Cooling Loas San Isidro Mun Hall
Cooling Loas San Isidro Mun Hall
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 32.3 14 14 0.56
West 64.6 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 103.3 26.0 0.37
West 86.1 41.0 0.37
East 150.6 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 96.8 20.0 1.13
Partition 322.4 15.0 0.36
Ceiling 318.6 15.0 0.36
Floor 318.6 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 19 20.0 1.08
Internal Heat
People 10 255 0
Lights 319 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 19 73.5 0.68
People 10 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 723 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 19 20.0 1.08
hum diff const
Latent 19 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH
SOUTH 32.3 103.3
- WEST 64.6 86.1
253 EAST 150.6
5,712 NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 318.60 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 9 ft
994 NO OF F.A.CHANGES 15 PER HR.
1,306 NO. OF PEOPLE 10 0.03
1,728 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
2,189 BPF 0.1
1,741 CFM/PERSON 10
1,720 EXHAUST 0
2,026 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 41 PARTITIONS (1 if Mod.Partitions exists else
CEILING 319 (1 if Mod.Ceiling Panels exist
2,437 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,631 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.84 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.84 REV. TR
- Dehumd. CFM 1040 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
25,192
5% 1,089 FRESH AIR REQUIREMENT
26,281 NOS CFM/PER
PEOPLE 10
- EXHAUST
0.10 96 NO. OF A/CHANGES
2,437 TOTAL FRESH AIR
683 Ventilation cfm/ft2 319 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,542 INSIDE 69.0 58.9
4,757
5% 238 DIFF. -13.0
4,995
31,276 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 372 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 860 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
32,507 3. ENTERING AIR MOISTURE CONTENT
5% 1,625 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
34,133 ( Tadp + (BF(Tedb - T adp)))
3.5554939369 2.84 5. SUPPLY AIR CFM
0.84 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,040 bypassing RA only, use deh. CFM
365.60
372.32
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 19
0
0
19
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.02 0F
23.40
75.36 0F
68.63 Gr./lb
51.33 0F
1059.02 0F
T ewb = F
0
T lwb = F
0
330.86
349.35
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 75
0
0
75
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.84 0F
23.40
76.06 0F
76.25 Gr./lb
51.32 0F
1408.72 0F
T ewb = F
0
T lwb = F
0
314.95
338.26
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 124
0
0
124
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
53.21 0F
23.40
76.38 0F
79.94 Gr./lb
51.32 0F
1803.20 0F
T ewb = F
0
T lwb = F
0
308.82
332.56
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 93
0
0
93
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
53.27 0F
23.40
76.43 0F
80.52 Gr./lb
51.32 0F
1305.67 0F
T ewb = F
0
T lwb = F
0
349.60
365.59
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 102
0
0
102
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.62 0F
23.40
75.88 0F
74.19 Gr./lb
51.33 0F
2323.55 0F
T ewb = F
0
T lwb = F
0
397.47
403.66
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 23
0
0
23
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
51.96 0F
23.40
75.31 0F
68.06 Gr./lb
51.33 0F
1472.34 0F
T ewb = F
0
T lwb = F
0
GROUND FLOOR
1 MAO1 8 4 32 3.2 10 4.0 1
2 MAO2 8 4 32 3.2 10 4.0 1
3 Storage1 6 3 18 2.2 8 2.7 1
4 Storage2 6 3 18 2.2 8 2.8 1
5 GSO 5 4 20 2.2 9 2.7 1
6 MDRRMO 8 4 32 3.6 9 4.5 1
7 Post Office 6 4 24 3.1 8 3.9 1
8 MTO 6 8 48 6.0 8 7.5 1
9 LCR 28.00 3.6 8 4.6 1
10 MASSO/DAR 10.5 6 63 6.4 10 7.9 1
315 29.3 10.8
18
1 WATER WORKS 29.61 2.8 10 3.6 1
2 ENGG 46.20 4.0 11 5.0 1
3 CONF1 34.65 3.9 9 4.9 1
4 CONF2 46.20 5.3 9 6.7 1
Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 180.8 39 13 0.56
South 0.0 14 14 0.56
West 64.6 158 163 0.56
East 138.6 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 176.5 41.0 0.37
East 90.4 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 516.5 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 383.9 20.0 1.13
Partition 180.8 15.0 0.36
Ceiling 516.5 15.0 0.36
Floor 516.5 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 77 20.0 1.08
Internal Heat
People 15 255 0
Lights 516 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 77 73.5 0.68
People 15 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 1209 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 77 20.0 1.08
hum diff const
Latent 77 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 180.8
SOUTH
3,948 WEST 64.6 176.5
- EAST 138.6 90.4
5,712 NW 0.0
12,262 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 516.48 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
2,677 NO. OF PEOPLE 15 0.03
1,037 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
4,132 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
8,677 BPF 0.1
976 CFM/PERSON 10
EXHAUST 0
3,285 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 167 PARTITIONS (1 if Mod.Partitions exists else
CEILING 516 (1 if Mod.Ceiling Panels exist
3,951 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
2,644 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.87 REV. ESHR
ADP 49.00 REV. ADP
- TR 5.98 REV. TR
- Dehumd. CFM 2190 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
52,881
5% 2,473 FRESH AIR REQUIREMENT
55,354 NOS CFM/PER
PEOPLE 15
- EXHAUST
0.10 387 NO. OF A/CHANGES
3,951 TOTAL FRESH AIR
683 Ventilation cfm/ft2 516 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
2,578 INSIDE 69.0 58.9
7,599
5% 380 DIFF. -13.0
7,979
63,334 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 1,506 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 3,485 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
68,325 3. ENTERING AIR MOISTURE CONTENT
5% 3,416 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
71,741 ( Tadp + (BF(Tedb - T adp)))
7.4730467582 5.98 5. SUPPLY AIR CFM
0.87 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
2,190 bypassing RA only, use deh. CFM
366.37
379.33
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 77
0
0
77
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.40 0F
23.40
75.68 0F
72.08 Gr./lb
51.33 0F
2267.82 0F
T ewb = F
0
T lwb = F
0
387.12
392.04
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 15
0
0
15
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
51.89 0F
23.40
75.25 0F
67.47 Gr./lb
51.34 0F
1234.43 0F
T ewb = F
0
T lwb = F
0
379.03
384.77
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 21
0
0
21
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
51.95 0F
23.40
75.30 0F
67.97 Gr./lb
51.33 0F
1385.56 0F
T ewb = F
0
T lwb = F
0
344.51
359.51
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 32
0
0
32
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.58 0F
23.40
75.83 0F
73.75 Gr./lb
51.33 0F
773.31 0F
T ewb = F
0
T lwb = F
0
382.19
387.40
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 12
0
0
12
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
51.91 0F
23.40
75.27 0F
67.66 Gr./lb
51.34 0F
864.47 0F
T ewb = F
0
T lwb = F
0
380.12
385.48
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 12
0
0
12
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
51.93 0F
23.40
75.28 0F
67.76 Gr./lb
51.34 0F
835.50 0F
T ewb = F
0
T lwb = F
0
372.38
378.83
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 21
0
0
21
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.00 0F
23.40
75.34 0F
68.41 Gr./lb
51.33 0F
1213.43 0F
T ewb = F
0
T lwb = F
0
372.38
378.83
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 21
0
0
21
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.00 0F
23.40
75.34 0F
68.41 Gr./lb
51.33 0F
1213.43 0F
T ewb = F
0
T lwb = F
0
374.38
380.66
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 21
0
0
21
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
51.99 0F
23.40
75.33 0F
68.30 Gr./lb
51.33 0F
1250.62 0F
T ewb = F
0
T lwb = F
0
333.53
351.02
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 39
0
0
39
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.77 0F
23.40
76.00 0F
75.55 Gr./lb
51.32 0F
777.75 0F
T ewb = F
0
T lwb = F
0
381.63
386.88
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 12
0
0
12
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
51.92 0F
23.40
75.27 0F
67.69 Gr./lb
51.34 0F
856.43 0F
T ewb = F
0
T lwb = F
0
383.62
388.72
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 12
0
0
12
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
51.91 0F
23.40
75.26 0F
67.59 Gr./lb
51.34 0F
885.39 0F
T ewb = F
0
T lwb = F
0
347.02
361.68
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 32
0
0
32
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.55 0F
23.40
75.81 0F
73.48 Gr./lb
51.33 0F
796.56 0F
T ewb = F
0
T lwb = F
0
388.89
393.64
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
2 15
0
0
15
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
51.88 0F
23.40
75.24 0F
67.37 Gr./lb
51.34 0F
1284.90 0F
T ewb = F
0
T lwb = F
0
370.60
382.92
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 77
0
0
77
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.35 0F
23.40
75.64 0F
71.65 Gr./lb
51.33 0F
2407.64 0F
T ewb = F
0
T lwb = F
0
349.05
363.42
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
5 32
0
0
32
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
52.53 0F
23.40
75.79 0F
73.26 Gr./lb
51.33 0F
816.14 0F
T ewb = F
0
T lwb = F
0
Load Calculation
Ground Floor RULE OF THUMB
L W SQM BTU/SQM
Water Works 8 6 48 700
Assessors Office 6.5 5 32.5 700
3 3.5 10.5 700
Accounting 8 6 48 800
5.7 6 34.2 800
BIR 3 5 15 900
Second Floor
Vice Mayor's Office 5.5 4 22 900
VM Conference Room 5.5 4.5 24.75 900
SB Session Hall 10.5 8 84 900
LiCensing Area 5.5 4 22 900
Public Waiting Area 4 5.5 22 900
C:\Progr
amData\
FLEXnet\
adskflex
_00691b
00_tsf.da
ta.backu
p
TONS
TONS HP SQM/TON TON HP CAPACITY TYPE
2.8 3.5 18 2.67 3.33 3TR Floor Mounted
1.9 2.4 18 1.81 2.26 3TR Floor Mounted
0.6 0.8 18 0.58 0.73
2.99
3.2 4.0 16 4.00 5.00 5TR Floor Mounted
- 0.1 - 0.2 16 - 0.14 - 0.17
18 - -
2.4 3.0 20 2.20 2.75 3HP Floor Mounted
18 - -
3.2 4.0 16 3.00 3.75 3TR x 2u Floor Mounted
2.3 2.9 16 2.14 2.67 Floor Mounted
18 - -
5.4 6.7 16 5.38 6.72 3TR Floor Mounted
0.9 1.1 16 0.88 1.09 5TR Floor Mounted
18 -
1.1 1.4 18 0.83 1.04 1.5HP Wall Mounted
18 - -
4.8 6.0 16 4.00 5.00 5TR x2 Floor Mounted
4.8 6.0 16 4.00 5.00 Floor Mounted
2.7 3.4 16 2.25 2.81 Floor Mounted
44.9 45.0 0
check
5.5
1.36
18hp
R Value of Concrete Wall