SF6 GAS-INSULATED
METAL-ENCLOSED SWITCHGEAR

72.5kV~126kV Single-phase-enclosure type GIS

Xian Electric Import & Export Co.,Ltd.


A Member of China Xian Electric Group
China Xian Electric Group ( XD for short ):

XD is the largest base for manufacturing complete sets of ultra-high voltage AC transmission
and transformation equipment in China.

XD is the largest base for manufacturing complete sets of ultra-high voltage DC transmission
and transformation equipment in China.

XD is the largest base for researching and developing complete sets of ultra-high voltage AC
& DC transmission and transformation equipment in China , and is appointed by the state as
the national profession center responsible for the quality supervision, examination and test.

XD is the largest base for exporting complete sets of ultra-high voltage AC & DC transmission
and transformation equipment in China.
Main Products

 126kV /72.5kV Single-phase-enclosure type GIS 1


126kV/72.5kV GIS

The product is a compact GIS designed for system voltages up to 126kV and for rated
short-circuit currents up to 31.5kA. The circuit breaker is operated by a spring operating
mechanism which is used for three pole operation.
FEATURES

1 Compact design
It is one of the most compact designs of single phase enclosure GIS in the world. The width of a typical bay
is 1200mm or 1500mm. The inner conductors and enclosures are made of corrosion-resistant aluminum. A
bay with double busbar weights approx. 2,500 kg.

2 Superior interrupting capability


The circuit breaker is equipped with self-energized interrupter that is characterized by a self-adapting ability
breaking of both small and large currents.
These breakers can cope with all known switching phenomena. Their efficiently designed interrupter clears
both the severe rate of rise of the recovery voltage of short-line faults and the high recovery voltage peak of
out-of-phase interruption. In magnetizing current switching, the overvoltage is less than twice the applied
voltage. No restrike or reignition occurs in charging current switching.

3 Reduced maintenance work


Since the spring operating mechanism requires neither compressed air nor hydraulic fluid, inspection and
maintenance work is minimized. Also, these breakers seldom require inspection since SF6 gas deterioration
and arcing contact wear, owing to arc breaking, are negligible.

4 Perfect assembling and testing conditions and minimum work at site


The GIS is assembled and tested against similar conditions of assembling site, packed in transport unit after
tested, for easy and convenient transport and minimizing work at site.

5 Lower leakage of SF6 gas


The mode of separated monitoring is used in the SF6 gas system of GIS, doing away with SF6 valves and SF6
piping system. New self-sealed adapters and SF6 gas densimeters are used to get rid of the possibility of SF6
leakage outside the GIS, lowering the SF6 gas leakage.

STRUCTION

In the GIS all elements are single phase enclosure except the main bus which is three phase enclosure. The
enclosure is coaxial with the inner conductor supported by the insulators or spacers. Tulip contactors are
used to adjoin the inner conductors together. Cable sealing end or SF6 outdoor bushing can be used to
connect GIS with overhead lines or transformers.
The auxiliary electrical units required for command input, warning, locking, SF6 density monitoring etc are
accommodated in local control panel of each bay.

=N O
Key


1 CB Circuit breaker

3 
2 DS Disconnector ( isolator )
4
2 
3 ES Earthing ( grounding ) switch
3 
4 CT Current transformer
2 2
7 3 
5 LA Lightning Arrestor

6 PT Voltage ( potential) transformer

7 LCP Local contring mechanism
11 11

8 CSE Cable-sealing-end chamber

9 BSG Bushing

10 GCB Gas Circuit breaker
Double-Busbar Scheme (Bushing inlet/outlet) 
11 M1-M2 Main busbar

2 2
4 4
3 3
2 2 8 2
7 3 3
7

11 11 11

Double-Busbar Scheme (Cable inlet/outlet) Single-Busbar Scheme

STANDARD BAYS

At present, the design and production of the GIS have been performed according to the special properties of
program and standard function units and bays, accomplishing the standard and modular design and production.
Several typical standard bays are shown below.
1 InIet or Outlet bay

Single-Busbar Scheme

BSG
ES
DS
CT ES
DS
850

DS ES
GCB ES
CT
ES
LCP CB

ES
1575

DS
M
AM

BUS
120

520 915

ES BSG
DS
CT
DS ES
850

ES DS
GCB
ES
LCP ES CT

CB
1575

M ES
DS
AM

BUS
120

520 915

DS CSE
CT ES
DS
ES
850

ES
DS
GCB CSE
ES CT ES
LCP
CB
1575

M DS
ES
AM
120

BUS
520 915

=P Q
Double-Busbar Scheme

BSG

ES
DS
ES
CT DS

ES
850

GCB DS ES
DS CT

ES
CB
LCP
ES
DS
1575

DS
M1 M2
AM BUS1

BUS2
120

520 915 769

CSE
DS
CT ES
850

ES
GCB DS DS ES DS
CSE
ES ES
CT
LCP

CB
1575

M1 M2 ES
AM DS
DS
BUS1
120

BUS2
520 915 769 1368

Bridge-Type Scheme

BSG
ES
DS ES DS
CT ES
LA DS
850

GCB DS ES
ES CT
ES
DS LA
LCP CB
1575

ES
M DS

AM

BUS
120

520 915 1995 619


ES
ES
DS BSG
DS

ES DS ES
ES

ES ES
2028

PT
PT

M BUS
120

2 Busbar connection bay

ES

CT ES
DS
850

DS
GCB ES
CT
ES

LCP CB
1575

ES
M1 M2 DS

AM
BUS1
120

520 BUS2
915 769

3 Measurement and protection bay

ES ES CT
ES

DS DS
ES ES

DS
ES ES
LA
LA LA PT DS
LA
BUS1
PT
M1 M2
PT PT
BUS2

520 1220 769 1220 619

=R S
TYPICAL LAYOUT

1 Single-Busbar Sectional Scheme

BSG BSG CSE

CSE BSG BSG


DS ES DS ES DS ES
DS
DS ES DS ES DS ES
ES ES ES ES ES
CT CT CT ES
CT ES ES ES ES ES
CT CT CT
CB CB CB
CB DS
ES ES ES CB CB CB
DS DS DS ES DS
DS LA ES ES ES
DS DS DS
PT LA
BUS1
BUS2 PT

7500

1500

1500

1500 1500 1500 1500 1500 1500

10500
2 Bridge-Type Scheme

BSG BSG
ES DS ES DS
DS ES DS ES
LA LA
ES ES
CT CT

CB CB
ES ES
DS DS
DS CT CB DS

ES ES

ES DS ES ES DS ES

ES DS ES DS
PT PT

BSG BSG

7000

1500 500 1500 1500 1500 500 1500

12000

=T U
3 Double-Busbar Sectional Scheme

BSG CSE CSE CSE CSE BSG

DS
DS ES DS ES DS ES DS ES DS ES DS ES
ES ES ES ES
ES
ES ES ES CT ES ES ES
CT CT CT DS DS CT CT CT
CB
CB ES CB ES CB ES CB ES CB ES CB ES
ES
LA LA DS
DS DS DS DS DS DS DS DS DS DS DS DS

PT PT BUS1

BUS2

10500

1500 1500 1500 1500 1500 1500 1500 1500


RATINGS

Main Technical Data for 72.5kV~126kV GIS ( Based on IEC )

Ratings
Item Remarks
72.5kV 126kV

Installaton Indoor or outdoor

Ambient temperature  -30~40

Humidity (per month) %  95 At 25


Applied ambient
Height above sea level m 1000
conditions
Wind velocity m/s  35

Horizontal acceleration: 0.4 Accelerated


Earthquake intensity g
Vertical acceleration: 0.2 simultaneously
3.2 Calculated to
Creepage distance cm/kV
rated voltage

Rated voltage kV 72.5 126

Rated current A 1250/1600/2000

Rated short-time withstand current (3s) kA 31.5

Peak withstand current kA 80

General data Lightning impulse withstand voltage(peak) kV 325 550

Power frequency withstand voltage(r.m.s) kV 140 230 1 min

MPa CB: 0.5


Rated SF6 gas pressure(exclusive of CB) 20
Other unit: 0.45
Annual leakage rate of SF6 gas % 1

Rated current A 1250/1600/2000

Rated breaking current kA 31.5

Rated short-time withstand current (3s) kA 31.5

Peak withstand current kA 80

Full breaking time ms  60


Circuit breaker
Rated operating duty O-0.3s-CO-180s-CO

First-pole-clean factor 1.5

Operating mechanism Spring

==V NM
Ratings
Item Unit Remarks
72.5kV 126kV

Operating time Open: 8;


s
Close: 8
Disconnector
Operating mechanism Motor/Motor spring

Open: 8;
Operating time s Close: 8
Earthing switch Motor spring for FES;
Operating mechanism
Manual or Motor for ES

Rated current A 1250/1600/2000

Type of enclosure 3 phases in 1 enclosure


Busbar
Material enclosure Al.

Material conductor Al.

Rated current ratio 300-500-750-1000-1250-1500-2000/5

Current transformer Capacitive VA 20/30/40/50


Measurement: 0.5;
Accuracy
Protection: 5P20

Rated primary voltage kV 72.5/ 3 126/ 3

Rated secondary voltage V 100/ 3


Voltage transformer

Voltage of remaining voltage winding V 100

Rated burden VA 100~150

Type Metal oxide-zinc

Rated voltage of LA kV 42 73

DC 1mA, reference voltage kV  128  145

Lightning arrester Max, lightning impulse residual voltage(peak)(8/20us) kV ==== 235  260