You are on page 1of 2

No.

of Conductors (n) 3
Area (mm2) 240
Length of the Cable (duct) section (m) 800
Linear mass of the cable (kg/m) 4.55
Coefficient of Dynamic Friction 0.4
Maximum Pulling tension for Aluminium Conductors (Tmax) 36000
Tension at L length of the Cable 14268.8

Length of section (m) Pulling Tension T (N)


100 1783.6
200 3567.2
300 5350.8
400 7134.4
500 8918
600 10701.6
700 12485.2
800 14268.8
mm2
m
kg/m

Newton
Newton

You might also like