Cooling and Dehumidifying Heat Load Est

Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 32.3 14 14 0.56
West 64.6 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 103.3 26.0 0.37
West 86.1 41.0 0.37
East 150.6 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 96.8 20.0 1.13
Partition 322.4 15.0 0.36
Ceiling 318.6 15.0 0.36
Floor 318.6 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 19 20.0 1.08
Internal Heat
People 10 255 0
Lights 319 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 19 73.5 0.68
People 10 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 723 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 19 20.0 1.08
hum diff const
Latent 19 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH
SOUTH 32.3 103.3
- WEST 64.6 86.1
253 EAST 150.6
5,712 NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 318.60 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 9 ft
994 NO OF F.A.CHANGES 15 PER HR.
1,306 NO. OF PEOPLE 10 0.03
1,728 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
2,189 BPF 0.1
1,741 CFM/PERSON 10
1,720 EXHAUST 0
2,026 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 41 PARTITIONS (1 if Mod.Partitions exists else
CEILING 319 (1 if Mod.Ceiling Panels exist
2,437 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,631 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.84 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.84 REV. TR
- Dehumd. CFM 1040 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
25,192
5% 1,089 FRESH AIR REQUIREMENT
26,281 NOS CFM/PER
PEOPLE 10
- EXHAUST
0.10 96 NO. OF A/CHANGES
2,437 TOTAL FRESH AIR
683 Ventilation cfm/ft2 319 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,542 INSIDE 69.0 58.9
4,757
5% 238 DIFF. -13.0
4,995
31,276 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 372 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 860 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
32,507 3. ENTERING AIR MOISTURE CONTENT
5% 1,625 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
34,133 ( Tadp + (BF(Tedb - T adp)))
3.5554939369 2.84 5. SUPPLY AIR CFM
0.84 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,040 bypassing RA only, use deh. CFM

365.60
372.32
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS glass wall


PARTNS WALL 0.360 3.00 16.8
135.6 GLASS 0.560
51.2 ALL GLASS 1.130 3.00 11.2
PARTITION 0.360 241.024
135.6 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
322.4
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.01
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 19
0
0

19
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.02 0F
23.40

75.36 0F

68.63 Gr./lb

51.33 0F

1059.02 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 65.4 39 13 0.56
South 24.2 14 14 0.56
West 38.7 158 163 0.56
East 32.3 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 251.0 12.0 0.37
South 24.2 26.0 0.37
West 105.9 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 160.6 20.0 1.13
Partition 374.4 15.0 0.36
Ceiling 497.1 15.0 0.36
Floor 497.1 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 75 20.0 1.08
Internal Heat
People 15 255 0
Lights 497 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 75 73.5 0.68
People 15 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 1100 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 75 20.0 1.08
hum diff const
Latent 75 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 65.4 251.0
SOUTH 24.2 24.2
1,428 WEST 38.7 105.9
190 EAST 32.3
3,427 NW 0.0
2,856 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 497.11 sft
ROOF HEIGHT 13 ft
1,114 FALSE CEILING HT. 9 ft
233 NO OF F.A.CHANGES 15 PER HR.
1,606 NO. OF PEOPLE 15 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
3,629 BPF 0.1
2,022 CFM/PERSON 10
2,684 EXHAUST 0
3,162 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 161 PARTITIONS (1 if Mod.Partitions exists else
CEILING 497 (1 if Mod.Ceiling Panels exist
3,803 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
2,545 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.82 REV. ESHR
ADP 49.00 REV. ADP
- TR 4.03 REV. TR
- Dehumd. CFM 1334 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
32,274
5% 1,443 FRESH AIR REQUIREMENT
33,717 NOS CFM/PER
PEOPLE 15
- EXHAUST
0.10 373 NO. OF A/CHANGES
3,803 TOTAL FRESH AIR
683 Ventilation cfm/ft2 497 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
2,345 INSIDE 69.0 58.9
7,203
5% 360 DIFF. -13.0
7,564
41,280 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 1,450 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 3,355 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
46,085 3. ENTERING AIR MOISTURE CONTENT
5% 2,304 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
48,389 ( Tadp + (BF(Tedb - T adp)))
5.0404988585 4.03 5. SUPPLY AIR CFM
0.82 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,334 bypassing RA only, use deh. CFM

330.86
349.35
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS glass wall


PARTNS WALL 0.360 3.00 16.8
GLASS 0.560
271.2 ALL GLASS 1.130 3.00 11.2
PARTITION 0.360 241.024
103.3 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
374.4
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 51.23
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 75
0
0

75
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.84 0F
23.40

76.06 0F

76.25 Gr./lb

51.32 0F

1408.72 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 65.4 39 13 0.56
South 24.2 14 14 0.56
West 38.7 158 163 0.56
East 64.6 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 251.0 12.0 0.37
South 24.2 26.0 0.37
West 105.9 41.0 0.37
East 71.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 497.1 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 192.9 20.0 1.13
Partition 367.6 15.0 0.36
Ceiling 15.0 0.36
Floor 497.1 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 124 20.0 1.08
Internal Heat
People 25 255 0
Lights 497 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 124 73.5 0.68
People 25 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 1100 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 124 20.0 1.08
hum diff const
Latent 124 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 65.4 251.0
SOUTH 24.2 24.2
1,428 WEST 38.7 105.9
190 EAST 64.6 71.0
3,427 NW 0.0
5,712 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 497.11 sft
ROOF HEIGHT 13 ft
1,114 FALSE CEILING HT. 9 ft
233 NO OF F.A.CHANGES 15 PER HR.
1,606 NO. OF PEOPLE 25 0.05
815 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
3,977 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
4,359 BPF 0.1
1,985 CFM/PERSON 10
- EXHAUST 0
3,162 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 268 PARTITIONS (1 if Mod.Partitions exists else
CEILING 497 (1 if Mod.Ceiling Panels exist
6,338 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
2,545 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.80 REV. ESHR
ADP 49.00 REV. ADP
- TR 5.33 REV. TR
- Dehumd. CFM 1679 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
40,572
5% 1,858 FRESH AIR REQUIREMENT
42,430 NOS CFM/PER
PEOPLE 25
- EXHAUST
0.10 621 NO. OF A/CHANGES
6,338 TOTAL FRESH AIR
683 Ventilation cfm/ft2 497 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
2,345 INSIDE 69.0 58.9
9,987
5% 499 DIFF. -13.0
10,487
52,916 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 2,416 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 5,591 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
60,923 3. ENTERING AIR MOISTURE CONTENT
5% 3,046 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
63,970 ( Tadp + (BF(Tedb - T adp)))
6.6634953613 5.33 5. SUPPLY AIR CFM
0.80 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,679 bypassing RA only, use deh. CFM

314.95
338.26
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS glass wall


PARTNS WALL 0.360 3.00 16.8
GLASS 0.560
135.6 ALL GLASS 1.130 3.00 11.2
PARTITION 0.360 241.024
232.0 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
367.6
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 50.73
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 124
0
0

124
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

53.21 0F
23.40

76.38 0F

79.94 Gr./lb

51.32 0F

1803.20 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 32.3 14 14 0.56
West 72.6 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 103.3 26.0 0.37
West 159.4 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 372.8 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 104.9 20.0 1.13
Partition 232.0 15.0 0.36
Ceiling 15.0 0.36
Floor 372.8 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 93 20.0 1.08
Internal Heat
People 19 255 0
Lights 373 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 93 73.5 0.68
People 19 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 905 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 93 20.0 1.08
hum diff const
Latent 93 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH
SOUTH 32.3 103.3
- WEST 72.6 159.4
253 EAST
6,426 NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 372.83 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 9 ft
994 NO OF F.A.CHANGES 15 PER HR.
2,417 NO. OF PEOPLE 19 0.05
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
2,983 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
2,371 BPF 0.1
1,253 CFM/PERSON 10
- EXHAUST 0
2,371 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 201 PARTITIONS (1 if Mod.Partitions exists else
CEILING 373 (1 if Mod.Ceiling Panels exist
4,754 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,909 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.79 REV. ESHR
ADP 49.00 REV. ADP
- TR 3.93 REV. TR
- Dehumd. CFM 1212 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
29,345
5% 1,297 FRESH AIR REQUIREMENT
30,641 NOS CFM/PER
PEOPLE 19
- EXHAUST
0.10 466 NO. OF A/CHANGES
4,754 TOTAL FRESH AIR
683 Ventilation cfm/ft2 373 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,929 INSIDE 69.0 58.9
7,831
5% 392 DIFF. -13.0
8,223
38,864 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 1,812 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 4,193 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
44,870 3. ENTERING AIR MOISTURE CONTENT
5% 2,243 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
47,113 ( Tadp + (BF(Tedb - T adp)))
4.9076197147 3.93 5. SUPPLY AIR CFM
0.79 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,212 bypassing RA only, use deh. CFM

308.82
332.56
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS glass wall


PARTNS WALL 0.360 3.00 16.8
GLASS 0.560
ALL GLASS 1.130 3.00 11.2
PARTITION 0.360 241.024
232.0 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
232.0
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 50.28
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 93
0
0

93
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

53.27 0F
23.40

76.43 0F

80.52 Gr./lb

51.32 0F

1305.67 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 316.3 39 13 0.56
South 316.3 14 14 0.56
West 60.3 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 90.4 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 692.9 20.0 1.13
Partition 301.3 15.0 0.36
Ceiling 677.9 15.0 0.36
Floor 677.9 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 102 20.0 1.08
Internal Heat
People 20 255 0
Lights 678 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 102 73.5 0.68
People 20 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 1446 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 102 20.0 1.08
hum diff const
Latent 102 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 316.3
SOUTH 316.3
6,909 WEST 60.3 90.4
2,480 EAST
5,331 NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 677.88 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 9 ft
- NO OF F.A.CHANGES 15 PER HR.
1,371 NO. OF PEOPLE 20 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
15,661 BPF 0.1
1,627 CFM/PERSON 10
3,661 EXHAUST 0
4,311 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 220 PARTITIONS (1 if Mod.Partitions exists else
CEILING 678 (1 if Mod.Ceiling Panels exist
5,186 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
3,470 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.85 REV. ESHR
ADP 49.00 REV. ADP
- TR 6.36 REV. TR
- Dehumd. CFM 2222 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
53,640
5% 2,511 FRESH AIR REQUIREMENT
56,151 NOS CFM/PER
PEOPLE 20
- EXHAUST
0.10 508 NO. OF A/CHANGES
5,186 TOTAL FRESH AIR
683 Ventilation cfm/ft2 678 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
3,083 INSIDE 69.0 58.9
9,460
5% 473 DIFF. -13.0
9,933
66,084 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 1,977 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 4,574 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
72,635 3. ENTERING AIR MOISTURE CONTENT
5% 3,632 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
76,267 ( Tadp + (BF(Tedb - T adp)))
7.9444348663 6.36 5. SUPPLY AIR CFM
0.85 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
2,222 bypassing RA only, use deh. CFM

349.60
365.59
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS glass wall


PARTNS WALL 0.360 3.00 16.8
GLASS 0.560
120.5 ALL GLASS 1.130 3.00 11.2
PARTITION 0.360 241.024
180.8 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
301.3
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.24
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 102
0
0

102
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.62 0F
23.40

75.88 0F

74.19 Gr./lb

51.33 0F

2323.55 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 32.3 14 14 0.56
West 32.3 158 163 0.56
East 120.5 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 148.5 26.0 0.37
West 88.2 41.0 0.37
East 120.5 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 185.1 20.0 1.13
Partition 301.3 15.0 0.36
Ceiling 301.3 15.0 0.36
Floor 301.3 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 23 20.0 1.08
Internal Heat
People 5 255 0
Lights 301 1.5 3.413
Equipment 1.50 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 23 73.5 0.68
People 5 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 691 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 23 20.0 1.08
hum diff const
Latent 23 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH
SOUTH 32.3 148.5
- WEST 32.3 88.2
253 EAST 120.5 120.5
2,856 NW 0.0
10,663 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 301.28 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 9 ft
1,428 NO OF F.A.CHANGES 15 PER HR.
1,338 NO. OF PEOPLE 5 0.015
1,382 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
4,183 BPF 0.1
1,627 CFM/PERSON 10
1,627 EXHAUST 0
1,916 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 49 PARTITIONS (1 if Mod.Partitions exists else
CEILING 301 (1 if Mod.Ceiling Panels exist
1,152 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,542 ADP&SHR 0 (1 if ADP & SHR revised else
5,120 Motor bkw IF ADP & SHR REVIS
- SHR 0.91 REV. ESHR
ADP 49.00 REV. ADP
- TR 3.65 REV. TR
- Dehumd. CFM 1450 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
35,137
5% 1,501 FRESH AIR REQUIREMENT
36,638 NOS CFM/PER
PEOPLE 5
- EXHAUST
0.10 113 NO. OF A/CHANGES
1,152 TOTAL FRESH AIR
683 Ventilation cfm/ft2 301 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,473 INSIDE 69.0 58.9
3,421
5% 171 DIFF. -13.0
3,592
40,229 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 439 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 1,017 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
41,685 3. ENTERING AIR MOISTURE CONTENT
5% 2,084 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
43,770 ( Tadp + (BF(Tedb - T adp)))
4.55933057 3.65 5. SUPPLY AIR CFM
0.91 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,450 bypassing RA only, use deh. CFM

397.47
403.66
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360 glass wall
180.8 GLASS 0.560 3.00 16.8
ALL GLASS 1.130 3.00 16.8
120.5 PARTITION 0.360 3.00 11.2
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
301.3
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 53.77
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 23
0
0

23
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

51.96 0F
23.40

75.31 0F

68.06 Gr./lb

51.33 0F

1472.34 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Tubigon Municipal Hall
USE INVERTER TYPE REFRIGERANT R410A
Second Floor LNGTH WIDTH SQM TON sqm/tom hp QTY
1 Acctg Storage 8 4 32 3.3 10 4.1 1
2 Acctg Staff 6 4 24 2.2 11 2.8 1
3 Municipal Acct 6 3 18 2.2 8 2.8 1
4 MLGOO 6 3 18 2.3 8 2.8 1
5 Mayor 5 4 20 2.2 9 2.8 1
6 MBO 6 4 24 3.3 7.4 4.1 1
7 SB Secretary 6 8 48 6.3 8 7.9 1
8 Councilor Office 5 4 20 2.2 9 2.8 1
204 24.0 8.5

GROUND FLOOR
1 MAO1 8 4 32 3.2 10 4.0 1
2 MAO2 8 4 32 3.2 10 4.0 1
3 Storage1 6 3 18 2.2 8 2.7 1
4 Storage2 6 3 18 2.2 8 2.8 1
5 GSO 5 4 20 2.2 9 2.7 1
6 MDRRMO 8 4 32 3.6 9 4.5 1
7 Post Office 6 4 24 3.1 8 3.9 1
8 MTO 6 8 48 6.0 8 7.5 1
9 LCR 28.00 3.6 8 4.6 1
10 MASSO/DAR 10.5 6 63 6.4 10 7.9 1
315 29.3 10.8
18
1 WATER WORKS 29.61 2.8 10 3.6 1
2 ENGG 46.20 4.0 11 5.0 1
3 CONF1 34.65 3.9 9 4.9 1
4 CONF2 46.20 5.3 9 6.7 1
Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 180.8 39 13 0.56
South 0.0 14 14 0.56
West 64.6 158 163 0.56
East 138.6 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 176.5 41.0 0.37
East 90.4 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 516.5 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 383.9 20.0 1.13
Partition 180.8 15.0 0.36
Ceiling 516.5 15.0 0.36
Floor 516.5 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 77 20.0 1.08
Internal Heat
People 15 255 0
Lights 516 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 77 73.5 0.68
People 15 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 1209 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 77 20.0 1.08
hum diff const
Latent 77 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 180.8
SOUTH
3,948 WEST 64.6 176.5
- EAST 138.6 90.4
5,712 NW 0.0
12,262 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 516.48 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
2,677 NO. OF PEOPLE 15 0.03
1,037 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
4,132 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
8,677 BPF 0.1
976 CFM/PERSON 10
EXHAUST 0
3,285 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 167 PARTITIONS (1 if Mod.Partitions exists else
CEILING 516 (1 if Mod.Ceiling Panels exist
3,951 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
2,644 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.87 REV. ESHR
ADP 49.00 REV. ADP
- TR 5.98 REV. TR
- Dehumd. CFM 2190 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
52,881
5% 2,473 FRESH AIR REQUIREMENT
55,354 NOS CFM/PER
PEOPLE 15
- EXHAUST
0.10 387 NO. OF A/CHANGES
3,951 TOTAL FRESH AIR
683 Ventilation cfm/ft2 516 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
2,578 INSIDE 69.0 58.9
7,599
5% 380 DIFF. -13.0
7,979
63,334 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 1,506 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 3,485 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
68,325 3. ENTERING AIR MOISTURE CONTENT
5% 3,416 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
71,741 ( Tadp + (BF(Tedb - T adp)))
7.4730467582 5.98 5. SUPPLY AIR CFM
0.87 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
2,190 bypassing RA only, use deh. CFM

366.37
379.33
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS glass wall


PARTNS WALL 0.360 3.00 16.8
GLASS 0.560
180.8 ALL GLASS 1.130 3.00 11.2
PARTITION 0.360 241.024
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
180.8
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.85
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 77
0
0

77
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.40 0F
23.40

75.68 0F

72.08 Gr./lb

51.33 0F

2267.82 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 51.6 158 163 0.56
East 96.4 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 68.9 41.0 0.37
East 24.1 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 148.1 20.0 1.13
Partition 361.5 15.0 0.36
Ceiling 258.2 15.0 0.36
Floor 258.2 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 15 20.0 1.08
Internal Heat
People 8 255 0
Lights 258 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 15 73.5 0.68
People 8 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 585 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 15 20.0 1.08
hum diff const
Latent 15 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH
SOUTH
- WEST 51.6 68.9
- EAST 96.4 24.1
4,570 NW 0.0
8,530 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 258.24 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
1,045 NO. OF PEOPLE 8 0.03
276 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
3,346 BPF 0.1
1,952 CFM/PERSON 10
1,394 EXHAUST 0
1,642 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 33 PARTITIONS (1 if Mod.Partitions exists else
CEILING 258 (1 if Mod.Ceiling Panels exist
1,976 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,322 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.88 REV. ESHR
ADP 49.00 REV. ADP
- TR 3.15 REV. TR
- Dehumd. CFM 1219 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
29,501
5% 1,304 FRESH AIR REQUIREMENT
30,805 NOS CFM/PER
PEOPLE 8
- EXHAUST
0.10 77 NO. OF A/CHANGES
1,976 TOTAL FRESH AIR
683 Ventilation cfm/ft2 258 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,248 INSIDE 69.0 58.9
3,983
5% 199 DIFF. -13.0
4,183
34,988 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 301 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 697 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
35,986 3. ENTERING AIR MOISTURE CONTENT
5% 1,799 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
37,785 ( Tadp + (BF(Tedb - T adp)))
3.9359539841 3.15 5. SUPPLY AIR CFM
0.88 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,219 bypassing RA only, use deh. CFM

387.12
392.04
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360 11.4 34.2
180.8 GLASS 0.560 15.96 13.68
180.8 ALL GLASS 1.130 27.36 47.88
PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
361.5
The ADP Table 32.56
FOR 75.0 & 50%RH 9
SHR ADP 6.375
1 55.2 0.00 47.935
0.92 54 53.01
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 15
0
0

15
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

51.89 0F
23.40

75.25 0F

67.47 Gr./lb

51.34 0F

1234.43 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 32.3 158 163 0.56
East 120.5 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 60.3 12.0 0.37
South 60.3 26.0 0.37
West 88.2 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 152.8 20.0 1.13
Partition 361.5 15.0 0.36
Ceiling 344.3 15.0 0.36
Floor 344.3 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 21 20.0 1.08
Internal Heat
People 10 255 0
Lights 344 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 21 73.5 0.68
People 10 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 777 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 21 20.0 1.08
hum diff const
Latent 21 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 60.3
SOUTH 60.3
- WEST 32.3 88.2
- EAST 120.5
2,856 NW 0.0
10,663 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 344.32 sft
ROOF HEIGHT 13 ft
268 FALSE CEILING HT. 13 ft
580 NO OF F.A.CHANGES 15 PER HR.
1,338 NO. OF PEOPLE 10 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
3,453 BPF 0.1
1,952 CFM/PERSON 10
1,859 EXHAUST 0
2,190 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 45 PARTITIONS (1 if Mod.Partitions exists else
CEILING 344 (1 if Mod.Ceiling Panels exist
2,634 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,763 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.87 REV. ESHR
ADP 49.00 REV. ADP
- TR 3.60 REV. TR
- Dehumd. CFM 1365 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
33,014
5% 1,480 FRESH AIR REQUIREMENT
34,494 NOS CFM/PER
PEOPLE 10
- EXHAUST
0.10 103 NO. OF A/CHANGES
2,634 TOTAL FRESH AIR
683 Ventilation cfm/ft2 344 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,656 INSIDE 69.0 58.9
5,076
5% 254 DIFF. -13.0
5,330
39,824 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 402 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 929 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
41,155 3. ENTERING AIR MOISTURE CONTENT
5% 2,058 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
43,212 ( Tadp + (BF(Tedb - T adp)))
4.5012894836 3.60 5. SUPPLY AIR CFM
0.87 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,365 bypassing RA only, use deh. CFM

379.03
384.77
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360 11.4 34.2
180.8 GLASS 0.560 15.96 13.68
180.8 ALL GLASS 1.130 27.36 47.88
PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
361.5
The ADP Table 32.56
FOR 75.0 & 50%RH 9
SHR ADP 6.375
1 55.2 0.00 47.935
0.92 54 52.65
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 21
0
0

21
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

51.95 0F
23.40

75.30 0F

67.97 Gr./lb

51.33 0F

1385.56 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 32.3 39 13 0.56
South 30.1 14 14 0.56
West 32.3 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 148.5 12.0 0.37
South 0.0 26.0 0.37
West 88.2 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 94.7 20.0 1.13
Partition 241.0 15.0 0.36
Ceiling 215.2 15.0 0.36
Floor 215.2 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 32 20.0 1.08
Internal Heat
People 6 255 0
Lights 215 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 32 73.5 0.68
People 6 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 519 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 32 20.0 1.08
hum diff const
Latent 32 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 32.3 148.5
SOUTH 30.1
705 WEST 32.3 88.2
236 EAST
2,856 NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 215.20 sft
ROOF HEIGHT 13 ft
659 FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
1,338 NO. OF PEOPLE 6 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
2,140 BPF 0.1
1,302 CFM/PERSON 10
1,162 EXHAUST 0
1,369 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 70 PARTITIONS (1 if Mod.Partitions exists else
CEILING 215 (1 if Mod.Ceiling Panels exist
1,646 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,102 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.83 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.15 REV. TR
- Dehumd. CFM 741 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
17,998
5% 729 FRESH AIR REQUIREMENT
18,727 NOS CFM/PER
PEOPLE 6
- EXHAUST
0.10 161 NO. OF A/CHANGES
1,646 TOTAL FRESH AIR
683 Ventilation cfm/ft2 215 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,106 INSIDE 69.0 58.9
3,596
5% 180 DIFF. -13.0
3,776
22,503 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 628 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 1,452 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
24,583 3. ENTERING AIR MOISTURE CONTENT
5% 1,229 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
25,812 ( Tadp + (BF(Tedb - T adp)))
2.68873146 2.15 5. SUPPLY AIR CFM
0.83 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
741 bypassing RA only, use deh. CFM

344.51
359.51
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360 glass wall
GLASS 0.560 3.00 16.8
120.5 ALL GLASS 1.130
PARTITION 0.360 3.00 11.2
120.5 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
241.0
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 51.74
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 32
0
0

32
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.58 0F
23.40

75.83 0F

73.75 Gr./lb

51.33 0F

773.31 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 24.1 39 13 0.56
South 90.4 14 14 0.56
West 0.0 158 163 0.56
East 60.3 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 174.7 20.0 1.13
Partition 367.6 15.0 0.36
Ceiling 193.7 15.0 0.36
Floor 193.7 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 12 20.0 1.08
Internal Heat
People 6 255 0
Lights 194 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 12 73.5 0.68
People 6 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 387 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 12 20.0 1.08
hum diff const
Latent 12 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 24.1
SOUTH 90.4
526 WEST
709 EAST 60.3
- NW 0.0
5,331 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 193.68 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
- NO. OF PEOPLE 6 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
3,949 BPF 0.1
1,985 CFM/PERSON 10
1,046 EXHAUST 0
1,232 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 25 PARTITIONS (1 if Mod.Partitions exists else
CEILING 194 (1 if Mod.Ceiling Panels exist
1,482 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
992 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.87 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.23 REV. TR
- Dehumd. CFM 853 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
20,689
5% 864 FRESH AIR REQUIREMENT
21,553 NOS CFM/PER
PEOPLE 6
- EXHAUST
0.10 58 NO. OF A/CHANGES
1,482 TOTAL FRESH AIR
683 Ventilation cfm/ft2 194 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
826 INSIDE 69.0 58.9
3,048
5% 152 DIFF. -13.0
3,201
24,754 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 226 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 523 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
25,502 3. ENTERING AIR MOISTURE CONTENT
5% 1,275 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
26,778 ( Tadp + (BF(Tedb - T adp)))
2.7893346314 2.23 5. SUPPLY AIR CFM
0.87 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
853 bypassing RA only, use deh. CFM

382.19
387.40
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360
66.3 GLASS 0.560
ALL GLASS 1.130
180.8 PARTITION 0.360
120.5 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
367.6
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.77
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 12
0
0

12
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

51.91 0F
23.40

75.27 0F

67.66 Gr./lb

51.34 0F

864.47 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 24.1 39 13 0.56
South 90.4 14 14 0.56
West 60.3 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 174.7 20.0 1.13
Partition 238.4 15.0 0.36
Ceiling 193.7 15.0 0.36
Floor 193.7 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 12 20.0 1.08
Internal Heat
People 6 255 0
Lights 194 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 12 73.5 0.68
People 6 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 387 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 12 20.0 1.08
hum diff const
Latent 12 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 24.1
SOUTH 90.4
526 WEST 60.3
709 EAST
5,331 NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 193.68 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
- NO. OF PEOPLE 6 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
3,949 BPF 0.1
1,288 CFM/PERSON 10
1,046 EXHAUST 0
1,232 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 25 PARTITIONS (1 if Mod.Partitions exists else
CEILING 194 (1 if Mod.Ceiling Panels exist
1,482 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
992 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.87 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.17 REV. TR
- Dehumd. CFM 824 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
19,992
5% 829 FRESH AIR REQUIREMENT
20,821 NOS CFM/PER
PEOPLE 6
- EXHAUST
0.10 58 NO. OF A/CHANGES
1,482 TOTAL FRESH AIR
683 Ventilation cfm/ft2 194 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
826 INSIDE 69.0 58.9
3,048
5% 152 DIFF. -13.0
3,201
24,022 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 226 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 523 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
24,770 3. ENTERING AIR MOISTURE CONTENT
5% 1,239 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
26,009 ( Tadp + (BF(Tedb - T adp)))
2.7092600564 2.17 5. SUPPLY AIR CFM
0.87 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
824 bypassing RA only, use deh. CFM

380.12
385.48
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360 11.4 34.2
66.3 GLASS 0.560 15.96 13.68
ALL GLASS 1.130 27.36 47.88
120.5 PARTITION 0.360
51.6 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
238.4
The ADP Table 32.56
FOR 75.0 & 50%RH 9
SHR ADP 6.375
1 55.2 0.00 47.935
0.92 54 52.67
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 12
0
0

12
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

51.93 0F
23.40

75.28 0F

67.76 Gr./lb

51.34 0F

835.50 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 45.2 158 163 0.56
East 64.6 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 120.5 12.0 0.37
South 120.5 26.0 0.37
West 0.0 41.0 0.37
East 176.5 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 109.8 20.0 1.13
Partition 195.8 15.0 0.36
Ceiling 344.3 15.0 0.36
Floor 344.3 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 21 20.0 1.08
Internal Heat
People 10 255 0
Lights 344 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 21 73.5 0.68
People 10 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 689 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 21 20.0 1.08
hum diff const
Latent 21 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 120.5
SOUTH 120.5
- WEST 45.2
- EAST 64.6 176.5
3,999 NW 0.0
5,712 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 344.32 sft
ROOF HEIGHT 13 ft
535 FALSE CEILING HT. 13 ft
1,159 NO OF F.A.CHANGES 15 PER HR.
- NO. OF PEOPLE 10 0.03
2,024 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
2,480 BPF 0.1
1,057 CFM/PERSON 10
1,859 EXHAUST 0
2,190 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 45 PARTITIONS (1 if Mod.Partitions exists else
CEILING 344 (1 if Mod.Ceiling Panels exist
2,634 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,763 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.85 REV. ESHR
ADP 49.00 REV. ADP
- TR 3.20 REV. TR
- Dehumd. CFM 1193 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
28,871
5% 1,273 FRESH AIR REQUIREMENT
30,144 NOS CFM/PER
PEOPLE 10
- EXHAUST
0.10 103 NO. OF A/CHANGES
2,634 TOTAL FRESH AIR
683 Ventilation cfm/ft2 344 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,468 INSIDE 69.0 58.9
4,888
5% 244 DIFF. -13.0
5,132
35,276 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 402 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 929 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
36,607 3. ENTERING AIR MOISTURE CONTENT
5% 1,830 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
38,437 ( Tadp + (BF(Tedb - T adp)))
4.0038994918 3.20 5. SUPPLY AIR CFM
0.85 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,193 bypassing RA only, use deh. CFM

372.38
378.83
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS glass wall


PARTNS WALL 0.360 6.00 11.2
GLASS 0.560
ALL GLASS 1.130 3.00 11.2
195.8 PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
195.8
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.36
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 21
0
0

21
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.00 0F
23.40

75.34 0F

68.41 Gr./lb

51.33 0F

1213.43 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 45.2 158 163 0.56
East 64.6 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 120.5 12.0 0.37
South 120.5 26.0 0.37
West 0.0 41.0 0.37
East 176.5 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 109.8 20.0 1.13
Partition 195.8 15.0 0.36
Ceiling 344.3 15.0 0.36
Floor 344.3 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 21 20.0 1.08
Internal Heat
People 10 255 0
Lights 344 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 21 73.5 0.68
People 10 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 689 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 21 20.0 1.08
hum diff const
Latent 21 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 120.5
SOUTH 120.5
- WEST 45.2
- EAST 64.6 176.5
3,999 NW 0.0
5,712 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 344.32 sft
ROOF HEIGHT 13 ft
535 FALSE CEILING HT. 13 ft
1,159 NO OF F.A.CHANGES 15 PER HR.
- NO. OF PEOPLE 10 0.03
2,024 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
- DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
2,480 BPF 0.1
1,057 CFM/PERSON 10
1,859 EXHAUST 0
2,190 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 45 PARTITIONS (1 if Mod.Partitions exists else
CEILING 344 (1 if Mod.Ceiling Panels exist
2,634 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,763 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.85 REV. ESHR
ADP 49.00 REV. ADP
- TR 3.20 REV. TR
- Dehumd. CFM 1193 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
28,871
5% 1,273 FRESH AIR REQUIREMENT
30,144 NOS CFM/PER
PEOPLE 10
- EXHAUST
0.10 103 NO. OF A/CHANGES
2,634 TOTAL FRESH AIR
683 Ventilation cfm/ft2 344 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,468 INSIDE 69.0 58.9
4,888
5% 244 DIFF. -13.0
5,132
35,276 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 402 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 929 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
36,607 3. ENTERING AIR MOISTURE CONTENT
5% 1,830 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
38,437 ( Tadp + (BF(Tedb - T adp)))
4.0038994918 3.20 5. SUPPLY AIR CFM
0.85 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,193 bypassing RA only, use deh. CFM

372.38
378.83
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS glass wall


PARTNS WALL 0.360 6.00 11.2
GLASS 0.560
ALL GLASS 1.130 3.00 11.2
195.8 PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
195.8
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.36
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 21
0
0

21
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.00 0F
23.40

75.34 0F

68.41 Gr./lb

51.33 0F

1213.43 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 45.2 158 163 0.56
East 64.6 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 120.5 12.0 0.37
South 120.5 26.0 0.37
West 0.0 41.0 0.37
East 176.5 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 344.3 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 109.8 20.0 1.13
Partition 195.8 15.0 0.36
Ceiling 344.3 15.0 0.36
Floor 344.3 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 21 20.0 1.08
Internal Heat
People 10 255 0
Lights 344 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 21 73.5 0.68
People 10 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 689 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 21 20.0 1.08
hum diff const
Latent 21 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 120.5
SOUTH 120.5
- WEST 45.2
- EAST 64.6 176.5
3,999 NW 0.0
5,712 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 344.32 sft
ROOF HEIGHT 13 ft
535 FALSE CEILING HT. 13 ft
1,159 NO OF F.A.CHANGES 15 PER HR.
- NO. OF PEOPLE 10 0.03
2,024 Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
2,755 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
2,480 BPF 0.1
1,057 CFM/PERSON 10
EXHAUST 0
2,190 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 45 PARTITIONS (1 if Mod.Partitions exists else
CEILING 344 (1 if Mod.Ceiling Panels exist
2,634 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,763 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.86 REV. ESHR
ADP 49.00 REV. ADP
- TR 3.29 REV. TR
- Dehumd. CFM 1230 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
29,766
5% 1,318 FRESH AIR REQUIREMENT
31,084 NOS CFM/PER
PEOPLE 10
- EXHAUST
0.10 103 NO. OF A/CHANGES
2,634 TOTAL FRESH AIR
683 Ventilation cfm/ft2 344 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,468 INSIDE 69.0 58.9
4,888
5% 244 DIFF. -13.0
5,132
36,216 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 402 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 929 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
37,547 3. ENTERING AIR MOISTURE CONTENT
5% 1,877 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
39,424 ( Tadp + (BF(Tedb - T adp)))
4.1067112918 3.29 5. SUPPLY AIR CFM
0.86 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,230 bypassing RA only, use deh. CFM

374.38
380.66
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS glass wall


PARTNS WALL 0.360 6.00 11.2
GLASS 0.560
ALL GLASS 1.130 3.00 11.2
195.8 PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
195.8
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.46
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 21
0
0

21
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

51.99 0F
23.40

75.33 0F

68.30 Gr./lb

51.33 0F

1250.62 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 32.3 39 13 0.56
South 120.5 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 88.2 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 258.2 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 152.8 20.0 1.13
Partition 361.5 15.0 0.36
Ceiling 258.2 15.0 0.36
Floor 258.2 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 39 20.0 1.08
Internal Heat
People 8 255 0
Lights 258 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 39 73.5 0.68
People 8 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 516 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 39 20.0 1.08
hum diff const
Latent 39 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 32.3 88.2
SOUTH 120.5
705 WEST
945 EAST
- NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 258.24 sft
ROOF HEIGHT 13 ft
392 FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
- NO. OF PEOPLE 8 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
2,066 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
3,453 BPF 0.1
1,952 CFM/PERSON 10
EXHAUST 0
1,642 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 84 PARTITIONS (1 if Mod.Partitions exists else
CEILING 258 (1 if Mod.Ceiling Panels exist
1,976 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,322 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.82 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.22 REV. TR
- Dehumd. CFM 739 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
17,950
5% 727 FRESH AIR REQUIREMENT
18,676 NOS CFM/PER
PEOPLE 8
- EXHAUST
0.10 194 NO. OF A/CHANGES
1,976 TOTAL FRESH AIR
683 Ventilation cfm/ft2 258 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,101 INSIDE 69.0 58.9
3,953
5% 198 DIFF. -13.0
4,150
22,827 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 753 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 1,743 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
25,322 3. ENTERING AIR MOISTURE CONTENT
5% 1,266 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
26,589 ( Tadp + (BF(Tedb - T adp)))
2.7696474589 2.22 5. SUPPLY AIR CFM
0.82 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
739 bypassing RA only, use deh. CFM

333.53
351.02
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360 glass wall
GLASS 0.560 3.00 11.2
ALL GLASS 1.130
180.8 PARTITION 0.360 3.00 11.2
180.8 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
361.5
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 51.27
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 39
0
0

39
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.77 0F
23.40

76.00 0F

75.55 Gr./lb

51.32 0F

777.75 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 24.1 39 13 0.56
South 90.4 14 14 0.56
West 60.3 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 193.7 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 174.7 20.0 1.13
Partition 238.4 15.0 0.36
Ceiling 193.7 15.0 0.36
Floor 193.7 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 12 20.0 1.08
Internal Heat
People 6 255 0
Lights 194 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 12 73.5 0.68
People 6 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 387 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 12 20.0 1.08
hum diff const
Latent 12 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 24.1
SOUTH 90.4
526 WEST 60.3
709 EAST
5,331 NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 193.68 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
- NO. OF PEOPLE 6 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
1,549 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
3,949 BPF 0.1
1,288 CFM/PERSON 10
EXHAUST 0
1,232 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 25 PARTITIONS (1 if Mod.Partitions exists else
CEILING 194 (1 if Mod.Ceiling Panels exist
1,482 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
992 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.87 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.21 REV. TR
- Dehumd. CFM 845 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
20,496
5% 854 FRESH AIR REQUIREMENT
21,350 NOS CFM/PER
PEOPLE 6
- EXHAUST
0.10 58 NO. OF A/CHANGES
1,482 TOTAL FRESH AIR
683 Ventilation cfm/ft2 194 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
826 INSIDE 69.0 58.9
3,048
5% 152 DIFF. -13.0
3,201
24,550 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 226 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 523 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
25,299 3. ENTERING AIR MOISTURE CONTENT
5% 1,265 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
26,564 ( Tadp + (BF(Tedb - T adp)))
2.7670916939 2.21 5. SUPPLY AIR CFM
0.87 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
845 bypassing RA only, use deh. CFM

381.63
386.88
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360 11.4 34.2
66.3 GLASS 0.560 15.96 13.68
ALL GLASS 1.130 27.36 47.88
120.5 PARTITION 0.360
51.6 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
238.4
The ADP Table 32.56
FOR 75.0 & 50%RH 9
SHR ADP 6.375
1 55.2 0.00 47.935
0.92 54 52.74
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 12
0
0

12
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

51.92 0F
23.40

75.27 0F

67.69 Gr./lb

51.34 0F

856.43 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 24.1 39 13 0.56
South 90.4 14 14 0.56
West 0.0 158 163 0.56
East 60.3 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 193.7 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 174.7 20.0 1.13
Partition 367.6 15.0 0.36
Ceiling 193.7 15.0 0.36
Floor 193.7 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 12 20.0 1.08
Internal Heat
People 6 255 0
Lights 194 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 12 73.5 0.68
People 6 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 387 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 12 20.0 1.08
hum diff const
Latent 12 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 24.1
SOUTH 90.4
526 WEST
709 EAST 60.3
- NW 0.0
5,331 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 193.68 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
- NO. OF PEOPLE 6 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
1,549 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
3,949 BPF 0.1
1,985 CFM/PERSON 10
EXHAUST 0
1,232 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 25 PARTITIONS (1 if Mod.Partitions exists else
CEILING 194 (1 if Mod.Ceiling Panels exist
1,482 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
992 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.87 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.28 REV. TR
- Dehumd. CFM 874 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
21,193
5% 889 FRESH AIR REQUIREMENT
22,082 NOS CFM/PER
PEOPLE 6
- EXHAUST
0.10 58 NO. OF A/CHANGES
1,482 TOTAL FRESH AIR
683 Ventilation cfm/ft2 194 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
826 INSIDE 69.0 58.9
3,048
5% 152 DIFF. -13.0
3,201
25,283 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 226 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 523 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
26,031 3. ENTERING AIR MOISTURE CONTENT
5% 1,302 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
27,333 ( Tadp + (BF(Tedb - T adp)))
2.8471662689 2.28 5. SUPPLY AIR CFM
0.87 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
874 bypassing RA only, use deh. CFM

383.62
388.72
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360
66.3 GLASS 0.560
ALL GLASS 1.130
180.8 PARTITION 0.360
120.5 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
367.6
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 52.84
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 12
0
0

12
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

51.91 0F
23.40

75.26 0F

67.59 Gr./lb

51.34 0F

885.39 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 32.3 39 13 0.56
South 30.1 14 14 0.56
West 32.3 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 148.5 12.0 0.37
South 0.0 26.0 0.37
West 88.2 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 215.2 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 94.7 20.0 1.13
Partition 241.0 15.0 0.36
Ceiling 215.2 15.0 0.36
Floor 215.2 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 32 20.0 1.08
Internal Heat
People 6 255 0
Lights 215 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 32 73.5 0.68
People 6 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 519 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 32 20.0 1.08
hum diff const
Latent 32 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 32.3 148.5
SOUTH 30.1
705 WEST 32.3 88.2
236 EAST
2,856 NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 215.20 sft
ROOF HEIGHT 13 ft
659 FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
1,338 NO. OF PEOPLE 6 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
1,722 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
2,140 BPF 0.1
1,302 CFM/PERSON 10
EXHAUST 0
1,369 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 70 PARTITIONS (1 if Mod.Partitions exists else
CEILING 215 (1 if Mod.Ceiling Panels exist
1,646 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,102 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.84 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.20 REV. TR
- Dehumd. CFM 764 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
18,558
5% 757 FRESH AIR REQUIREMENT
19,315 NOS CFM/PER
PEOPLE 6
- EXHAUST
0.10 161 NO. OF A/CHANGES
1,646 TOTAL FRESH AIR
683 Ventilation cfm/ft2 215 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,106 INSIDE 69.0 58.9
3,596
5% 180 DIFF. -13.0
3,776
23,090 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 628 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 1,452 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
25,170 3. ENTERING AIR MOISTURE CONTENT
5% 1,259 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
26,429 ( Tadp + (BF(Tedb - T adp)))
2.752988835 2.20 5. SUPPLY AIR CFM
0.84 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
764 bypassing RA only, use deh. CFM

347.02
361.68
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360 glass wall
GLASS 0.560 3.00 16.8
120.5 ALL GLASS 1.130
PARTITION 0.360 3.00 11.2
120.5 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
241.0
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 51.88
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 32
0
0

32
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.55 0F
23.40

75.81 0F

73.48 Gr./lb

51.33 0F

796.56 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 32.3 158 163 0.56
East 120.5 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 88.2 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 258.2 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 152.8 20.0 1.13
Partition 361.5 15.0 0.36
Ceiling 258.2 15.0 0.36
Floor 258.2 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 15 20.0 1.08
Internal Heat
People 8 255 0
Lights 258 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 15 73.5 0.68
People 8 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 605 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 15 20.0 1.08
hum diff const
Latent 15 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH
SOUTH
- WEST 32.3 88.2
- EAST 120.5
2,856 NW 0.0
10,663 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 258.24 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
1,338 NO. OF PEOPLE 8 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
2,066 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
3,453 BPF 0.1
1,952 CFM/PERSON 10
EXHAUST 0
1,642 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 33 PARTITIONS (1 if Mod.Partitions exists else
CEILING 258 (1 if Mod.Ceiling Panels exist
1,976 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,322 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.88 REV. ESHR
ADP 49.00 REV. ADP
- TR 3.26 REV. TR
- Dehumd. CFM 1269 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
30,715
5% 1,365 FRESH AIR REQUIREMENT
32,080 NOS CFM/PER
PEOPLE 8
- EXHAUST
0.10 77 NO. OF A/CHANGES
1,976 TOTAL FRESH AIR
683 Ventilation cfm/ft2 258 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,289 INSIDE 69.0 58.9
4,025
5% 201 DIFF. -13.0
4,226
36,306 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 301 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 697 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
37,305 3. ENTERING AIR MOISTURE CONTENT
5% 1,865 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
39,170 ( Tadp + (BF(Tedb - T adp)))
4.0801940238 3.26 5. SUPPLY AIR CFM
0.88 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
1,269 bypassing RA only, use deh. CFM

388.89
393.64
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360 11.4 34.2
180.8 GLASS 0.560 15.96 13.68
180.8 ALL GLASS 1.130 27.36 47.88
PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
361.5
The ADP Table 32.56
FOR 75.0 & 50%RH 9
SHR ADP 6.375
1 55.2 0.00 47.935
0.92 54 53.09
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
2 15
0
0

15
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

51.88 0F
23.40

75.24 0F

67.37 Gr./lb

51.34 0F

1284.90 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 64.6 158 163 0.56
East 241.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 180.8 12.0 0.37
South 60.3 26.0 0.37
West 176.5 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 516.5 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 305.6 20.0 1.13
Partition 120.5 15.0 0.36
Ceiling 516.5 15.0 0.36
Floor 516.5 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 77 20.0 1.08
Internal Heat
People 15 255 0
Lights 516 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 77 73.5 0.68
People 15 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 1209 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 77 20.0 1.08
hum diff const
Latent 77 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 180.8
SOUTH 60.3
- WEST 64.6 176.5
- EAST 241.0
5,712 NW 0.0
21,326 NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 516.48 sft
ROOF HEIGHT 13 ft
803 FALSE CEILING HT. 13 ft
580 NO OF F.A.CHANGES 15 PER HR.
2,677 NO. OF PEOPLE 15 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
4,132 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
6,906 BPF 0.1
651 CFM/PERSON 10
EXHAUST 0
3,285 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 167 PARTITIONS (1 if Mod.Partitions exists else
CEILING 516 (1 if Mod.Ceiling Panels exist
3,951 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
2,644 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.88 REV. ESHR
ADP 49.00 REV. ADP
- TR 6.29 REV. TR
- Dehumd. CFM 2330 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
56,246
5% 2,642 FRESH AIR REQUIREMENT
58,888 NOS CFM/PER
PEOPLE 15
- EXHAUST
0.10 387 NO. OF A/CHANGES
3,951 TOTAL FRESH AIR
683 Ventilation cfm/ft2 516 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
2,578 INSIDE 69.0 58.9
7,599
5% 380 DIFF. -13.0
7,979
66,867 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 1,506 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 3,485 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
71,859 3. ENTERING AIR MOISTURE CONTENT
5% 3,593 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
75,452 ( Tadp + (BF(Tedb - T adp)))
7.8595370745 6.29 5. SUPPLY AIR CFM
0.88 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
2,330 bypassing RA only, use deh. CFM

370.60
382.92
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS glass wall


PARTNS WALL 0.360 3.00 16.8
GLASS 0.560
120.5 ALL GLASS 1.130 3.00 11.2
PARTITION 0.360 241.024
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
120.5
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 53.02
0.84 52 0.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 77
0
0

77
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.35 0F
23.40

75.64 0F

71.65 Gr./lb

51.33 0F

2407.64 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 24.1 39 13 0.56
South 32.3 14 14 0.56
West 32.3 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 148.5 26.0 0.37
West 88.2 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 215.2 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 88.7 20.0 1.13
Partition 241.0 15.0 0.36
Ceiling 215.2 15.0 0.36
Floor 215.2 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 32 20.0 1.08
Internal Heat
People 6 255 0
Lights 215 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 32 73.5 0.68
People 6 255
Appilances 0.20 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 519 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 32 20.0 1.08
hum diff const
Latent 32 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH 24.1
SOUTH 32.3 148.5
526 WEST 32.3 88.2
253 EAST
2,856 NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 215.20 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 13 ft
1,428 NO OF F.A.CHANGES 15 PER HR.
1,338 NO. OF PEOPLE 6 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
1,722 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
2,004 BPF 0.1
1,302 CFM/PERSON 10
EXHAUST 0
1,369 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 70 PARTITIONS (1 if Mod.Partitions exists else
CEILING 215 (1 if Mod.Ceiling Panels exist
1,646 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,102 ADP&SHR 0 (1 if ADP & SHR revised else
3,413 Motor bkw IF ADP & SHR REVIS
- SHR 0.84 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.25 REV. TR
- Dehumd. CFM 784 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
19,029
5% 781 FRESH AIR REQUIREMENT
19,810 NOS CFM/PER
PEOPLE 6
- EXHAUST
0.10 161 NO. OF A/CHANGES
1,646 TOTAL FRESH AIR
683 Ventilation cfm/ft2 215 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,106 INSIDE 69.0 58.9
3,596
5% 180 DIFF. -13.0
3,776
23,585 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 628 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 1,452 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
25,665 3. ENTERING AIR MOISTURE CONTENT
5% 1,283 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
26,948 ( Tadp + (BF(Tedb - T adp)))
2.8071103505 2.25 5. SUPPLY AIR CFM
0.84 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
784 bypassing RA only, use deh. CFM

349.05
363.42
RH TH GR/LB
138.4
50% 64.9
0.0 73.5

REAS (ft2) U' FACTORS


PARTNS WALL 0.360 glass wall
120.5 GLASS 0.560 3.00 16.8
ALL GLASS 1.130 3.00 16.8
PARTITION 0.360 3.00 11.2
120.5 M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
241.0
The ADP Table
FOR 75.0 & 50%RH
SHR ADP
1 55.2 0.00
0.92 54 0.00
0.84 52 52.00
0.78 50 0.00
0.74 48 0.00
0.71 46 0.00
0.69 44 0.00
0.66 40 0.00
0.64 34 0.00

fl. gain exists else 0)

Roof provided Insulation else 0)


Mod.Partitions exists else 0)
Mod.Ceiling Panels exists else 0)
Pre-cooling/TFA exists else 0)
ADP & SHR revised else 0)
IF ADP & SHR REVISED,CONSIDER FOLWG
0.97
50
0.00
AIR QTY CFM 0
HEAT IN KWTO INCREASE ADP 0.00

UIREMENT
ACH NET (CFM)
5 32
0
0

32
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2

-1.8 8.5

52.53 0F
23.40

75.79 0F

73.26 Gr./lb

51.33 0F

816.14 0F

T ewb = F
0

T lwb = F
0

pply CFM, when


Tubigon Municipal Hall

Load Calculation
Ground Floor RULE OF THUMB
L W SQM BTU/SQM
Water Works 8 6 48 700
Assessors Office 6.5 5 32.5 700
3 3.5 10.5 700

Local Civil Registrar 8 8 64 600


-1.25 1.75 -2.1875 700

Budget 8 5.5 44 650

Accounting 8 6 48 800
5.7 6 34.2 800

Treasurer's 10.75 8 86 750


4 3.5 14 750

BIR 3 5 15 900

Public Waiting Area 8 8 64 900


8 8 64 900
4.5 8 36 900

Second Floor
Vice Mayor's Office 5.5 4 22 900
VM Conference Room 5.5 4.5 24.75 900
SB Session Hall 10.5 8 84 900
LiCensing Area 5.5 4 22 900
Public Waiting Area 4 5.5 22 900

HRMO 5 5.5 27.5 900


Administrator 4.5 5.5 24.75 900
Mayor's Conference Room 6.5 5 32.5 900
Mayor's Office 5.5 5 27.5 900
Mayor's Staff Lounge 5 4 20 900
Hallway 20 3 60 900
Lounge Area 8 4 32 900

sb members hall 24 6 144 900


C:\Progr
amData\
FLEXnet\
adskflex
_00691b
00_tsf.da
ta
https://www.landfx.com/kb/autocad-fxcad/erro

C:\Progr
amData\
FLEXnet\
adskflex
_00691b
00_tsf.da
ta.backu
p
TONS
TONS HP SQM/TON TON HP CAPACITY TYPE
2.8 3.5 18 2.67 3.33 3TR Floor Mounted
1.9 2.4 18 1.81 2.26 3TR Floor Mounted
0.6 0.8 18 0.58 0.73
2.99
3.2 4.0 16 4.00 5.00 5TR Floor Mounted
- 0.1 - 0.2 16 - 0.14 - 0.17
18 - -
2.4 3.0 20 2.20 2.75 3HP Floor Mounted
18 - -
3.2 4.0 16 3.00 3.75 3TR x 2u Floor Mounted
2.3 2.9 16 2.14 2.67 Floor Mounted
18 - -
5.4 6.7 16 5.38 6.72 3TR Floor Mounted
0.9 1.1 16 0.88 1.09 5TR Floor Mounted
18 -
1.1 1.4 18 0.83 1.04 1.5HP Wall Mounted
18 - -
4.8 6.0 16 4.00 5.00 5TR x2 Floor Mounted
4.8 6.0 16 4.00 5.00 Floor Mounted
2.7 3.4 16 2.25 2.81 Floor Mounted
44.9 45.0 0

1.7 2.1 16 1.38 1.72 2HP Wall Mounted


1.9 2.3 16 1.55 1.93 3TR Floor Mounted
6.3 7.9 16 5.25 6.56 3TRX2U Floor Mounted
1.7 2.1 16 1.38 1.72 2.5HP Wall Mounted
1.7 2.1 16 1.38 1.72 3hp Wall Mounted

2.1 2.6 16 1.72 2.15 2.5HP Wall Mounted


1.9 2.3 16 1.55 1.93 2.5HP Wall Mounted
2.4 3.0 16 2.03 2.54 3TR Floor Mounted
2.1 2.6 16 1.72 2.15 3TR Wall Mounted
1.5 1.9 16 1.25 1.56 2.5hp Wall Mounted
4.5 5.6 16 3.75 4.69 5TR Floor Mounted
2.4 3.0 16 2.00 2.50 3TR Floor Mounted

10.8 13.5 16 9.00 11.25 3 Floor Mounted


ww.landfx.com/kb/autocad-fxcad/errors/item/1319-security-system-not-functioning.html

check

5.5
1.36
18hp
R Value of Concrete Wall

Outside Air 0.25


Plastering 3/4inch 0.15
CHB 6 0.91
Plastering 3/4inch 0.15
Inside Air 0.61