You are on page 1of 60

Installation, Operation,

and Maintenance

Tracer® UC400 Programmable Controller


Ordering Number BMUC400AAA0100011

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.

February 2015 BAS-SVX20F-EN


Introduction
The Tracer® UC400 Programmable Controller is a multi-purpose, programmable controller.
Programming is done through the Tracer Graphical Programming (TGP2) Editor (see “Other
Resources,” p. 55). This field-installed device is designed to control the following types of
equipment:
• Single- and dual-duct variable-air-volume (VAV) units
• Fan coils
• Unit ventilators
• Blower coils
• Water-source heat pumps (WSHP)
• Small air handlers
This guide provides information on installing, operating, and maintaining the controller.

Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any person
of such revision or change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

Revision History
BAS-SVX20F-EN; replaced Figure 8, Page 16 with table format. Update to correct the addressing.

© 2015 Trane. All rights reserved. BAS-SVX20F-EN


Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Agency Listings and Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Packaged Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation; Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
UC400 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensions and Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mounting, Removing, or Repositioning the Controller on a DIN Rail . . . 11
XM30/32/70 Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation; Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Conformance to Regulatory Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Connecting Wires to Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
BACnet MS/TP Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Setting the Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Connection Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Transformer Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Connect the Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Power On Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Device Pre-power Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Providing Low-voltage Power for Inputs/Outputs . . . . . . . . . . . . . . . . . . 24
Terminal Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Pressure Transducer Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Binary Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
0–10 Vdc Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
0–20 mA Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Variable Resistance Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Relays (Dry Contact/Binary Outputs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

BAS-SVX20F-EN 3
LED Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
LED Descriptions and Activities with Troubleshooting Tips . . . . . . . . . . . . . 34
Configuration and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
UC400 Setup and Configuration Task Summary . . . . . . . . . . . . . . . . . . . . . . 37
Task 1: Load Application Code on a Blank UC400 . . . . . . . . . . . . . . . . . . 37
Task 2: Choose a UC400 Configuration Option . . . . . . . . . . . . . . . . . . . . . 38
Task 3: Specify Controller Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Task 4: Set Up and Discover XM30/32/70 Expansion Modules . . . . . . . . 39
Task 5: Specifying an Equipment Configuration . . . . . . . . . . . . . . . . . . . 40
Task 6: Commissioning the Hard-Wired Points . . . . . . . . . . . . . . . . . . . . 41
Task 7: Modify or Create TGP2 Programs as Needed . . . . . . . . . . . . . . . 41
Task 8: Monitoring and Viewing Point, Alarm, and Controller Status . . 41
Task 9: Backing Up and Restoring Files and Configurations . . . . . . . . . . 42

Commissioning and Troubleshooting in Powered State . . . . . . . . . . . . . . . . . . . 43


Voltage Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Resistive Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Current Inputs- Methods 1 or 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
24 Vac Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Binary Inputs, 24 Vac Detect- Methods 1 or 2 . . . . . . . . . . . . . . . . . . . . . . . . . 47
Binary Inputs- Based on Analog Output Connection . . . . . . . . . . . . . . . . . . . 47
Open-collector Based Binary Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Voltage Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Current Analog Output- Methods 1 or 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Binary Output, TRIAC High Side Switching- Methods 1 or 2 . . . . . . . . . . . . 50
Binary Output, TRIAC Low Side Switching- Methods 1 or 2 . . . . . . . . . . . . . 51
Ground Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Other Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Declaration of CE Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

4 BAS-SVX20F-EN
General Information
Specifications

Table 1. UC400 controller specifications


Storage

Temperature -48°F to 203°F (-44°C to 95°C)

Relative humidity Between 5% to 95% (non condensing)

Operating

Temperature -40°F to 158°F (-40°C to 70°C)

Humidity Between 5% to 95% (nonconducting)

20.4–27.6 Vac (24 Vac, ±15% nominal) 50–60 Hz 24 VA


Power (24 VA plus binary output loads for a maximum of 12 VA for each binary
output)

Mounting weight of controller Mounting surface must support 0.80 lb. (0.364 kg)

Environmental rating (enclosure) NEMA 1

Altitude Maximum 9842 ft. (3000 m)

Installation UL 840: Category 3

Pollution UL 840: Degree 2

Sensors
The UC400 controller supports the following sensor types:
• Zone temperature sensors (resistive and thermistor)
• Linear 0–20 mA, such as humidity sensors
• Linear 0–10 Vdc, such as indoor air-quality sensors
• 3-wire pressure transducer inputs
Table 2 provides information about the different types of device connections:

Table 2. UC400 controller device connections


Connection Quantity Types Range Notes

Temperature 10 kΩ thermistor
AI1 to AI4 can be configured for timed override
Analog input capability.
5 Setpoint 189 Ω to 889 Ω
(AI1 to AI5)
Resistive 100 Ω to 100 kΩ Typically used for fan speed switch.

BAS-SVX20F-EN 5
General Information

Table 2. UC400 controller device connections (continued)


Connection Quantity Types Range Notes

Linear 0–20 mA

Linear 0–10 Vdc


These inputs may be configured to be thermistor or
Temperature 10 kΩ thermistor
resistive inputs, 0–10 Vdc inputs, or 0–20 mA inputs.
Setpoint 189 Ω to 889 Ω
Universal input
2
(UI1 and UI2) Resistive 100 Ω to 100 kΩ

Binary Open collector/dry contact Low impedance relay contacts recommended.

Minimum dwell time is 25 ms On and 25 ms Off.


Pulse Solid state open collector (Takes a maximum of 1048576 samples before the
counter resets.)

Binary input
(BI1 to BI3)
The UC400 controller provides (sources) 24 Vac for
3 24 Vac detect sensing contact closure by using the recommended
connections.
(See caution on
following page.)

3 Relay 2.88 A @24 Vac pilot duty


Binary output • General purpose General Purpose (Resistive)
(BO1 to BO3) • Motor 10 A max up to 277 Vac Power needs to be wired to the binary output. All
10 A max up to 30 Vdc outputs are isolated from each other and from ground
Other • Pilot duty or power. Ranges given are per contact.
(See caution on Ranges
• Resistive Motor Duty (Inductive)
following page.)
1/3 hp at 125 Vac (7.5 A max)
1/2 hp at 277 Vac (7.5 A max)

Binary output
Use for modulating TRIAC. User determines whether
(BO4 to BO9)
closing high side (providing voltage to the grounded
0.5 A max @24-277 Vac,
6 TRIAC load) or low side (providing ground to the power load).
resistive and pilot duty
Ranges given are per contact and power comes
(See caution on from TRIAC SUPPLY circuit.
following page.)

Linear output 0–20 mA


Analog output/
binary input Linear output 0–10 Vdc
Each termination must be configured as either an
2
(AO1/BI4 and analog output or binary input.
Binary input Dry contact
AO2/BI5)
PWM output 80 Hz signal @ 15 Vdc

Pressure inputs Pressure inputs supplied with 5 volts of power.


2 3-wire 0–5 in H2O
(PI1 and PI2) Designed for Kavlico™ pressure transducers.

Overall Point
23
Total

CAUTION
Electrical Shock Hazard!
Do not mix Class 1 and Class 2 voltage wiring in an enclosure or on a controller without an
approved barrier between the wiring.

6 BAS-SVX20F-EN
General Information

Expansion Modules
If you need additional points, you can add up to eight (8) XM30 expansion modules.
Important: Two of the expansion modules can be powered directly by the UC400 power supply,
but they must not exceed the 200 mA current limit of the IMC connector. Calculate
the power requirements before attempting to power the expansion modules with
the UC400 power supply. If the calculated load exceeds 200 mA or if you need more
than two XM30 expansion modules, install separate DC power supplies. See “XM30/
32/70 Expansion Modules,” p. 12.

Agency Listings and Compliance


Below is a listing compliance with Conformity European (CE) and Underwriters Laboratories (UL)
standards for the UC400 controller:
• UL916 PAZX- Open Energy Management Equipment
• UL94-5V Flammability
• CE Marked
• FCC Part 15, Subpart B, Class B Limit
• AS/NZS CISPR 22:2006
• VCCI V-3/2008.04
• ICES-003, Issue 4:2004

Packaged Contents
Visually inspect all parts for obvious defects or damage. All components are thoroughly inspected
before leaving the factory. Any claims for damage incurred in shipping should be filed immediately
with the carrier.
The following items are included in the UC400 package:
• UC400 controller
• DIN rail and DIN rail mounting screws
• Terminal connectors
• Installation guide
Note: For factory-mount controllers, the terminal connectors are part of the harness connector
(see “Other Resources,” p. 53). For field-mounted controllers, the quantities will vary
depending on user requirements.

BAS-SVX20F-EN 7
General Information

Accessories
Two (2) accessory options are available for the UC400:
• Enclosure for remote mounting, p/n X13651534, which includes:
– Pre-mounted DIN rail
– Transformer (line voltage to 24 Vac)
– Transformer to unit controller cable/harness
– Convenience power outlet (available only on 115 V version)
– Four #10 (5 mm) wall anchors and four #10 x 1.5 inch (5 x 40 mm) screws

• XM30 expansion module, which includes:


– IMC cable
– Pluggable terminal connectors (not installed)
– Installation sheet

Required Tools
The following tools are required to install and initially test the UC400 controller:
• Drill and appropriate bits for DIN rail mounting
• A #2 Phillips-head screwdriver
• A 1/8 inch (3.2 mm) wide, flat-bladed screwdriver
• Digital multimeter

8 BAS-SVX20F-EN
Installation; Mounting
This section provides instructions for physical installation of a UC400 controller and an XM30
expansion module.

UC400 Controller
The following sections provide dimensions and installation instructions for mounting, removal, or
repositioning the UC400 controller on a DIN rail.

Dimensions and Clearances

Figure 1. Controller dimensions

5.65 in. (143.5 mm) 2.17 in.


(8 units)* (55 mm)

1.73 in
(44 mm)

4.00 in.
(101.6 mm)

*DIN Standard 43 880, Built-in Equipment for Electrical Installations, Overall Dimensions
and Related Mounting Dimensions

BAS-SVX20F-EN 9
Installation; Mounting

Figure 2. DIN rail clearance

4.00 in.
(101.6 mm)

2.3 in. (58.4 mm)


7.08 in.
wiring clearance
(180 mm)
between terminal
connectors

Terminal Connector

10 BAS-SVX20F-EN
Installation; Mounting

Mounting, Removing, or Repositioning the Controller on a DIN Rail

NOTICE:
Avoid Equipment Damage!
Do not use excessive force to install or remove the controller from the DIN rail. Excessive force
could result in damage to the plastic enclosure.

Important: Always install devices on a horizontally oriented DIN rail to allow proper ventilation.

Mounting the controller


1. Hook the controller over the top of the DIN rail.
2. Gently push on lower half of device in the direction of the arrow until the release clip locks into
place.

Figure 3. Mounting a UC400 on the DIN rail

BAS-SVX20F-EN 11
Installation; Mounting

Removing or repositioning the controller


1. Disconnect all connectors.
2. Insert a screwdriver blade into the slotted release clip shown in Figure 4 and gently pry upward
to disengage the clip.
3. While holding tension on the clip, lift the controller upward to free it from the DIN rail.
4. Reposition the controller by sliding it sideways or by removing it completely and reattaching it.
5. Gently push on lower half of device in the direction of the arrow until the release clip locks into
place.

Figure 4. Slotted release clip on the back of the UC400

Slotted release clip shown from back side

Pry upward

XM30/32/70 Expansion Modules


The UC400 controller has 23 built-in points and supports up to eight (8) XM30 expansion modules.
Each expansion module adds up to four (4) additional points. However, the controller can only
supply up to 200 mA of electrical current, which is enough to power only two expansion modules.
The third and all subsequent expansion modules must be powered by a (recommended) Trane
PM014 power module or third-party equivalent. (See Tracer XM30, XM32, and XM70 Expansion
Modules Installation, Operations, and Maintenance (BAS-SVX46) for more information.)

12 BAS-SVX20F-EN
Installation; Wiring
This section provides instructions for all of the wiring on a new UC400 controller.

Overview
Figure 5. Wiring Overview Outline

Read General
Instructions (p. 14)

BACnet MS/TP Link

Setting the Address Wiring


(p. 14) (p. 17)

Power Supply

Wiring Power On Check


(p. 19) (p. 20)

I/O

Device Pre-Power Wiring


Checks (p. 20) (pp. 24-30)

Pressure Transducer Variable Resistance


Inputs Analog Inputs
(p. 25) (p. 29)

Binary Inputs Analog Outputs


(p. 26) (p. 30)

0–10 Vdc Analog Inputs Relays (Dry Contact/


(p. 27) Binary Outputs)
(p. 30)

0–20 mA Analog Inputs


(p. 28)

BAS-SVX20F-EN 13
Installation; Wiring

General Instructions
Conformance to Regulatory Standards
All wiring must comply with the National Electrical Code (NEC)™ and local electrical codes.

Connecting Wires to Terminals


Use the following procedure when connecting wires to the UC400 controller or the XM30
expansion module:
1. Strip the wires to expose 0.28 inch (7 mm) of bare wire.
2. Insert the wire into a terminal connector.
3. Tighten the terminal screw to 0.5 to 0.6 N-m (71 to 85 ozf-in or 4.4 to 5.3 lbf-in.)
4. Tug on the wires after tightening the screws to ensure all wires are secure.

Figure 6. Checking wire connections

BACnet MS/TP Link


Setting the Address
Note: To set rotary dials for the XM30 expansion module, see Tracer XM30 Expansion Module
Installation Sheet (X39641148-01).
The rotary address dials on the UC400 serve one or two purposes depending upon the network:
• They are always used for the MAC Address.
• The MAC Address is sometimes all or part of the BACnet Device ID.

14 BAS-SVX20F-EN
Installation; Wiring

Figure 7. Setting Rotary Dials

IMC 24 24 24 +24 IMC


VAC VAC VAC VDC
XFRM BI1 BI2 BI3 LINK IMC

AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5


BI4 BI5
1

P1 P2

LINK IMC
TX
RX

SERVICE

SERVICE TOOL

ADDRESS
9 1 9 1 9 1 BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9
23

23
78

78

78

3
4 56 4 56 4 56

0 0 0

x100 x10 x1

CONNECT AC POWER TO THE TRAIC SUPPLY TO POWER THE TRIACS

RELAYS TRIAC SUPPLY TRIACS


BO1 BO2 BO3
NO NC C NO NC C NO NC C A B BO4 BO5 BO6 BO7 BO8 B BO9 A

Use a 1/8 inch (3.2 mm) flathead screwdriver to set rotary address dials. Dials rotate in either direction.

MAC Address
The MAC Address is required by the RS-485 communication protocol on which BACnet operates.
A UC400 controller can use a MAC Address from 001 to 120.
Important: Each device on the link must have a unique MAC Address/Device ID. A duplicate
address or a 000 address setting will interrupt communications and cause the Tracer
SC device installation process to fail.

BACnet Device ID
The BACnet Device ID is required by the BACnet network. Each device must have a unique number
from 001 to 4094302.
BACnet networks without a Tracer SC system controller. On BACnet networks without a
Tracer SC system controller, the Device ID can be assigned one of two ways:
• It can be the same number as the MAC Address, determined by the rotary address dials on the
UC400 controller. For example, if the rotary address dials are set to 042, both the MAC Address
and the BACnet Device ID are 042.
• It can be soft set using Tracer TU service tool. If the BACnet Device ID is set using the Tracer TU
service tool, the rotary address dials only affect the MAC Address, they do not affect the BACnet
Device ID. (See the TracerUC400 Controller Protocol Implementation Conformance Statement
(PICS) [BAS-PRG007-EN] for related information.

BAS-SVX20F-EN 15
Installation; Wiring

BACnet networks with a Tracer SC system controller. On BACnet networks with a Tracer
SC system controller, the Device ID for the UC400 controller is always soft set by the system
controller using the following scheme (illustrated in Table 3).
• The first three digits are determined by the address rotary dials on the Tracer SC system
controller.
• The fourth digit is determined by the link number to which the UC400 controller is attached.
• The last three digits are determined by the rotary address dials on the UC400 controller.
Note: The BACnet Device ID is displayed as the Software Device ID on the Tracer TU Controller
Settings Page in the Protocol group.

Table 3. Calculating the BACnet device ID


Tracer SC rotary switch value (21) 0 2 1
Tracer SC BACnet MS/TP link number (1) 1
Unit controller MAC address (38) 0 3 8
BACnet Device ID: 211038 0 2 1 1 0 3 8

16 BAS-SVX20F-EN
Installation; Wiring

Connection Wiring
BACnet MS/TP link wiring must be field-supplied and installed in compliance with the National
Electrical Code and local codes. The wire must be low-capacitance, 18-gauge, stranded, tinned-
copper, shielded, twisted-pair. Figure 8, p. 17 shows an example of BACnet link wiring with
multiple UC400 controllers.
Note: For more details on this topic, see the Tracer SC Unit Controller Wiring Guide listed under
“Other Resources,” p. 53.

Figure 8. BACnet MS/TP link wiring.

+ IM + IM + IM
VDC VDC VDC
BI LINK IMC BI LINK IMC BI LINK IMC

+
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI

P P P P P P
+

LINK IM LINK IM LINK IM


TX TX TX
RX RX RX

SERVI SERVI SERVI

SERVICE TOOL SERVICE TOOL SERVICE TOOL

Tracer SC UC400 UC400 UC400

Zone Sensors

Trane BACnet
Terminator
Zone sensor
communications
jack wiring

BAS-SVX20F-EN 17
Installation; Wiring

Power Supply

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.

CAUTION
Personal Injury and Equipment Damage!
After installation, make sure to check that the 24 Vac transformer is grounded through the
controller. Failure to check could result in personal injury and/or damage to equipment.
Measure the voltage between chassis ground and any ground terminal on the UC400
controller. Expected result: Vac ≤ 4.0 V.

NOTICE:
Avoid Equipment Damage!
Sharing 24 Vac power between controllers could cause equipment damage.

A separate transformer is recommended for each UC400 controller. The line input to the
transformer must be equipped with a circuit breaker sized to handle the maximum transformer line
current.
If a single transformer is shared by multiple UC400 controllers:
• The transformer must have sufficient capacity.
• Polarity must be maintained for every UC400 controller powered by the transformer.
Important: If the polarity is inadvertently reversed between two controllers powered by the
same transformer, a difference of 24 Vac will occur between the grounds of each
controller, which can result in:
• Partial or full loss of communication on the entire BACnet MS/TP link
• Improper function of UC400 outputs
• Damage to the transformer or a blown transformer fuse

Transformer Recommendations
The UC400 controller can be powered with 24 Vac or 24 Vdc. You must use a 24 Vac power supply
for proper operation of the binary inputs, which require 24 Vac detection, and also to use the spare
24 Vac outputs to power relays and TRIACS.
• AC transformer requirements: UL listed, Class 2 power transformer, 24 Vac ±15%, device max
load 24 VA, BCI application 6 VA. The transformer must be sized to provide adequate power to
the controller (21 VA) and outputs (maximum of 10A per relay output and 0.5A per TRIAC
output). (See the power budget table under “Calculating power consumption,” p. 24 and binary
output requirements in “UC400 controller device connections,” p. 5.)
• DC power supply requirements: UL listed, Class 2 power supply, 24 Vdc ±15%, device max load
420 mA, BCI application 90 mA.
• CE-compliant installations: The transformer must be CE marked and SELV compliant per IEC
standards.

18 BAS-SVX20F-EN
Installation; Wiring

Wiring Requirements
To ensure proper operation of the UC400 controller, install the power supply circuit in accordance
with the following guidelines:
• The controller must receive AC power from a dedicated power circuit; failure to comply may
cause the controller to malfunction.
• A dedicated power circuit disconnect switch must be near the controller, easily accessible by
the operator, and marked as the disconnecting device for the controller.
• DO NOT run AC power wires in the same wire bundle with input/output wires; failure to comply
may cause the controller to malfunction due to electrical noise.
• 18 AWG (0.823 mm2) copper wire is recommended for the circuit between the transformer and
the controller.

Connect the Wires


1. Disconnect power to the transformer.
2. Ground one of the terminals on the controller to the enclosure (if the enclosure is adequately
grounded) or to an alternate earth ground.

Figure 9. Connecting 24 Vac transformer and ground.

24 Vac
The UC400 controller is not grounded
transformer through the enclosure.

A pigtail connection should be used between the


chassis ground on the device and an earth ground, if
the device is not grounded through one leg of the
transformer wiring.

IMC 24 24 24 +24 IMC


VAC VAC VAC VDC
XFRM BI1 BI2 BI3 LINK IMC

AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5


BI4 BI5
1

P1 P2

LINK IMC
TX
RX

SERVICE

SERVICE TOOL

ADDRESS
9 1 9 1 9 1 BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9
23

23
78

78

78

4 56 4 56 4 56

CONNECT AC POWER TO THE TRAIC SUPPLY TO POWER THE TRIACS

RELAYS TRIAC SUPPLY TRIACS


x1 BO1 BO2 BO3
NO NC C NO NC C NO NC C A B BO4 BO5 BO6 BO7 BO8 B BO9 A

BAS-SVX20F-EN 19
Installation; Wiring

Power On Check
1. Verify that the 24 Vac connector and the chassis ground are properly wired.
2. Remove the lockout/tagout from the line voltage power to the electrical cabinet.
3. Energize the transformer to apply power to the UC400 controller.
4. Observe the UC400 controller when power is applied to verify the power check sequence:
a. The power LED lights red for 1 second.
b. The power LED lights green.
• If the sequence completes as described, the controller is properly booted and ready for the
application code. See “Task 1: Load Application Code on a Blank UC400,” p. 37.
• If the power LED flashes red, a fault condition exists. See “LED Descriptions and Activities
with Troubleshooting Tips,” p. 34. If there are other problems after powering, see
“Commissioning and Troubleshooting in Powered State,” p. 43

Inputs and Outputs


This section describes how to wire the inputs and outputs to the UC400 controller.

Device Pre-power Checks


Before you connect any inputs or outputs to the UC400 controller, perform these pre-power checks.

Basic checks
For devices with input/output types listed below, verify their basic functionality:
• Binary inputs: check that they are opening and closing. Also check for 24 Vac if they provide their
own power. With a Trane-provided 24 Vac, check to make sure it is dry contact and working.
• Thermistors: check for 10K using a digital multimeter (DMM).
• Thumb wheels: verify mechanical operation.
• Binary outputs: check for any dead shorts.
• Analog outputs: check that no A/C voltage is present and that the load has no 24 Vac across it
or 120 Vac.

Point check diagrams


This section shows diagrams and describes methods to check device input/output points before the
connection to the UC400 controller has been made and power has been applied. The step numbers
in each illustration correspond to the information in each table. (See Table 2, p. 5 for a list of device
connections.)
Note: The UC400 controller should not be connected to the input and output devices during the
pre-power checks, so the controller is not shown in the diagrams. Similar illustrations in the
section, “Commissioning and Troubleshooting in Powered State,” p. 43 show the location
of the UC400 controller.

20 BAS-SVX20F-EN
Installation; Wiring

Resistive inputs

Checkout
Procedure Measurement Expected Value
Measure AC voltage across the Vac ≈ 0.0 V
Step 1
resistive termination. AC voltage will affect further measurement.
Measure DC voltage across the Vdc ≈ 0.0 V
Step 2
resistive termination. DC voltage will affect further measurement.
Compare the measured resistance with the expected value
Measure the resistance across the
Step 3 based on the manufacturer’s specification and current
resistive termination.
conditions.

Voltage inputs

Checkout
Procedure Measurement Expected Value
Measure AC voltage across the Vac ≈ 0.0 V
Step 1
voltage input. AC voltage will affect further measurement.
Compare the measured voltage with the expected value
Measure DC voltage across the
Step 2 based on the manufacturer’s specification and current
voltage termination.
conditions.

BAS-SVX20F-EN 21
Installation; Wiring

Current inputs

Checkout
Procedure Measurement Expected Value
Measure AC voltage across the Vac ≈ 0.0 V
Step 1
current input. AC voltage will affect further measurement.
Measure DC voltage across the
Step 2 Vdc ≈ 0.0 V.
current input.
Compare the measured current with the expected value
Measure the DC current across the
Step 3 based on the manufacturer’s specification and current
current input.
conditions.

Binary inputs, 24 Vac detect

Checkout
Procedure Measurement Expected Value
Measure AC voltage across the Vac ≈ 0.0 V
Step 1
resistive termination. AC voltage will affect further measurement.
Measure DC voltage across the Vdc ≈ 0.0 V
Step 2
resistive termination. DC voltage will affect further measurements.
Measure the resistance across the
Step 3
resistive termination.

22 BAS-SVX20F-EN
Installation; Wiring

Binary inputs based on analog output connection

Checkout
Procedure Measurement Expected Value
Measure AC voltage across the Vac ≈ 0.0 V
Step 1
resistive termination. AC voltage will affect further measurement.
Measure DC voltage across the Vdc ≈ 0.0 V
Step 2
resistive termination. DC voltage will affect further measurements.
Measure the resistance across the
Step 3
resistive termination.

Wiring Requirements

NOTICE:
Avoid Equipment Damage!
Remove power to the UC400 controller before making input/output connections. Failure to do
so may cause damage to the controller, power transformer, or input/output devices due to
inadvertent connections to power circuits.

Maximum wire lengths


Type Inputs Outputs
Binary 1,000 ft (300 m) 1,000 ft (300 m)
0–20 mA 1,000 ft (300 m) 1,000 ft (300 m)
0–10 Vdc 300 ft (100 m) 300 ft (100 m)
Thermistor/Resistive 300 ft (100 m) Not Applicable
• All wiring must be in accordance with the NEC and local codes.
• Use only 18–22 AWG (1.02 mm to 0.65 mm diameter), stranded, tinned-copper, shielded, twisted-pair wire.
Shielding is optional for binary inputs and analog 0 - 20mA inputs.
• 24 Vdc output wiring distances are dependent on the receiving unit specifications. Output wiring must comply with
the receiving unit’s wiring specifications.
• DO NOT run input/output wires or communication wires in the same wire bundle with AC power wires.

BAS-SVX20F-EN 23
Installation; Wiring

Providing Low-voltage Power for Inputs/Outputs


The UC400 controller can provide low-voltage power to the inputs/outputs. More than one input
or output can receive power from a given screw terminal as long as the total amount of power
consumed does not exceed the terminal’s limit.
The UC400 controller requires 24 Vac, UL-listed, Class 2 power transformer. This section provides
information about checking power budget consumption for the UC400 in an un-powered state.

Calculating power consumption


Apply these rules when calculating the necessary power consumption:
• Total available power is determined by the transformer rating.
• Reserve 12 VA to power XM30 expansion modules.
• The total of the 24 Vac output and inputs should not exceed the remaining power.
Use the following table as a guideline for the UC400 controller power consumption.
Table 4. UC400 Power Budget

VA Draw Per I/O Maximum Total VA Draw


Item Sub (a) (24 VAC) (24 Vac)
UC400 controller
8 VA
(No input/output)
5 x AI 0.2 VA per AI 1 VA
2 x UI 0.13 VA per UI 0.25 VA
2 x PI 0.13 VA per PI 0.25 VA
UC400 Board
3 x BI 0.17 VA per BI 0.5 VA
2 x AO 1 VA per AO 2 VA
3 x BO (relay) 1 VA per relay (no load) 3 VA
6 x BO (TRIAC) 0.34 VA per TRIAC (no load) 1 VA
Subtotal for controller 16 VA
200 mA(b) 1 VA per 25mA DC 8 VA
24 Vdc Supply
Total for controller 24 VA
Binary Outputs- Relay and TRIAC
See Table 2, p. 5, Device
BO1 to BO3 Relay See Table 2, p. 5, Device Connections
Connections
BO4 to BO9 TRIAC 0.5 A - 12 VA@ 24 Vac 12 VA Maximum
(a) A: amp, AI: analog input, AO: analog output, BI: binary input, BO: binary output, PI: pressure input, UI: universal input,
VA: voltage ampere, Vac: volts alternating current, Vdc: volts direct current
(b) Expansion Modules: If all analog outputs are configured for current and the devices are powered at the maximum current
draw, then the XM30 maximum current draw is 115 mA. Do not exceed the UC400 controller 200 mA output limit.

Terminal Locations

NOTICE:
Avoid Equipment Damage!
Remove power to the UC400 controller before making input/output connections. Failure to do
so may cause damage to the controller, power transformer, or input/output devices due to
inadvertent connections to power circuits.

24 BAS-SVX20F-EN
Installation; Wiring

Figure 10. Terminal locations

I/O Bus Terminals/Comm Links


Separate transformer input from
Auxiliary 24 Vac outputs
Comm In

Ground 24 Vac Comm Out


Binary Zone sensor service tool
24 Vac Inputs connection
Auxiliary 24 Vdc output
IMC 24 24 24 +24 IMC
VAC VAC VAC VDC
XFRM BI1 BI2 BI3 LINK IMC

AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5


BI4 BI5
1

P1 P2
Analog Universal Analog
Outputs Inputs Inputs
Pressure
Inputs

IMC 24 24 24 +24 IMC


VAC VAC VAC VDC
XFRM BI1 BI2 BI3 LINK IMC

AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5


BI4 BI5
1

P1 P2

LINK IMC
TX
RX

SERVICE

SERVICE TOOL

ADDRESS
9 1 9 1 9 1 BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9
23

23
78

78

78

4 56 4 56 4 56

CONNECT AC POWER TO THE TRAIC SUPPLY TO POWER THE TRIACS

RELAYS TRIAC SUPPLY TRIACS


BO1 BO2 BO3
NO NC C NO NC C NO NC C A B BO4 BO5 BO6 BO7 BO8 B BO9 A

CONNECT AC POWER TO THE TRAIC SUPPLY TO POWER THE TRIACS

RELAYS TRIAC SUPPLY TRIACS


BO1 BO2 BO3
NO NC C NO NC C NO NC C A B BO4 BO5 BO6 BO7 BO8 B BO9 A

Relays Binary Output/Triac

Note: The screw terminal blocks are not shown in this illustration, but they must be
inserted before you can connect wires to the identified terminal locations.

Pressure Transducer Inputs


The pressure inputs P1 and P2 (shown in Figure 10) are designed for 3-wire pressure sensor
transducers, specifically Kavlico brand, which require 5 Vdc input.
Important: If using a different brand of pressure sensor transducer, contact Trane for help
ensuring proper operation.
• P1 is typically used alone in single-duct applications when only one pressure measurement is
needed.
• P1 and P2 are typically used together in dual-duct applications when two pressure
measurements are needed. Examples include dual-duct VAV control and duct pressure
measurement.

BAS-SVX20F-EN 25
Installation; Wiring

Binary Inputs
Connect to the binary inputs to monitor statuses such as fan on/off or alarm resets.
1. Connect the common wire to a common terminal as shown below.
Note: Because the common terminals are in parallel, wiring can be made to any common
terminal.
2. Connect the shield wire (if present) to a common terminal at the termination board and tape
it back at the input device.
3. Connect the signal wire to an available input terminal.
4. Use the Tracer™ TU service tool to configure the input for binary operation.

Figure 11. Typical wiring, binary inputs to UI or BI terminals

If using a universal input terminals configured


as a binary input (shown using 2-wire with If using binary input terminals
shielding) (shown using 2-wire without shielding)

Signal 1000 ft (300 m)


Signal 1000 ft (300 m) maximum
maximum

Common
Common

Connect shield wire to a


common terminal at
controller; tape it back at 24 24
the input device VAC VAC
BI1

24
AO2 UI1 UI2 VAC
BI5 BI1 BI2
IMC 24 24 24 +24 IMC
VAC VAC VAC VDC
XFRM BI1 BI2 BI3 LINK IMC

AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5


BI4 BI5
1

P1 P2

LINK IMC
TX
RX

SERVICE

SERVICE TOOL

ADDRESS
9 1 9 1 9 1 BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9
23

23
78

78

78

4 56 4 56 4 56

0 0 0

x100 x10 x1

CONNECT AC POWER TO THE TRAIC SUPPLY TO POWER THE TRIACS

RELAYS TRIAC SUPPLY TRIACS


BO1 BO2 BO3
NO NC C NO NC C NO NC C A B BO4 BO5 BO6 BO7 BO8 B BO9 A

Note: Polarity is normally open (NO) or ON. However, you can use the Polarity control (toggle) on
the Binary Input Point Configuration dialog box to reverse polarity to normally closed (NC)
or OFF. For example, you might reverse polarity when using a binary input with a freeze stat
to open the contacts to shut off power when a temperature declines to a given setpoint.
Access the Point Configuration dialog box from either the Tracer TU Controller Settings
Utility Binary point list screen or the right-click menus on the Tracer TU Status Utility Binary
point list screen.

26 BAS-SVX20F-EN
Installation; Wiring

0–10 Vdc Analog Inputs


The two universal inputs can be used to receive a 0–10 Vdc analog signal from sensors such as
indoor air quality sensors and pressure sensors. To wire a 0–10 Vdc analog input:
1. Connect the shield wire (as common connection) to a common terminal as shown in Figure 12.
2. Connect the signal wire to an available input terminal.
3. Connect the supply wire to a 24 Vdc or 24 Vac terminal as required.
4. Use the Tracer TU service tool to configure the universal input for analog operation.

Figure 12. Typical wiring, 0–10 Vdc

24 Vdc
300 ft
(100 m)
0–10 Vdc out max.

Common

24 24
VAC VAC
BI1
+24 IM
VDC
AO2 UI1 UI2 MC
BI5

IMC 24 24 24 +24 IMC


VAC VAC VAC VDC
XFRM BI1 BI2 BI3 LINK IMC

AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5


BI4 BI5
1

P1 P2

LINK IMC
TX
RX

SERVICE

SERVICE TOOL

ADDRESS
9 1 9 1 9 1 BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9
23

23
78

78

78

4 56 4 56 4 56

0 0 0

x100 x10 x1

CONNECT AC POWER TO THE TRAIC SUPPLY TO POWER THE TRIACS

RELAYS TRIAC SUPPLY TRIACS


BO1 BO2 BO3
NO NC C NO NC C NO NC C A B BO4 BO5 BO6 BO7 BO8 B BO9 A

BAS-SVX20F-EN 27
Installation; Wiring

0–20 mA Analog Inputs


The universal inputs can be used to receive a 0–20 mA analog signal from sensors such as humidity
sensors and pressure sensors.
To wire a 0–20 mA analog input:
1. Connect the shield to a common terminal at the terminal board and tape it back at the input
device.
Important: Do not use the shield as the common connection. For 3-wire applications, use a 3-
conductor cable with shield and for 2-wire applications, use a 2-conductor cable with
separate shield.
2. Connect the signal wire to an available universal input terminal.
3. Connect the supply wire to a 24 Vdc or 24 Vac terminal as required.
4. Use the Tracer TU service tool to configure the universal input for analog operation.

Figure 13. Typical wiring, 0–20 mA

24 Vdc 1000 ft
(300 m)
0–20 mA out max.
0–20 mA sensor
(current source)
Common
Tape back shield
24 Vdc
0–20 mA sensor
(current controller)
.
0–20 mA out ax
m
)
m
0
( 30
ft
0
1 00
24
VAC
BI1 B
+24 IM
VDC
UI1 UI2 MC

IMC 24 24 24 +24 IMC


VAC VAC VAC VDC
XFRM BI1 BI2 BI3 LINK IMC

AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5


BI4 BI5
1

P1 P2

LINK IMC
TX
RX

SERVICE

SERVICE TOOL

ADDRESS
9 1 9 1 9 1 BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9
23

23
78

78

78

4 56 4 56 4 56

0 0 0

x100 x10 x1

CONNECT AC POWER TO THE TRAIC SUPPLY TO POWER THE TRIACS

RELAYS TRIAC SUPPLY TRIACS


BO1 BO2 BO3
NO NC C NO NC C NO NC C A B BO4 BO5 BO6 BO7 BO8 B BO9 A

28 BAS-SVX20F-EN
Installation; Wiring

Variable Resistance Analog Inputs


Variable resistance analog inputs include 10K thermistors, resistive, and setpoint thumb wheels on
zone sensors.
1. Connect the shield to a common terminal at the terminal board and tape it back at the input
device.
Important: Do not use the shield as the common connection. For 3-wire applications, use a
3-conductor cable with shield and for 2-wire applications, use a 2-conductor cable
with separate shield.
2. Connect the signal wire to an available input terminal.
3. Use the Tracer TU service tool to configure the input for analog operation.

Figure 14. Typical wiring, variable resistance


300 ft
Signal (100 m)
Temperature max.
sensor
Common
Tape back
shield

300 ft
Signal (100 m) Zone UC400
Variable max. Sensor Terminatio
resistance
Output n Type Range
Common Zone Temp AI1 Thermistor 10k Ω

Time zone sensor Zone Temp


Tape back AI2 Setpoint 189 Ω−889 Ω
shield Setpoint
100 Ω−
Fan Mode AI3 Resistive
100k Ω
Setpoint
Common Comm+(a) IMC+
Temperature } {

Comm- IMC-
(a) For Comm+/- wiring, use 18 AWG, shielded, twisted-pair wire.
300 ft
(100 m)
max.
IMC 24 24 24 +24 IMC
VAC VAC VAC VDC
XFRM BI1 BI2 BI3 LINK IMC

AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5


BI4 BI5
1

P1 P2

LINK IMC
TX
RX

SERVICE

SERVICE TOOL

ADDRESS
9 1 9 1 9 1 BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9
23

23
78

78

78

4 56 4 56 4 56

0 0 0

x100 x10 x1

CONNECT AC POWER TO THE TRAIC SUPPLY TO POWER THE TRIACS

RELAYS TRIAC SUPPLY TRIACS


BO1 BO2 BO3
NO NC C NO NC C NO NC C A B BO4 BO5 BO6 BO7 BO8 B BO9 A

BAS-SVX20F-EN 29
Installation; Wiring

Analog Outputs
The UC400 has two analog outputs. These outputs can be used for 0–10 Vdc outputs or 0–20 mA
outputs, which can control actuators or secondary controllers.
Note: Output wiring specifications must comply with the receiving device wiring requirements.
1. Connect the shield to a common terminal at the terminal board and tape it back at the input
device.
Important: Do not use the shield as the common connection. For 2-wire applications, use a
2-conductor cable with separate shield.
2. Connect the signal wire to an available output terminal.
3. Connect the supply wire to a 24 Vdc or 24 Vac terminal as required.
4. Use the Tracer TU service tool to configure the input for analog operation.

Figure 15. Typical wiring, analog outputs

DC powered
actuator
300 ft
(100 m)
24 Vdc max.
Signal
Common Tape back shields

Signal Connect to 24 Vdc or


300 ft 24 Vac as required
(100 m)
Common max.

IMC 24 24 24 +24 IMC


VAC VAC VAC VDC
XFRM BI1 BI2 BI3 LINK IMC

0–10 Vdc output (Load > AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5

500 Ω or 0–20 mA output


BI4 BI5
1

(Load < 500 Ω) P1 P2

LINK IMC
TX
RX

SERVICE

SERVICE TOOL

ADDRESS
9 1 9 1 9 1 BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9
23

23
78

78

78

4 56 4 56 4 56

0 0 0

x100 x10 x1

CONNECT AC POWER TO THE TRAIC SUPPLY TO POWER THE TRIACS

RELAYS TRIAC SUPPLY TRIACS


BO1 BO2 BO3
NO NC C NO NC C NO NC C A B BO4 BO5 BO6 BO7 BO8 B BO9 A

Relays (Dry Contact/Binary Outputs)


The UC400 has three relay binary outputs used as powered outputs. All outputs are isolated from
one another and from the ground and power.
Note: Output wiring specifications must comply with the receiving device wiring requirements.

NOTICE:
Be aware of inrush current!
Controlling coil-based loads: Inrush current (the initial surge of a current into a load before it
attains normal operating condition) can be more than three times greater than the operating
current.

Important: Use pilot relays for dry contact outputs for load currents greater than 0.5 amperes
and use powered outputs for load currents less than 0.5 amperes.

30 BAS-SVX20F-EN
Installation; Wiring

To wire relay binary outputs:


1. Connect the shield to a common terminal at the terminal board and tape it back at the output
device.
2. Connect the signal wire to an available output terminal.
3. Use the Tracer TU service tool to configure the input for binary operation.
Note: Polarity is normally open (NO) or ON. However, you can use the Polarity control (toggle) on
the Binary Output Point Configuration dialog box to reverse polarity to normally closed (NC)
or OFF.

Figure 16. Typical wiring, relays (binary outputs)

c
D Va
GN 24

IMC 24 24 24 +24 IMC


VAC VAC VAC VDC
XFRM BI1 BI2 BI3 LINK IMC

AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5


BI4 BI5
1

P1 P2

LINK IMC
TX
RX

SERVICE

SERVICE TOOL

ADDRESS
9 1 9 1 9 1 BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9
23

23
78

78

78

4 56 4 56 4 56

0 0 0

x100 x10 x1

CONNECT AC POWER TO THE TRAIC SUPPLY TO POWER THE TRIACS

RELAYS TRIAC SUPPLY TRIACS


BO1 BO2 BO3
NO NC C NO NC C NO NC C A B BO4 BO5 BO6 BO7 BO8 B BO9 A

Powered Pilot relay


output Tape back (24 Vac coil)
shield
Signal Signal

Common 1000 ft 1000 ft Common


(300 m) max. (300 m) max.

Tape back
shield

BAS-SVX20F-EN 31
Installation; Wiring

TRIAC (low/high side switching, binary outputs)


The UC400 has six (6) TRIAC binary outputs. To wire TRIAC binary outputs (low/high), refer to the
illustration below.

Figure 17. Typical wiring, TRIAC binary outputs

c
Va
24 D
N
G
Low Side Switching

Analog Outputs Universal Inputs Analog Inputs

Note: The benefit of using low side


switching is to minimize the risk of
burning up binary outputs due to
inadvertent shorts to the ground .
Relays Binary Output/TRIAC

ly c
D

pp Va
N

Su 24
G

To
c
Va
24 D
N
G

High Side Switching

Analog Outputs Universal Inputs Analog Inputs

Relays Binary Output/TRIAC


ly c
pp Va

D
N
Su 24

G
To

32 BAS-SVX20F-EN
Operation
This section describes how to verify and interpret the UC400 LEDs and how to safely operate the
UC400. LEDs are used to provide serviceability of controllers and XM30 expansion modules.

LED Locations
The UC400 and XM30 expansion module have the following LEDs located on the front (see the
illustration in Figure 18):
• Marquee LED
• Communication Status LEDs and IMC Status LEDs
• Service Button LED
• Binary Output Relay (3)/TRIAC (9) Status LEDs (only the UC400)
For detailed information about wiring communication links, see Tracer SC Unit Controller Wiring
Guide (BAS-SVNO3) listed in the section, “Other Resources,” p. 53.

Figure 18. Controller LEDs

IMC 24 IMC
VDC
IMC

Marquee XM30 Marquee


IMC
Communication TX
Communication
RX

Service SERVICE Service


Binary Output-Relay TRIAC LEDs (9)
ADDRESS
9 01 9 01
78

23

78

23

456 456
x10 x1

UI/AO
1 2 3 4

Marquee LED

LINK IMC
TX
RX
SERVICE

BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9

BAS-SVX20F-EN 33
Operation

LED Descriptions and Activities with Troubleshooting Tips


There are 15 LEDs on the front of the UC400 unit. The following table provides a description of LED
activity, an indication or troubleshooting tip for each, and any relative notes. See Figure 18, p. 33,
for locations of these LEDs and to “Task 4: Set Up and Discover XM30/32/70 Expansion Modules,”
p. 39 for a description of the XM30 LED activities.
Table 5. LED Activities and Troubleshooting Tips

Indication and
LED Name Activities Troubleshooting Tips Notes
Shows solid green when the unit is
Indicates normal operation
powered and no alarm exists
Shows blinking green during a
Indicates normal operation
device reset or firmware download
• If low power; could be under
voltage or the microprocessor
has malfunction. Follow the
troubleshoot procedure “24 Vac
Shows solid red when the unit is Measurement,” p. 46 to measure
for the expected value range. In When powering the UC400 and
powered, but represents low
addition, see Table 4, p. 24, for a expansion module, the Marquee
power or a malfunction
list of 24 Vac draws. LED will blink RED, blink GREEN
(indicating activated and
• If malfunction; un-power and
Marquee LED controller/expansion module are
then re-power unit to bring the
communicating), and then stay
unit back up to normal operation.
GREEN CONTINUOSLY
An alarm or fault condition will (indicating normal power
occur if the value for a given point operation).
Shows blinking red when an alarm is invalid or outside the configured
or fault exists limits for the point. Alarm and fault
conditions vary, and they can be
configured by the programmer.
Indicates power is OFF or there is a
malfunction
LED not lit
• OFF or malfunction; cycle the
power and see Table 4, p. 24.
Blinks at the data transfer rate TX LED: Regardless of connectivity
TX blinks green when the unit transfers data to or not, this LED will constantly blink
other devices on the link as it continually looks for devices to
communicate to.
Blinks at the data transfer rate
when the unit receives data from
other devices on the link LED not lit:
RX blinks yellow Determine if, for example, a Tracer
• ON solid yellow; indicates SC or BACnet device is trying to
Link and IMC talk to the controller or if it is
there is reverse polarity
capable of talking to the controller.
Also determine if the
Indicates that the controller is not communication status shows down
detecting communication all of the time. In addition, check
LED is not lit polarity and baud rate.
• Not lit; cycle the power to
reestablish communication See “Ground Measurements,” p. 52
for a check-out procedure.
Shows solid green when the LED When the UC400 is placed into
has been pressed boot mode, the system will not
run any applications such as
trending, scheduling, and TGP2
runtime. The controller will be
placed into boot mode if the
Service
Indicates controller is operating service pin is held in when
LED not lit power is applied. In boot mode,
normally
the controller is non-
operational and is waiting for a
new main application to be
downloaded.

34 BAS-SVX20F-EN
Operation

Table 5. LED Activities and Troubleshooting Tips (continued)

Indication and
LED Name Activities Troubleshooting Tips Notes
Indicates a corresponding binary If the user is currently powering
output has been commanded ON the UC400 from a USB port, the Led
lights will turn ON. However, the
• Relay coil; indicates that a binary outputs will not be
Shows solid yellow command has been made to activated.
energize
• TRIAC; indicates that a Commanded ON; As an example
command has been made to turn of commanded ON, a command
ON could be a manual command such
as an override or a command could
Binary B01 through B09 be from TGP2 based on a list of
conditions that are met telling
these outputs to turn ON.
Indicates that a relay output is de-
energized or no power to the board LED not lit:
LED not lit Did the user command it to be ON?
• Not lit; cycle power to If yes, see the Marquee LED at the
reestablish communication top of this table. In addition, see
“24 Vac Measurement,” p. 46 and
“Ground Measurements,” p. 52 for
check-out procedures.

BAS-SVX20F-EN 35
Configuration and Maintenance
This section briefly outlines the tasks you need to perform to configure and maintain a UC400 using
the Tracer TU service tool.
Important: Because the UC400 is a self-serviceable unit, this device is not intended to be
disassembled by the user for maintenance.

Prerequisites
This manual was written with the assumption that you have basic knowledge using the Tracer TU
service tool. Basic Tracer TU operations, such as connecting to a controller directly using a USB
cable or connecting indirectly using Tracer SC pass-through and starting a Tracer TU session are
explained in the Tracer TU Getting Started Guide (TTU-SVN02) (for users outside of Trane). It is
included on the Tracer TU installation CD. The Guide (TTU-SVN01) is also available to Trane
personnel on the Trane portal. In addition, you can refer to the Tracer TU Connection Help, which
you can access from the Help button on the Startup Task Panel that appears when Tracer TU is
started. (See “Other Resources,” p. 53 for additional information available in related documents.)

Figure 19. Tracer TU Help and literature supporting the UC400

36 BAS-SVX20F-EN
Configuration and Maintenance

UC400 Setup and Configuration Task Summary


Perform the following tasks using the Tracer TU service tool.
“Task 1: Load Application Code on a Blank UC400”
“Task 2: Choose a UC400 Configuration Option”
“Task 3: Specify Controller Settings”
“Task 4: Set Up and Discover XM30/32/70 Expansion Modules”
“Task 5: Specifying an Equipment Configuration”
“Task 6: Commissioning the Hard-Wired Points”
“Task 7: Modify or Create TGP2 Programs as Needed”
“Task 8: Monitoring and Viewing Point, Alarm, and Controller Status”
“Task 9: Backing Up and Restoring Files and Configurations”
Each task description also points to the Table of Contents (TOC) location of appropriate topics you
can refer to in the Tracer TU Help for Programmable Controllers.
Important: For a more comprehensive and detailed discussion of all the UC 400 setup and
configuration tasks summarized here, see the Tracer UC400/UC600 with Tracer SC
System Controller Programming Guide (BAS-SVP06).

Task 1: Load Application Code on a Blank UC400


All UC400 controllers ship without application code (firmware). Before configuring the UC400,
check for the controller application code using the Tracer™ TU service tool, as follows:
1. Start the Tracer TU service tool to establish a connection with the UC400.
If no firmware is present, the following message appears.

2. Click OK.
To load or upgrade the firmware, follow the procedure in “Upgrading Controller Firmware” under
the “Managing Configurations, Firmware, and Programs” book of the TOC as shown here:

BAS-SVX20F-EN 37
Configuration and Maintenance

Task 2: Choose a UC400 Configuration Option


First, get an overview of the parts of a UC400 configuration. See “The Main Parts of Device Setup
and Configuration” in the “An Overview of Device Setup and Configuration” book in the Tracer TU
Help for Programmable Controllers as shown here.

Then read “Point Configuration Overview” (under the “Configuring and Managing Points” book
in the TOC) carefully for an explanation of your configuration options. Also read the linked topics
relevant to the approach you want to take.

You have two main configuration options:


• Use the Tracer TU Configuration Screen to create a “factory configuration”
Note: You can make some modifications to Trane factory blower coil, fan coil, or unit ventilator
configurations. See “An Overview of Editable Factory Configurations” under the
“Configuring and Commission Equipment” TOC book > “Trane Factory Blower Coils,
Fan Coils, and Unit Vents”.
• Create or edit a custom (field programmed) configuration.

38 BAS-SVX20F-EN
Configuration and Maintenance

Task 3: Specify Controller Settings


Complete the following tasks:
• Configure units of measure.
• Specify controller date and time.
• Specify the baud rate, if other than the default (76800).
For procedural information, see the “Modifying Controller Settings” book in the TOC as shown
here.

Task 4: Set Up and Discover XM30/32/70 Expansion Modules


Perform the following steps:
1. Mount, wire, address, and power the expansion module as described in the Installation
Instructions that accompany the unit.
(See “Other Resources,” p. 53 for the titles and part numbers of these documents.)
2. Set up the module(s) using the controls on the Expansion Modules box on the Controller
Settings screen.
Note: If you add an expansion module on the Controller Settings page, but the module is not
connected to the controller, you will have to discover it on the Controller Status screen
after it is connected and powered.
See “Setting Up And Discovering Expansion Modules” under the Modifying Controller Settings
book for the procedural information.

BAS-SVX20F-EN 39
Configuration and Maintenance

Task 5: Specifying an Equipment Configuration


Go to the information sources supporting the configuration option you choose.

Option 1: Use the Tracer TU Configuration screen to create a “factory


configuration.”
(See the topics under the “VAV Boxes”, “Trane Factory Blower Coils, Fan Coils and Unit Vents”, or
Variable-Speed Water Source Heat Pumps (VS-WSHPs)” sub-books in “Configuring and
Commissioning Equipment”)

Option 2: Create a Custom Configuration.


This option requires a thorough knowledge of the devices and the network you are installing,
including an understanding of the TGP2 programs and the points they use. Complete the following
steps:
1. Create points or open a previously created points file, make any edits, and save them to the
UC400.
Note: You can create, edit, and load points, either in Tracer TU, or in the TGP2 Editor. (See the
Configuring and Managing Points TOC book in the Tracer Graphical Programming
(TGP2) Editor Help.)
Be aware of the maximum point counts.
Table 6. Maximum Number of Points by Type
Type Number
Analog Input 40
Analog Output 16
Analog Value 128
Binary Input 32
Binary Output 24
Binary Value 48
Multistate Input 8
Multistate Output 8
Multistate Value 32

2. Specify setpoint values and equipment parameters on the Setpoints and Setup Parameters
screens (Equipment Utility).
Note: You will supply the necessary TGP2 programs after you commission the hard-wired points.
(See Task 7).

40 BAS-SVX20F-EN
Configuration and Maintenance

Task 6: Commissioning the Hard-Wired Points


After you have all points configured, saved, and downloaded to the controller, you are ready to
commission or test them by overriding Output and Value points. See the topics under the
“Overriding, Comparing, and Changing the Service Status of Points” book in the TOC.

Notice:
Possible Equipment Damage!
Follow proper equipment safety procedures when controlling outputs.

Task 7: Modify or Create TGP2 Programs as Needed


Now that you have the hardware points in place and tested, you can create or edit TGP2 programs
that will run the equipment according to the sequence of operations specified for your job. (See
the topics under the “Developing and Managing TGP2 Programs” TOC book in the Tracer Graphical
Programming (TGP2) Editor Help for programming procedures. Also see the “TGP2 Block
Reference” TOC book to learn how the various blocks work and for information about their
properties.
Finally, for more in-depth TGP2 programming instruction, see the Tracer Graphical Programming
(TGP2) Applications Guide (BAS-APG008-EN).)

Task 8: Monitoring and Viewing Point, Alarm, and Controller Status


See the topics under the “Viewing the Status of Points and Alarms” book in the TOC.

BAS-SVX20F-EN 41
Configuration and Maintenance

Task 9: Backing Up and Restoring Files and Configurations


You can upload, back up, replace, or update configuration files, controller firmware, and TGP2
programs using the File Transfer Utility and the Backup Utility. See the topics under “Managing
Configurations, Firmware, and Files” book in the TOC.

42 BAS-SVX20F-EN
Commissioning and Troubleshooting in Powered State
This section provides illustrations and methods about how to check the UC400 points after making
connection and applying power (indicated in each illustration by the terminal connector and UC400
label). The step numbers or method numbers in each illustration correspond to the information in
each table. (See Table 2, p. 5 for a list of device connections.)
To test inputs/outputs requires the following equipment:
• Digital multimeter (DMM)
• Small flat-tip screwdriver
Note: The Out of Service and Override features in Tracer TU can be used to simulate operation for
testing the input/output interaction. By placing a point out of service or overriding at the
priority required for control, the user can enter a value for the point sufficient to trigger a
reaction at the output based on the TGP2 logic controlling the output.
Voltage Inputs

Checkout Procedure Measurement Expected Value


Measure AC voltage across the Vac ≈ 0.0 V
Step 1
voltage termination AC voltage will affect further measurement
Measure DC voltage across the
Step 2 Compare to input status in Tracer TU
voltage termination

BAS-SVX20F-EN 43
Commissioning and Troubleshooting in Powered State

Resistive Inputs

Checkout Procedure Measurement Expected Value


Vac ≈ 0.0 V
Step 1 Measure AC voltage across the resistive termination
AC voltage will affect further measurement
Step 2 Measure DC voltage across the resistive termination See the charts below

Measured Voltage Across a Thermistor Input Measured Voltage Across a Thermistor Input
4 4
Voltage Measured Across Input–Vdc

Voltage Measured Across Input–Vdc

3.5 3.5

3 3

2.5 2.5

2 2

1.5 1.5

1 1

0.5 0.5

0 0
0 50 100 150 200 -40 -20 0 20 40 60 80 100

Thermistor Input–°F Thermistor Input–°C

Measured Voltage Across a Resistive Input


2.5
Voltage Measured Across Input–Vdc

Charts showing
measurements 2

across thermistor
input (Fahrenheit
1.5
and Celsius) and
resistive input.
1

0.5

0
0 2 4 6 8 10 12 14 16 18 20

Resistive Input–kΩ (Ohms)

44 BAS-SVX20F-EN
Commissioning and Troubleshooting in Powered State

Current Inputs- Methods 1 or 2

General Information Checkout Procedure Measurement Expected Value


Method 1 takes advantage of Measure AC voltage across the Vac ≈ 0.0 V
Step 1
the very low input resistance of current input AC voltage will affect further measurement
a DMM in current measurement
mode. However, this method Measure DC voltage across the
Step 2 Vdc ≈ 0.0 V
affects the value of the UC400 current input
will use while controlling
outputs. When the meter is set
to current mode, the current Measure DC current across the
Step 3 Compare to input status in Tracer TU
current input
flowing into the UC400 circuit
will drop to zero or near zero.

General Information Checkout Procedure Measurement Expected Value


Method 2 interferes less in Measure AC voltage across the Vac ≈ 0.0 V
Step 1
regards to the system. In voltage voltage input AC voltage will affect further measurement
mode, the DMM affects the circuit
less. Additional information is
needed to translate the voltage Measure DC voltage across the
Step 2 See the chart below
measured to current flowing voltage termination
through the circuit.

Measured Voltage Across a Linear Current Input


4.5
Voltage Measured Across Input–Vdc

3.5

2.5

1.5

0.5

0
0 2 4 6 8 10 12 14 16 18 20

Linear Current Input–mA

BAS-SVX20F-EN 45
Commissioning and Troubleshooting in Powered State

24 Vac Measurement

General Information Checkout Procedure Measurement Expected Value


Checking the voltage that is powering the Measure AC voltage with the
UC400 is often a necessary step when UC400 connected. Perform this
Step 1 20.0 Vac ≤ Vac ≤ 30.0 Vac
commissioning or troubleshooting. measurement while the unit is
Operational issues and LED operation may under load.
result in a need to measure the input
power.

When troubleshooting, it is faster to take


measurements while the load is in place. Measure AC voltage with the
If Step 1 indicates an out-of-specification UC400 unconnected. Perform this
voltage, disconnect the UC400 and Step 2 20.0 Vac ≤ Vac ≤ 30.0 Vac
measurement while the unit is not
measure the AC voltage across the under load.
transformer. These measurements can
direct the technician towards the problem
source.

46 BAS-SVX20F-EN
Commissioning and Troubleshooting in Powered State

Binary Inputs, 24 Vac Detect- Methods 1 or 2

General Information and Checkout Procedure Measurement Expected Value


Method 1 Vac ≈ 0.0 V (state = ON)
Measure AC voltage across
Voltage across binary input measured without reference to chassis Vac ≈ 24.0 V (state = OFF)
the binary input
ground.
Method 2
Voltage across binary input measured with reference to chassis ground. Any Measure DC voltage across Vac ≈ 0.0 V (state = ON)
connection with chassis ground symbol can serve as a ground reference for the binary input Vac ≈ 24.0 V (state = OFF)
this method.

Binary Inputs- Based on Analog Output Connection

General Information Checkout Procedure Measurement Expected Value


The UC400 analog output Measure AC voltage across the Vac ≈ 0.0 V
Step 1
connections can be configured binary input AC voltage will affect further measurement
as binary inputs. This can be
used only with dry contact or Measure DC voltage across the Vdc ≤ 2.0 V (state = ON)
Step 2
open collector-type sensors. binary input Vfc ≥ 2.0 V (state = OFF)

BAS-SVX20F-EN 47
Commissioning and Troubleshooting in Powered State

Open-collector Based Binary Sensors

Measurement Procedure Expected Value


Vdc ≤ 0.2 V (BJT = ON)
Measure DC voltage across the binary input UI: Vdc ≈ 3.3 V (BJT = OFF)
AO: Vdc ≈ 22.0 V (BJT = ON)

Open-collector based binary sensors use a bipolar junction transistor (BJT; a three-terminal device in which
emitter-to-collector current is controlled by base current) as the switching device in place of a relay. The term, open
collector, refers to the collector connection on the transistor itself. Open-collector circuits are used for their low
fatigue rate and quick response relative to relay-based outputs.
The circuit within the pulse meter is completed when adding a pull-up resistance and reference voltage. On the
UC400, both universal input (UI) and analog output (AO) circuits add the necessary resistance and voltage without
external parts.
Note: The reference voltage must always be DC.
The voltage across the pulse meter terminals will bounce between Vsat (saturation voltage) of the transistor in the
pulse meter and the Vref (reference voltage) provided by the UI or AO circuits of the UC400. Most bipolar transistors
have a Vsat of less than 0.2 Vdc.
The DMM sampling rate may be too slow to measure pulse meter output transitions.
Note: Check the specifications of the DMM being used. It may be necessary to use an oscilloscope to measure
the transition voltages.

48 BAS-SVX20F-EN
Commissioning and Troubleshooting in Powered State

Voltage Analog Output

Measurement Procedure Expected Value


Compare to the expected value
Measure DC voltage across the voltage based on request from controller.
termination This request may be based on an
override of the output value.

Current Analog Output- Methods 1 or 2

General Information and Checkout Procedure Measurement Expected Value


Method 1
Measure DC current Compare expected value based on request
Shorting the current output- this method leaves the circuit intact,
across the current from controller. This request may be based
however, it will cause the vast majority of the current to flow through
termination on an override of the output value.
the meter instead of the load (NOTE LOAD RESISTANCE).
Method 2
Measure DC current Compare expected value based on request
Measuring current directly- this method is most the typical way to
across the current from controller. This request may be based
measure current and has the advantage of leaving the load in the loop.
termination on an override of the output value.
However, the circuit must be broken when using this method.

BAS-SVX20F-EN 49
Commissioning and Troubleshooting in Powered State

Binary Output, TRIAC High Side Switching- Methods 1 or 2

Checkout Procedure Measurement Expected Value


Measure AC voltage across the Vac ≈ 0.0 V (TRIAC = OFF)
Method 1
binary output Vac ≥ 24.0 V (TRIAC = ON)
Measure AC voltage across the Vac ≈ 0.0 V (TRIAC = ON)
Method 2
binary input Vac ≥ 24.0 V (TRIAC = OFF)

50 BAS-SVX20F-EN
Commissioning and Troubleshooting in Powered State

Binary Output, TRIAC Low Side Switching- Methods 1 or 2

Checkout Procedure Measurement Expected Value


Measure AC voltage across the Vac ≈ 0.0 V (TRIAC = OFF)
Method 1
binary output Vac ≥ 24.0 V (TRIAC = ON)
Measure AC voltage across the Vac ≈ 0.0 V (TRIAC = ON)
Method 2
binary input Vac ≥ 24.0 V (TRIAC = OFF)

BAS-SVX20F-EN 51
Commissioning and Troubleshooting in Powered State

Ground Measurements

VDDCC ADDCC

VAACC Ω Method #3

Chassis
C h a ssi s
ground
ground

P1 P2

UC400
U C400

S E RV
R V ICE
IC E TOOL
TOOL

0 1
2
3

4
5

x1
x 1
BO1
B O1

NO
NO N
NCC C

General Information and Checkout Procedure Measurement Expected Value


Method 1
AC voltage between shield conductors and device chassis ground- Measure AC voltage across
the voltage difference between BACnet MS/TP device chassis ground the voltage termination and
connections should be close to zero. If the voltage difference is greater confirm that only one end of Vac ≤ 2.0 V
that 4.0 Vac, there will be marginal communication or intermittent the shield conductor is tied
communication problems. If the voltage difference is greater that 7.0 Vac, to the earth ground
some devices will no longer communicate.
Method 2
Measure AC voltage across
AC voltage between earth ground and device chassis ground- the
the voltage termination and Vac ≤ 4.0 V
chassis ground of the UC400 needs to be connected to earth ground by
confirm that only one end of (Must comply with National Electrical
some route.
the shield conductor is tied Code™ and local electrical codes)
to the earth ground
Note: Do not assume that the building frame is a valid earth ground.
Method 3
Measure AC voltage across Vac ≤ 4.0 V
AC voltage between case (nominal chassis ground) and device
the voltage termination. For (Must comply with National Electrical
chassis ground connector- in this illustration the connection appears
this measurement, confirm Code™ and local electrical codes)
as a short. However, it is possible that the chassis ground connection on
that only one end of the
the controller may actually be connected to the equipment metal some
shield conductor is tied to Typically, this should be
distance away. Use this measurement method if there are communication
the earth ground. Vac ≤ 1.0 V
issues or input stability problems.

52 BAS-SVX20F-EN
Other Resources
For more detailed information, refer to the following documentation:
• Tracer SC System Controller Installation and Setup (BAS-SVX31)
• Tracer SC Unit Controller Wiring Guide (BAS-SVN03)
• Tracer Graphics Editor Online Help
• Tracer Graphical Programming 2 (TGP2) Editor Online Help
• Tracer Graphical Programming (TGP2) Application Guide (BAS-APG008)
• Tracer TU Online Help
• Tracer TU Service Tool Getting Started Guide (TTU-SVN01)
• Tracer UC400 Enclosure Installation Sheet (X39641147-01)
• Tracer UC400 Programmable BACnet Controller (For Factory Installation on VAV) Installation,
Operation, and Maintenance (VAV-SVX07)
• Tracer UC400 Protocol Implementation Conformance Statement (PICS) (BAS-PRG007-EN)
• Tracer XM30 Expansion Module Installation Sheet (X39641148-01)
• Tracer XM32 Expansion Module Installation Instructions (X39641174-01)
• Tracer XM70 Expansion Module Installation Sheet (X39641179-01)

BAS-SVX20F-EN 53
Declaration of CE Conformity
Manufacturer name: Trane
Manufacturer address: 3600 Pammel Creek Road
LaCrosse, WI 54601
USA

The manufacturer hereby declares that the product:


Product name: Tracer™ UC400 Unit Controller
Model numbers: UC400

Conforms to the following standards or other normative documents:


Electrical equipment for measurement, control,
Electromagnetic Emission: EN61326-1:2006 and laboratory use—EMC requirements, part 1:
General Requirements
EN55022:2006 (CISPR
(by Council Directive 2004/108/EEC) 22:2005+A1:2005) Radiated Class B Limit (30 MHz—1000 MHz, 1 GHz—2 GHz)
Emissions
EN55022:2006 (CISPR
22:2005+A1:2005) Radiated 150 kHz—30 MHz
Emissions

Electromagnetic Immunity for Industrial: EN61326-1:2006


EN61000-4-2: 1995+A1:
(by Council Directive 89/336/EEC) 1998+A2:2001 Electrostatic 8 kV air, 4 kV contact
Discharge (ESD)
10 V/m, 80 MHz—1000 MHz
EN61000-4-3: 2002 Radiated Fields 3 V/m, 1.4 GHz—2.0 GHz
1 V/m, 200 GHz—2.7 GHz
I/O port, 1 kV
EN61000-4-4: 2004 Fast Transients
AC inputs and output ports, 2 kV
EN61000-4-5: 1995+A1: 2001
AC input ports (L/L), differential mode, 1 kV
Surge Transients
EN61000-4-6: 1996+A1: 2001
3 V, 0.15 MHz—80 MHz
Conducted Disturbance
EN61000-4-8: 1993+A1: 2001
30 A/m, 50 Hz
Power Frequency Magnetic Field
EN61000-4-11: Second Edition: 0% Vnom, 1 cycle; 70% Vnom, 25 cycle; 40%
2004 Voltage Dips and Interruptions Vnom, 10 cycle; 0% Vnom, 250 cycle

Where and When Issued: Electromagnetic Emission 09/03/2008


Electromagnetic Immunity 02/19/2009
Mark of Compliance:
European Contact
Societe Trane (Epinal, France)
1, rue des Ameriques, B.P. 6
F-88191 Golbey Cedex, France
Phone: (33) 329.31.73.00
Fax: (33) 329.81.24.98

This document validates CE conformity of the Tracer UC400 Unit Controller

54 BAS-SVX20F-EN
Index
A I current analog output 49
agency listings 7 input/output requirements 23 current inputs 45
alarm status 41 ground measurements 52
application code
K open collector 48
loading 37 Kavlico 6, 25 resistive inputs 44
voltage analog output 49
procedure 37 L voltage inputs 43
B LED pre-power check
backing up files 42 binary 35 binary inputs based on analog
baud rate 39 descriptions and activities 34 output connection 23
binary inputs link and IMC 34 binary inputs, 24 Vac detect 22
reversing polarity 26 marquee 34 current inputs 22
service 34 resistive inputs 21
C link wiring voltage inputs 21
calculating power consumption 24 BACnet MS/TP 14 pressure sensor inputs 25
commissioning (See powered state) literature programs (See TGP2 programs)
comparing points 41, 42 other resources 53
configuration options supporting UC400 36 R
custom 38 restoring files and configurations 42
M
factory 38 S
Configuration screen maintenance
backup and restore 42 specifications 5
factory configurations 40
Controller Settings configuration options 38 T
baud rate 39 controller settings 39
TGP2 Editor
date and time 39 equipment configurations 40
creating programs 41
units 39 expansion modules 39
TGP2 programs
controller status 41 firmware 38
creating 41
custom configuration maximum point creation 40
information resources 41
creating 40 overriding points 42
Tracer TU
max number of points 40 prerequisites 36
backing up configurations 42
maximum point creation 40
D commissioning hard-wired
O points 41
date and time 39 creating a configuration 40
Declaration of Conformity 54 operation 33
ordering options 8 expansion module setup 39
device connections 5 Help library 36
dimensions 9 other resources 53
overriding points 42 loading application code 37
DIN rail monitoring points, alarms, and
clearance 10 P UC status 41
mounting or removing 11 points prerequsites for using 36
DMM 20, 43 comparing 41 restoring configurations 42
E maximum count 40 specifying controller settings 39
monitoring 41 UC400 configuration options 38
expansion modules
overriding 42 transformer recommendations 18
discovery 39
putting out of service 42 troubleshooting (See powered state)
setup 39
polarity typical wiring
F reversing 26 0–10 Vdc 27
factory configurations 40 powered state 0–20 mA 28
firmware 24 Vac measurement 46 analog outputs 30
loading 37, 38 binary input, 24 Vac detect 47 binary 26
missing application binary input, analog output relays 31
message 38 connection 47 TRIAC 32

BAS-SVX20F-EN 55
Index

variable resistance 29

U
units of measure. 39
un-powered state
calculating power
consumption 24

W
wiring
2-wire applications 28
3-wire applications 28
analog outputs 30
low-voltage power 24
relays 30
screw terminal locations 24
TRIAC 32

X
XM modules
information resources 12
installing 12

56 BAS-SVX20E-EN
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.Trane.com.

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

© 2015 Trane. All rights reserved.


BAS-SVX20F-EN 23 Feb 2015 We are committed to using environmentally
Supersedes BAS-SVX20E-EN (09 Sep 2014) conscious print practices that reduce waste.

You might also like