You are on page 1of 3

KW/ton = 12 / EER

KW/ton = 12 / (COP x 3.412)


COP = EER / 3.412
COP = 12 / (KW/ton) / 3.412
EER = 12 / KW/ton
EER = COP x 3.412
If a chillers efficiency is rated at 1 KW/ton,

COP = 3.5
EER = 12
VJAP BC Roy Hospital

Make DB DB

Type of Chiller WC WC

Chiller TR - operating 306.6 303.8

Power consumtion 211.5 187.8

KW/TR 0.6898239 0.6181698486

EER 17.395745 19.4121405751

COP 5.0849882 5.6744053128

IPLV (or NPLV) = 0.01A+0.42B+0.45C+0.12D

A = COP or EER @ 100% Load

B = COP or EER @ 75% Load

C = COP or EER @ 50% Load

D = COP or EER @ 25% Load


IIT - BBSR IIT - KGP RPSG GMCH

DB DB DB DB

WC WC WC WC

277.8 378.3 230.3

168.9 253.8 151.6

0.6079913607 0.6708961142 0.6582718194

19.7371225577 17.8865248227 18.2295514512

5.7694015077 5.482 5.228449232 5.3287200968


Durgapur
BFHC CFSL Airport CCCL Marut

DB DB Daikin DB

WC WC WC AC

198.67 177.8 167.4 125.6

136.11 113.7 106.19 141.8

0.6851059546 0.6394825647 0.634348865 1.1289809

17.5155389024 18.765171504 18.9170355 10.629055

5.1200055254 5.4852883671 5.529680065 3.1070023