‘When the speed controller power supply is switched on, the power units, as well as a certain number of control components are
connected to the mains supply ; contact with these parts is extremely dangerous,
‘After disconnecting the ALTIVAR from the mains voltage, wait § minutes before carrying out any operation inside the controller.
This period corresponds to the time constant for the discharge of the capacitors. The + and — terminals (or PA and PB on the 45
10 110 kW speed controllers) are also connected to the potential of the capacitors.
During operation, the motor can be stopped by cancelling the run command or the speed reference, while the speed controller
remains energized. untimely restarting needs to be prevented for personnel safety reasons, this electronic nteriockis inadequate,
Provision must be made for the disconnection of the power circuit.
NOTE,
‘The speed controller includes safety devicos which, in the event of a fault, can trigger the stopping of the controller, and hence:
the motor. The motor itself can also be subjectto stoppage by mochanical jamming. Finally, votage fluctuations and power supoly
failures in particular, can also cause the motor to stop,
‘The disappearance of the fault causing the stoppage can initiate a restart involving a hazard for certain types of machines or
installations, especially those which must conform to specific safely regulations.
{tis important that in such cases the user should take appropriate stops to prevent such restarting possiblities. For example, by
the use of an underspeed detector, causing the disconnection of the speed controller power supply in the event of a non-
programmed motor stoppage.
‘As ageneral rule, the speed controller power supply must always be switched off before carrying out any operation on either the
slectrical or the mechanical parts of the installation or the machine.
¥
Power Drive Service Ltd. www.inverter.co.uk +44(1942) 260206Contents
GENERAL INFORMATION
PRELIMINARY CHECKS.
DESIGN AND OPERATION
ALTIVAR 1,110 22KW Technology
Functional block dagram
Description of functions
ALTIVAR 4510 110KW Technology
Funetional block dagram
Description of functions
TECHNICAL CHARACTERISTICS
INSTALLATION
ALTIVAR 1,1 1022 KW Dimonsions - Weights
Cimatic environment
Mounting precautions
‘Mounting in general purpose metal enclosure
‘Mounting in dust and damp protecting metal enclosure
ALTIVAR 450 110 KW Dimensions - Weights
Giimatic environment
Mounting precautions
‘Speed controler vontiation
Mounting in general purpose metal enctosure
Mounting in dust and damp protecting metal enclosure
CONNECTIONS:
‘ALTIVAR 1.11022 KW Terminal sips
Recommended creuit diagram
ALTIVAR 4510 110 KW Terminal stipe
Recommended circuit diagram
Alternative circuit diagram
Recommendations
Thermal protection of the motor
Function ofthe contol inputs
Usiisation of tho control inputs
Function ofthe speed setpoint inputs
Usiisaion of the speed set-point inputs
Stator frequency display
Wiring precautions
RECOMMENDATIONS FOR USE OF THE MOTOR/SPEED CONTROLLER COMBINATION
‘Available torque
‘Association with diferent motors
Motor instalation
‘Adaplation tothe driven machino
‘Adaptation to tho mains supply
‘Automatic restarting
FRostaring while running
INTIAL SETTING UP_
Layout of he setting contols
Modification of the sotings
‘OPERATIONAL ASSISTANCE
Using the dialogue panot
Operational and setting parameter codes
— _ 2.
Power Drive Service Ltd. www.inverter.co.uk +44(1942) 260206