VICTAULIC® IS AN ISO 9001 CERTIFIED COMPANY
All materials, including pipe, machinery, structures and buildings Installation to cold condition (80°F to 40°F)
experience dimension changes as a result of changes in 80°F (26°C) 0.580" per 100 ft.
temperatures. This report covers considerations for 40°F (4°C) 0.300" per 100 ft.
accommodating thermal expansion and contraction. Movement
due to other causes (e.g.: seismic, etc.) must be added to pipe line Difference: 0.280" per 100 ft. or 0.672" per 240 ft.
thermal growth. Pipe subjected to temperature changes will be Installation to hot condition (80°F to 220°F)
placed in a condition of stress, exerting potentially damaging
220°F(104°C) 1.680" per 100 ft.
reactive forces and moments on components or equipment.
80°F(26°C) 0.580" per 100 ft.
Three common methods of accommodating this pipe movement
are to 1) provide an expansion joint; 2) allow the system to “free- Difference: 1.100" per 100 ft. or 2.640" per 240 ft.
float” whereby the pipe would be allowed to move in a desired Therefore, the expansion joint is to be set up with at least the
direction through the use of anchoring and/or guidance, if capability to allow 0.672" of pipe contraction and at least 2.640" of
necessary, taking into account the capability of branch connection pipe expansion when installed at 80°F (26°C).
or changes in direction which may have resultant harmful bending
moments; or 3) utilize the linear movement/deflection capabilities of
flexible grooved couplings.
TABLE 1
The selection of either of these methods is dependent on the type
Thermal Expansion Thermal Expansion
of piping system and the designer's preference. Since it is of Pipe of Pipe
impossible to predict all system designs, it is the intent here to call Inches per 100 ft. Inches per 100 ft.
attention to the mechanical advantages of the grooved piping mm per 100 meters mm per 100 meters
method and how it can be used to the piping system designer's Temp. Carbon Stain. Temp. Carbon Stain.
benefit. These examples are presented to stimulate thought and °F/°C Steel Copper Steel °F/°C Steel Copper Steel
should not be considered as recommendations for a specific –40 –0.288 –0.421 –0.461 180 1.360 2.051 2.074
–40 –24,0 –35,1 –38,4 82 113,2 170,9 172,9
system.
–20 –0.145 –0.210 – 0.230 200 1.520 2.296 2.304
The first step in accommodating thermal movement is to compute –28 –12,1 –17,4 –19,0 93 126,6 191,3 191,9
the exact change in the linear length of the piping system over the 0 0 0 0 212 1.610 2.428 2.442
–17 0 0 0 100 134,2 202,4 203,4
distance of interest, along with a suitable safety factor. The actual
20 0.148 0.238 0.230 220 1.680 2.516 2.534
expansion of 100-foot pipe lengths has been computed at different –6 12,5 19,7 19,0 104 140,1 209,7 211,3
temperatures for the most common piping materials (carbon steel, 32 0.230 0.366 0.369 230 1.760 2.636 2.650
stainless steel and copper tubing) and are shown in Table 1. These 0 19,0 30,5 30,8 110 146,7 219,8 220,8
values should not be applied to pipe of alternate materials as they 40 0.300 0.451 0.461 260 2.020 — —
will vary. Expansion coefficients may vary 5% or more when 4 24,9 37,7 38,4 126 168,3 — —
obtained from different sources and should be taken into account. 60 0.448 0.684 0.691 280 2.180 — —
15 37,4 57,1 57,7 137 181,8 — —
An example illustrating the use of Table 1 follows:
80 0.580 0.896 0.922 300 2.350 — —
Given: 240-foot long carbon steel pipe 26 48,2 74,8 76,8 148 195,9 — —
Maximum operating temperature = 220°F (104°C) 100 0.753 1.134 1.152 320 2.530 — —
Minimum operating temperature = 40°F (4°C) 37 62,7 94,5 96,1 160 211,0 — —
Temperature at time of installation = 80°F (26°C) 120 0.910 1.366 1.382 340 2.700 — —
48 75,8 113,9 115,2 171 225,1 — —
Note: To assure the maximum life for the service 140 1.064 1.590 1.613 350 2.790 — —
intended, proper gasket selection is essential. 60 88,6 132,6 134,5 176 232,6 — —
Reference should always be made to the latest 160 1.200 1.804 1.843
71 100,1 150,3 153,6
Victaulic Gasket Selection Guide for
recommendations.
Calculation: From Table 1, carbon steel pipe expansion
220°F (104°C) 1.680" per 100 ft. of carbon steel pipe
40°F (4°C) 0.300" per 100 ft. of carbon steel pipe
Difference: 1.380" per 100 ft. of carbon steel pipe for
temperatures 40°F to 220°F
Therefore, 240-feet of pipe = 240 (1.380) = 3.312"
100
® REGISTERED TRADEMARK OF VICTAULIC – © COPYRIGHT 1998 VICTAULIC – PRINTED IN U.S.A. 1554 REV C
expansion joints. The force acting on the intermediate anchor is 24 24.000 8' - 0" 28' - 0"
600 610,0 2438,4 8534,4
due to friction at guides, weight of supports or hangers, and the
activation force required to compress or expand an expansion
joint.
Pipe alignment guides are essential to ensure axial movement "The Mover"
Intermediate 2nd 1st 1st 2nd Intermediate
of the expansion joint. Whenever possible, the expansion joint Guide Guide Guide Guide Guide Guide
should be located adjacent to an anchor within four (4) pipe
diameters. The first and second alignment guides on the
opposite side of the expansion joint should be located a
maximum distance of four (4) and fourteen (14) pipe diameters,
respectively. Additional intermediate guides may be required Support
throughout the system for pipe alignment. If the expansion joint 14D 4D
cannot be located adjacent to an anchor, install guides on both
sides of the unit, as mentioned.
∆ L Movement Due G
Y
to Pressure Thrusts
Θ
D
Θ Offset Must be of
Sufficient Length L
Y = L SIN Θ
Θ = SIN -1 G
3. Victaulic Flexible Grooved Couplings Utilizing Their Linear D
Movement and Deflection Capabilities. Y= G✕L
D
When designing piping joined with flexible mechanical grooved
type couplings, it is necessary to give consideration to certain Y = Misalignment (Inches)
characteristics of these couplings. These characteristics G = Maximum Allowable Pipe End Movement (Inches) as
distinguish flexible groove type couplings from other types and shown under performance data (published value to be
methods of pipe joining. When this is understood, the designer reduced by Design Tolerance).
can utilize the many advantages that these couplings provide.
Θ = Maximum Deflection (Degrees) from Center Line as
Linear movement available at flexible grooved pipe joints is shown under performance data (published value to be
published under performance data for each Victaulic coupling reduced by Design Tolerance).
style. These values are MAXIMUMS. For design and illustration
D = Pipe Outside Diameter (Inches)
purposes, these figures should be reduced by the following
factors to allow for pipe groove tolerances. L = Pipe Length (Inches)
NOTE: Joints which are fully deflected can no longer provide
linear movement. Partially deflected joints will provide some
portion of linear movement.
Flexible grooved type couplings allow angular flexibility and
rotational movement to take place at joints. These features
provide advantages in installing and engineering piping
systems, but must be considered when determining hanger and
support spacing.
LINEAR MOVEMENT TOLERANCE
³⁄₄ - 3¹⁄₂" (20 - 90 mm) – Reduce published figures by 50%
4" (100 mm) and larger – Reduce published figures by 25%
Standard roll grooved pipe will provide one-half the
expansion/contraction or deflection capabilities of the same
size standard cut groove pipe. Sag Due to
Flexibility
Where full linear movement is required, the Victaulic Style 155
Expansion Joint can be used with special, precisely grooved
nipples. Refer to Section 09.05 for additional information.
Angular deflection available at flexible grooved pipe joints is Front Side
published under Performance Data for each Victaulic coupling Elevation View
style. These values are MAXIMUMS. For design and illustration
purposes, these figures should be reduced by the following As illustrated above, it is obvious that this system would require
factors to allow for pipe grooving tolerances. further hangers (or use of Zero-Flex ® rigid couplings) to
Θ = Maximum angular deflection between center lines as shown eliminate the drooping of the pipes that would occur. Hanger
under Performance Data. positions must be considered in relation to the angular and
rotational movement that will occur at joints.
Flexible couplings allow linear movement, therefore,
consideration must be given to pressure thrusts which would
allow the pipe ends to move to the maximum extent allowed by
the coupling, which would accumulate at the end of the system,
if the joints had been installed butted or only partially opened
when pressurized.
Θ
Θ
ANGULAR MOVEMENT TOLERANCE
³⁄₄ - 3¹⁄₂" (20 - 90 mm) – Reduce published figures by 50%
4" (100 mm) and larger – Reduce published figures by 25%
Standard cut grooved pipe will provide double the
expansion/contraction or deflection capabilities of the same
size standard roll groove pipe.
Movement Due
to Pressure Thrust
Plan View
(Zero Pressure)
Offset
Plan View
(Pressurized)
Offsets have to be capable of deflecting sufficiently to prevent Hanger
harmful bending moments which would be induced at the joints
of the offset. Note, if the pipes were to expand due to thermal
changes, then further growth of the pipes would also take place
at the ends. Gross effect of
Lateral
Angular deflection at butted or fully spaced joints is not possible Force inadequate lateral
restraint on suspended system.
unless the ends of the pipes can shorten and grow as required. (illustration exaggerated for clarity)
F FULLY APART
Θ Expansion Only
Lateral forces (F) will always act on deflected joints due to FULLY BUTTED
internal pressure. A fully deflected joint will no longer be Contraction Only
capable of providing the full linear movement normally available
at the joint.
Joints Deflected
No Expansion/Contraction
Available
PARTIALLY GAPPED
Expansion and Contraction
The grooved piping method will not allow both maximum linear
movement and maximum angular movement simultaneously at
the same joint. If both are expected simultaneously, systems
should be designed with sufficient joints to accommodate both,
including allowance for recommended tolerances. = Anchor = Lateral Resistance
For anchored systems, where pressure thrusts do not act to
hold the joints in tension, or in systems where the joints have Movement in piping systems due to thermal changes can be
been intentionally deflected (e.g., curves), provide lateral accommodated with the grooved piping method. Sufficient
restraint to prevent movement of the pipes due to pressure flexible joints must be available to accommodate anticipated
thrusts acting at deflections. Lightweight hangers are not movement, including Movement Tolerance. If anticipated
adequate in preventing sideways movement of pipes. It should movement will be greater than provided by the total number of
be anticipated that small deflections will occur in all straight joints in the system, additional expansion in the form of a
lines and side thrusts will be exerted on the joints. Victaulic Style 150 Mover or Style 155 Expansion Joint should
be used (Refer to Section 09.04 or 09.05).
Example 1
FIGURE B
Thermal Contraction
Pipeline Shrinks – Loop Expands
7 14 24
6.5
3 13 20 &
22
6 12
18
5.5 11
2¹⁄₂
10 16
5
4.5 2 9
14
4 8
12
3.5 1¹⁄₂ 7 10
1¹⁄₄ 6
3
8
2.5 1 5
4 6
2
³⁄₄ 5
1.5 3
4
1 2
.5 1
0 0
1 2 3 4 5 1 2 3 4 5
Design Thermal Expansion † (Inches) Design Thermal Expansion † (Inches)
(∆ X) (∆ X)
FIGURE E
EXPANSION LOOP DESIGN UTILIZING VICTAULIC FLEXIBLE COUPLINGS AND FITTINGS*
VICTAULIC ROLL GROOVED PIPE
Nominal Pipe Size Nominal Pipe Size
(Inches) (Inches)
Length of Perpendicular Branches of Expansion Loop (feet) (A)
Length of Perpendicular Branches of Expansion Loop (feet) (A)
14 3¹⁄₂ 28
24
13 3 26
20 &
12 24 22
22 18
11
2¹⁄₂ 20
10
16
9 18
2
8 16 14
14 12
7 1¹⁄₂ 10
6 12
1¹⁄₄
10 8
5
1
4 8 6
3
³⁄₄ 6 5
4 4
2
1 2
0 0
1 2 3 4 5 1 2 3 4 5
Design Thermal Expansion † (Inches) Design Thermal Expansion † (Inches)
(∆ X) (∆ X)
* Based on pipe grooved in accordance with Victaulic specifications. † Valves include design tolerances: 50% reduction for sizes below 4"/25% reduction for sizes 4" and larger.
material, expands and contracts with these temperature NOTE: Expansion Loop should be located between two anchors and the pipe should
be guided so as to direct the movement into the loop.
changes. Table 1 in Section 26.02 shows the actual expansion
of 100-foot (30,5 m) pipe lengths for copper tubing. Calculations
for the anticipated expansion/contraction can be obtained from References:
the example shown in 26.02.
(1) Copper/Brass/Bronze Product Handbook, Copper
The necessary length of copper tube expansion loop can be Development Association, Inc.
calculated from the following formulas (1) (2):
(2) Source book on Copper and Copper Alloys, American
3EDe Society for Metals.
L= --------------
S
L = Loop length, in inches, as shown in the figure below:
2H + W = L
H = 2W
5W = L
L = 88.32
De