SCHEDULE OF EQUIPMENT
TP-1 TRANSFER PUMP TWO (2)- UNITS HORIZONTAL 135 85 7.5 ELECTRIC DRIVEN, 3Ø 60 380 REDUCED WYE DELTA COMPLETE WITH ACCESSORIES GROUND 1-UNIT OPERATIONAL
POTABLE IDENTICAL TYPE OPEN DRIP PROOF VOLTAGE MAGNETIC STARTER, (REFER TO TECH. SPECS.) LEVEL 1-UNIT STANDBY OR
H-O-A SWITCHES, OVERLOAD (ALTERNATE OPERATION)
RELAYS AND ALTERNATOR
TP-2 TRANSFER PUMP TWO (2)- UNITS HORIZONTAL 135 85 7.5 ELECTRIC DRIVEN, 3Ø 60 380 REDUCED WYE DELTA COMPLETE WITH ACCESSORIES GROUND 1-UNIT OPERATIONAL
NON-POTABLE IDENTICAL TYPE OPEN DRIP PROOF VOLTAGE MAGNETIC STARTER, (REFER TO TECH. SPECS.) LEVEL 1-UNIT STANDBY OR
H-O-A SWITCHES, OVERLOAD (ALTERNATE OPERATION)
RELAYS AND ALTERNATOR
BP-1 BOOSTER PUMP TWO (2)- UNITS HORIZONTAL CENTRIFUGAL, 150 105 10 ELECTRIC DRIVEN, 3Ø 60 380 REDUCED WYE DELTA COMPLETE WITH ACCESSORIES ROOF DECK 2 UNITS TO RUN AT PEAK
POTABLE IDENTICAL END SUCTION CLOSED OPEN DRIP PROOF VOLTAGE MAGNETIC STARTER, (REFER TO TECH. SPECS.) LEVEL 1-UNIT STANDBY OR
TO SUPPLY UNITS BELOW COUPLED TO ELECTRIC H-O-A SWITCHES, OVERLOAD (ALTERNATE OPERATION)
ROOF DECK MOTOR ON A COMMON BASE RELAYS AND ALTERNATOR
BP-2 BOOSTER PUMP TWO (2)- UNITS HORIZONTAL CENTRIFUGAL, 120 105 7.5 ELECTRIC DRIVEN, 3Ø 60 380 REDUCED WYE DELTA COMPLETE WITH ACCESSORIES ROOF DECK 2 UNITS TO RUN AT PEAK
POTABLE IDENTICAL END SUCTION CLOSED OPEN DRIP PROOF VOLTAGE MAGNETIC STARTER, (REFER TO TECH. SPECS.) LEVEL 1-UNIT STANDBY OR
TO SUPPLY UNITS BELOW COUPLED TO ELECTRIC H-O-A SWITCHES, OVERLOAD (ALTERNATE OPERATION)
ROOF DECK MOTOR ON A COMMON BASE RELAYS AND ALTERNATOR
BP-3 BOOSTER (FILTER)) TWO (2)- UNITS HORIZONTAL CENTRIFUGAL, 100 100 7.5 ELECTRIC DRIVEN, 3Ø 60 380 REDUCED WYE DELTA COMPLETE WITH ACCESSORIES GROUND 1-UNIT OPERATIONAL
PUMP FOR RAINWATER IDENTICAL END SUCTION CLOSED OPEN DRIP PROOF VOLTAGE MAGNETIC STARTER, (REFER TO TECH.SPECS) LEVEL 1-UNIT STANDBY OR
COUPLED TO ELECTRIC H-O-A SWITCHES, OVERLOAD (ALTERNATE OPERATION)
MOTOR ON A COMMON BASE RELAYS AND ALTERNATOR
BP-4 BOOSTER PUMP TWO (2)- UNITS HORIZONTAL CENTRIFUGAL, 100 100 7.5 ELECTRIC DRIVEN, 3Ø 60 380 REDUCED WYE DELTA COMPLETE WITH ACCESSORIES GROUND 1-UNIT OPERATIONAL
FOR IRRIGATION IDENTICAL END SUCTION CLOSED OPEN DRIP VOLTAGE MAGNETIC STARTER, (REFER TO TECH. SPECS) LEVEL 1-UNIT STAND BY OR
COUPLED TO ELECTRIC H-O-A SWITCHES,OVERLOAD (ALTERNATE OPERATION)
MOTOR ON A COMMON BASE RELAYS AND ALTERNATOR
SP SUMP PUMP ONE (1) UNIT PERPORTABLE SUBMERSIBLE 20 20 0.8 ELECTRIC DRIVEN 1 60 230 FULL VOLTAGE MAGNETIC COMPLETE WITH ACCESSORIES BELOW ELEV. AUTOMATIC OPERATION
FOR ELEVATOR PIT ELEVATOR NON-CLOG STARTER, H-O-A SWITCHES, (REFER TO TECH. SPECS.) PIT
FLOAT CONTROLS, OVERLOAD
CURRENT RELAYS &
ALTERNATION
FP-1 FIRE PUMP ONE (1)- UNIT VERTICAL TURBINE TYPE 750 254 75 ELECTRIC DRIVEN 3Ø 60 380 WYE DELTA OPEN TRANSITION COMPLETE WITH ACCESSORIES GROUND
TYPE STARTING (REFER TO TECH. SPECS.) LEVEL
254
20
JP-1 JOCKEY PUMP ONE (1)- UNIT SUBMERSIBLE TYPE 3 ELECTRIC DRIVEN 3Ø 60 380 FURNISH READY FOR WIRING COMPLETE WITH ACCESSORIES BASEMENT
JOCKEY PUMP, GENERAL ELEC- (REFER TO TECH. SPECS.) 5 LEVEL
TRIC CRI 35 TYPE “F” WITH H-O-A
SWITCH AND TIMER RUN RELAYS,
WITH THREE OVERLOAD RELAYS
Page 1
TANKS: CAPACITY
1 FRP TYPE ELEVATED 8,000 GALS
POTABLEWATER TANK
SUBMITTED BY:
ENRIQUE T. VILLEGAS
PLUMBING/FIRE PRO CONSULTANT
Page 2