You are on page 1of 32

FIRE DETECTION SYSTEM

Fire Alarm System is designed to provide warning Alarm to the outbreak of fire
so that appropriate fire fighting action could be taken before the situation gets
out of control.

There are two primary functions of fire alarm system.

1. Detect fire or fire condition


2. Give alarm in all parts of the Areas
Design, Arrangements and Installation

The design, arrangements and installation of the automatic fire detection and
alarm system are to comply with Chapter 9 of the IMO FSS Code as well as any
additional or more requirements in 4-7-3/11 of the ABS Steel Vessel Rules or in
5-2-5/1.1 of the ABS MODU Rules.

FSS Code" means the International Code for Fire Safety Systems.

.
Fire Detection Indicating Location. The fire detection main indicator is to be at a manned
control station and is to be clearly to indicate where fire has been detected.

• Control and monitor input signals from all connected Sensors ,alarms and manual call
points. (FSS Code Chapter 9 2.1.2/1)

• Provide output signals to the navigation bridge, continuously manned central control
station or onboard safety center to notify the crew of fire and fault conditions.
(FSS Code Chapter 9 2.1.2/2)
• Monitor power supplies and circuits necessary for the operation of the system
for loss of power and fault conditions . (FSS Code Chapter 9 2.1.2/3)

• The system may be arranged with output signals to other fire safety systems
which includes. (FSS Code Chapter 9 2.1.2/4)

Paging systems, Public address systems ,General Alarm.

Fan stops ,fire doors ,fire dampers.


Sources of power supply as per standards.
It should not less than two sources of power supply Main & Emergency for Fire
Detection System. (FSS Code Chapter 9 2.2/2.2.1)

Cables in the circuits shall be flame retardant. (FSS Code Chapter 9 2.3.3)

Installation Requirements:

A Loop/section of fire detectors which covers a control station, Bridge or


accommodation space shall not include with machinery space area of category A.
(FSS Code Chapter 9 2.4.1.2)
Positioning of detectors
• Positioning of detectors as per (FSS Code Chapter 9 2.4.2)

• Detectors shall be located for optimum performance.

• Positions near beams and ventilation ducts, or other positions where


air flow could affect performance, this should be avoided.

• Detectors shall be located on the overhead at a minimum distance of


0.5 m away from bulkheads.

• One manually operated call point is to be located at each exit.


Accommodation and Service Spaces (MODU Part 5)

An automatic fire detection and alarm system is to be provided in all accommodation


and service spaces.

Accommodation space is to be fitted with smoke detectors. Thermal detectors are to


be fitted in galleys.

Smoke detectors are to be provided in all electrical rooms and control stations.

Flame or thermal detectors are to be installed in open drilling and/or mud processing
areas.

Smoke detectors may be used in enclosed mud processing areas.

Manually Operated Alarm System

Sufficient manual fire alarm stations are to be installed throughout the


accommodation spaces, service spaces, and control stations. One manually operated
call point is to be located at each exit.
.
Visual and audible fire Alarm
• The activation of any Detector or MCP shall initiate a
visual and audible alarm signal at the FDS control
panel and indicating units. If the signals have not been
acknowledged within 2 min, an audible fire alarm shall
be automatically sounded throughout the crew
accommodation control stations and machinery
spaces. Those alarm are not an integral part of system
(Ref. FSS Code Ch. 9.2.5.1.1)

• Clear information shall be displayed about the spaces


covered and the location of the sections at FDS panel.
If addressable system exact location to be display.
MODEL : SALWICO CCP

Salwico CCP System is Multi Loop


Addressable Fire Detection System
The Salwico CCP Comprises :

• Control/Repeater M4.3 ( For Manage and Supervise the system)

• Loop MX (connect addressable detector loop)

• I/O M70 (For conventional zone and Programmable I/O Module)

• I/0 M700 (For Alarms and Programmable I/O Module)

• Relay M 8, (Programmable relay contacts)

• Bus Con M10/20 (for Communication )

• Charger M (for power to the system and battery charger)

• PSU M AC/DC 5A (Power supply Module AC/DC)


An example of a system block diagram
The Control/Repeater Panel M 4.3 is a control panel with a 4.3" graphical color
display used to manage and supervise a system.
It can mounts on any flat surface independently . It is equipped with
communication buses for connecting to the system, and it provides the
following features:
Alarm buzzer
• LED status indicators
• Backbone Bus Interface
• Ethernet connection
• RS-422/RS-485 interface
• RS-232/RS-485 interface
• Three USB interfaces
• Two configurable powered I/Os
• Two programmable relay
outputs
1. Main indicators
2. Status
3. Menu
4. Navigation & Command Key
5. Display
6. Alarm Buttons
1. Main indicators
Fire alarm: Indicates existence of a fire alarm and gives direct access to the Fire alarm
list.
Indications: Flashing red light An un-muted fire alarm in the system.
Steady red light All fire alarms are muted.

Pre-Alarm: The Pre-Alarm indicates existence of a pre-alarm and gives direct access to
the Pre-Alarm list.
Indications: Flashing orange light An un-muted pre-alarm in the system.
Steady orange light All pre-alarms are muted.

Fault : Indicates existence of a fault and gives direct access to the Fault alarm list.
Indications: Flashing yellow light An un-muted fault in the system.
Steady yellow light All faults are muted.
Disablements : Indicates existence of a disablement and activates the disablements menu.
Indications: Steady yellow light At least one disabled function in the system.

Shortcut : Activates the customer specific shortcut list.


Indications: Steady orange light.
The alternatives in the shortcut list and the corresponding indicators.
(Shortcut 1, Shortcut 2 and Shortcut 3) are programmed via the definition program.

2.Status
This button gives direct access to the System status summary list with Alarms
(Fire and Pre-Alarms), Maintenance (Faults and Warnings) and Disablements
(Active and Periodic).

3. Menu
This button gives direct access to the main menu and all system functions.

4. Navigation and Command Keys


The arrow keys are used to navigate menus, select different menu alternatives,
and show details for list items.

ESC
The Escape button is used to go to the top menu screen.
OK : This button is used to select a menu alternative or to accept a function. The OK
button is also in some cases used to show details for a selected list entry.

5. Display : It has a backlisted 4.3" graphical screen, 480×272, 16-bit color


screen.

6. Alarm buttons

Multiple alarms
Press this button to scroll through the different alarms. The list always returns to
the first fire alarm after 30 seconds of inactivity.

Reset
This green button is used to reset a selected alarm, fault or disablement.

Mute
This red button is used to mute (acknowledge) and silence alarms.
The following information is displayed in the Control Panel:
• Number of alarm(s)
• First, last and current list entry
• Zone in alarm
• Type of unit in alarm
• Address number of unit in alarm (only for addressable loop)
• Supplementary text (if defined in system configuration)
The system has a special test mode function which makes the testing easier.
When a zone is in test mode:

• External alarm devices and controls are by default not activated in case of a fire.

• LED indicators on loop units begin to blink.

• Each tested loop unit will indicate activation by its LED indicator.

• If a printer is connected to the system, alarms will automatically be printed as a


result of the tested units.
Test the Control Panel Display
With the function Test display it is possible to test:
• The display
• All indications on the control panel
1 To test the control panel display, use: Menu > 5 Settings > 4 Test display.
Smoke Detectors Test
Use suitable test equipment, available at your authorized dealer
Recommended: Aerosal /Smoke Capsule (Solo/Testifier)
Spray test gas on the detector for 0.5 seconds. Wait 10 seconds. Check if the alarm has been
activated if not Spray the detector for 1 second and the detector will be activated.
Heat Detectors Test
Use suitable test equipment, available at your authorized dealer
Recommended: Testifier Heat kit

To test the heat detector, apply heat to the sensing element.


If other test equipment is used, for example, a heating gun, do not over-heat the detector by
holding the heat-source too close to the detector. This could damage the detector.

Flame Detectors Test


Danger!
Cigarette lighter should not be used for testing in explosive areas.
Test flame detectors using a test lamp.
Test for Cable Break
Measure the resistance between the + and - poles. Connect an ohm meter between
the + poles. The measured value should be less then 185 Ohm.

Measure and repeat the procedure for the - poles.

Test for Short Circuits


Measure the resistance between the + pole and the - pole. Connect an ohm-meter
between the two poles The measured value should be more than 100 KOhm.

Test for Earth Failure


Measure between the + and - pole and earth to detect an earth fault. Connect the
ohm meter between the + pole and earth. The measured value should be more than
50 kOhm. Values below 8 kOhm (±2 kOhm) will be indicated as earth fault.

Measure and repeat the procedure for the - pole.


.
Address the Units Modules or Field Devices.

Loop units with address switches


On units with a DIP switch, the address is set using the 8 pole DIP switch located
on each addressable unit as shown in the following figure. The DIP switch values
follow the binary system.

Loop units without address switches


Programming Tool, page 22.
For addressable units without a DIP switch, the address is set with the address
programming tool EV-AD.
I/O M 70
Operating voltage range 19-30 VDC
Max. current per channel 70 mA
Max. total current 0.6 A
ELR fire zones 10 kΩ
ELR input 30 k Ω
Operating temperature range -5°C to +55°C

General Description
I/O M 70 provides eight programmable I/O 70
channels, each individual channel can be configured as either:
• Programmable Inputs
• Programmable Outputs max 70mA for buzzers, relays etc
• Conventional detector zones

• The module is identified by a physical address on the Backbone


Bus. The address is set with an 8-pole DIP switch.

• The DIP switch value follows the binary system. The address no.
can be set from 1 to 126 using DIP-switch poles 1 to 7.

• When the DIP-switch pole 8 is set to On, outputs no. 5-8 are
constantly active as long as the module is powered.
I/O M 700

Operating voltage range 19-30 VDC


Current consumption (at 24 V) 17 mA
Max. output current per channel 700 mA
Max. total current 4,0 A
ELR input 30 kΩ (optional)
Operating temperature range -5°C to +55°C
Weight (with housing) 130g

I/O M 700 provides eight programmable I/O 700 channels, used for either:
• Programmable Inputs
• Outputs max 700mA for magnets, power supply etc.
Use the I/O M 700 as an input module, or use it to monitor, control, and/or
supply units such as alarm devices, magnets. It also can provide constant power
supply to other system modules such as Control and Repeater Panels etc.

The module is identified by a physical address on the


Backbone Bus. The address is set with an 8-pole DIP switch.

The DIP switch value follows the binary system. The


address no. can be set from 1 to 126 using DIP-switch poles
1 to 7.

When the DIP-switch pole 8 is set to On, outputs no. 5-8


are constantly active as long as the module is powered
LOOP MX
The module is identified by a physical address on
the Backbone Bus. The address is set with an 8-pole
DIP switch.
Loop M X enables the connection of one
addressable detector loop.

Operating voltage range 19-30 VDC


Max no. of loop units 254
Relay M 8 provides eight programmable relay contacts.

Each of these relay contacts provide a potential free change-over


contact.

Use to control units such as sirens, magnets, flashlight, alarms and


ventilation fans.

The module is identified by a physical address on the Backbone Bus.


The address is set with an 8-pole DIP switch.
PSU M AC/DC 5A

Input voltage AC 85 – 264 V


Frequency range AC 45 – 65 Hz
Output voltage 24 V DC
Output voltage range 18 – 29,5 V
Working current 5 A

Charger M H
Charger M provides power to the system through the
Backbone Bus and charge the battery.

The DIP switch value follows the binary system.


The address no. can be set from 1 to 126 using the
DIP-switch pole 1 to 7.
Fire Detection System Field Devices:

1.Smoke Detector
2.Heat Detector
3.Flame Detector
4.Manual Call Points
5.Audio Visual Alarm
6.Timers
Smoke detectors
1. Photoelectric Smoke Detector.

Photoelectric light smoke detectors employ a light source and a


light sensitive device. When smoke particles block the light
beam, the light sensitive device identifies the reduction in light
and its Respond.

2. Ionization Smoke Detector

Ionization-type smoke detector have a small amount of


radioactive material between two electrically charged plates,
which ionizes the air and causes current to flow between the
plates. When smoke enters the chamber, it disrupts the flow of
ions, thus reducing the flow of current and activating the alarm.
Heat detectors
1. Fixed temp type heat detector

This is the most common type of heat detector. Fixed


temperature detectors operate when the heat
sensitive reaches the set point

2. Rate-of-Rise type heat detector

Rate-of-Rise (ROR) heat detectors operate on a rapid rise in


element temperature increase per minute. This type of heat
detector can operate at a lower temperature fire condition
than would be possible if the threshold were fixed.
Flame detectors

1. Ultraviolet light (UV)

The combustion flames of most carbon-based fuels emit


sufficient UV radiation to enable the UV flame detector to
prove the presence of a flame in a combustion chamber.

2. Infrared (IR)

Infrared flame sensors are designed to work within


the infrared spectral band. A certain hot gasses will emit
patterns in the infrared region, which can then be analyzed
using a specialized thermal imaging camera.
THANK YOU

You might also like