,constantforcespringand


exposed shield wires (Figure 13 t

NOTE: Take csre not to cover exposed senti-Ltit1 insulotion shield. A minimam of 1" (25 mm) must be exposed.

NOTE: DO NOT complefely cover tlte ground braid x'ith electrical grode vinyl tape when applying over the Scotch|
Mastic Strip 2230 per Step 8.5. LEAI'E.1 rf I\lltL rI OF 1/4" (6 MM) OF EXPOSED GROL:l,lD BRAID between the
Wnyl Tape Marker applied in step 8.2 and tlte s¡art of the two half-lapped layers of electrical grade vinyl tupe covering
the Scotch'DMastic Strip 22j0 appliecl in Step 6.5.

SPECIAL NOTE FOR CLOTH OR PAPER SEITI-CO.\ INS(ILATION SHIELD


In cables with cloth or paper semi-conductire slti¿lds, il is recommended the shield be over-wrapped with one
half-lapped layer of highly strefched semi-conducrite rubber tape, such as Scotchu Electrical Semi-Conducting Tape 13.

Ground Braid (Must Lea',: 'i ' - -- of 1/4" (6 MM) Exposed. See Note Under Step 8.5.)

1-.1/2,, (38 mm)

-]-
Semi-Con (Note: A minimum of 1" (25 mm) must be exposed. See N0TE under 8,5.)

'- Shield Wires

Curtant Force Spring

Two Highly Stretched Half-Lapped Layers of Electrical Grade Vinyl Tape

Scoiche Mastic Strip 2230

Vinyl Tape Marker

Figure 13

9.0 lnstall Lug or Connector


Important Packaging Notice
In order to make sure that you receive an undamaged tenlination, this 3M Cold Shrink QT-III Silicone Rubber Termination
is packed with a RED SHIPPING CORE inside of the u'hite core. Please remove the red shipping core BEFORE you install
the termination. This shipping core can be recycled with other polypropylene waste.
9.1 Check to insure 3M Cold Shrink QT-I[ Silicone Rubber Termination assembly fits over the selected Iug
or connector BEFORE installing the lug or connector. If lug or connector (Figure 14) will not fit through the
termination core, clean the insulation (per Step 10.0) and slide termination on cabie before installing lug. DO NOT
REMOVE CORE AT THIS TIME.

Clearance

Figure 14

78-8113-5099-6 Rev G
3M'" Cold Shrink 0T-lll Silicone Rubber lndoor Tubular Termination K¡t W¡th High-K Sbess Relief

9.2 For 3M Compression Lugs and 3M Stem Connectors:


a. Refer to the hnal pages of this instruction document for 3M Connector and Lu,s ,-nmpin: rntbrmation.
b. ForAluminum Conductors - Thoroughly wire brush conductor strands to remore ¡i-::::um oride layer. lnsert
conductor into lug or connector and then remove conductor. This will transfer SoÍ1e r¡i:he antloxidant paste onto the
conductor. Wire brush the antioxidant paste into the strands. Immediately inserr ctrd;;tor into lug or connector barrel
as far as it will go.

NOTE: Die/crimper head rotation between consecutive crimps is RECOMIIE\DED.

c. Position connector or lug and crimp according to manufacturer's directions. Ren.r--,,,3 3\.3ss .rride inhibitor and
sharp crimp flashings following crimping.

9.3 For 3M Mechanical Shearbolt Lugs QL2 Series: Two Hole or 3M Mechanical Sh¡::::,,: C¡,lier-¡or QCI Series:
a. Refer to the Instructions that are packed with the Shearbolt product for the r:s:¿,.":r.': ¡:¡;edu¡e s.

10.0 CIean Cable lnsulation and Lug or Connector Barrel Using Standard Practice
10.1 If abrasive must be used:
a. Use on insulation only. DO NOT USE ABRASM ON SEMI-CO\ [\SLL{TIO\ SHIELD:
b. Use only aluminum oxide abrasive; grit 120 or finer, included in the ,i\f C:r-: Cieaninu Preparation Kit CC-2.
c. Be careful not to reduce the cable insulation diameter below that allou ed r\ ::e \1i.

10.2 Wipe the cable insulation with one of the solvent saturated pads from the :\f C::l; Cleanin_u Preparation Kit CC-2,
or other approved cable cleaner/solvent, AND ALLOW IT TO DRY BEFORE I\ST-{LL[\G TER\IINATION.
A clean lint-free cloth, or inexpensive paper towel, can be used to dry the ::su13rrc,n sudace rf ai¡ dn ine time is of
concern. DO NOTALLOW SOLVENT TO TOUCH SEMI-CON I-\SL L{TIO\ SHIELD:

11.0 lnstall Termination


11.1 Slide the termination body onto the cable and remove core. Make sure the ierninatron bodr (not the core) is butted
up to the edge of the vinyl tape marker previously applied in Step 8.1 iFrg;re 15 r. Puil the core r.rhile unwinding.
counterclockwise, starting with the loose end (Figure 15). Be sure to alrern¿te the pulling and unu-inding actions
(pull-unwind-pu1l-unwind-etc.) to help prevent the core material from bindrng up as the core is being removed.

NOTE: Once the termination body makes confact over the mastic seal area, there is no need to continue supporting the
assembly. DO NOT PUSH OR PULL ON THE TERMINATIOI{ ASSEIIBLI-I|HILE ¿'.\ II7-\DL\G THE CORE.

Cou¡ie.::.:,:,,, sa

Vinyl Tape Marker NoTE: The material being removec :: f s s:E: s r rec
(Applied in Step 8.2) oolvmers and can be recvcled. /\
LJ
Figure i 5

11.2 Connect ground braid to system ground according to standard practice

12 78-ti113-5099-6 Rev G
3M'" Cold Shrink 0T-lll Silicone Rubber lndmr Tubular Termination K¡t W¡th High-K Stress Relief

Correct lnstallation of Termination on Wire Shielded Cable

--*
:a
Ridge at End of Cable
lnsulation Shield (Semi-Con)
Ridge at EnC
of High-K Tube

EnvironmenhlTop
Seal

High-K Stress
Relief Tube

lnstructions for UniShield' Cable


12.0 Prepare Cable
as shown in Table I (For Use With Compression Lugs or
12.1 Check to be sure cable size fits within kit range
Connectors), or Table 2 (For Use With 3M Nfechanical Shearbolt Lugs QL2 Series: Two Hole).

12.2 Prepare cable using dimensions shown in Figures 16,17 ard 18. BE SURE TO ALLOW FOR DEPTH OF
TERMINAL LUG OR CONNECTOR.

12,3 lf using a Crimp Type (Compression) lug, measure the depth of the barrel, or if using a Crimp Type (Compression)
connector, measure to the barrel center stop/midpoint, and see the NOTE below, and Table 5, concerning Aluminum
Lug and Connector growth allowances, in order to calculate the Insulation Removal Length. Table l0 (located in the
final pages of this Instruction document) can used to assist in calculating the total Jacket Removal Length when using
a compression lug or connector.

If using 3M Shearbolt Lugs QL2 Series: Two Hole, or 3M Mechanical Shearbolt Connector QCI Series,
proceed to Step 12.5.

12.4 Install constant force spring as shown in Figure 16. Pull shield wires through semi-conductive jacket to leading edge
ofconstant lorce spring (Figure l6).

ltrOTE: Provide additional exposed conductor distance fo accounf for growth during crimping of ALUMIIITLIM lugs
or connectors as follows:

Aluminum Lug
and Gonnector
2-350 400 - 650 750-1000 1250 - 2000
1/4" (6 mm) 1/2" (13 mm) 3/4" (19 mm) Field determined
Growth Allowance

Table 5

78-8113-5099-6 Rev G i3
rryr uoro bnnnK 0T-lll Silicone Rubber lndoor Tubular Termination Kit With High-K Stress Relief

lnsulation Removal Length = Depth 0f Compression Lug or Conneütor


+ Growth Allowance 0R lnsulation Cutback dimension from
Shearboli Lug or Connector lnstructions

7-112" (191 mm)

Semi-Conductr,;¿ -.: . ..
Constant Force Spring

Shield Wires

Figure 't6

12.5 If using 3M Mechanical Shearbolt Lugs QL2 Series: Two Hole, or 3M Mechanical Shearbolt Connector QCI Series,
refer to the Instructions that are packed with the Shearbolt product for the Inzulation Cutback lengh for the specific
Shearbolt Lug or Connector being used. Table I I (located in the final pages of üis Instn¡ction document) can used to
assist in calculating the total Semi-Conductive Jacket Removal Length when usirg 3M Shearbolt Lugs QL2 Series:
Two Hole, or 3M Shearbolt Connector QCI Series.
12.6 Remove constant force spring. Bend shield wires back upon semi-conductir-e jacket l-112" (38 mm). Cut excess
shield wire and discard (Figure l7).

lnsulation Removal Length = Depth 0f Compressbn Lug 0r


+ Growth Allowance 0R lnsulation Cutback d¡mension from
Shearbolt Lug or Connector Instructions

9" (229 mm)

1-112" (38 mm)

Semi-Conductive Jackei

Shield Wires Bent Back Over Semi-Conductive Jacket

Figure 17
12.7 Remove semi-conductive jacket to dimension shou'n in Figure 18.
NOTE: To ease jackel removal, install constant force spring as shown in Figure I I and ring-cut 80% through jacket.
Remove jacket sections by pulling against constant force spring. DO MT BELL SEI[I-CO\ JACKET! Remove
constantforce spring.

NOTE: It is imperative to remove all remnsnts of the semi-condactive jacket, even if the semi-conductive jacket comes
off as one layen There should not be any rentoining black areas, or particles, on ¡he cable insulation layen

14 78-8 I 1 3-5099-6 Rev G


3M'" Cold Shrink 0T-lll Silicone Rubber lndoor Tubular Termination K¡t W¡th High-K Stress Relief

-.- ::¡:n Removal Length = Depth 0f Compression Lug or Connector


- j':,',1¡ Ailowance 0R lnsulation Cutback dimension from
: -.:':0tt Lug or Connector lnstructions

6" (152 mm)

1-112" (38 mm)

Semi-Conductive Jacket

Cut Line

Constant Force Spring

S^reld W¡res Bent Back over Semi-Conductive Jacket

Figure 18

13.0 Install Ground Braid


13.l Select a Scotch6 Mastic Strip 2230 from kit and remove white release liners. Using light tension apply a SINGLE
WRAP of mastic around the cable semi-conductive jacket ll4" (6 mm) from shield wires (Figure l9). Cut
off excess.

-i f* rr+'to m'r

Semi-Conductive Jacket

Shield Wires Bent Back over Semi-Conductive Jacket

1st Scotch@ Masüc Strip 2230 - S¡I{GLE l¡lrRAP

Figure
'!9

13.2 Position pre-formed ground braid with short tail directly over cut edge of folded back shield wires. PLEASE NOTE:
The ground braid needs to make fu1l contact with the shield wires. Position long tail of ground braid, extending over
cable semi-conductive jacket with solder block over mastic strip (Figure 20). Secure ground braid to cable semi-
conductive jacket 4-112" (114 mm) from cable Semi-Conductive Jacket edge using vinyl tape (See NOTE and
Figure 20).
NOTE: Position vinyl tape with care, it also serves as a marker for positioning the terminution.

78-8113-5099-6 Rev G 15
3M'" Gold Shrink 0T-lll Silicone Rubber lndoor Tubular Termination K¡t With High-K Stress Relief

¡ --- - 4-1 t2" (114 nn)


f,Áf,f,¡
,^^Á^
AAAÁ¿
'AAAA
AAÁA/
.AAAA
,1AAÁ/

trAÁA/
AAÁA¡
ÁAAAJ
YYYY!

Semi-Conductive Jackei ::..


Shield Wire

Ground Braid

Solder Block

l st Scotch'a lvlastic Sirip 2230 - SINGLE WRAP

Vinyl Tape Marker


-
Figure 20
13.3 Wrap ground braid around cable shield *'ires one complete wrap, trim excess at approximateh a i.,< ;eJee ansle.
and line up with the pre-bent 45 degree angle already on the ground brard. to prevent orrerlap. Secure rn place s'ith
constant force spring. Wrap spring in same direction as ground braid (Figure l1). Cinch (tighten)the sprinu after
wrapping the final winding.

13.4 Select second Scotch" Mastic Strip 2230 from kit and remove white release Liners. Apply' a second S[\-GLE WRAP
of mastic over solder block on ground braid and previously applied mastlc (Figure I1 ). Cut otT ercess.

Constant Force Spring

Shield Wires

Ground Braid

1st Scotch@ Mastic Strip 2230 - SINGLE WRAP

Solder Block

2nd Scotcho lvlastic SÍip 2230 - SINGLE WRAP

Figure 21

13.5 Wrap two highly stretched half--lapped i¡rers olelectrical grade vinyl tape ar..,-:.J ::r,.-s:rc seal. constant force spring
and exposed shield wires (Figure il r.

I,{OTE: Take care nol to cover exposed Setni-Cottductive Jacket. A minimum oJ' 1 " l) 5 mm ) m u\t be exposed.

NOTE: DO NOT completel_v cover Íhe grLturrd braid with electrical grade viry:l fape *'hen applring oter the Scofch'ú
Mastic Strip 2230 per Step 13.5. LE.1l E 1 III\I\IL'M OF l/4" (6 MM)OF EXPOSED GRO| \ D BR 4ID between the
Wnyl Tape Marker applied in step 13.) and tlte sÍart oJ'the two half-lappetl layers of electrical grade rintl tape covering
the Scofch'q Mastic Strip 2230 applied irt Srep 13.5.

16 78-E I 1 3-5099-6 Rev G


3M'" Cold Shrink QT-lll Silicone Rubber lndoor Tubular Termination K¡t W¡th High-K Stress Relief

Grourc 3'a: \'-.: -:are [4inimum of114" (6 MM) Exposed. See Note UnderStep 13.5.)

1-'112" (38 mm)


|-
--
Semi-Conductive Jacket (NOTE: A minimum of 1" (25 mm) must be exposed.)

Shield Wires

i:nstant Force Spring


-,r: - ghly Stretched Halllapped Layers of Electrical Grade Vinyl Tape
- i
Sc¡::. Mastic Strip 2230

Vinyl Tape [,larker

Figure22

14.0 lnstall Lug or Connector


Important Packaging Noüce
In order to make sure that you receive an undamaged termination, this 3M Cold Shrink QT-III Silicone Rubber Termination
is packed with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install
the termination. This shipping core can be recycled with other polypropylene waste.

14.1 Check to insure 3M Cold Shrink QT -m Silicone Rubber Termination fits over the selected lug or connector
BEFORE installing the lug or connector. If lug or connector (Figure 23) will not fit through the termination core,
clean the insulation (per Step 15.0) and slide termination on cable before installing lug or connector. DO NOT
REMOVE CORE AT THIS TIME.

Figure 23

14.2 For 3M Compression Lugs and 3M Stem Connectors:


a. Refer to the final pages of this Instruction document for 3M Connector and Lug crimping information.
b. For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. lnsert
conductor into lug or connector and then remove conductor. This will transfer some of the antioxidant paste onto the
conductor. Wire brush the antioxidant paste into the strands. Immediateiy insert conductor into lug or connector barrel
as far as it will go.

NOTE: Die/crimper head rotation between consecutive crimps is Recommended.

c. Position connector or lug and crimp according to manufacturer's directions. Remove excess oxide inhibitor and
sharp crimp flashings following crimping.

14.3 For 3M Mechanical Shearbolt Lugs QL2 Series: Two Hole or 3M Mechanical Shearbolt Connector QCI Series:
a. Refer to the Instructions that are packed ivith the Shearbolt product for the installation procedures.

78-8 I I 3-5099-6 Rev G 1-


3M'" Gold Shrink 0T-lll Silicone Rubber lndoor Tubular Termination K¡t W¡th High-K Stress Relief

15.0 Clean Cable lnsulation and Lug or Connector Barrel Using Standard Practice
15.1 If abrasive must be used:
a. Use on insulation only. DO NOT USE ABRASM ON SEMI-CON INSULATIOI{ SHIELD!
b. Use only aluminum oxide abrasive; grit 120 or finer, included in the 3M Cable Cleaning Preparation Kif CC-2.
c. Be careful not to reduce the cable insulation diameter below that allowed by the kit-

15.2 Wipe the cable insulation with one of the solvent saturated pads from the 3M Cable Cleaning Preparation Kit CC-2,
or other approved cable cleaner/solvent, AND ALLOW IT TO DRY BEFORE niST^{LLDiG TER}IIiATION.
A clean lint-free cloth, or inexpensive paper towel, can be used to dry the insulation surface if air dry-ing time is of
concern. DO NOTALLOW SOLVENT TO TOUCH SEMI-CON INSULATIO\ SHTFLD!

16.0 lnstall Termination


16.l Slide the termination body onto the cable and remove core. Make sure the termination bo{ tnot the core) is butted
up to the edge of the vinyl tape marker previously applied in Step 13.2 (Figue l4). hrll üe core while unwinding,
counterclockwise, starting with the loose end (Figure 24).Be sure to altemate the pulling and uo*inding actions
(pu11-unwind-pull-unwind-etc.) to help prevent the core material from binding rry as the co¡e is being removed.

NOTE: Once the terminalion body makes contact over the mastic seal area, the¡e is no need to confinue supporting the
assembly. DO NOT PaSH OR PULL ON THE TERMINATION ASSEMBLY frHILE LTTWINDING THE CORE.

UUU .: - -.'.,::

llt
lll
Vinyl Tape Marker I'I0TE: The material being remoyed at th¡s step is mixed
(Applied in Step 13.2) polymers and can be recycled, D
LJ

Figure 24

16.2 Connect ground braid to system ground according to standard practice.

Correct lnstallation of Termination on UníShield@ Shielded Cable

tll
ttt lllr
lllr
--;l
-d-Jl
-l

Vinyl Tape
Marker
Ridge at End of Cable
lnsulation Shield (Semi-Con)

8ic,q: a: :-:
cr ! !-'' --:=

Environmental Top
Seal

H¡gh-K Stress
Rel¡ef Tube

l8 78-8 I I 3-5099-6 Rev G


3M'" Cold Shrink QT-lll Silicone Rubber lndoor Tubular Termination K¡t With High-K Stress Relief

Jacket Renror a! f,.¡lculation Tahle - Tape Shield C¿tbte


- C'rimp 1r pe tCornpression) Lugs / Connectors -
7622-T-118,7622-T-110(L).'óli-T-11ü.1{tz$-'f-fiA,7625-T-1tr{t.7625-T-lll}{L),7526-T-ll0
mm
CABLE PREPARAIION ITEM }IOTES
-Add this column-

Insulation Length 229 mm Value from Figure 1

Insulation Remc¡val Length -


Depth ol'Crimp T),pe
Measure full ciepth of bore for lugs and to
(Compression) Terminal Lug or' + +
the center stop lor connectors.
Connector Barrel
(Sec NOTES column.)
Growth Allowance
See Table 3 for correct growth allowance.
(Aluminum Only) for Crimp
Type (Compression) Lug / + +
This measurement applies only to
Connector
Aluminum lugs / connectors.
(See NOTES column.)

TOTAL JACKET REMOVAL


LENGTH
Table 6

Jacket Removal Calculation Table - Tape Shield Cable


- 3MrM Mechanical Shearbolt QL2 Series Lugs l3MrM Mechanical Shearbolt Connectors QCI Series -
7622-T-llQ,7§:22-T-tl0(L\,7623-T-110,7624-T-110,7625-T-119,7625-T-ll0(L),7626-"1-110
lnches mm
CABLE PREPARATION ITEI\4 NOTES
-Add this column- -Add this column-

Insulation Lengfh 9.0" 229 mm Value from Figure I

Obtain Insulation Removal Length:

Insulation Removal Length : For Mechanical Shearbolt Lugs see


Depth of Mechanical Shearbolt 3MrM Mechanical Shearbolt Lugs QL2
QL2 Series Terminal Lug or QCI + Series: Two Hole lnstructions.
Series Connector Barrel
(See NOTES column.) For Mechanical Shearbolt Connectors
see 3MrM Mechanical Shearbolt
Connectors QCI Series Instructions.

TOTAL JACKET REMOVAL


LENGTH
Table 7

78-8113-5099-6 Rev G 19
3M'" Cold Shrink QT-lll Silicone Rubber lndoor Tubular Termination K¡t W¡ttr High-K Stress Relief

Tooling lndex
Lug and Grimprns lnfurmation for 3M'" ScotchloK" Copper Lugs

30014 thru 30045 31036 thru 31068


One hole 0ne hole-long barrel
I

3M*
Cable Stud
ScotchloK'
Size AWG/ Size
Copper Lug
kcmil. (inJ
Number
MD6

10 3001 4
6 1t4
5¡6
3001 5
3001 6
l-.,b u5cRT(1 )
I n,,u, (1)

10 3001 I
4 1/4 3001 I W]6l11r 4A!'/Gi 1i A4CRIl) u4cRT(1 )
30021

114 30022
2 5t16 30023 wr62i2) |
I

znwelrr A2cc' u2cRT(2, :,, :. .' z,


3/8 30024

5n6 30027
1 lAWG(1) Al CB(1) ulcRT(2)
318 30028

110
5/1 6
3/8
30031
30032
w163(2) 1/o(r) | nzsnlrr u25RT(1 ) (1)

2/0
318 30036 w241(2\ 2t0(1) M6R(r) u26RT(2) :::^2 45(1)
] tli
3/B 31 036 w241(3) 2/a?l A26R(2) u26RT(3) l.-..3 15¡2t (2)

112 30041 w243(2\ 3/0(1 ) A27R(1 ) u27RI(2) Jul l) (2)


3/0
1/2 31 041 w243(3) 3/0(2) A27R(21 u27RT(3) 50(2) (3)

1/2 30045 BG(3) 4i0(1 ) l)2BRrQ' Purprer2r ] eurpler2r I S+n1Z¡ \¿)


4t0 112 31 045 BG(4) 4t0(2\ A2BR(2) U28RT(3) | Purple(3)| Rurplel3) | 54H(3) (3)
1t2 31145 BG(4) 410\2) U2BRT13' r .3rs,Jr P¡rple 3 5.1H,3t (3)

112
250
112 áii+é 1w166(4) 1250(2) IMeR(2)
u29RT(3) ': ,,, 4 aa ! (2)

1t2 31 053
300 A30R(2) DtJ (Jl
1t2 3'l 153 '/.-tJ .

112 31 056
350 431 R(2) U31 RTt3r ;a: l 71H(4)
1t2 3l156

1t2 31 060
400
1/2 3t160
A32R(2) U32RT13I - Bluer4r l76H{4)

1t2 31066 I I I

500 5/B 31067 I - | - lns+n1z¡ u34RT(3) l.- - ¡


87H(4)
112 31166 I I

1t2 31 068
600 u36RT(3)
1t2 Jt tttó

Y39, Y45.
750 112 31172 Y46
u39RT(5)

Y45:
s44RT(6)
1 000 1t2 31178
Y46:
P44RT(6)

" Y45 and Y46 accept all Y35 d¡es ("[J sE:..
**
Anderson VC6-3 and VC6-FT requ re -.
:.

22 78-8113-5099-6 Rev G
3M'" Cold Shrink QT-lll Silicone Rubber lndoor Tubular Termination K¡t With High-K Stress Relief

Tooling lndex
Lug and Grimping lnfurmation for 3M" ScotchloK" Gopper/Aluminum Lugs

40016 thru 40079


40132 thru 40'178
One hole
) Two hole

g Tool-l lie Sets IMinimu m Numb er 0f Gri


C'
É¡
2

=o'=
§:ti:4. L_ .. .§;;§
,a:.lt!.t.i!:il

NE
utg
g
o
1r,
E

EE
0-
r:ltal§,lriat
t§t:i§:
l'-'Itgi ffit§w
§§§§
w& ffiffi#*
€t
G Ch =J
(5 o,, Ya4A
..lrfilflt
6 5ñ6 4001 6 w]6r(1) 6AWG(1) A6CAB( 1 ) .a::!-- (r) Grey(l) Grey(1) 2s(r) (1) BYl e(3) J(3)

4 5/ th 4A020 w162(3) 4AWG(1) A4CAB(1) U4CABTIl I (1) Green(2) Green{2) 37i1) (1) BY53(3) P(3)

3/8 40024 wr6s(3) 2AWG(1) A2CAB(1 ) t-Lir (1) Pink(2) P¡nk(2) 42H(2\ (r) BY23(3) 1t2(3)
2
112 40025 w163(3) 2AWG(1) A2CAB(1 ) t2!;3- l (r) Pink(2) Pink(2) 42H(2\ (1) BY2s(3) 112(3)

3t8 40028 1.4/163(3) lAwG(1) A1 CAR(] ) lJl CABTTT r (1) Gold(2) Gold(2) 45(1) {1) BY23(3) 1t2\3\
1
1/? 40029 \,\l163{3) lAWG(1) A1 CAR(1 ) U1 CART': r (1) Gold(2) Gold{2) 45ír ) (1) BY23(3) 1t213)

J/O 40432 w241(3) 1/0(1) 425AR(1 ) u2sARI(1) (1) Tan{2) Tan(2) 50(1 ) (r) BY25(3) 5/8*1 (3)
1t0 112 40033 w241(3) r/o(1) A2sAR(1) u25ART(1) (r) Tan(2) Tan(2) 50(1 ) (1) BY2s(3) 5/B-1 (3)
40132 \¡i241(3) r/0(r) A25AR(1 U2sART(1) (1) Tan(2) Tan(2) 50(1 ) (t) BY2s(3) 5/B-r (3)
)

1t2 40037 BG(4) 210l1l A26AR(2) U26ABTr2l (1) 0live(2) 0live(2) s4H(2) (:2\ BY31 C(3) 5/8-1 (3)
2t0
1t2 40137 BG(4) 2t011\ A26AR(2) U26ARTr2i (r) 0live(2) 0l¡ve(2) 54H(2) (2) BY31 C(s) 518-1 (3)

112 40041 w166(4) 3/o(1) A27AR\z) ü27ARTt,2) (1) Ruby(2) Ruby(2) 60(2) (2) 737(3)
30
1/2 401 41 w]66(4) 3/0(1 ) A27AR(z) u27ARr(2) (1) Ruby(2) Ruby(2) 6o(2) \2¡ 73713)

1t2 40045 w660(4) 4t0 {2J A2BAR(2) u28ARr(2) (1) White(4) 66(4) 12\ BY35C(4) 840(4)
4t0 5/8 40046 w660(4) 4t0 \2\ A2SAR(2) u28ARI{2) (1) Wh¡te(4) 66(4) (2) BYssC(4) 840(4)
1t2 401 45 w660(4) 4tB \2) A2BAR(2) u28ART(2) (1) White(4) 66(4) (2) 8Y35C(4) 840(4)

1t2 40049 w249(3) A29AR(2) u2gARr(2) (1) 71H\4) 71H(2) (3)


250 40050 w24s(3) A29AR(2) u29ARr(2) (1) 71n$) 71H(2) (3)

112 401 49 w24S(3) A29AR(2) u29ART(2) (1) 71 H(4) 71H12) (3)

1t2 40053 A3oAR(2) u30ART(2) (r) 76H(4) 76H(21 (3)


300
112 401 53 A3OAR(2) us0ART(2) (1) 76H(4) 76H12) (3)

112 40056 u31 ARr(2) (1) 87H(4) B7H(3) (3)


350 5/8 40057 u31 ARr(2) (1) 87H(4) 87H(3) (3)
112 401 56 u3lART(2) 0) 87H{4) 87H(3) (3)

400 1t2 401m u32ART(4) (1) e4H(4) 94H(4) (2)

5/8 40067 u34ARr(4) (1) 06H(4) 06H(3)


500
1 1
\2\
112 401 66 u34ART(4) (1) 1 06H(4) 1 06H(3) 12)

600 40170 u36AfiT(4) (t) 1 1 5H(3) (3)

750
5/8 40073 u39ART(4) t) 1 25H(4) (3)
1t2 40172 u39ART(4) (1) 1 25H(4) (3)

5/8 4007s S44ART(4) (1i 140H(4) (3)


1 000
1t2 40178 S44AHT(4) (1) 140H(4) (3)

- Y45 and Y46 accept all Y35 dies ("U" series). For Y45 use PT651 5 adapter. For Y46 use pUADp adapter.
-. Anderson VC6-3, VC6-FI, VCBC and Burndy Y1 000 require no die set.

78-8 1 1 3-5099-6 Rev G 1)


3M'" Cold Shrink 0T-lll Silicone nubber lndaor Tubuiar Termination Kit W¡th High-K Stress Relief

Tooling lndex
Crimping lnformation for
3M." Stem Connectors
Copper/Aluminum

Br'- l- BG(4) W24r (3)

Kearny 5/B-1 (4)


2,1 1,1/0 sc0001
4 2 sc0002 T&B Tan(2)

1/0 2/0 sc001 0


0live(2), Ian(2)

Anderson

B.'- l;, w249(3)


210 3/0 (ean:y ir 3l U :l 840(5)
3/0 4t0
4/0 T&B TBN,I 8 Redí.i)

Anderson t'2)

-
Y45 and Y46 accept all Y35 dies ("U" series). For Y45 use PT651 5 adapter. F0r ¡-r6 -.:e ?UADP adapter.
.. Anderson VC6 s dieless and does not require a die set.

3M Scotch and Scotchlok are trademarks of 3M Company

UniShield rs a trademark of General Cable Techno ogres Corporation,

lmpoñant Notice
All statements, technical information, and recommendat ons related to 3N{ s products are based on nformation be ieved to be reirab e
but the accuracy or completeness is not guaranteed, Before r.rsing this product, you must evaluate t and determine if it is su tal¡ e for
your intended application. You assume all risks and liab it], assoc ated with such use, Any staiements related to the product which are not
contained in 3M's current publications, or any contrary staiements contained 0n your purchase order shall have no force or effect unless
expressly agreed upon, in writing, by an authorized oif cer :f 3\,1

Warranty; Limited Remedy; Limited Liability.


This product will be free from defects in materia ai: '-:^:facture at the time of purchase 3M MAKES N0 0THER WARRANTIES
INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
lf this product is defective within the r,,;aTTan[ :,:':]
:.:..3:r above, your exclusive remedy shai be a. :i,' s .:.l:
.: "ac ace or reoa,r ihe
3M product or refund the purchase prce oÍ i.= i',' :--:-:i Except where prohibited by law,3M will not be liable for any direct,
indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory
asserted.

Electrical Markets Division


6801 River Place Blvd.
Austin, TX 78726-9000
800.245.3573 Please Rerycle. Printed in USA.
Fax 800.245.0329 O 3M 2018. All Righb Reserved.
www.3M.com/electr¡cal 7B-B113-5099-6 Rev G

You might also like