You are on page 1of 5

24 Fire safety

Meeting NFPA standards for


flame, smoke and gas detection
F ire is one of the most critical hazards
in any built environment, and
industrial processes and facilities that
is the NFPA (National Fire Protection
Association), including NFPA 72: National
Fire Alarm and Signaling Code and NFPA 70:
Within that chapter, Article 500 “Hazardous
(Classified) Locations, Classes I, II and III,
Divisions 1 and 2” stipulates that locations
involve volatile and potentially flammable National Electrical Code® (NEC®). While some be classified based on the flammables that
materials present special challenges for codes apply to residential and commercial could be present, and their concentration or
fire protection. settings (where smoke and heat detection quantity. Hazardous areas are broken down
are commonly adequate), hazardous-area into these three classes:
Hazardous conditions can occur in a fire and gas detection equipment must be • Class I — areas in which flammable gases,
range of industrial settings from oil certified for use in that hazardous location. flammable liquid-produced vapors, or
platforms and refineries to chemical This requirement is spelled out in the U.S. combustible liquid-produced vapors are
processing plants, as well as in specific by OSHA (Occupational Safety and Health or may be present in the air in quantities
applications as varied as paint lines, Administration) 1910 Subpart S. sufficient to produce explosive or ignitable
LNG terminals and turbine enclosures. mixtures
These types of high-risk locations and Before discussing hazardous-area fire • Class II — locations in which combustible
operations call for process-specific protection standards, it’s important to dust is present; dust is defined as solid
fire protection. understand what attributes make a process material less than 420 microns (0.017 in.)
or location “hazardous.” or smaller in diameter
This article, by Mike Hosch, Simon Pate • Class III — locations in which easily ignitable
and Mark Indgjer of Det-Tronics, looks Defining hazardous areas fibers or flyings, such as rayon, cotton, jute,
at the separate types of fire protection The definition of hazardous locations is based hemp and cocoa fiber are present
equipment for use in hazardous areas on a number of factors. The National Fire
and the leading U.S. standards for each. Protection Association in the U.S. covers Within each class, there are divisions based
these topics in great detail. According to its on the concentration of flammable materials,
The requirements for fire protection are website, NFPA has published more than 300 the form of handling and the frequency
legislated and subject to numerous codes codes and standards that affect “virtually with which the materials maybe present.
and standards, such as EN (European Norms) every building, process, service, design and For example, in Class I:
54 and ISO (International Organization for installation” with the goal of minimizing the • Division 1 is a location where combustible
Standardization) 7240. In the U.S., the risk and effects of fire. In particular, NFPA 70, materials are routinely present in ignitable
leading resource for fire safety standards Chapter 5 addresses “special occupancies.” concentrations.

www.hazardexonthenet.net
Fire safety 25

• Division 2 is one in which the same 3. Ignition source (i.e., heat) — which, Controlling ignition risk
materials are handled, processed, or used, depending on the fuel and conditions, from equipment
but in which the materials are normally can be as minimal as the spark of an Many industrial locations in which hazardous
confined and can escape only in case electric switch or electric motor, or a materials may be present are also areas
of accident or breakdown or failure of hot surface where electronic and electrical equipment
ventilation equipment. could provide sources of ignition. It is
To control the risk of fire, one of the therefore necessary to control ignition
Within Class I, locations are also defined by elements of the fire triangle must be sources, e.g., heat, arcing or sparking. If
zones (0, 1 or 2) per Article 505 of NFPA 70. eliminated. When possible, flammable electrical equipment (including flame and gas
For example, in a Class I, Zone 0 location, materials must be contained and detectors) must be located in a hazardous
ignitable concentrations of flammable gases kept away from oxygen, as well as area, per NFPA they must be designed
or vapors are present continuously or for long ignition sources such as sparks or hot to limit or isolate potential sources of
periods of time. surfaces. The primary goal should be ignition. NFPA 70 Section 500.7 “Protection
containment of the fuel source, i.e., Techniques” lists several techniques for
How to control fire risk in preventing leakage. The next step is to protecting electrical and electronic equipment
hazardous areas eliminate or minimize the risk of ignition. used in hazardous (classified) locations. The
In order to control fire risk, it’s important to Because oxygen is ever-present in the three acceptable protection methods for
understand the components needed for a atmosphere, it is difficult to eliminate Class I Division 1 are:
fire to start. Commonly referred to as the “fire this element from the fire triangle. • Explosion Proof (XP) — sparks or
triangle,” the essential elements are: Success in containing or reducing the explosions are contained within the
1. Oxygen — which can be a constituent or concentration of fuel determines the housing
outcome of various industrial processes, Division level of a hazardous area. Any • Purged and Pressurized — combustible
though its primary source is the ambient air hazardous area, by definition, has some gases and vapors are denied entry into the
2. Fuel — which is present in structures and degree of risk due to the presence of enclosure
used in processes of all kinds, but is of flammable materials at combustible • Intrinsically Safe (IS) — the entire power of
greater concern in locations defined as levels. the system is limited
hazardous
In addition to limiting electrical energy as an
ignition source, the surface temperature of
electrical equipment must also be controlled.
Equipment is marked (T1 – T6) to show the
environment for which it has been evaluated
and is considered suitable

What makes up a fire


protection system
A fire protection system is comprised of several
subsystems that can include, but are not
limited to: flame, smoke and gas detection;
notification and/or suppression activation;
and a controller that receives the inputs from
the detection devices, makes decisions and
Fire triangle
initiates appropriate action or actions.

www.hazardexonthenet.net
26 Fire safety

There is no single solution for fire detection be acceptable in lieu of heat detection if There are many factors to consider when
in hazardous areas. Effective protection is approved by the authority having jurisdiction selecting the type, quantity, location, and
based on the materials and fuels present, the and installed in accordance with NFPA 72.” spacing of flame detectors, including:
processes involved, the environment, and • Matching the spectral response of the
other control measures present. Based on Chapter 17 of NFPA 72 is titled “Initiating detector to the spectral emissions of the fire
these variables, an effective detection and Devices” and it provides requirements for the or fires to be detected.
suppression system may require multiple use of various types of detectors — radiant • Minimizing the possibility of spurious
technologies to effectively detect the hazards. energy-sensing (flame) smoke and gas — that nuisance alarms from non-fire sources
can be used to discover or recognize potential inherent to the hazard area.
Regardless of the application, many NFPA indications of fire. Below is an overview of
codes and standards for specific processes each detector type and some of the NFPA NFPA 72 addresses these selection factors in
reference NFPA 72, National Fire Alarm and standards applicable to each. Chapter 17:
Signaling Code, including: • 17.8.3.2.1 The location and spacing of
• NFPA 15 Standard for Water Spray Flame detectors detectors shall be the result of an engineering
Fixed Systems for Fire Protection — NFPA 72 describes a flame detector as “a evaluation that includes the following:
“The selection, location and spacing of radiant energy-sensing fire detector that 1) Size of the fire that is to be detected
automatic fire detectors for the actuation detects the radiant energy emitted by a 2) Fuel involved
of fixed water spray systems shall meet flame.” Flame detectors are line-of-sight 3) Sensitivity of the detector
or exceed the application requirements of devices that can employ several sensing 4) Field of view (FOV) of the detector
NFPA 72...“ technologies: ultraviolet (UV), infrared (IR), 5) Distance between the fire and the detector
• NFPA 30 Flammable and Combustible ultraviolet/infrared (UV/IR) and multi-spectrum 6) Radiant energy absorption of the
Liquids Code references numerous NFPA infrared (MSIR). atmosphere
codes, including NFPA 15, which in turn 7) Presence of extraneous sources of radiant
references NFPA 72. Radiant energy-sensing detectors are emissions
• NFPA 59A Standard for the Production, incorporated into hazardous-area fire 8) Purpose of the detection system
Storage, and Handling of Liquefied Natural protection systems particularly when either 9) Response time required
Gas (LNG) says, “...the detection system or both of two factors are present in the
shall be designed, installed and maintained application: 1) when rapid-fire detection and Smoke detectors
in accordance with NFPA 72 National Fire actuation response times are critical; and 2) A smoke detector detects the particles
Alarm Code.” when the impact of false alarms is potentially produced by combustion using a variety
• NFPA 70 National Electrical Code has disastrous in terms of damage, downtime of technologies. These can include
multiple references to NFPA 72. or both. Flame detectors used in hazardous ionization, cloud chamber, photoelectric light
• NFPA 409 Standard on Aircraft Hangars areas must be hazardous-location-rated and obscuration, photoelectric light scattering and
says, “Listed detection systems shall performance-certified. video image detection. To be effective, smoke

www.hazardexonthenet.net
Fire safety 27

detectors should be located and spaced gas detection technology to use, and the requirements for ensuring fire and
in anticipation of airflow from sources likely placement of the devices. Combining various gas detection systems are designed,
to present fire risks, but without resulting in technologies and placing them in locations implemented, operated and maintained
unwarranted alarms. NFPA 72 describes the that maximize their effectiveness can mitigate to provide the required Safety Integrity
requirement this way: the impact of a hazard. Level (SIL) for specific hazardous events.

Resources
1. NFPA 70 National Electrical Code
www.nfpa.org/70
2. NFPA 72 National Fire Alarm and Signaling
Code www.nfpa.org/72
3. International Electrotechnical Commission
www.iec.ch/functionalsafety/
4. Factory Mutual
www.fmapprovals.com
5. European Norms
Example of disposition of different types of gas detection within a plant
www.cen.eu
• 17.7.1.9 The location of smoke detectors Fire protection system controller 6. ISO 7240 Fire detection and alarm systems
shall be based on an evaluation of potential A safety system controller (SSC) receives www.iso.org
ambient sources of smoke, moisture, dust, and interprets input from multiple detectors 7. UL Standards (Underwriters Laboratories)
or fumes, and electrical or mechanical and makes executive decisions regarding ulstandards.ul.com
influences, to minimize nuisance alarms. notification and further activity including
suppression. While the primary function of NFPA 70®, National Electrical Code® and
Combustible gas detectors detectors is to detect a hazard and then NEC® are registered trademarks of the
NFPA 72 describes a gas detector as signal to alert that an event has occurred, it National Fire Protection Association, Quincy,
“a device that detects the presence of a is also essential that detectors are capable Mass., USA.
specified gas concentration.” Detectors are of maximizing false alarm rejection – so they
intended for specific types of gas or vapor and do not alarm to non-hazardous events, such
should be chosen accordingly, as specified in as arc welding. NFPA 72 defines a nuisance About the authors
NFPA 72: alarm this way: “An unwanted activation of a
• 17.10.2.4 The selection and placement of signaling system or an alarm initiating device
the gas detectors shall be based on an in response to a stimulus or condition that
engineering evaluation. is not the result of a potentially hazardous
Gas leak detection technologies can include: condition. In some cases, in order to prevent
• Acoustic detection for gas leaks — nuisance alarms, the SSC may discount
ultrasonic sensors detect leaks based on information from a single detector if it is not
noise patterns confirmed by other detectors in the area.
• Infrared detection along a line of sight —
detects gas along a path providing a large As is the case for individual detectors, the
area of detection SSC, if installed in a hazardous location, must
• Point detection of a combustible or toxic be rated for the location. Alternatively, the SSC
Simon J. Pate is Key Account Manager
gas by electrochemical, catalytic, or infrared can be located outside the hazardous location.
for the LNG market at Det-Tronics.
technologies — gases come into contact Simon has broad experience in the
with the detector, causing the detector to Beyond NFPA oil and gas industry, having worked
activate While the NFPA standards are both wide in process automation and functional
ranging and very detailed, they do not safety at EPCs, end users and
manufacturers. He received his BEng
A challenge related to gas detection is that address detector performance. Other
(Hons) degree from Kingston University.
the origin of gas leaks can often be difficult standards organizations or Nationally
Michael J. Hosch is the Flame
to predict. Gas leak detection can also be Recognized Testing Laboratories (NRTLs)
Detection Product Line Manager and
challenging due to varying environmental have metrological standards that support has worked with optical flame detection
conditions such as wind and rain, and the NFPA, such as Factory Mutual (FM) 3010 for Det-Tronics for over 25 years.
application factors such as machinery and for fire alarm systems and Underwriters
Mark Indgjer joined Det-Tronics as an
piping. These environmental and situational Laboratories (UL) 864. Application Engineer in 2017. Prior to
factors, as well as the many potential joining Det-Tronics, he held a variety of
sources of gas leaks, play major roles in In addition, the International Electrotechnical roles in his 25+ years in the fire industry.
selecting the type(s) of combustible and toxic Commission (IEC) 61508 defines the

www.hazardexonthenet.net
Reprinted with the permission of HazardEx, published by IML Group PLC, online at www.hazardexonthenet.net AR 1123 | January 2018

Corporate Office
6901 West 110th Street Phone: 952.946.6491
Minneapolis, MN 55438 USA Toll-free: 800.765.3473
www.det-tronics.com Fax: 952.829.8750
det-tronics@det-tronics.com
© 2018 Detector Electronics Corporation. All rights reserved.

You might also like