Professional Documents
Culture Documents
: 2250-0758
International Journal of Engineering and Management Research
Available at: www.ijemr.net
Page Number: 109-115
ABSTRACT
Regarding the power system large wind farms are greatly
affected stability and control issues. So it requires a deep
study to overcome this potential problems and it requires
advanced control and compensating devices to avoid &
recover large disturbances this paper involve the use of Static
Synchronous Compensator (STATCOM) for stabilizing the
grid voltage after grid-side disturbances such as a three phase
short circuit fault, temporary trip of a wind turbine and
sudden load changes. These will help to maintain and
regulate the proper voltage. The DC voltage at individual
wind turbine (WT) inverters is also stabilized to facilitate
continuous operation of wind turbines during disturbances.
I. INTRODUCTION
Figure 1: Line diagram of STATCOM
STATCOM is basically a voltage source 1.1 Features of STATCOM
converter, VSC that converts a dc voltage at its input • A STATCOM has both turn-on and turn-off
terminals into three-phase ac voltages at fundamental control capability (IGBTs).
frequency of controlled magnitude and phase angle. VSCs
• It generates an output ac voltage from a dc
use pulse width modulation, PWM, technology, which
voltage.
makes it capable of providing high quality ac output
• The ac voltage is controllable both in magnitude
voltage to the grid or even to a passive load (Uzunovic,
and phase angle.
2001). STATCOM provides shunt compensation in a
Flexible Alternating Current Transmission
similar way as SVC but utilizes a voltage source converter
Systems (FACTS) devices, namely STATIC synchronous
rather shunt capacitors and reactors (Machowski, 1997).
Compensator (STATCOM), Static Synchronous Series
The basic principle of operation of a STATCOM is the
Compensator (SSSC) and Unified Power Flow Controller
generation of a controllable AC voltage source behind a
(UPFC), are used to control the power flow through an
transformer leakage reactance by a voltage source
converter connected to a DC capacitor. The voltage electrical transmission line connecting various generators
and loads at its sending and receiving ends. FACTS
difference across the reactance produces active and
devices consist of a solid-state voltage source inverter with
reactive power exchanges between the STATCOM and the
several Gate Turn off (GTO) thyristor switch-based valves
power system (Wang and Li, 2000). The effect of
and a DC link capacitor, a magnetic circuit, and a
stabilizing controls on STATCOM controllers have been
controller. The quality of AC waveforms generated by the
investigated also in several recent reporting (Wang and Li,
FACTS devices depends on the valves and the various
2000), (Wang, 1999).
configuration magnetic circuits. The inverter configuration
used in this paper can be utilized to build a voltage source
inverter.
109
II. SYSTEM MODELLING We will compare it with the equal area criterion to
match the relative transient stability with and without a
2.1 TWO MACHINE SYSTEM WITH MIDPOINT dynamic shunt compensator. First consider a case without
DYNAMIC COMPENSATOR compensation.
For the symmetrical system shown in the figure 2, Assume that a fault occurs between circuit
the doubling is shown by the increase in the p/δ curve from breaker a and b in figure 2 and is cleared by a and b circuit
a to b in figure 3. Without the compensator, curve a is breakers. Curve-1 in figure 3 shows the pre fault transient
given by the equation; power angle curve which has a maximum of
Curves shown are during the fault. A curve 3
P= result after the faulted line section is removed and differs
Where E is now the “emf behind transient from curve 1 is that X l is replaced by 3 . E’ is
reactance” (E’) of the two the generators and X1 is the assumed constant through the first swing period. If there is
total series reactance, equal to the sum of the line and no compensator, the system can, in principle, be pre loaded
transformer reactance (which are assumes identical). The to the transient stability power limit P 1 for the prescribed
effect of shunt capacitance is ignored. With an ideal fault, such that the available decelerating energy A 2 just
compensator that holds the midpoint voltage constant at balances the accelerating energyA 1. In practice, the power
the value ‘E’ the power angle curve b is obtained according level would be somewhat less than this, to provide a
to the equation; stability margin.
113
4.3 Analysis of model This time constant depends primarily on the power system
i) STATCOM Dynamic Response strength at bus B2 and on the programmed Vac Regulator
gains of the STATCOM. To see the impact of the regulator
gains, multiply the two gains of the Vac Regulator Gains
by two and rerun the simulation. You should observe a
much faster response with a small overshoot.
Looking at the Vm and Vref signals, you can see
that the STATCOM does not operate as a perfect voltage
regulator ( Vm does not follow exactly the reference
voltage Vref). This is due to the regulator droop (regulating
slope) of 0.03 pu. For a given maximum
capacitive/inductive range, this droop is used to extend the
linear operating range of the STATCOM and also to ensure
automatic load sharing with other voltage compensators (if
any). Set the droop parameter to 0 and the voltage
Figure 10: V ref signal (dotted lines) along with the regulator gains back to 5 (Kp) and 1000 (Ki). If you then
measured positive-sequence voltage vm at the STATCOM run a simulation, you will see that the measured voltage
We will now verify the dynamic response of our Vm now follows perfectly the reference voltage Vref.
model. Open the STATCOM dialog box and select
"Display Control parameters". Verify that the "Mode of ii) Comparison between STATCOM & SVC under fault
operation" is set to "Voltage regulation" and that "External condition
control of reference voltage Vref" is selected. Also, the
"droop" parameter should be set to 0.03 and the "Vac
Regulator Gains" to 5 (proportional gain Kp) and 1000
(integral gain Ki). Close the STATCOM dialog block and
open the "Step Vref" block (the red timer block connected
to the "Vref" input of the STATCOM). This block should
be programmed to modify the reference voltage Vref as
follows: Initially Vref is set to 1 pu; at t=0.2 s, Vref is
decreased to 0.97 pu; then at t=0.4 s, Vref is increased to
1.03; and finally at 0.6 s, Vref is set back to 1 pu. Also,
make sure that the fault breaker at bus B1will not operate Figure 12: Measured voltage Vm on both systems
during the simulation (the parameters "Switching of phase
A, B and C" should not be selected). We will now compare our STATCOM model with
a SVC model having the same rating (+/- 100 MVA). If
you double-click on the "SVC Power System" (the
magenta block), you will see a SVC connected to a power
grid similar to the power grid on which our STATCOM is
connected. A remote fault will be simulated on both
systems using a fault breaker in series with fault
impedance. The value of the fault impedance has been
programmed to produce 30% voltage sag at bus B2.Before
running the simulation; you will first disable the "Step
Vref" block by multiplying the time vector by 100. You
will then program the fault breaker by selecting the
Figure 11: The reactive power Q m absorbed (positive parameters "Switching of phase A, B and C" and verify
value) or generated (negative value) by the STATCOM that the breaker is programmed (look at the "Transition
Run the simulation and look at the times" parameter) to operate at t=0.2 s for a duration of 10
"VQ_STATCOM" scope. The first graph displays the Vref cycles. Check also that the fault breaker inside the "SVC
signal (magenta trace) along with the measured positive- Power System" has the same parameters. Finally, set the
sequence voltage Vm at the STATCOM bus (yellow trace). STATCOM droop back to its original value (0.03 pu).
The second graph displays the reactive power Qm (yellow
trace) absorbed (positive value) or generated (negative
value) by the STATCOM. The signal Qref (magenta trace)
is not relevant to our simulation because the STATCOM is
in "Voltage regulation" and not in "Var Control".
Looking at the Qm signal we can determine that
the closed-loop time constant of the system is about 20 ms.
114
[3] Reactive power control in electric systems by Timothy
J.E. Miller.
[4] Hingorani, N.G. and L. Gyugyi, 1999. “Understanding
FACTS”, IEEE Press, New York.
[5] Macho ski, J., 1997. “Power System Dynamics and
Stability”, John Wiley & Sons.
[6] Hamad, A.E., 1986. “Analysis of Power System
Stability Enhamsement by Static VAr Compensators”,
IEEE Transactions on power Systems, 1(4): 222-227.
[7] M. Sajedihir, Y. Hoseinpoor , P.Mosadegh Ardabili, T.
Pirazadeh., 2011. “Analysis and Simulation of a
STATCOM for Midpoint Voltage Regulation of
Transmission Lines”, Australian Journal of Basic and
Figure 13: The measured reactive power Qm generated by Applied Sciences, 5(10): 1157-1163.
the SVC and the STATCOM
Run the simulation and look at the "SVC vs
STATCOM" scope. The first graph displays the measured
voltage Vm on both systems (magenta trace for the SVC).
The second graph displays the measured reactive power
Qm generated by the SVC (magenta trace) and the
STATCOM (yellow trace). During the 10-cycle fault, a key
difference between the SVC and the STATCOM can be
observed. The reactive power generated by the SVC is -
0.48 pu and the reactive power generated by the
STATCOM is -0.71 pu. We can then see that the maximum
capacitive power generated by a SVC is proportional to the
square of the system voltage (constant susceptance) while
the maximum capacitive power generated by a STATCOM
decreases linearly with voltage decrease (constant current).
This ability to provide more capacitive power during a
fault is one important advantage of the STATCOM over
the SVC. In addition, the STATCOM will normally exhibit
a faster response than the SVC because with the voltage-
sourced converter, the STATCOM has no delay associated
with the thyristor firing (in the order of 4 ms for a SVC).
V. CONCLUSION
In this Paper, We observed the voltage can be
500 KV transmission Line at Mid-point which can be used
in the industrial lines as well as interconnected power grid
network of transmission Lines. We have compared the
output and performance of SVC and STATCOM with
respect to the analytical and Simulation studies. So, from
the output characteristic of SVC and STATCOM. We can
conclude that both these devices improve the behavior of
power system under the transient voltage condition by
using MATLAB based modeling and simulation.
REFERENCES
[1] Zhou, E.Z., 1993. “Application of static VAR
compensators to Increase Power System Damping”,
IEEE Transactions on power system, 8(2):655-661.
[2] Wang, H.F. and F. Li, 2000. “Design of STATCOM
Multivariable Sampled Regulator”, Int. conf. on
Electric Utility Deregulation and power Tech, City
University, London.
115
Copyright © 2011-14. Vandana Publications. All Rights Reserved.