You are on page 1of 3

Actuator-Sensor-Interface

I/O Modules for Operation in the Field (IP 65/67)


Compact modules
Actuator-Sensor-Interface

■ Overview

nsa0008vg

nsa0218vg
nsa0217vg

nsa0220v
K60 K60 K45 K45

Design Mounting Addressing


The AS-Interface compact Compact modules of Series One feature that is common to
modules belong to a new gen- K60 and K45 are mounted us- all compact modules from Sie-
eration of AS-Interface mod- ing a mounting plate. For each mens is the integrated address-
ules to a high degree of protec- series one mounting plate is ing socket. This socket can be
tion. Digital, analog and pneu- available for wall mounting and used to assign an address to a
matic compact modules are one is available for mounting on module via an addressing unit
available. standard rails. in the installed state. The IP 67
degree of protection is assured
They comprise a top section The mounting plate for Series
due to the ability to seal the
which is the actual module and K45 for wall mounting has an
socket with a covering cap.
a base section which is the identical hole pattern to the
mounting plate. The top sec- mounting plates of Series K60.
tion contains all the electronics,
For Series K45, a mounting
connections for sensors and
plate is available with an inte-
actuators, an addressing sock-
grated adapter for mounting on
et and status/diagnostics LEDs.
standard rails. Apart from
The mounting plate accepts the mounting on standard rails, this
AS-Interface flat cables and al- mounting plate can also be
lows the module to be wall used for wall mounting. The
mounted or snapped onto a drilled hole pattern of this
standard rail. mounting plate is identical to
that of the coupling module (ap-
Two series of compact modules
plication module). Application
are available:
modules in existing installa-
• Series K60 tions can be replaced with K45
compact modules without any
• Series K45
problems.

Siemens NS K · 2002 1/41


Actuator-Sensor-Interface
I/O Modules for Operation in the Field (IP 65/67)
Compact modules
Actuator-Sensor-Interface

■ Overview
LED diagnostics indication Display characteristics of the K60 compact modules
The new generation of AS-Inter- LED States Status description
face modules (compact mod-
ules, SlimLine modules) fea- AUX PWR On Off Off
tures comprehensive diagnostic
indication. This supports diag- AS-Interface On On Off On Flashing On
nosis at a glance. FAULT Off Off Off On On Flashing
The status of a module is either
displayed via two LEDs or one Sensor overload with RESET of slaves
dual LED with continuous or Slave has address = 0
flashing light. No communication:
Compact modules of Series – Master in STOP mode
K60 have three LEDs for diag- – Slave not entered in the LPS
nostic indication. – Slave has wrong IO&D code
– Slave in RESET state
NSA_00312

Compact modules of Series Module completely without voltage


K45 that are labeled "SAP4.1" UAux failure
have one single and one dual
Normal operation and UAux applied
LED (two-colour LED) for status
and diagnostic indication.
Display characteristics of the K45 compact modules

LED States Status description


AUX PWR On Off Off
AS-i / FAULT On On Off On Flashing Flashing

Flashing

Sensor overload with RESET of slaves


Slave has address = 0
No communication:
– Master in STOP mode
– Slave not entered in the LPS
– Slave has wrong IO&D code
– Slave in RESET state
NSA0_00313

Module completely without voltage


UAux failure
Normal operation and UAux applied

Terminal assignment, K60 Series, digital


Input, pnp (M12 socket) Output, pnp (M12 socket) DC 24 V

Standard assignment Standard assignment


1 2 Pin 1: Supply L+ 1 2 Pin 1: not assigned
Pin 2: Input signal (bridged with Pin 4) Pin 2: not assigned
5 Pin 3: Supply L– 5 Pin 3: Supply L–
Pin 4: Input signal (bridged with Pin 2) Pin 4: Output signal
4 3 PIN 5: Ground connection 4 3 PIN 5: Ground connection
NSA00006a NSA00007a
g_nsa_xx_00006g g_nsa_xx_00007g
Y assignment Y assignment
Y cable/single cable
1 2 Pin 1: Supply L+ 1 2 Pin 1:
Pin 2: Input signal 2 Pin 2: Output signal 2
5 Pin 3: Supply L– 5 Pin 3: Supply L–
Pin 4: Input signal 1 Pin 4: Output signal 1
4 3 PIN 5: Ground connection PIN 5: Ground connection
4 3
NSA00008

NSA00009

g_nsa_de_00008b g_nsa_xx_00009b

Y-II assignment Y-II assignment


Y-cable/Single cable Single cable Single cable
Pin 1: 1 2 1 2 Pin 1: Pin 1: 1 2 1 2 Pin 1:
Supply L+ Supply L+ Pin 2: Pin 2:
Pin 2: 5 5 Pin 2: Output signal 2 5 5 Pin 3:
Input signal 2 Pin 3: Pin 3: Supply L–
Pin 3: 4 3 4 3 Supply L– Supply L– 4 3 4 3 Pin 4:
Supply L– Pin 4: Pin 4: Output signal 2
NSA00010a

NSA00011

Pin 4: Input signal 2 Output signal 1 Pin 5:


Input signal 1 Pin 5: Pin 5: Earth connection
Pin 5: Earth connection Earth connection
Earth connection IN1 IN2 IN2 g_nsa_de_00010b g_nsa_xx_00011b
Left column (plan view) Right column (plan view) Left column (plan view) Right column (plan view)

1/42 Siemens NS K · 2002


Actuator-Sensor-Interface
I/O Modules for Operation in the Field (IP 65/67)
Compact modules

Overview
Terminal assignment, K45 Series, digital
Input, pnp (M8 socket)
Standard assignment
4 1: Supply L+
3: Supply L–
4: Input signal
3 1
g_nsa_xx_00196m
NSA00196

Input, pnp (M12 socket) Output, pnp (M12 socket) DC 24 V

Standard assignment Standard assignment


1 2 1: Supply L+ 1 2 1: Not assigned
2: Input signal (bridged with Pin 4) 2: Not assigned
5 3: Supply L– 5 3: Supply L–
4: Input signal (bridged with Pin 2) 4: Output signal
4 3 5: Ground connection 4 3 5: Ground connection
NSA00006a g_nsa_xx_00006g NSA00007a g_nsa_xx_00007g

Terminal assignment, K60 Series, analog


Input modules Output modules

3RK1 207–1BQ0.–0AA3 3RK1 207–1BQ0.–0AA3 3RK1 207–3BQ0.–0AA3 3RK1 207–1BQ0.–0AA3


3RK1 207–1BQ4.–0AA3 3RK1 207–1BQ4.–0AA3 3RK1 207–3BQ4.–0AA3 3RK1 207–1BQ4.–0AA3
Current input 4-wire sensor Current input 2-wire sensor Thermo-resistor 2-wire sensor Current output

1 2 1 2 1 2
1 2

5 5 Pt 100 5
5
NSA00014
NSA00016
4 3 4 3 4 3
4 3 Bridge from In– to M(3)
NSA00013 NSA00015
can be set internally via g_nsa_xx_00016b
g_nsa_xx_00013b
parameterisation
g_nsa_xx_00014b g_nsa_xx_00015b

3RK1 207–2BQ0.–0AA3 3RK1 207–3BQ0.–0AA3 3RK1 207–3BQ0.–0AA3 3RK1 207–2BQ0.–0AA3


3RK1 207–2BQ4.–0AA3 3RK1 207–3BQ4–0AA3 3RK1 207–3BQ4.–0AA3 3RK1 207–2BQ4.–0AA3
Voltage input 4-wire sensor Thermo-resistor 4-wire sensor Thermo-resistor 3-wire sensor Voltage output
g_nsa_xx_00019b

1 2 1 2 1 2
1 2

5 5 Pt 100 5
5 Pt 100
NSA00020
4 3 4 3 4 3
4 3
NSA00017 NSA00018
g_nsa_xx_00020b
g_nsa_xx_00017b g_nsa_xx_00018b NSA00019

Pin 1: Supply L+ (DC 24 V) Pin 1: Imeas+ Pin 5: Cable shield


Pin 2: Imeas+ Pin 2: Supply L+
Pin 3: Supply L– (ground) Pin 3: Imeas–
Pin 4: Imeas– Pin 4: Supply L– (ground)
Pin 5: Cable shield Pin 5: Cable shield
All pin assignments are shown without external sensor supply.
max 50 mA for both channels from Pin 1 and Pin 3.

Terminal assignment, K60 Series, pneumatic


Input Output

Y-cable/Single cable Single cable • Pneumatic outputs


• Connection via standard
Pin 1: Supply L+ 1 2 1 2 Pin 1: Supply L+
Pin 2: Input signal 2 Pin 2: 8 mm hose plug-in connector
Pin 3: Supply L– 5 5 Pin 3: Supply L–
Pin 4: Input signal 1 Pin 4: Input signal 2
PIN 5: Ground connec- 4 3 4 3 Pin 5: Earth connection
tion
NSA00010a

IN1 IN2 IN2 g_nsa_de_00010b


Left column (plan view) Right column (plan view)

Siemens NS K · 2002 1/43