Professional Documents
Culture Documents
net/publication/262568520
CITATIONS READS
16 9,715
4 authors, including:
Some of the authors of this publication are also working on these related projects:
Research on Integration of Photovoltaic Sources into the Power Grid View project
Research on Optimizing the Integration of Renewable Energy Sources into the Electrical Power Systems View project
All content following this page was uploaded by Ioan Viorel Banu on 26 May 2014.
Fig. 1. Simulink model of the 100kW Grid-Connected PV Array. Fig. 3. Simulink model of the 20kV utility grid.
The islanding condition occurs in the studied network when
the three-phase circuit breaker CB2 on the 110kV side of
utility grid is in open position; that disconnects the utility grid
from the rest of the EPS; if that happens, the locally generated
power is less than the connected local loads need. The
islanding can also be present when a grid fault appears at 5km
away of PCC of the PV System. Fig. 6. Simulink model of the over/ under frequency protection.
The AI protection schemes are presented below. Detailed
description of AI detection relays and their setting are shown The Simulink implementation of ROCOF protection is
in Fig. 4 – 8. The detection times of different AI protection depicted in Fig. 7. The ROCOF relay monitors the frequency
relays are compared. The trip signals of these relays are not (to calculate the rate of change of frequency that is compared
connected to the circuit breaker on the 20kV side of PCC of with the ROCOF threshold) and terminal voltage Vt (pu) of
PV System. The low voltage ride through (LVRT), or fault the PV inverter (that is compared to a set threshold). If both
ride through (FRT) capability of Grid-Connected PV Systems conditions are satisfied the relay is activated. The PCC
will be discussed in a future study. voltage threshold of ROCOF relay is chosen as in [15]. The
The Simulink implementation of over/under current, frequency is estimated by means of the PLL.
over/under voltage and over/under frequency protection
schemes are depicted in Fig. 4 – 6. The OI/UI, OV/UV, and
OF/UF relays operate on the same principle by monitoring
some parameters (the three-phase voltage, three-phase current
or the system frequency) and compare them with some preset
thresholds that represent the settings of the relays.
Fig. 11. Id and Iq currents (pu) of VSC Control. Fig. 14. The RMS value of voltage in PCC.
Fig. 18. Anti-islanding relays detection time in case study 1 (CB2 open).
Fig. 17. Relay status and trip time of anti-islanding protection device (ms). Fig. 19. AI relays detection time in case study 2 (different grid faults).
TABLE II
DETECTION TIME (S) OF ANTI-ISLANDING PROTECTION DEVICES
Type of Anti-Islanding Detection Method
Test
Scenario OC OV UV OF UF ROCOF Vector Shift
Case
ST* DT**(s) ST DT (s) ST DT (s) ST DT ST DT (s) ST DT (s) ST DT (s)
local load greater than local
1 0.0103 0 – 1 0.0064 0 – 1 0.0536 1 0.0635 1 0.0635
generation
1.
local load less than local
CB2 1 0.0126 0 – 1 0.0089 1 0.0623 0 – 1 0.1503 1 0.1503
generation
open
local load matches closely with
1 0.0123 0 – 1 0.0085 1 0.0632 0 – 1 0.1503 1 0.1503
local generation
single-phase-to-ground fault 1 0.0027 1 0.0081 1 0.0068 0 – 0 – 0 – 0 –
2. phase-to-phase fault 1 0.0093 0 – 1 0.0045 0 – 0 – 0 – 0 –
Grid phase-to-phase-to-ground fault 1 0.0023 1 0.005 1 0.0039 0 – 0 – 0 – 1 0.1679
fault three-phase fault 1 0.0066 0 – 1 0.0041 0 – 1 0.0734 1 0.0588 1 0.0614
three-phase-to-ground fault 1 0.0066 1 0.1728 1 0.0041 0 – 1 0.0734 1 0.0588 1 0.0614
* Status of the relay;
** Detection time (s) of anti-islanding condition.
Long detection times for ROCOF and Vector Shift relays international standards, the AI relays have to be inserted at
are obtained due to a set threshold (Fig. 7 and Fig. 8) that the points where islanding conditions may occur. The
must be exceeded by the terminal voltage Vt of PV inverter. theoretical simulation results are useful to select these points
In absence of this condition, the optimal value for ROCOF and design the AI protection devices for Grid-Tied PV
threshold limit that is exceeded after islanding or when the Systems.
grid faults occurs is 12Hz/s, as can be seen in Fig. 16. REFERENCES
Another solution for AI detection can be implemented by
[1] D. Rekioua and E. Matagne, Optimization of Photovoltaic Power
monitoring the dc link voltage, whose value grows Systems, Modelization, Simulation and Control. Springer, 2012.
significantly (Fig. 10). [2] IEEE Std 1547-2003, Standard for Interconnecting Distributed
Resources with Electric Power Systems, IEEE, 2003.
IV. CONCLUSIONS [3] R. Teodorescu, M. Liserre and P. Rodríguez, Grid Converters for
Photovoltaic and Wind Power Systems. John Wiley & Sons, Ltd., 2011.
This paper studies and compares different AI detection [4] CIGRE Working Group B5.34, “The Impact of Renewable Energy
techniques such as passive AI prevention by standard Sources and Distributed Generation on Substation Protection and
protection schemes: OI/UI, OV/UV, OF/UF, as well as Automation,” CIGRE, 2010.
[5] IEEE Std 1547.2-2008, IEEE Application Guide for IEEE Std 1547™,
ROCOF and Vector Shift in case of a 100kW Grid-Connected IEEE Standard for Interconnecting Distributed Resources with Electric
PV Array. The PV System is completely disconnected from Power Systems, IEEE, 2008.
EPS and continues to energize a 20kV utility grid at 50Hz, [6] M. Ciobotaru, V. Agelidis, and R. Teodorescu, “Accurate and less-
disturbing active anti-islanding method based on PLL for grid-
and respectively various grid faults occurs at 5km away from connected PV Inverters,” IEEE Power Electronics Specialists
the PCC of the PV System. The effectiveness of different AI Conference (PESC), pp. 4569-4576, 2008.
detection algorithms is tested and the impact on network fault [7] M. Bollen and F. Hassann, Integration of Distributed Generation in the
Power System. Wiley-IEEE Press, 2011.
conditions and relays behavior during islanding is studied. [8] IEEE Std 1547.1-2005, IEEE standard conformance test procedures for
From the results provided by the performed Matlab/ equipment interconnecting distributed resources with electric power
Simulink simulations, it was observed that using traditional systems,” IEEE, 2005.
[9] IEEE Std 929-2000, IEEE recommended practice for utility interface of
relays for islanding detection such as the OC or UV resulted photovoltaic (PV) systems, IEEE, 2000.
in significantly better performance in respect to detection time [10] K. N. Edhura K. Ahmad, J. Selvaraj, and N. A. Rahim, “A review of the
of islanding conditions. The ROCOF and Vector Shift relays islanding detection methods in grid-connected PV inverters,”
Renewable and Sustainable Energy Reviews, vol.21, pp. 756-766, 2013.
have a detection time comparable with frequency relays. [11] F. De Mango, M. Liserre, A. Dell’Aquila and A. Pigazo “Overview of
However, if the ROCOF threshold is exceeded, the formation anti-islanding algorithms for PV systems. Part I: passive methods,” 12th
of an island is quickly detected. The terminal voltage of PV International Power Electronics and Motion Control Conference (EPE-
PEMC), pp. 1878-1883, 2006.
inverter needs to exceed a certain threshold when the [12] F. De Mango, M. Liserre, and A. Dell’Aquila, “Overview of anti-
frequency is not stabilized by VSC. The UC relay failed islanding algorithms for PV systems. Part II: active methods,” 12th
entirely to detect the islanding in both analyzed cases. International Power Electronics and Motion Control Conference (EPE-
PEMC), pp.1884-1889, 2006.
The effects of unintentional islanding were observed from [13] P. Giroux, G. Sybille, Hydro-Quebec Research Institute (IREQ), and C.
simulation of transient grid faults on a power distribution Osorio, S. Chandrachood, The Mathworks, “100-kW Grid-Connected
network. The protection equipment needs to distinguish PV Array demo detailed model,” MathWorks File Exchange, 2012.
[14] I. V. Banu, R. Beniuga and M. Istrate, “Comparative Analysis of the
between islanding event and grid faults. The Grid-Tied PV Perturb-and-Observe and Incremental Conductance MPPT Methods,”
System protections should detect the fault and trip before Proceedings of the International Symposium on Advanced Topics in
islanding occurs as a result of the opening of the circuit Electrical Engineering (ATEE), pp. 1-4, 2013.
[15] K. O. Samaroo, “Methodology of Selection, Setting and Analysis of
breaker in response to a downstream fault. In order to Anti-Islanding Protection for Distribution Generation System,”
minimize these effects and to perform according to the University Of Guyana, Department of Electrical Engineering, 2012.