I- Arrangements
1- Year – Round Commercial AHU
1-Mixing plenum
1-Mixing plenum 1-Mixing plenum
2-Filter G4
2-Cooling Coil 2-Electric Heater
3-Cooling Coil
4-Electric Heater
5-Supply Fan
2- Year – Round Commercial AHU Central Heating
Panel Filter Cooling Coil
G4 SHF= 0.9 : 0.7 Heating Coil
Mixing Box
Supply Fan
Sand trap
louvers
1-Mixing plenum
1-Mixing plenum 2-Filter G4 1-Mixing plenum
2-Cooling Coil 3-Cooling Coil 2-Electric Heater
4-Electric Heater
5-Supply Fan
6- Sound attenuator
5- Year – Round AHU in Dry Summer Climate
1-Mixing plenum
2-Filter G4
1-Mixing plenum 1-Mixing plenum
3-Precooling Coil
2-Precooling Coil 2-Heating Coil
4-Heating Coil
3-Air Washer 3-Air Washer
5-Air Washer
6-Eliminator
7-Supply Fan
6- Year – Round AHU Year- Round Humidity Control
Pharmaceutical Clean Single Room Class “ C “
Cooling Coil
SHF= 0.7 : 0.6 Empty Module
Panel Filter Steam Humidifier
G4 Bag Filter Heating / Reheating HEPA Filter
Mixing Box
F9 Coil Supply Fan H13
Sand trap
louvers
Sand trap
louvers
Swirl Diffuser
With Treminal HEPA Filter
H13
Mixing Box
Sand trap
louvers
2- Filter G4 2- Filter G4
1-Fresh Intake
2- Filter G4
3-Decisscent Wheel ( 1 )
4-After Cooler Coil ( 1 )
5-Decisscent Wheel ( 2 )
6-After Cooler Coil ( 2 )
7-Supply Fan
8-Rigid Bag Filter F9
14- Year – Round AHU Year-Round Cooling
Mixing Box
With Modulating
Dampers ( winter )
1-Mixing plenum
1-Mixing plenum
2-Filter G4
2-Chilled Water Spray 1-Mixing plenum
3-Air Washer /
Chilled Water 2-Air Washer
Spray
4-Eliminator
5-Supply Fan
II- Modules Specifications
Specifications
Computer Computer
Main Specifications
Psychrometric Calculations
• Supply Air Rate m3/ hr
• Outside Air Rate in m3 / hr
• Cooling Capacity in tons-ref ( or kW )
• Heating Capacity in kW
• Steam Humidifier Capacity in kg / hr
• Washer Capacity make-up water in lit / min
Cooling Coils
1. Air Rate
2. Heating Capacity
3. Air Inlet Condition
4. Maximum Steam Pressure or Temperature
Air Washer
1. Air Rate
2. Water Consumption
3. Air Inlet Condition
4. Operating Wet bulb
5. Wetting Ratio
6. Humidifying Efficiency
Filters
Coarse Dust Filter ( G ) < 7 μm > 0.7 μm
Substitution Rated
Type Rated ΔP Pa
ΔP Pa Efficiency
G1 30 150 60 -65 %
G2 50 180 65 – 75 %
G3 75 250 75 – 90 %
G4 150 250 90 – 95 %
Filters
Fine Dust Filter ( F ) < 0.7 μm > 0.5 μm
Air Rate is recommended
Substitution Rated
Type Rated ΔP Pa
ΔP Pa Efficiency
F5 85 350 50 – 60 %
F6 100 350 60 – 80 %
F7 120 350 80 – 90 %
F8 150 450 90 – 95 %
F9 250 450 95 – 98 %
Filters
High Efficiency Filter ( HEPA ) ( H < 0.5 μm)
Air Rate is recommended
Substitution Rated
Type Rated ΔP Pa
ΔP Pa Efficiency
Substitution Rated
Type Rated ΔP Pa
ΔP Pa Efficiency