Professional Documents
Culture Documents
3.7 Displacer Level Devices: D. S. Kayser B. G. Lipták C. G. Langford
3.7 Displacer Level Devices: D. S. Kayser B. G. Lipták C. G. Langford
C. G. LANGFORD (2003)
Design Pressure Set by the flange rating of the chamber or by the maximum working pressure of the
displacer, usually up to 100 PSIG (7 bars, 0.7 MPa) for the flexible disc and up to
600 PSIG (41 bars, 4.1 MPa) for the diaphragm-sealed designs. The flexible shaft
unit can operate up to 1000 PSIG (69 bars, 6.9 MPa); torque-tube designs are available
up to 2500 PSIG (170 bars, 17 MPa); magnetically coupled units can be used up to
6100 PSIG (410 bars, 41 MPa). Verify ratings with the manufacturer.
®
Design Temperature Generally in the range of −50 to 451°F (−45 to 230°C). Inconel torque tubes can
operate from −350 to 850°F (−212 to 454°C). For electronic transmitters, the tem-
perature of the topworks must be kept below 180°F (82°C). If the process temperature
is above 500°F (260°C) or below 0°F (−18°C), thermal insulation barriers or torque-
tube extensions are usually recommended.
®
Materials of Construction Displacers are available in type 316 stainless steel, Monel , polypropylene, or solid
®
Teflon . The hanger cable assemblies can be obtained in type 316 stainless steel,
® ®
Monel , and Hastelloy C. The cage (chamber) is usually carbon or stainless steel.
Inaccuracy Varies widely with application and the instrument, typically 0.5% of full scale.
Range Standard displacers are available in lengths of 14 to 60 in. (0.35 to 1.5 m). The range
of special units can go up to 60 ft (18 m).
Cost Displacer-type switches cost from $200 to $500, and a 32-in. (0.81-m) electronic
transmitter costs about $2500; add $500 to $700 for an external steel chamber.
465
© 2003 by Béla Lipták
466 Level Measurement
This simple device is limited to applications in open tanks. mounted on a flexible cable attached to a support spring.
In practical industrial service, the basic problem is to seal the When the tank is empty, the spring must support the full
process from the spring scale or other force-detecting mecha- weight of the displacer. As the level rises, and the displacer
nism. This seal has to be frictionless and useful over a wide becomes immersed in the liquid, the downward force on the
range of pressures, temperatures, and corrosion conditions. support spring is reduced, and a small stem movement occurs
The variations in the design of this seal provide the basis to to activate the switch.
distinguish the types of displacement detectors that are in use Figure 3.7a also illustrates how the displacer level switch
and are discussed below. They are the magnetically coupled systems might be tested when installed in open tanks and
switch, the torque tube, the diaphragm and force bar, the spring sumps, or on floating roofs. The technician or operator can
balance, the flexible disc, and the flexible shaft design. Each attach a testing cable as shown on the right side of Figure 3.7a.
of these units operates on Archimedes’ principle but is different Once the cable is attached, lifting on the cable simulates a
as far as its seals are concerned. All of them can be used to high-level condition, changing the state of the switch to prove
detect a liquid–vapor interface, a liquid–liquid interface, and, the operation of the switch and probably the wiring.
if the level is constant, the changes in density as well. The In the next section, the operation of different switching
flexible disc unit is available as a pneumatic transmitter, and contacts and the designs of the different float chambers are
the flexible shaft unit is available as a high-gain pneumatic described. Although this information is provided for float-
controller or as a switch. The other designs are available with type switches, it is also applicable for displacer-type units.
integral pneumatic or electronic transmitters or controllers. When deciding between float-type and displacer-type level
switches, the following advantages can be noted for the latter:
DISPLACER SWITCH 1. The maximum differential between high and low set-
tings can be as much as 50 ft (15 m).
The major difference between a float level switch and a dis- 2. Level settings are adjusted by moving the displacer(s)
placer level switch is that a float moves with the surface, to a new elevation on the cable.
whereas a displacer is partially or totally immersed and moves 3. Moderate surface turbulence is less apt to cause switch
very little with process changes. Switching arrangements and chatter, because the cable is in tension.
installation considerations are similar for the displacer and 4. Within broad ranges, fluid density has no effect on the
float switches. Float-type switches are covered in the next displacer sizing diameter, making units interchange-
section, and the discussion here will be limited to the design able between services of varying density simply by
features of the displacer switch. Figure 3.7a shows a displacer changing the support spring.
5. The displacer switch is less apt to cause spurious trips
in vibrating services, because the cable is always in
tension. This is an important consideration for auto-
matic shutdown systems such as may be used at com-
pressor suction drums.
Flexible
Cable Displacers
TORQUE-TUBE DISPLACERS
Low Level The torque tube shown in Figure 3.7c uses a tube in torsion to
provide the spring function. The hollow torsion tube supports
FIG. 3.7a the displacer, which is always heavier than the process fluid,
Displacement level switches. and also provides a frictionless pressure seal. This makes it
Float-Arm
Extension
Flexible Shaft
11/2" NPT
Limit-Stop
Bracket
Float-Arm
Displacer
Float Formed Section
SPDT Micro Switch
FIG. 3.7b
Side-mounted displacer switch. (Courtesy of Siemens Moore Energy & Automation.)
Torque Tube Torque of a knife-edge bearing support. A limit stop prevents acci-
Torque
Flange Rod dental overstressing of the torque tube by limiting the down-
Arm
Torque ward motion of the torque arm. The angular displacement of
Torque
Arm Tube the torque tube and torque arm are the same at the knife edge
Block end of the tube. At the flange end, the tube is anchored in
place and does not rotate, but the torque rod is free to rotate
the same amount as it did at the knife edge. The angular
displacement, which amounts to about 5° or 6°, is linearly
proportional to the apparent weight of the displacer and thus
to the level or density. With the pressure sealing problem
solved, it is a simple matter to convert the angular displace-
Limit
Stop
ment to a usable electronic or pneumatic analog signal. The
®
standard torque-tube material is Inconel , but the torque tube
Knife ® ®
Edge
Nozzle is also available in stainless steel, Hastelloy , Monel , nickel,
or Durimet. Note that the mechanical design requires the
Flapper technician to be knowledgeable and careful in doing main-
Displacer tenance or repairs.
Sizing of Displacers
FIG. 3.7c The technique given below for determining the desirable
Torque tube displacer level detector. displacer diameter is applicable for all types of buoyant-force
detectors, not just the torque-tube design. The displacer diam-
eter sets the weight change of the displacer per level incre-
possible to transfer the changes in the apparent weight of the ment. The torque tube is designed to twist a fixed amount for
displacer through the wall of the pressure vessel into a mea- each increment of buoyancy change. Therefore, in selecting
suring device. Figure 3.7c is a schematic presentation of the the displacer diameter, the torque-tube characteristics, the
displacer and torque tube. The displacers are typically cylin- density of the process fluid, and the level span must be
drical and can be furnished in a wide selection of plastic and considered. For purposes of this discussion, it will be assumed
alloy materials. Although any length displacer up to 60 ft that the motion of the torque rod will be used to operate a
(18 m) can be obtained, the most common lengths cataloged proportional band controller. Proportional band (PB) refers
are 14, 32, 48, and 60 in. (0.3, 0.8, 1.2, and 1.5 m). The to the response sensitivity of the controller, and it determines
3 3
volume of a standard displacer is 100 in. (1638 cm ), and the percentage change in output signal in response to a 1%
the diameter is reduced as the length increases. change in the level. A 100% apparent proportional band
The torque arm connects the displacer to the torque tube setting means that the level in the tank has to cover the
and absorbs any lateral forces. Friction is minimized by use displacer completely to generate a full output signal, and that
the level has to drop to the bottom of the displacer to generate ranges of standard and thin-wall torque tubes for one design
the minimum output. A controller set to a PB of 100% can at various proportional band settings. The thin-wall tube
be used as a transmitter if the process fluid is water. At 50% requires one-half as much force for full range operation as
apparent proportional band, a level variation of 50% of the the standard-wall tube. Review the technical literature for the
displacer length produces minimum to maximum output, and, actual device used to confirm the actual numerical constants
at 25% setting, a level variation of 25% will generate the min- to use. The calculations here are only examples.
imum to maximum output.
The term apparent proportional band is necessary to dis- Interface Measurement
tinguish the actual band setting on the instrument based on
water density at standard temperature from the resulting In most liquid level measurement applications, the specific
apparent band related to the density of the process fluid being gravity of the liquid is 0.5 (or greater), and it generates
measured. Figure 3.7d shows the relationship between the sufficient force on the torque tube for a full range of output
two terms as a function of process liquid density. It can be signals, even with the use of a standard volume displacer,
seen from Figure 3.7d that, if the band setting on the instru- unless a very narrow proportional band is required. This may
ment is 50%, the output of the controller will change 50% not be true for liquid–liquid interface applications. Difference
of the level change with a liquid gravity of 1. It will change in buoyant forces is generated only by the density difference
100% with a gravity of 0.5, and, with a specific gravity of between the two fluids, and the displacer must be completely
0.1, the output will equal 10 times the level change. The submerged for meaningful readings. Therefore, available
process fluid density thus affects the apparent gain of the forces are smaller, and the sizing of displacers for liquid–liquid
controller in an inverse linear fashion. interface is more difficult and requires more attention.
Because the weight change per unit level change gener- On interface applications, it is advisable to select a dis-
ated by the displacer is balanced by the torsion spring con- placer diameter to result in a 100% apparent proportional
stant, the characteristics of the torque tube must be consid- band when the actual band setting is 20%. This leaves addi-
ered. The range of a standard torque tube matches the buoyant tional adjustment capability to the operator who, if required,
3 3
force generated by a 100 in. (1638 cm ) displacer in water can reduce the actual band to 10% (the minimum recom-
for a band setting of 100%. This is equivalent to a force range mended) to achieve a reduction in apparent band to 50%. An
of 0 to 3.6 lbf (0 to 1.6 kgf). Table 3.7e below lists the force example will illustrate this.
Assume an installation in which the specific gravity of
the light fluid is 0.98 and of the heavy fluid is 1.02, and the
Actual (Water Based) required displacer is 32 in. (812 mm) long. Furthermore, it
Proportional Band is desired to generate full controller output over a level inter-
face change of 16 in. (406 mm). To select a displacer diameter
100 SG = 1.0 SG = 0.25 suitable for these requirements, it is necessary to calculate
SG = 0.1
the displacer volume that will generate the force range
SG = 0.5
80 required by a thin-wall tube when the level variation is 16 in.
SG = 0.2
60 (406 mm). A thin-wall tube at an actual band of 20% requires
a full-range force of 0.36 lbf (0.16 kgf). The calculation of
40
displacer volume to generate this force is as follows:
20
Apparent Volume for 16 in. length
0
Proportion
100 200 300 400 500 600 800 1000
Band = (torque tube force)/( ∆SG)(wt. of 1 in.3 H 2O)
FIG. 3.7d
Relationship between apparent and actual proportional band.
= 0.36/(0.004)(0.036) = 250 in.3 3.7(1)
Pressure Vessel
2" or Larger Nozzle
Overlapping
Gage Glasses
1 " or Larger
Gate Valve
FIG. 3.7f Reducer to " Pipe
Side-mounted displacer. (Courtesy of Siemens Moore Energy &
" Gate Valve (Drain)
Automation.) These Assemblies
May be Elbows
given can be used for all displacer applications including
density detection. Standard displacer diameters are 3, 4, and
FIG. 3.7g
6 in. (76, 102, and 152 mm), but special sizes and designs
The installation of an external cage displacer on a standpipe with
are also available (Figure 3.7f). Carefully review the engi-
two level gauge sections. (Courtesy of the American Petroleum
neering specifications or check with the manufacturer for the Institute, API RP 550.)
details that apply to the specific instrument being considered.
In a large vessel, the interface may have a very slow but
the bottom of the vessel if it becomes disconnected from the
substantial wave motion if the difference between densities
torque tube.
is small. The gravity forces are small, and the fluids have
For installations in which the vessel cannot be opened
little friction to damp out any fluid motion. If no sight port
and drained to perform maintenance on the displacer, it may
is located so as to make this motion visible, the operator will
be installed in a level chamber mounted outside of the tank
have the impression that the signal or the control is cycling.
and isolated from the process by means of lockable valves.
Local safety rules must be observed. A single barrier between
Rag Layer
vessel and the environment may require special precautions.
Another cause of measurement doubt and confusion is the It has been typical practice to install a level gauge to
common situation of a rag layer of material, lighter than the approximately match the span of the displacer to provide
heavy layer and heavier than the light layer, that will accumu- visual observation of the level. Figure 3.7g shows the instal-
late between the two desired layers. If there is no mechanism lation of a displacer transmitter and level gauge mounted on
or procedure to remove this material, it will become ever deeper a standpipe or level chamber. Note that the two units have
until it suddenly appears in the upper layer outlet. In continuous independent isolation and drain valves. Some users prefer to
processes, even tiny amounts of undesired materials will eliminate the installation of breakable sight glasses for envi-
always accumulate wherever conditions make this possible. ronmental and safety reasons.
When an external chamber is used, it may be necessary
Features and Installation to heat-trace and insulate the level chamber for freeze or fire
protection. The density measurement is for the liquid in the
Torque-tube level devices can be mounted internally or exter- chamber and may not represent the vessel contents density
nally to the vessel. Internal displacers are used where it is if the level chamber temperature is not the same as the vessel
possible to drain the tank for level detector maintenance. If bulk temperature. For liquid–liquid interface applications, the
the displacer is to be internally mounted, it is good practice standpipe must have three connections to the vessel: one in
to install it inside of a stilling well, which may be fabricated the heavy liquid layer, one in the light liquid layer, and one
from a piece of pipe. To avoid errors, the standpipe must have in the vapor space that vents back into the vessel.
a number of vertical slots or holes along its length to permit Special torque-tube and displacer designs are available
a free but restrained flow of liquids, and it should have a stop for operating pressures up to 2500 PSIG (17 MPa). For high-
bar across the bottom to prevent the displacer from falling to temperature installations, the torque-tube material may be the
limiting factor. The spring characteristics of the tube will Magnet Nozzle Air
change at sufficiently high temperatures. Low temperatures Attraction Pilot
Output
have little effect on the spring characteristics of the tube. For Ball
®
torque-tube materials, Inconel is suitable for temperatures Air
between −350 and 850°F (−212 and 454°C). All other mate- Enclosing
Supply
Tube
rials are limited to 500°F (260°C) except bronze, which is
rated at 300°F (150°C). Torque-tube extensions will provide
substantial thermal isolation for the instrument case. Installa-
tion details will also affect the instrument temperature. When Range
Spring
the process is at a temperature above 500°F (260°C), finned
extensions are recommended; when it is below 0°F (−18°C),
plain extensions may be used. The extensions should not be
insulated. Additional thermal insulation or thermal radiation Magnetic Coupling with
Electronic Output
barriers can be used to protect the indicating and transmitting
Displacer
portions of the instrument. Note that pneumatic transmitters
may have a higher allowable temperature than the electronic
version. Jacketed displacer chambers are available for hard-
to-handle services if field-applied tracing is judged to be inad-
FIG. 3.7h
equate. The process connections on external chamber displac- The old spring balance, magnetically coupled displacer.
ers are normally 1.5 or 2 in. (38 or 51 mm) and often flanged,
so they may be used in mildly dirty services. Consider blow-
down or drain valves where appropriate and permissible. It is to the displacer movement. The movement is about 1 in.
preferred not to use external chambers if there is a likelihood (25 mm) full range. The ball is centered within the enclosing
of plugging because of solids accumulation. tube, and its movement is nearly frictionless. A follower
The torque-tube displacer can be furnished with pneu- mechanism moves with the magnetic ball for indication and
matic or electronic transmitters or with local control. Con- signal transmission.
trollers are available with gain, integral, and/or derivative Other design features and accessories are similar to the ones
control action. An output gauge should be installed on the discussed in the section on torque-tube design. The spring-
transmitter signal to indicate level and for troubleshooting. balanced displacers are also available with corrosion-resistant
It may also be good practice to install an independent level wetted parts and are suitable for operating temperatures
gauge. The torque tube and displacer design has an excellent between −250°F (−157°C) and 600°F (316°C). Because the
field record for accuracy and reliability. Over time, accumu- interior-to-exterior motion is magnetically coupled, units
lated noncondensable and solids may compromise accuracy, with very high pressure ratings to 6000 PSIG (41 MPa) are
and some verification of proper performance is desirable. The available. The merits and disadvantages of the spring-balanced
torque-tube seal is virtually trouble-free if properly specified design are similar to those of the torque-tube units, except
to meet the process requirements. In processes in which level that the movement of the displacer is greater, and the range
setpoint changes are infrequent, or where speed of response spring is exposed to the process. Greater movement almost
is a concern, displacer units are often used as local level always causes faster wear at pivot points. The range spring
controllers, even if a sophisticated control system is used. exposure creates difficulty in installations where vapor space
The units may also be furnished with transmitter/controller condensation, polymerization, or crystallization is expected,
combinations, allowing the advantage of local control with because material buildup on the spring will interfere with
remote process indication. proper operation. Inert gas purging of the spring chamber has
been used to prevent the process vapors from entering the
chamber, but the large flow rates required make this solution
SPRING-BALANCE DISPLACER impractical.
Displacer
TABLE 3.7j
Data on Displacer Materials, Sizes, and Other Features (Typical)*
Metric Displacer Data
Maximum
Working
Pressure English Displacer Data
Approximate Relative Permissible Process
OD bar or Maximum Working Density of Displacer Liquid Relative
Material L (mm) (mm) MPa kg/cm L(in.) OD (in.) Pressure (PSI) (Specific Gravity) Density Limits (SG Term)
316 SS 356 76 6.9 69 14 3 1000 2.95 0.42 and 1.6
610 51 10.3 103 24 2 1500 2.52 0.56 and 2.2
610 76 6.9 69 24 3 1000 1.69 0.25 and 0.98
813 51 10.3 103 32 2 1500 2.28 0.42 and 1.6
813 76 6.9 69 32 3 1010 1.22 0.18 and 0.7
1016 51 10.3 103 40 2 1500 2.38 0.33 and 1.4
1219 42 10.3 103 48 1.66 1500 2.27 0.39 and 1.6
1270 51 7.6 76 50 2 1100 1.90 0.27 and 1.0
1524 38 10.3 103 60 1.5 1500 2.41 0.39 and 1.6
1524 76 10.3 103 60 3 600 1.31 0.10 and 0.4
1829 33 10.3 103 72 1.31 1500 2.58 0.42 and 1.7
2134 32 10.3 103 84 1.25 1500 2.60 0.40 and 1.6
2438 27 10.3 103 96 1.05 1500 2.96 0.49 and 2.0
2540 32 10.3 103 100 1.25 1500 2.43 0.34 and 1.4
2743 27 10.3 103 108 1.05 1500 2.80 0.44 and 1.8
2743 51 6.7 67 108 2 975 1.64 0.12 and 0.5
3048 25 10.0 100 120 1 1450 2.47 0.44 and 1.8
3810 25 10.0 100 150 1 1450 2.44 0.35 and 1.4
®
Monel 356 76 6.9 69 14 3 1000 1.63 0.42 and 1.6
610 76 6.5 65 24 3 950 1.69 0.25 and 0.98
813 51 10.3 103 32 2 1500 2.28 0.42 and 1.6
1524 51 6.9 69 60 2 1000 1.88 0.22 and 0.89
2134 33 10.3 103 84 1.31 1500 2.60 0.36 and 1.5
3658 25 5.2 52 144 1 750 2.47 0.37 and 1.5
Solid PTFE 356 76 10.3 103 14 3 1500 2.28 0.42 and 1.6
813 51 10.3 103 32 2 1500 2.28 0.42 and 1.6
1219 41 18.3 183 48 1.6 2650 2.28 0.42 and 1.6
Mounting
An increase in level moves the tongue, gradually closing the
Float Flange
Flexible vent of the pilot and increasing the output signal to the control
Arm
Shaft valve. By turning the mounting flange 180°, the control pilot
action can be reversed so that an increase in level will be
Float accompanied by a decrease in the signal to the valve. The unit
can also be provided as an on–off switch with either pneu-
Extension matic or electric output.
Limit-Stop
Tongue As with other displacer designs, this device can be used
Bracket
to control interface or fluid density, but it is very limited in
FIG. 3.7k adjustment flexibility as compared to the torque-tube design.
Flexible shaft level controller. (Courtesy of Siemens Moore Energy The flexible shaft unit has a narrow and fixed proportional
and Automation.) band without integral action. The ball float has a throttling