YK CHILLER PARAMETERS (GRAFIC PANEL)

CHILLER COMPONENT CHILLER PARAMETER NORMAL RANGE


OVER
COMPRESSOR Oil Level NORMAL
LOW
Oil Temp (F) 50 ◦F above cond saturated
Differential Oil Press (Psid) 25 - 45
High Oil Pressure (Pisg) 50 - 80
Low Oil Pressure (Psig) 30 - 50
Sensor Reference Mils open/close (using limit switch)
Speed Oil Drain Temp (F) N/A
Oil Pump Frequency (Hertz) 0 - 50 Hz
Volts 415
MOTOR Rated Load Amps According to chiller FLA
%FLA 40 - 103
Running Amps -
Evaporator Pressure (Psig) 32 - 38
COOLER Entering Water Temp (F) 50 - 60
Leaving Water Temp (F) 40 - 50
Evaporator Saturated Temp (F) 35 - 45
Small Temp Difference (F) 0-4
Inlet Water Pressure (Psig) Depend at site
Outlet Water Pressure (Psig) Depend at site
Design Pressure Drop Check at design data
Condenser Pressure (Psig) 100 - 125
CONDENSER Entering Water Temp (F) 82 - 88
Leaving Water Temp (F) 92 - 98
Discharge Temp (F) 105 - 125
Condenser Saturated Temp (F) 90 - 98
Discharge Superheat (F) 15 - 25
Small Temp Difference (F) 0-4
Inlet Water Pressure (Psig) Depend at site
Outlet Water Pressure (Psig) Depend at site
Design Pressure Drop Check at design data