! Example to show behaviors of different distribution transformer connections

New Circuit.Connections

! Substation transformer
New Transformer.substation phases=3 windings=2 XHL=8
~ wdg=1 Bus=SourceBus.1.2.3 kV=115 kVA=25000 %R=.4 Conn=Delta
~ wdg=2 Bus=B1.1.2.3.0 kV=12.47 kVA=25000 %R=.4 Conn=wye

! Add a series of Default lines (1 km each) and install a transformer


New Line.Line1 Bus1=B1 Bus2=B2 Length=1 Units=km
New Line.Line2 Bus1=B2 Bus2=B3 Length=1 Units=km
New Line.Line3 Bus1=B3 Bus2=B4 Length=1 Units=km
New Line.Line4 Bus1=B4 Bus2=B5 Length=1 Units=km

! Define Transformers for each location (B2..B5)


New Transformer.T2 phases=3 windings=2 XHL=5
~ wdg=1 Bus=B2.1.2.3.0 kV=12.47 kVA=500 %R=.4 Conn=Delta
~ wdg=2 Bus=B2LV.1.2.3.0 kV=.208 kVA=500 %R=.4 Conn=wye

New Transformer.T3 phases=3 windings=2 XHL=5


~ wdg=1 Bus=B3.1.2.3.0 kV=12.47 kVA=500 %R=.4 Conn=Wye
~ wdg=2 Bus=B3LV.1.2.3.0 kV=.208 kVA=500 %R=.4 Conn=wye

! change Transformer at B4 to YynD


New Transformer.T4 phases=3 windings=3 XHL=5 XHT=50 XLT=45
~ wdg=1 Bus=B4.1.2.3.4 kV=12.47 kVA=500 %R=.4 Conn=Wye ! Ungrounded
~ wdg=2 Bus=B4LV.1.2.3.0 kV=.208 kVA=500 %R=.4 Conn=wye
~ wdg=3 Bus=B4LVPhantom.1.2.3.0 kV=.208 kVA=500 %R=.4 Conn=Delta

New Transformer.T5 phases=3 windings=2 XHL=5


~ wdg=1 Bus=B5.1.2.3.0 kV=12.47 kVA=500 %R=.4 Conn=Wye
~ wdg=2 Bus=B5LV.1.2.3.0 kV=.208 kVA=500 %R=.4 Conn=Delta

/**** Block Comment

! Add 3-phase loads at each location


New Load.Load2 Bus1=B2LV.1.2.3.0 phases=3 kV=0.208 kW=400 PF=0.95 conn=wye
New Load.Load3 Bus1=B3LV.1.2.3.0 phases=3 kV=0.208 kW=400 PF=0.95 conn=wye
New Load.Load4 Bus1=B4LV.1.2.3.0 phases=3 kV=0.208 kW=400 PF=0.95 conn=wye
New Load.Load5 Bus1=B5LV.1.2.3.0 phases=3 kV=0.208 kW=400 PF=0.95 conn=delta
****/

! Add 1-phase loads at each location


New Load.Load2-1ph Bus1=B2LV.1.0 phases=1 kV=0.120 kW=20 PF=0.98 conn=wye
New Load.Load3-1ph Bus1=B3LV.1.0 phases=1 kV=0.120 kW=20 PF=0.98 conn=wye
New Load.Load4-1ph Bus1=B4LV.1.0 phases=1 kV=0.120 kW=20 PF=0.98 conn=wye
New Load.Load5-1ph Bus1=B5LV.1.0 phases=1 kV=0.120 kW=20 PF=0.98 conn=wye

Set voltagebases=[115, 12.47 .208]


calcvoltagebases

Solve
Show V LN Nodes
Show currents element
Show powers kVA element