You are on page 1of 54

Name of Room/ Stall ADIDAS

Dimensions 10m x 5m
Location Ground Floor
Application Retail store
Note: Adidas is a type variety store for
shoes, clothes, etc.

A. WALL
a. FACING NORTH
ATOTAL= AWALL-AWINDOW
A= [L• H] wall-[L•H] window
A= [10 • 3] wall-2[3 • 3] window
.
A= 12m2( )2
A= 129.10ft2
QWALL = U•A•CLTDCORRECTION
QWALL = 0.3472 • 129.10 • 22.96oF
QWALL = 1029.15 BTU/hr.

b. FACING WEST
ATOTAL= AWALL-AWINDOW
A=[L•H] wall
.
A=[5 •3]wall ( )2 = 161.38 ft2
QWALL = U•A•CLTDCORRECTION
QWALL = 0.3472 • 161.38 • 27.11oF
QWALL = 1519 BTU/hr.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent room/stall (Vans stall) is
also Air Conditioned

C. GLASS PARTITION
AREA = [L•H] GLASS – [L•H] ENTRANCE DOOR
= [5 • 3] – [(2 • 2.4)]
.
= 10.2m2( )2
= 109.74 ft2

QGLASS = U•A•∆T
= 0.81 BTU/h.ft2.oF • 109.74 ft2• 10oF
= 889 BTU/hr

D. PLENUM
No Heat Load Calculation for Plenum (ceiling) – the room/area (National Book
Store) On the Second Floor that Overlaps it is also Air Conditioned

E. SOLAR
QSOLAR= A•SC•SHGF•CLF

FACING NORTH
.
Q SOLAR = 2(3m•3m) • 0.55 • 39 • 0.75
= 3115.36 Btu/hr.

1
ROOF
No Heat Load Calculation for Roof – The stall is located on the ground floor

F. OCCUPANTS
3.28 𝑓𝑡 2
AREA = LXW = 5m • 10m = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐
No. Of Occupants = A/N
.
= /
= 13.45 or 14 persons

Qs = no. of occupancy • SHG • CLF


= 14 • 315 Btu/hr. • 1
= 4410 Btu/hr.

QL = no. of occupancy • LHG • CLF


= 14 • 325 Btu/hr. • 1
= 4550 Btu/hr.

G. APPLIANCES
a. COMPUTER
QAPPLIANCES = no. of sources • rated energy • FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.

H. LIGHTING
Wattage = A • N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 • 4.5 watts/𝑓𝑡 = 2420.64 watts

Qlighting = wattage • CLF • 3.413 Btu/hr


= 2420.64 watts •1 • 3.413 Btu/hr
= 8261.64 Btu/hr

Name of Room/Stall VANS


Dimensions 10m x 5m
Location Ground Floor
Application Retail store

Note: Vans is a stall for shoes & foot wears.

2
A. WALL
a. FACING NORTH
ATOTAL= AWALL-AWINDOW
A=[L•H]wall-[L•H]window
.
A= [5 • 3]wall-[3 • 3]window= 6m2 = 64.6 ft2
QWALL = U • A • CLTDCORRECTION
QWALL = 0.3472 • 64.6 • 22.96oF
QWALL = 515 BTU/hr.

b. FACING WEST
ATOTAL= AWALL-AWINDOW
A= [L • H] wall- [ L • H] window
A= [5 • 3] wall- [3 •3] window
.
A= 6m2
A= 64.6 ft2
QWALL = U • A • CLTDCORRECTION
QWALL = 0.3472 • 64.6 ft2 • 27.11oF
QWALL = 608.10BTU/hr.

B. PARTITION WALL
NO Heat Load Calculation for Partition Wall – Adjacent rooms (Adidas and Fila
stall) are also Air Conditioned

C. PARTITION GLASS
A = [L • H] GLASS – [L • H] ENTRANCE DOOR
= [5 • 3] – [2 • 2.4]
.
= 10.52m2
= 34.51 ft2
QGLASS = U • A • ∆T
= 0.81 BTU/h.ft2.oF • 34.51 ft2 • 10oF
= 279.53BTU/hr.

D. PLENUM
No Heat Load Calculation for Plenum (ceiling) – the room/area (National Book
Store) On the Second Floor that Overlaps it is also Air Conditioned
E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING NORTH
.
Q SOLAR = (3mx3m) (0.55)(39)(0.75)
Q SOLAR = 3115.36 Btu/hr.

FACING WEST
.
Q SOLAR = (3mx3m) (0.55)(227)(0.17)
Q SOLAR = 2055.1 Btu/hr.

F. ROOF
No Roof Heat Load Calculation – the stall is located on the ground floor

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = LXW = 5m x 10m = 50 𝑚 = 537.92 𝒇𝒕𝟐
1𝑚

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

3
Qs = no. of occupancy (SHG)(CLF)
= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.

H. APPLIANCES
a. COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41) = 3751BTU/hr
I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
(4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of Room/Stall FILA


Dimensions 10m x 5m
Location Ground Floor
Application Retail store
Note: Fila is a stall for shoes & foot wears

A. WALL
a. FACING WEST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(L)(H)] window
A= [(5)(3)] wall - [(3)(3)] window
.
A= 6m2
A= 64.6 ft2

QWALL = (U)(A) (CLTDCORRECTION)


QWALL = (0.3472) (64.6 ft2) (27.11oF)
QWALL = 608.10BTU/hr

4
B. PARTITION WALL
NO Heat Load Calculation for Partition Wall – Adjacent rooms (Vans and Converse
stall) are also Air Conditioned

C. GLASS PARTITION
AREA = [(L)(H)]GLASS – [(L)(H)]ENTRANCE DOOR
= [(5)(3)] – [(2x2.4)]
.
= 10.52m2
= 34.51 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (34.51 ft2) (10oF)
= 279.53BTU/hr

D. PLENUM
No Heat Load Calculation for Plenum (ceiling) – the room/area (National Book
Store) On the Second Floor that Overlaps it is also Air Conditioned

E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING WEST
.
QSOLAR= (3mx3m) (0.55)(227)(0.17)
Q SOLAR = 2055.1 Btu/hr

F. ROOF
No Roof Heat Load Calculation – the stall is located on the ground floor

G. OCCUPANTS
AREA = LXW
3.28 𝑓𝑡 2
AREA = 5m x 10m = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.

H. APPLIANCES
a. COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41) = 3751BTU/hr.

I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

5
Name of Room/Stall CONVERSE
Dimensions 10m x 5m
Location Ground Floor
Application Retail store
Note: Converse is a stall for shoes and foot wares

A. WALL
a. FACING WEST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(3)(3)] window
A= [(5)(3)] wall - [(3)(3)] window
.
A= 6m2
A= 64.6 ft2
QWALL = (U)(A) (CLTDCORRECTION)
QWALL = (0.3472) (64.6 ft2) (27.11oF)
QWALL = 608.10BTU/hr.

B. PARTITION WALL
NO Heat Load Calculation for Partition Wall – Adjacent rooms (Vans and
Converse stall) are also Air Conditioned

C. PARTITION GLASS
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5)(3)] – [(2x2.4)]
.
= 10.52m2
= 34.51 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (34.51 ft2) (10oF)
= 279.53BTU/hr.

D. PLENUM
No Heat Load Calculation for Plenum (ceiling) - the room/area (Oppo stall) On the
Second Floor that Overlaps it is also Air Conditioned

E. SOLAR
QSOLAR = A(SC)(SHGF)(CLF)

FACING WEST
.
Q SOLAR = (3mx3m) (0.55)(227)(0.17)
= 2055.1 Btu/hr

6
F. ROOF
No Heat Load Calculation for Roof – the stall is located on the ground floor

G. OCCUPANTS
AREA = LXW
3.28 𝑓𝑡 2
AREA = 5m x 10m = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

QS = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr)(1)
= 4410 Btu/hr
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr)(1)
= 4550 Btu/hr

H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41) = 3751BTU/hr
I. LIGHTING
3.28 𝑓𝑡 2
Wattage = A x N = 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
Wattage = 2420.64 watts

Qlighting = wattage (CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of Room/Stall WATSON


Dimensions 10m x 5m
Location Ground Floor
Application Retail store
Note: Watson is a stall for drugs or medicines

A. WALL
a. FACING WEST
ATOTAL= AWALL-AWINDOW
A=[(L)(H)]wall-[(3)(3)]window
A=[(5)(3)]wall-[(3)(3)]window
.
A= 6m2 = 64.6 ft2

7
QWALL = (U)(A) (CLTDCORRECTION)
= (0.3472) (64.6 ft2) (27.11oF)
= 608.10BTU/hr

B. PARTITION WALL
NO Heat Load Calculation for Partition Wall – Adjacent rooms (Converse and
Generic stall) are also Air Conditioned

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(10) (3)] – [(2x2.4)]
.
= 25.2m2
= 271.2 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (271.2 ft2) (10oF)
= 2196.8 BTU/hr.

D. PLENUM
No Heat Load Calculation for Plenum - the room/area (Vivo stall) On the Second
Floor that Overlaps it is also Air Conditioned

E. SOLAR
QSOLAR = A(SC)(SHGF)(CLF)

FACING WEST
.
Q SOLAR = (3mx3m) (0.55)(227)(0.17)
= 2055.1 Btu/hr

F. ROOF
No Heat Load Calculation for Roof – the stall is located on the ground floor

G. OCCUPANTS
AREA = LXW
= 5m x 10m
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= = 13.45 or 14 people

QS = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.

QL = no. of occupancy (LHG)(CLF)


= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.

H. APPLIANCES
a. COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751 BTU/hr.
I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 ) = 2420.64 watts

8
Qlighting = wattage (CLF) (3.413 Btu/hr.)
= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of Room/Stall GENERICA DRUG


Dimensions 10m x 5m
Location Ground Floor
Application Retail store
Note: Generica Drug is a stall for drugs or medicines

A. WALL
No Heat Load Calculation for Wall – there is no wall/s exposed from the outside.

B. PARTITION WALL
AREA = [(𝐿)(𝐻)] Partition Wall
= (10m) (3m)
.
= 30 m2
= 322.75 ft2
QWALL = U•A•∆T
= (0.3021 BTU/h.ft2.oF) (322.75 ft2) (10F)
= 975.1 BTU/hr.

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(10•3 + 5(3)] – [(2x2.4)]
.
= 40.2m2
= 432.6 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (432.6 ft2) (10oF)
= 3504.1 BTU/hr

D. PLENUM
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5379.2 BTU/hr

9
E. SOLAR
No Heat Load Calculation for Solar – the stall is located inside the building and no
window glass exposed directly to sunlight

F. ROOF
No Heat Load Calculation for Roof – the stall is located on the ground floor

G. OCCUPANTS
AREA = LXW
3.28 𝑓𝑡 2
= 5m x 10m = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= = 13.45 or 14 people

QS = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.

H. APPLIANCES
a. COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751 BTU/hr.

I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage (CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of Room/Stall MERCURY


Dimensions 10m x 5m
Location Ground Floor
Application Retail store
Note: Mercury Drug is a stall for drugs
and medicines

10
A. WALL
a. FACING WEST
ATOTAL= AWALL-AWINDOW
A=[(L)(H)] wall - [(3)(3)] window
A= [(5)(3)] wall - [(3)(3)] window
.
A= 6m2
A= 64.6 ft2

QWALL = (U)(A) (CLTDCORRECTION)


QWALL = (0.3472) (64.6 ft2) (27.11oF)
QWALL = 608.10BTU/hr.

B. PARTITION WALL
NO Heat Load Calculation for Partition Wall – Adjacent room/area (Mang Inasal
restaurant) is also Air Conditioned

C. GLASS PARTITION
a. A = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(10) (3)] – [(2x2.4)]
.
= 25.2m2
= 271.2 ft2

b. A = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR


= [(5)(3)]
.
= 15 m2
= 161.4 ft2

Total Area = 271.2 ft2 + 161.4 ft2 = 432.6 ft2

QGLASS = U•A•∆T
= (0.81 BTU/h.ft2.oF) (432.6 ft2) (10oF)
= 3504.1 BTU/hr.

D. PLENUM
No Heat Load Calculation for Plenum - the room/area (Vivo stall) On the Second
Floor that Overlaps it is also Air Conditioned

E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING WEST
.
QSOLAR = (3mx3m) (0.55)(227)(0.17)
= 2055.1 Btu/hr.

F. ROOF
No Heat Load Calculation for Roof – the room/area is located on the ground floor
G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 5m x 10m = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐
No. Of Occupants = A/N
.
= = 13.45 or 14 people

QS = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.

QL = no. of occupancy (LHG)(CLF)


14(325 Btu/hr.) (1) = 4550 Btu/hr.

11
H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 5 x 2200 x 0.5 (3.41)
= 18755 Btu/hr.

I. LIGHTING
Wattage =AxN
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF)(3.413 Btu/hr)


= 2420.64 watts(1)(3.413 Btu/hr)
= 8261.64 Btu/hr

Name of Room/Stall INASAL


Dimensions 20m x 20m
Location Ground Floor
Application Retail store
Note: Inasal or Mang Inasal is a restaurant
known for its unlimited rice promo.

A. WALL
a. FACING WEST
ATOTAL= AWALL-AWINDOW
A = [(L)(H)] wall - [(3)(3)] window
A = [15•3] wall - 3[3•3] window
.
A = 33m2
A = 193.65 ft2

12
QWALL = (U)(A) (CLTDCORRECTION)
= (0.3472) (193.65 ft2) (27.11oF)
= 1822.75 BTU/hr.

b. FACING SOUTH
ATOTAL= AWALL-AWINDOW
A = [(L)(H)] wall- [(3)(3)] window
A = [(20) (3)] wall-4[(3)(3)] window
.
A = 24m2
A = 258.2 ft2

QWALL = (U)(A) (CLTDCORRECTION)


= (0.3472) (258.2 ft2) (27.94oF)
= 2504.74 BTU/hr.

B. PARTITION WALL
AREA = [(𝐿)(𝐻)] Partition Wall
= (35m) (3m)
.
= 105 m2
= 1129.63 ft2

QWALL = U•A•∆T
= (0.3021 BTU/h.ft2.oF) (1158.7 ft2) (10F)
= 3412.61 BTU/hr.

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [10 • 3] – [(3x2.4)]
.
= 22.8 m2
= 245.29 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (245.29 ft2) (10oF)
= 1986.85 BTU/hr.

D. PLENUM
No Heat Load Calculation for Plenum (ceiling) - the room/area (Vivo stall) On
the Second Floor that Overlaps it is also Air Conditioned

E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING WEST
.
AREA = (20mx3m) (0.55)(227)(0.17)
Q SOLAR = 13700.5 Btu/hr.

FACING SOUTH
.
Area = (20mx3m) (0.55)(45)(0.35)
Q SOLAR = 5591.7 Btu/hr.

F. ROOF
No Heat Load Calculation for Roof – the room/area is located on the ground floor

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 20m x 20m = 400 𝑚 1𝑚
= 4303.4 𝑓𝑡
No. Of Occupants = A/N
.
= = 286.9 or 287 person

13
QS = no. of occupancy (SHG)(CLF)
= 287(255 Btu/hr.) (1)
= 73185 Btu/hr.

QL = no. of occupancy (LHG)(CLF)


= 287(325 Btu/hr.) (1)
= 93275 Btu/hr.

H. APPLIANCES
a. COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 2 x 2200 x 0.5 (3.41)
= 7502 Btu/Hr.

b. DEEP FAT FRYER


QAPPLIANCES
Qs= SHG X CLF
= 6500 x 0.82 x 1 = 5330 Btu/hr.

c. RANGE HEAVY DUTY TOP SECTION OVEN


QAPPLIANCES
Qs= SHG X CLF
= 6500 x 0.82 x 1
= 5330 Btu/hr.

d. DRY FOOD WARMER PER 𝑓𝑡 TOP


QAPPLIANCES
Qs = SHG X CLF
= 320 x 0.86 x 1
= 275.2 Btu/hr.

e. HOT PLATE
QAPPLIANCES
Qs = SHG X CLF
= 5300 x 0.829x 1
= 4393.7 Btu/hr.

f. FRYER
QAPPLIANCES
Qs = SHG X CLF
= 730 x 0.82 x 1
= 598.6 Btu/hr.

g. OVEN BAKING PER 𝑓𝑡 HEARTH


QAPPLIANCES
Qs = SHG X CLF
= 730 x 0.82 x 1
= 598.6 Btu/hr.

h. OVEN ROASTING PER 𝑓𝑡 HEARTH


QAPPLIANCES
Qs= SHG X CLF
= 730 x 0.82 x 1
= 598.6 Btu/hr.
I. LIGHTING
Wattage =AxN
3.28 𝑓𝑡 2
= 400 𝑚 1𝑚
= 4303.4 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 19365.12 watts

14
Qlighting = wattage(CLF) (3.413 Btu/hr.)
= 19365.12 watts (1) (3.413 Btu/hr.)
= 66093.15 Btu/hr.

Name of Room/Stall SM STORE


Dimensions 25m x 25m
Location Ground Floor
Application Retail store
Note: SM Store is a stall for general merchandize

A. WALL
a. FACING EAST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(3)(3)] window
A= [(25) (3)] wall - 5[(3)(3)] window
.
A= 30m2
A= 322.8 ft2

QWALL = (U)(A) (CLTDCORRECTION)


QWALL = (0.3472) (322.8 ft2) (39.56oF)
QWALL = 4433.75 BTU/hr.

c. FACING SOUTH
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall-[(L)(W)] window
A= [(25) (3)] wall-5[(3)(3)] window
.
A= 30m2
A= 322.8 ft2

QWALL = (U)(A) (CLTDCORRECTION)


QWALL = (0.3472) (322.8 ft2) (27.94oF)
QWALL = 3131.41 BTU/hr.

15
B. PARTITION WALL
AREA = [(𝐿)(𝐻)] Partition Wall
= (15m) (3m)
.
= 45 m2
= 484.13 ft2
QWALL = U•A•∆T
= (0.3021 BTU/h.ft2.oF) (484.13 ft2) (10F)
= 1 462.56 BTU/hr.

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(20) (3)] – [(3x2.4)]
.
= 52.8 m2
= 568.04 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (568.04 ft2) (10oF)
= 4 601.12 BTU/hr.

D. PLENUM (Ceiling)
Qs = U(A)(T)(D)
.
= 1 BTU/h.ft2.oF [375m2 (10oF)
= 40 344 BTU/hr.

E. SOLAR
QSOLAR = A(SC)(SHGF)(CLF)

FACING EAST
.
Q SOLAR = 5(3mx3m) (0.55)(227)(0.17)
= 10 275.37 Btu/hr.

FACING SOUTH
.
Q SOLAR = 5(3mx3m) (0.55)(45)(0.35)
= 2 516.26 Btu/hr.
F. ROOF
No Heat Load Calculation for Roof – the room/area is located on the ground floor

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 25m x 25m = 625 𝑚 1𝑚
= 6724 𝒇𝒕𝟐
No. Of Occupants = A/N
=

= 168.1 ≈ 196 persons


QS = no. of occupancy (SHG)(CLF)
= 169 (315 Btu/hr.) (1)
= 53 235 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 169 (325 Btu/hr.) (1)
= 54 925 Btu/hr.

H. APPLIANCES
COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 2 x 2200 x 0.5 (3.41)
= 7 502 Btu/hr.
I. LIGHTING

16
Wattage = A x N
3.28 𝑓𝑡 2
Wattage = 25m x 25m = 625 𝑚 1𝑚
= 6724 𝑓𝑡 (4.5 watts/𝑓𝑡 )
Wattage = 30258 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 30258 watts (1) (3.413 Btu/hr.)
= 103 270.6 Btu/hr.

Name of Room/Stall GOLDILOCKS


Dimensions 7.5m x 5m
Location Ground Floor
Application Retail store
Note: Goldilocks is a stall for cakes and pastries

A. WALL
FACING EAST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(L)(H)] window
A= [(5)(3)] wall - [(3)(3)] window
.
A= 6m2
A= 64.6 ft2

QWALL = (U)(A) (CLTDCORRECTION)


QWALL = (0.3472) (64.6 ft2) (39.56)
QWALL = 887.3 BTU/hr.

B. PARTITION WALL
NO Heat Load Calculation for Partition Wall – Adjacent rooms/areas (SM Store
& Red Ribbon) are also Air Conditioned

C. PARTITION GLASS
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(7.5) (3)] – [(2x2.4)]
.
= 17.7m2
= 190.4 ft2

17
QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (190.4 ft2) (10oF)
= 1542.3 BTU/hr.

D. PLENUM (Ceiling)
No Heat Load Calculation for Plenum (ceiling) - The room/area (Levi’s stall) On
the Second Floor that Overlaps it is also Air Conditioned

E. SOLAR
QSOLAR = A(SC)(SHGF)(CLF)

FACING EAST
.
QSOLAR = (3mx3m (0.55)(227)(0.17)
= 2055.17 Btu/hr.

F. ROOF
No Heat Load Calculation for roof – the area is located on the ground floor

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 7.5m x 5m = 37.5 𝑚 1𝑚
= 403.44 𝒇𝒕𝟐
No. Of Occupants = A/N
.
= = 26.90 or 27 persons

QS = no. of occupancy (SHG)(CLF)


= 27(315 Btu/hr.) (1)
= 2805 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 27 (325 Btu/hr.) (1)
= 8775 Btu/hr.

a. APPLIANCESCOMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751 Btu/hr.

I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
Wattage = 37.5 𝑚 1𝑚
= 403.44 𝑓𝑡 (3 watts/𝑓𝑡 )
= 1210.32 watts

Qlighting = wattage (CLF) (3.413 Btu/hr.)


= 1210.32 watts (1) (3.413 Btu/hr.)
= 4130.82 Btu/hr.

18
Name of Room/Stall RED RIBBON
Dimensions 7.5 m x 5 m
Location Ground Floor
Application Retail store
Note: Red Ribbon is a stall for cakes and pastries

A. WALL
No Heat Load Calculation for Wall – there is no wall/s exposed from the outside.

B. PARTITION WALL
AREA =[(𝐿)(𝐻)] Partition Wall
= (5m) (3m)
.
= 15 m2( )2
= 161.8 ft2

QWALL = U.A. ∆T
= (0.3021 BTU/h.ft2.oF) (161.8 ft2) (10F)
= 488.8 BTU/hr.

C. GLASS PARTITION
Area = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(7.5) (3)] – [(2x2.4)]
.
= 17.7m2( )2
= 190.4 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (190.4 ft2) (10oF)
= 1542.3 BTU/hr.

D. PLENUM
QS = U(A)(TD)
.
= 1 BTU/h.ft2.oF [25m2( )2](10)
= 2689.60 BTU/hr.

E. SOLAR
No Heat Load Calculation for Solar – the stall is located inside the building and
no window glass exposed directly to sunlight

19
F. ROOF
No Heat Load Calculation for Roof – the stall is located on the ground floor

G. OCCUPANTS
3.28𝑓𝑡
AREA = 7.5m x 5m = 37.5 𝑚 1𝑚 = 403.44 𝒇𝒕𝟐
No. Of Occupants = A/N
.
=

= 26.90 or 27 persons

QS = no. of occupancy (SHG)(CLF)


= 27(315 Btu/hr.) (1)
= 2805 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 27 (325 Btu/hr.) (1)
= 8775 Btu/hr.

H. APPLIANCES
b. COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751 Btu/hr.
I. LIGHTING
Wattage = A x N
3.28𝑓𝑡
Wattage = 37.5 𝑚 1 𝑚 = 403.44 𝑓𝑡 (3 watts/𝑓𝑡 )
Wattage = 1210.32 watts

Qlighting = wattage(CLF)(3.413 Btu/hr.)


= 1210.32 watts (1) (3.413 Btu/hr.) = 4130.82 Btu/hr.

Name of room/stall DUNKIN’ DONUT


Dimensions 7.5m x 5m
Location Ground Floor
Application Cafeteria – multi use
Note: Dunkin’ Donut is a stall for donuts

A. WALL
a. FACING EAST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(L)(H)] window
A= [(5)(3)] wall - [(3)(3)] window

20
.
A= 6m2 = 64.6 ft2
QWALL = (U)(A) (CLTDCORRECTION)
QWALL = (0.3472) (64.6 ft2) (39.56)
QWALL = 884.55 BTU/hr.

B. PARTITION WALL
NO Heat Load Calculation for Partition Wall – Adjacent rooms (Jollibee and Mister
Donut) are also Air Conditioned

C. PARTITION GLASS
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(7.5) (3)] – [(2x2.4)]
.
= 17.7m2
= 190.4 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (190.4 ft2) (10oF)
= 1542.3 BTU/hr.

D. PLENUM
No Heat Load Calculation for Plenum (ceiling) – The room/area (Cinema) On the Second
Floor that overlaps it is also Air Conditioned

E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING EAST
.
Q SOLAR = (3mx3m) (0.55)(227)(0.17)
Q SOLAR = 2055.10 Btu/hr.

F. ROOF
No Heat Load Calculation for Roof – the stall is located on the ground floor

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 7.5m x 5m = 37.5 𝑚 1𝑚
= 403.44 𝒇𝒕𝟐

No. Of Occupants = A/N


.
=

= 26.90 or 27 persons

QS = no. of occupancy (SHG)(CLF)


= 27(315 Btu/hr) (1)
= 2805 Btu/hr

QL = no. of occupancy (LHG)(CLF)


= 27 (325 Btu/hr.) (1)
= 8775 Btu/hr.

H. APPLIANCES
COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751 Btu/hr.

21
I. LIGHTING
Wattage =AxN
3.28 𝑓𝑡 2
= 37.5 𝑚 1𝑚
= 403.44 𝑓𝑡 (3 watts/𝑓𝑡 )
= 1210.32 watts

Qlighting = wattage(CLF)(3.413 Btu/hr)


= 1210.32 watts (1) (3.413 Btu/hr)
= 4130.82 Btu/hr

Name of room/stall MISTER DONUT


Dimensions 7.5m x 5m
Location Ground Floor
Application Cafeteria – multi use
Note: Mister Donut is a stall for donuts

A. WALL
No Heat Load Calculation for Wall – there is no wall/s exposed from the outside.

B. PARTITION WALL
NO Heat Load Calculation for Partition Wall – Adjacent rooms (Jollibee and
Mister Donut) are also Air Conditioned

C. GLASS PARTITION
a. AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(7.5)(3)] – [(2x2.4)]
.
= 17.7m2
= 190.4 ft2
b. AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5)(3)]
.
= 15m2
= 161.4 ft2

AT = 190.4 ft2 + 161.4 ft2 = 351.8 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (351.8 ft2) (10oF)
= 2849.6 BTU/hr.

22
D. PLENUM
No Heat Load Calculation for Plenum (ceiling) – The room/area (Cinema) On the
Second Floor that Overlaps it is also Air Conditioned

E. SOLAR
No Heat Load Calculation for Solar – the stall is located inside the building and no
window glass exposed directly to sunlight

F. ROOF
No Heat Load Calculation for Roof – the stall is located on the ground floor
G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 7.5m x 5m = 37.5 𝑚 1𝑚
= 403.44 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= = 26.90 or 27 persons

QS = no. of occupancy (SHG)(CLF)


= 27(315 Btu/hr.) (1)
= 2805 Btu/hr.

QL = no. of occupancy (LHG)(CLF)


= 27 (325 Btu/hr.) (1)
= 8775 Btu/hr.

H. APPLIANCES
COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751 Btu/hr
I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 37.5 𝑚 1𝑚
= 403.44 𝑓𝑡 (3 watts/𝑓𝑡 )
= 1210.32 watts

Qlighting = wattage(CLF)(3.413 Btu/hr)


= 1210.32 watts(1)(3.413 Btu/hr)
= 4130.82 Btu/hr

23
Name of Room/Stall JOLLIBEE .
Dimensions 20m x 20m - 25m
Location Ground Floor
Application Restaurant
Note: Jollibee is a restaurant

A. WALL
a. FACING NORTH
ATOTAL= AWALL-AWINDOW
A=[(L)(H)] wall-[(L)(H)] window
A= [(15) (3)] wall-4[(3)(3)] window
.
A= 18m2
A= 193.65 ft2

QWALL = (U)(A) (CLTDCORRECTION)


QWALL = (0.3472) (193.65 ft2) (22.96)
QWALL = 1543.72 BTU/hr

b. FACING EAST
ATOTAL= AWALL-AWINDOW
A=[(L)(H)] wall- [(3)(3)] window
A= [(20) (3)] wall-3[(3)(3)] window
.
A= 33m2
A= 355.03 ft2

QWALL = (U)(A) (CLTDCORRECTION)


QWALL = (0.3472) (355.03 ft2) (39.56oF)
QWALL = 4876.42 BTU/hr.

24
B. PARTITION WALL
A=[(𝐿)(𝐻)] Partition Wall
= (15m) (3m) - (0.9m) (2.4m)
.
= 42.84 m2
= 461 ft2

QWALL = U.A. ∆T
QWALL = (0.3021 BTU/h.ft2.oF) (461 ft2) (10F)
QWALL = 1392.68 BTU/hr.

C. GLASS PARTITION
a. A= [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5)(3)] – [(2x2.4)]
.
= 10.2m2
= 109.74 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (109.74 ft2) (10oF)
= 889 BTU/hr.

D. PLENUM
No Heat Load Calculation for Plenum (ceiling) – The room/area (Cinema) On the
Second Floor that Overlaps it is also Air Conditioned

E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING NORTH
.
Q SOLAR = (20mx3m) (0.55)(39)(0.75)
= 10384.55 Btu/hr.

FACING EAST
.
Q SOLAR = (20mx3m) (0.55)(227)(0.17)
= 13700.5 Btu/hr.

F. ROOF
No Heat Load Calculation for Roof – the stall is located on the ground floor

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 20m x 20m = (400 – 50)m2 = 350𝑚 1𝑚
= 3765.44 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= = 251.03 ≈ 252 people

QS = no. of occupancy (SHG)(CLF)


= 252 (225 Btu/hr.) (1)
= 64 260 Btu/hr.

QL = no. of occupancy (LHG)(CLF)


= 252 (325 Btu/hr.) (1)
= 81 900 Btu/hr.

a. APPLIANCES COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 5 x 2200 x 0.5 (3.41)
= 18755 Btu/hr.

25
b. DEEP FAT FRYER
QAPPLIANCES
Qs = SHG X CLF
= 6500 x 0.82 x 1
= 5330 Btu/hr.

c. RANGE HEAVY DUTY TOP SECTION OVEN


QAPPLIANCES
Qs = SHG X CLF
= 6500 x 0.82 x 1
= 5330 Btu/hr.

d. DRY FOOD WARMER PER 𝑓𝑡 TOP


QAPPLIANCES
Qs = SHG X CLF
= 320 x 0.86 x 1
= 275.2 Btu/hr.
e. HOT PLATE
QAPPLIANCES
Qs = SHG X CLF
= 5300 x 0.829x 1
= 4393.7 Btu/hr.
f. FRYER
QAPPLIANCES
Qs = SHG X CLF
= 730 x 0.82 x 1
= 598.6 Btu/hr.

g. OVEN BAKING PER 𝑓𝑡 HEARTH


QAPPLIANCES
Qs= SHG X CLF
= 730 x 0.82 x 1
= 598.6 Btu/hr.

h. OVEN ROASTING PER 𝑓𝑡 HEARTH


QAPPLIANCES
Qs= SHG X CLF
= 730 x 0.82 x 1
= 598.6 Btu/hr.
I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
Wattage = 20m x 20m = (400 – 50)m2 = 350 𝑚 1𝑚
= 3765.44 𝑓𝑡 (3 watts/𝑓𝑡 )
= 11 296.32 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


=11 296.32 watts (1) (3.413 Btu/hr.)
= 38 554.34 Btu/hr.

26
Name of room/stall GENERICS
Dimensions 5m x 10m
Location Ground Floor
Application Retail store
Note: Generics is a stall for drugs

A. WALL
No Heat Load Calculation for Wall – there is no wall/s exposed from the outside.

B. PARTITION WALL
AREA =[(𝐿)(𝐻)] Partition Wall
.
= (5m)(3m) = 15 m2
= 161.4 ft2
QWALL = U•A•∆T
= (0.3021 BTU/h.ft2.oF) (161.4 ft2) (10F)
= 487.6 BTU/hr.
C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(15) (3)] – [(2x2.4)]
.
= 40.2m2
= 432.50 ft2

QGLASS= U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (432.50 ft2) (10oF)
= 3503.20 BTU/hr.

D. PLENUM
No Heat Load Calculation for Plenum (ceiling) – The room/area (Xiaomi & Apple
Stall) On the Second Floor that Overlaps it are also Air Conditioned

E. SOLAR
No Heat Load Calculation for Solar – the stall is located inside the building and
no window glass exposed directly to sunlight

F. ROOF
No Heat Load Calculation for Roof – the stall is located on the ground floor

G. OCCUPANTS
AREA = LXW
3.28 𝑓𝑡 2
= 5m x 10m = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

27
No. Of Occupants = A/N
.
= = 13.45 or 14 people

QS = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.

H. APPLIANCES
COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751 Btu/hr.

I. LIGHTING
Wattage =AxN
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of room/stall NATIONAL BOOK STORE


Dimensions 15m x 15m
Location Second Floor
Application Retail store
Note: National Book Store is a stall/grocery store for
books and school supplies.

28
A. WALL
a. FACING NORTH
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall-[(L)(H)] window
A= [(15) (3)] wall-3[(3)(3)] window
.
A= 18m2
A= 193.65 ft2

QWALL = (U)(A) (CLTDCORRECTION)


= (0.3472) (193.65 ft2) (22.96)
= 1543.72 BTU/hr.
b. FACING WEST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall- [(L)(H)] window
A= [(15) (3)] wall-3[(3)(3)] window
.
A= 18m2
A= 193.65 ft2

QWALL = (U)(A) (CLTDCORRECTION)


= (0.3472) (193.65 ft2) (27.11oF)
= 1822.75 BTU/hr.

B. PARTITION WALL
AREA = [(𝐿)(𝐻)] Partition Wall
= (7.5m) (3m)
.
= 22.5 m2
= 242.10 ft2
QWALL = U.A. ∆T
= (0.3021 BTU/h.ft2.oF) (242.06 ft2) (10F)
= 731.26 BTU/hr.

C. PARTITION GLASS
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(12.5) (3)] – [(3x2.4)]
.
= 30.3 m2
= 326 ft2

QGLASS= U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (326 ft2) (10oF)
= 2640.60 BTU/hr.

D. PLENUM
a. (flooring)
QS = U(A)(TD)
.
= 1 BTU/h.ft2.oF [75m2 ](10)
= 6455.04 BTU/hr.

b. (ceiling)
QS = U(A)(TD)
.
= 1 BTU/h.ft2.oF [225m2 ](10)
= 24 206.40 BTU/hr.

E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)
FACING NORTH
.
Q SOLAR = 3(3mx3m) (0.55)(39)(0.75)
Q SOLAR = 4763.10 Btu/hr.

29
FACING WEST
.
Q SOLAR = 3 (3mx3m) (0.55)(227)(0.17)
Q SOLAR = 29 738.47 Btu/hr.

F. ROOF
.
AREA = 225m2 = 2420.64 ft2

QROOF = 0.2415 BTU/h.ft2.oF (2420.64 ft2) (28oF)


= 16 868.37 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 15m x 15m = 225 𝑚 1𝑚
= 2420.64 𝒇𝒕𝟐
No. Of Occupants = A/N
.
= = 60.52 or 61 person

Qs = no. of occupancy (SHG)(CLF)


61(315 Btu/hr)(1)
=19 215 Btu/hr

QL = no. of occupancy (LHG)(CLF)


61(325 Btu/hr)(1)
= 19 825 Btu/hr

H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751 Btu/hr.

I. LIGHTING
Wattage = A x N

3.28 𝑓𝑡 2
Wattage = 225 𝑚 1𝑚
= 2420.64 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 10 892.88 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 10 892.88 watts (1) (3.413 Btu/hr.)
= 37 177.40 Btu/hr.

Name of Room/Stall OPPO


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Oppo is a stall for Oppo brand
mobiles and accessories

30
A. WALL
a. FACING WEST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(3)(3)] window
A= [(5)(3)] wall- [(3)(3)] window
.
A= 6m2
A= 64.6 ft2

QWALL = (U)(A) (CLTDCORRECTION)


QWALL = (0.3472) (64.6 ft2) (27.11oF)
QWALL = 608.10BTU/hr.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent rooms (National Book
Store and Vivo stall) are also Air Conditioned

C. GLASS PARTITION
A = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5)(3)] – [(2x2.4)]
.
= 10.2m2
= 109.74 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (109.74 ft2) (10oF)
= 889 BTU/hr.

D. PLENUM (Ceiling)
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5379.2 BTU/hr.
E. SOLAR
QSOLAR = A(SC)(SHGF)(CLF)

FACING WEST
.
Q SOLAR = (3mx3m) (0.55)(227)(0.82)
Q SOLAR = 9912.71 Btu/hr.

F. ROOF
.
AREA = 50m2 = 537.92 ft2
QROOF = 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐
No. Of Occupants = A/N
.
= /
= 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.

H. APPLIANCES

31
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.

I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of Room/Stall VIVO


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Vivo is a stall for Vivo brand
mobiles and accessories

A. WALL
FACING WEST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(3)(3)] window
A= [(5)(3)] wall- [(3)(3)] window
.
A= 6m2
A= 64.6 ft2

QWALL = (U)(A) (CLTDCORRECTION)


QWALL = (0.3472) (64.6 ft2) (27.11oF)
QWALL = 608.10BTU/hr.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent rooms (National Book Store
and Vivo stall) are also Air Conditioned

C. GLASS PARTITION
A = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5)(3)] – [(2x2.4)]
.
= 10.2m2
= 109.74 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (109.74 ft2) (10oF)
= 889 BTU/hr.

32
D. PLENUM (Ceiling)
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5379.2 BTU/hr.
E. SOLAR
QSOLAR = A(SC)(SHGF)(CLF)

FACING WEST
.
Q SOLAR = (3mx3m) (0.55)(227)(0.82)
Q SOLAR = 9912.71 Btu/hr.

F. ROOF
.
AREA = 50m2 = 537.92 ft2
QROOF = 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.

H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.

I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of room/stall SAMSUNG


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Samsung is a stall for Samsung
brand mobiles and accessories

33
A. WALL
FACING WEST
ATOTAL= AWALL-AWINDOW
Area = [(L)(H)] wall - [(3)(3)] window
= [(5)(3)] wall- [(3)(3)] window
.
= 6m2
= 64.6 ft2

QWALL = (U)(A) (CLTDCORRECTION)


= (0.3472) (64.6 ft2) (27.11oF)
= 608.10BTU/hr.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent rooms/stall (Vivo and
Dept. Store) are also Air Conditioned

C. PARTITION GLASS
Area = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5)(3)] – [(2x2.4)]
.
= 10.2m2
= 109.74 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (109.74 ft2) (10oF)
= 889 BTU/hr.
D. PLENUM
a. Flooring
Qs = U•A•TD
= 0.8 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 4303.36 BTU/hr.
b. Ceiling
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5379.2 BTU/hr.

E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING WEST
.
Area = (3mx3m) (0.55)(227)(0.82)
Q SOLAR = 9912.71 Btu/hr.

F. ROOF
.
AREA = 50m2 = 537.92 ft2
QROOF = 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = LXW = 50 𝑚 1𝑚
= 537.92 𝑓𝑡

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

QS = no. of occupancy (SHG)(CLF)


=14(315 Btu/hr.) (1)
= 4410 Btu/hr.

QL = no. of occupancy (LHG)(CLF)

34
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.

H. APPLIANCES
COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.
I. LIGHTING
Wattage =AxN
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 ) = 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

DEPARTMENT
Name of room/stall STORE
Dimensions 20m x 30m
Location Second Floor
Application Retail store
Note: Department Store is a store for general merchandise.

35
A. WALL
FACING WEST
ATOTAL= AWALL-AWINDOW
Area = [(L)(H)] wall - [(L)(H)] window
= [(30) (3)] wall- 6[(3)(3)] window
.
= 36m2
= 378.30 ft2
QWALL = (U)(A) (CLTDCORRECTION)
= (0.3472) (378.30 ft2) (27.11oF)
= 3560.78 BTU/hr.

FACING SOUTH
ATOTAL= AWALL-AWINDOW
Area = [(L)(H)] wall - [(L)(H)] window
= [(20) (3)] wall- 4[(3)(3)] window
.
= 24m2
= 258.20 ft2

QWALL = (U)(A) (CLTDCORRECTION)


= (0.3472) (258.20 ft2) (27.11oF)
= 2436 BTU/hr.

B. PARTITION WALL
AREA = [(𝐿)(𝐻)] Partition Wall
= (5m) (3m)
.
= 15 m2
= 161.38 ft2

QWALL = U.A. ∆T
= (0.3021 BTU/h.ft2.oF) (161.38 ft2) (10F)
= 487.53 BTU/hr.
C. PARTITION GLASS
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= 7[(5) (3)] – 2[(3) (2.4)]
3.28 𝑓𝑡 2
= 90.6 m2 1 𝑚
= 974.71 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (974.71 ft2) (10oF)
= 7895.15 BTU/hr.

D. PLENUM
b. Flooring
.
Area = 3(50)m +25m = 175 m2 = 1882.72 ft2
Qs = U•A•TD
= 0.8 BTU/h.ft2.oF • 1882.72 ft2• 10oF
= 15 061.76 BTU/hr.

a. Ceiling
.
Area = 20m (30m) = 600 m2 = 6455.04 ft2
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 6455.04 ft2• 10oF
= 64 550.40 BTU/hr.

E. SOLAR
QSOLAR = A(SC)(SHGF)(CLF)

36
FACING WEST
.
QSOLAR = 6[(3)(3)] window (0.55)(227)(0.82)
= 59 476. 30 Btu/hr.

F. ROOF
.
AREA = 600m2 = 6 455.04 ft2
QROOF = 0.2415 BTU/h.ft2.oF (6 455.04 ft2) (28oF)
= 43 649 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = LXW = 600 𝑚 1𝑚
= 6 455.04 𝑓𝑡
No. Of Occupants = A/N
.
= /
= 161.38 or 162 persons

Qs = no. of occupancy (SHG)(CLF)


=162 (315 Btu/hr.) (1)
= 51 030 Btu/hr.

QL = no. of occupancy (LHG)(CLF)


= 162 (325 Btu/hr.) (1)
= 52 650 Btu/hr.

H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.
I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 600 𝑚 1𝑚
= 6455.04 𝑓𝑡 (4.5 watts/𝑓𝑡 ) = 29 047.68 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 29 047.68 watts (1) (3.413 Btu/hr.)
= 99 139.73 Btu/hr.

Name of room/stall BLUE CORNER


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Blue Corner is a stall for plain &
colored shirts

A. WALL
FACING EAST
ATOTAL= AWALL-AWINDOW = [(L)(H)] wall- [(3)(3)] window
.
A= [(5)(3)] wall- [(3)(3)] window = 6m2( )2 = 64.6 ft2

37
QWALL = (U)(A) (CLTDCORRECTION)
QWALL = (0.3472) (64.6 ft2) (39.56)
QWALL = 887.30 BTU/hr.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent rooms/stall (RRJ stall) is
also Air Conditioned

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(15) (3)] – [(2x2.4)]
.
= 40.2 m2( )2
= 432.50 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (432.50 ft2) (10oF)
= 3503.25 BTU/hr.
D. PLENUM (Ceiling)
.
Area = 5m (10m) = 50 m2 = 537.92 ft2
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5 379.20 BTU/hr.

E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING EAST
.
Q SOLAR = (3mx3m) (0.55)(227)(0.17)
= 2055.1 Btu/hr.

F. ROOF
.
AREA = 50m2 = 537.92 ft2

QROOF = U•A•CLDTcorrection
= 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

QS = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.
H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.

38
I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 ) = 2420.64 watts
Qlighting = wattage(CLF) (3.413 Btu/hr.)
= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of room/stall RRJ


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: RRJ is a stall for shirts

A. WALL
a. FACING EAST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(3)(3)] window
A= [(5)(3)] wall - [(3)(3)] window
.
A= 6m2( )2
A= 64.6 ft2

QWALL = (U)(A) (CLTDCORRECTION)


= (0.3472) (64.6 ft2) (39.56)
= 887.3.10BTU/hr.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent rooms/stalls (Blue corner
& Oxygen stall) are also Air Conditioned

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5) (3)] – [(2x2.4)]
.
= 10.2 m2( )2
= 109.74 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (109.74 ft2) (10oF) = 889 BTU/hr.

D. PLENUM (Ceiling)
.
Area = 5m (10m) = 50 m2 = 537.92 ft2

Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5 379.20 BTU/hr.

E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING EAST

39
3.28𝑓𝑡
Q SOLAR = (3mx3m)( 1 𝑚) (0.55)(227)(0.17)
= 2055.1 Btu/hr.

F. ROOF
.
AREA = 50m2 = 537.92 ft2

QROOF = U • A • CLDTcorrection
= 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

QS = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.

H. APPLIANCES
COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.
I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 ) = 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of room/stall OXYGEN


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Oxygen is a stall for
shirts/clothes

A. WALL
FACING EAST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(3)(3)] window
A= [(5)(3)] wall - [(3)(3)] window
.
A= 6m2 = 64.6 ft2

40
QWALL = (U)(A) (CLTDCORRECTION)
QWALL = (0.3472) (64.6 ft2) (39.56)
QWALL = 887.3.10BTU/hr.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent rooms/stalls (RRJ &
Levi’s stall) are also Air Conditioned

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5) (3)] – [(2x2.4)]
.
= 10.2 m2( )2
= 109.74 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (109.74 ft2) (10oF)
= 889 BTU/hr.

D. PLENUM (Ceiling)
.
AREA = 5m (10m) = 50 m2 = 537.92 ft2
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5 379.20 BTU/hr.

E. SOLAR
QSOLAR = A(SC)(SHGF)(CLF)

FACING EAST
3.28𝑓𝑡
Q SOLAR = (3mx3m)( 1 𝑚) (0.55)(227)(0.17)
= 2055.1 Btu/hr.

F. ROOF
.
AREA = 50m2 = 537.92 ft2

QROOF = U • A • CLDTcorrection
= 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.
H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.

41
I. LIGHTING
Wattage =AxN
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of room/stall LEVI’S


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Levi’s is a stall for shoes, jeans,
jackets, ect.

A. WALL
FACING EAST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(3)(3)] window
A= [(5)(3)] wall - [(3)(3)] window
.
A= 6m2 = 64.6 ft2

QWALL = (U)(A) (CLTDCORRECTION)


= (0.3472) (64.6 ft2) (39.56)
= 887.3.10BTU/hr.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent rooms/stalls (RRJ &
Levi’s stall) are also Air Conditioned

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5) (3)] – [(2x2.4)]
.
= 10.2 m2( )2
= 109.74 ft2
QGLASS= U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (109.74 ft2) (10oF)
= 889 BTU/hr.

D. PLENUM (Ceiling)
.
Area = 5m (10m) = 50 m2 = 537.92 ft2

Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF = 5 379.20 BTU/hr.

42
E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING EAST
.
Q SOLAR = (3mx3m) (0.55)(227)(0.17)
= 2055.1 Btu/hr.

F. ROOF
.
AREA = 50m2 = 537.92 ft2

QROOF = U • A • CLDTcorrection
= 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.
H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.

I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of room/stall BENCH


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Bench is a stall for shoes,
jeans, jackets, shirts, ect.

43
A. WALL
FACING EAST
ATOTAL= AWALL-AWINDOW
A= [(L)(H)] wall - [(3)(3)] window
A= [(5)(3)] wall - [(3)(3)] window
.
A= 6m2 = 64.6 ft2

QWALL = (U)(A) (CLTDCORRECTION)


= (0.3472) (64.6 ft2) (39.56)
= 887.3.10BTU/hr.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent rooms/stalls (RRJ &
Levi’s stall) are also Air Conditioned

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5) (3)] – [(2x2.4)]
.
= 10.2 m2
= 109.74 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (109.74 ft2) (10oF)
= 889 BTU/hr.

D. PLENUM
a. Flooring
Qs = U•A•TD
= 0.8 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 4303.36 BTU/hr.
b. Ceiling
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5379.2 BTU/hr.

E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING EAST
.
Q SOLAR = (3mx3m) (0.55)(227)(0.17)
= 2055.1 Btu/hr.

F. ROOF
.
AREA = 50m2 = 537.92 ft2

QROOF = U • A • CLDTcorrection
= 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.

44
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.

H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.

I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of room/stall CINEMA


Dimensions 20m x 25m
Location Second Floor
Application Theatre, Movie
Note: Note: Cinema is room for
movie/film viewing

A. WALL
a. FACING NORTH
ATOTAL= AWALL-AWINDOW
=[(L)(H)] wall - [(L)(H)] window
= [(20) (3)] wall - 4[(3)(3)] window
.
= 24m2
= 258.2 ft2

QWALL = (U)(A) (CLTDCORRECTION)


= (0.3472) (258.2 ft2) (22.96)
= 2058.30 BTU/hr.

45
b. FACING EAST
ATOTAL = AWALL-AWINDOW
= [(L)(H)] wall - [(L)(H)] window
= [(25) (3)] wall - 5[(3)(3)] window
.
= 30m2
= 322.75 ft2

QWALL = (U)(A) (CLTDCORRECTION)


= (0.3472) (322.75 ft2) (39.56oF)
= 4 433.75 BTU/hr.

B. PARTITION WALL
AREA =[(𝐿)(𝐻)] Partition Wall
= (20m) (3m) - (3m) (2.4m)
.
= 52.80 m2
= 568.04 ft2
QWALL = U.A. ∆T
= (0.3021 BTU/h.ft2.oF) (322.8 ft2) (10F)
= 975.2 BTU/hr.

C. PARTITION GLASS
No heat load for partition glass – all partitions were made of concrete

D. PLENUM
a. Flooring
Qs = U•A•TD
3.28 𝑓𝑡 2 2
= 0.8 BTU/h.ft2.oF • 75m2 1𝑚
ft • 10oF
= 6455.04 BTU/hr.
b. Ceiling
Qs = U•A•TD
3.28 𝑓𝑡 2 2
= 1 BTU/h.ft2.oF • 500m2 1𝑚
ft • 10oF
= 53 792 BTU/hr.
E. SOLAR
QSOLAR= A(SC)(SHGF)(CLF)

FACING NORTH
.
QSOLAR = 4[(3m)(3m)] (0.55)(39)(0.75)
= 6 230.73 Btu/hr.

FACING EAST
.
QSOLAR = 5[(3m)(3m)] (0.55)(227)(0.17)
= 10 275.37 Btu/hr.

F. ROOF
.
AREA = 500m2 = 5379.20 ft2

QROOF = U • A • CLDTcorrection
= 0.2415 BTU/h.ft2.oF (5379.20 ft2) (28oF)
= 36 374.15 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 500 𝑚 1𝑚
= 5379.20 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 537.92 or 538 persons

Qs = no. of occupancy (SHG)(CLF)


46
= 538 persons (210 Btu/hr.) (1)
= 112 980 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 538 persons (140 Btu/hr.) (1)
= 75 320 Btu/hr.
H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751 BTU/hr.
I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 500 𝑚 1𝑚
= 5379.20 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 24206.40 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 24206.40 watts (1) (3.413 Btu/hr.)
= 82 616.44 BTU/hr.

Name of room/stall NOKIA


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Nokia is a stall for Nokia Brand
mobile phones & accessories

A. WALL
No Heat Load Calculation for Wall – there is no wall/s exposed from the outside.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent rooms/stall (RRJ stall) is
also Air Conditioned

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(15) (3)] – [(2x2.4)]
.
= 40.2 m2( )2
= 432.50 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (432.50 ft2) (10oF)
= 3503.25 BTU/hr.

D. PLENUM
a. Flooring
Qs = U•A•TD
= 0.8 BTU/h.ft2.oF • 537.92 ft2• 10oF = 4303.36 BTU/hr.
47
b. Ceiling
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5379.2 BTU/hr.

E. SOLAR
No Heat Load Calculation for Solar – the stall is located inside the building and
no window glass exposed directly to sunlight
F. ROOF
.
AREA = 50m2 = 537.92 ft2

QROOF = U•A•CLDTcorrection
= 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.
H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.

I. LIGHTING
Wattage =AxN
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of room/stall APPLE


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Nokia is a stall for Nokia
Brand mobile phones & accessories

48
A. WALL
No Heat Load Calculation for Wall – there is no wall/s exposed from the outside.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent rooms/stall (RRJ stall) is
also Air Conditioned

C. PARTITION GLASS
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5) (3)] – [(2x2.4)]
.
= 10.20 m2( )2
= 109.74 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (109.74 ft2) (10oF)
= 889 BTU/hr.

D. PLENUM
a. Flooring
Qs = U•A•TD
.
= 0.8 BTU/h.ft2.oF • 25m2 • 10oF
= 2151.68 BTU/hr.
b. Ceiling
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5 379.20 BTU/hr.

E. SOLAR
No Heat Load Calculation for Solar – the stall is located inside the building and
no window glass exposed directly to sunlight

F. ROOF
.
AREA = 50m2 = 537.92 ft2

QROOF = U•A•CLDTcorrection
= 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= = 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.
H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.
I. LIGHTING
Wattage = A x N
49
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of room/stall XIAOMI


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Xiaomi is a stall for Xiaomi
Brand mobile phones & accessories

A. WALL
No Heat Load Calculation for Wall – there is no wall/s exposed from the outside.

B. PARTITION WALL
AREA =[(𝐿)(𝐻)] Partition Wall
= (10m) (3m)
.
= 30 m2
= 322.75 ft2
QWALL = U.A. ∆T
= (0.3021 BTU/h.ft2.oF) (322.75 ft2) (10F)
= 975.03 BTU/hr.

C. PARTITION GLASS
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(5) (3)] – [(2x2.4)]
.
= 10.20 m2( )2
= 109.74 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (109.74 ft2) (10oF)
= 889 BTU/hr.

D. PLENUM
a. Flooring
Qs = U•A•TD
.
= 0.8 BTU/h.ft2.oF • 25m2 • 10oF
= 2151.68 BTU/hr.

b. Ceiling
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF

50
= 5 379.20 BTU/hr.
E. SOLAR
No Heat Load Calculation for Solar – the stall is located inside the building and
no window glass exposed directly to sunlight

F. ROOF
.
AREA = 50m2 = 537.92 ft2

QROOF = U•A•CLDTcorrection
= 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.
H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.

I. LIGHTING
Wattage =AxN
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of Room/Stall JANSPORT


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Jansport is a stall for bags

51
A. WALL
No Heat Load Calculation for Wall – there is no wall/s exposed from the outside.

B. PARTITION WALL
AREA = [(𝐿)(𝐻)] Partition Wall
= (5m) (3m)
.
= 15 m2
= 161.38 ft2
QWALL = U.A. ∆T
= (0.3021 BTU/h.ft2.oF) (161.38 ft2) (10F)
= 487.53 BTU/hr.

C. GLASS PARTITION
AREA = [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(15) (3)] – [(2x2.4)]
.
= 40.2 m2( )2
= 432.50 ft2

QGLASS = U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (432.50 ft2) (10oF)
= 3503.25 BTU/hr.

D. PLENUM
b. Ceiling
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5379.2 BTU/hr.

E. SOLAR
No Heat Load Calculation for Solar – the stall is located inside the building and
no window glass exposed directly to sunlight

F. ROOF
.
AREA = 50m2 = 537.92 ft2

QROOF = U•A•CLDTcorrection
= 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

G. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= /
= 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.
H. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)

52
= 3751BTU/hr.
I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

Name of room/stall SAMSONITE


Dimensions 5m x 10m
Location Second Floor
Application Retail store
Note: Samsonite is a stall for bags

A. WALL
No Heat Load Calculation for Wall – there is no wall/s exposed from the outside.

B. PARTITION WALL
No Heat Load Calculation for Partition Wall – Adjacent room/stall (Jansport stall)
is also Air Conditioned

C. PARTITION GLASS
A= [(L)(H)] GLASS – [(L)(H)] ENTRANCE DOOR
= [(20) (3)] – [(2x2.4)]
.
= 55.2 m2( )2
= 593.86 ft2

QGLASS= U(A)(∆T)
= (0.81 BTU/h.ft2.oF) (593.86 ft2) (10oF)
= 4810.27 BTU/hr.

D. PLENUM (Ceiling)
Qs = U•A•TD
= 1 BTU/h.ft2.oF • 537.92 ft2• 10oF
= 5379.2 BTU/hr.

E. SOLAR
No Heat Load Calculation for Solar – the stall is located inside the building and
no window glass exposed directly to sunlight

I. ROOF
.
AREA = 50m2
AREA = 537.92 ft2

53
QROOF = U•A•CLDTcorrection
= 0.2415 BTU/h.ft2.oF (537.92 ft2) (28oF)
= 3637.41 Btu/hr.

J. OCCUPANTS
3.28 𝑓𝑡 2
AREA = 50 𝑚 1𝑚
= 537.92 𝒇𝒕𝟐

No. Of Occupants = A/N


.
= = 13.45 or 14 people

Qs = no. of occupancy (SHG)(CLF)


= 14(315 Btu/hr.) (1)
= 4410 Btu/hr.
QL = no. of occupancy (LHG)(CLF)
= 14(325 Btu/hr.) (1)
= 4550 Btu/hr.
K. APPLIANCES
 COMPUTER
QAPPLIANCES = no. of sources x rated energy x FL; (3.41)
= 1 x 2200 x 0.5 (3.41)
= 3751BTU/hr.
I. LIGHTING
Wattage = A x N
3.28 𝑓𝑡 2
= 50 𝑚 1𝑚
= 537.92 𝑓𝑡
= 537.92 𝑓𝑡 (4.5 watts/𝑓𝑡 )
= 2420.64 watts

Qlighting = wattage(CLF) (3.413 Btu/hr.)


= 2420.64 watts (1) (3.413 Btu/hr.)
= 8261.64 Btu/hr.

54