DSE7310/20 ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY

AUTO START & AUTO MAINS FAILURE BS EN 61000-6-2


EMC Generic Immunity Standard for
the Industrial Environment
CONTROL MODULES BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
FEATURES
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment

The DSE7310 is an Auto Start The DSE7320 will also monitor the The extensive list of features TEMPERATURE
Control Module and the DSE7320 is mains (utility) supply. The modules includes enhanced event and BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
an Auto Mains (Utility) Failure include USB, RS232 and RS485 performance monitoring, remote BS EN 60068-2-2
Control Module suitable for a wide ports as well as dedicated DSENet® communications and dual mutual Bb/Be Dry Heat +70 oC
variety of single, diesel or gas, terminals for system expansion. standby (DSE7310 only) to reduce VIBRATION
gen-set applications. engine wear. BS EN 60068-2-6
Both modules are compatible with Ten sweeps in each of three
major axes
Monitoring an extensive number of electronic (CAN) and non-electronic The modules can be easily 5 Hz to 8 Hz @ +/-7.5 mm,
engine parameters, the modules will (magnetic pick-up/alternator configured using the DSE 8 Hz to 500 Hz @ 2 gn
display warnings, shutdown and sensing) engines and offer an Configuration Suite PC software. HUMIDITY
engine status information on the extensive number of flexible inputs, Selected front panel editing is also BS EN 60068-2-30
back-lit LCD screen, illuminated outputs and extensive engine available. Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
LEDs, remote PC and via SMS text protections so the system can be BS EN 60068-2-78
alerts (with external modem). easily adapted to meet the most Cab Damp Heat Static 40 oC
demanding industry requirements. @ 93% RH 48 Hours

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
MODEM MODBUS PC
DSE2130
DSE2157
DSE2548 8 4 4
DSE2510/20
232 485

DSENET® RS232 AND USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER


EXPANSION RS485 PORT INPUTS SENDERS STOP SUPPLY 8-35V

DEUTZ
DSE7310/20 ISUZU
PERKINS
CATERPILLAR
7 MTU
VOLVO
OTHER
CUMMINS
SCANIA

MAINS (UTILITY) N/C VOLT FREE N/O VOLT GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
SENSING OUTPUT FREE OUTPUT ALTERNATOR OUTPUTS ENGINES &
DSE7320 ONLY (Flexible with CAN) MAGNETIC PICK-UP

VOLTS CURRENT VOLTS


D+
W/L +

1ph 1 1 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E N
N

ISSUE 6
®

DSEGenset

DSE7310/20 SPECIFICATION

DC SUPPLY

AUTO START & AUTO MAINS FAILURE CONTINUOUS VOLTAGE RATING


8 V to 35 V Continuous

CONTROL MODULES CRANKING DROPOUTS


Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
FEATURES supply recovers to 5 V. This is achieved
without the need for internal batteries.
DSE7320 LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT


340 mA at 12 V, 160 mA at 24 V
DSE7310 MAXIMUM STANDBY CURRENT
160 mA at 12 V, 80 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

MAINS (UTILITY) DSE7320 ONLY


VOLTAGE RANGE
15 V - 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage

KEY FEATURES • kW overload protection • DSENet® expansion compatible OUTPUT B (START)


15 A DC at supply voltage
• 4-Line back-lit LCD text display • Reverse power protection • Integral PLC editor
• Five key menu navigation • Power monitoring (kW h, kV Ar, OUTPUTS C & D
• Front panel editing with PIN kV A h, kV Ar h) KEY BENEFITS 8 A 250 V (Volt free)

protection • Load switching (load shedding • 132 x 64 pixel ratio display for AUXILIARY OUTPUTS E,F,G,H
• LED and LCD alarm indication and dummy load outputs) clarity 2 A DC at supply voltage
• Customisable status screens • Automatic load transfer (DSE7320) • Real-time clock provides
GENERATOR
• Power save mode • Unbalanced load protection accurate event logging VOLTAGE RANGE
• Support for up to three remote • Independent Earth Fault trip • Multiple date and time scheduler 15 V - 333 V AC (L-N)
display units • True dual mutual standby with • Set maintenance periods can
FREQUENCY RANGE
• 9 configurable inputs load balancing timer (DSE7310 be configured to maintain 3.5 Hz to 75 Hz
• 8 configurable outputs only) optimum engine performance
• Flexible sender inputs • USB connectivity • Ethernet communications (via MAGNETIC PICK UP
VOLTAGE RANGE
• Configurable timers and alarms • Backed up real time clock DSE860/865 modules), provides +/- 0.5 V to 70 V
• 3 configurable maintenance • Fully configurable via DSE advanced remote monitoring at
alarms Configuration Suite PC software low cost FREQUENCY RANGE
10,000 Hz (max)
• Multiple date and time scheduler • Configurable display languages • Modules can be integrated into
• Configurable event log (250) • Remote SCADA monitoring via building management systems DIMENSIONS
• Control logic facilities DSE Configuration Suite PC (BMS) OVERALL
240 mm x 181 mm x 42 mm
• Easy access diagnostic page software • Increased input and output 9.4” x 7.1” x 1.6”
• CAN and Magnetic Pick-up/Alt. • User selectable RS232 and expansion capability via DSENet®
sensing RS485 communications • Licence-free PC software PANEL CUT-OUT
220 mm x 160 mm
• Fuel usage monitor and low fuel • Configurable Gencomm pages • IP65 rating (with supplied 8.7” x 6.3”
alarms • Advanced SMS messaging gasket) offers increased
• Charge alternator failure alarm (additional external modem resistance to water ingress MAXIMUM PANEL THICKNESS
8 mm
• Manual speed control (on required) • PLC editor allows user 0.3”
compatible CAN engines) • Start & stop capability via SMS configurable functions to meet
• Manual fuel pump control messaging specific application
• Engine exerciser • Additional display screens to requirements
• “Protections disabled” feature help with modem diagnostics

RELATED MATERIALS
TITLE PART NO’S
DSE7310 Installation Instructions 053-028
DSE7320 Installation Instructions 053-029
DSE7200/7300 Quick Start Guide 057-101
DSE7200/7300 Operator Manual 057-074
DSE7200/7300 Configuration Suite PC Manual 057-077

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-051/10/11 (8)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457

You might also like