Professional Documents
Culture Documents
Heating With Coils and Jackets
Heating With Coils and Jackets
Indirect heating of fluids is covered in this tutorial including layouts, control and drainage of coils and
jackets, and heat transfer calculations.
Vessels can be heated in a number of different ways. This tutorial will deal with indirect heating. In these
systems, the heat is transferred across a heat transfer surface. Options include:
Submerged steam coils - A widely used form of heat transfer involves the installation inside a
tank of a steam coil immersed in a process fluid.
Steam jackets - Steam circulates in the annular space between a jacket and the vessel walls, and
heat is transferred through the wall of the vessel.
Tank coils are also extensively used in electroplating and metal treatment. Electroplating involves passing
articles through several process tanks so that metallic coatings can be deposited on to their surfaces. One of
the first stages in this process is known as pickling, where materials such as steel and copper are treated by
dipping them in tanks of acid or caustic solution to remove any scale or oxide (e.g. rust) which may have
formed.
Equation 2.5.3
The heat transfer area calculated is equivalent to the surface area of the coil, and will enable an appropriate
size and layout to be specified.
On the product side of the coil a thermal boundary layer will exist in which there is a temperature gradient
between the surface and the bulk fluid. If this temperature difference is relatively large, then the natural
convective currents will be significant and the heat transfer coefficient will be high.
Assisted circulation (such as stirring) that will induce forced convection, will also result in higher coefficients. As
convection is partially dependent on the bulk motion of the fluid, the viscosity (which varies with temperature)
also has an important bearing on the thermal boundary layer.
Additional variations can also occur on the steam side of the coil, especially with long lengths of pipe. The coil
inlet may have a high steam velocity and may be relatively free from water. However, further along the length
of the coil the steam velocity may be lower, and the coil may be running partially full of water. In very long coils,
such as those sometimes found in seagoing tankers or in large bulk storage tanks, a significant pressure drop
occurs along the length of the coil. To acheive the mean coil temperature, an average steam pressure of
approximately 75% of the inlet pressure may be used. In extreme cases the average pressure used may be as
low as 40% of the inlet pressure.
Another variable is the coil material itself. The thermal conductivity of the coil material may vary considerably.
However, overall heat transfer is governed to a large extent by the heat resistant films, and the thermal
conductivity of the coil material is not as significant as their combined effect. Table 2.10.1 provides typical
overall heat transfer coefficients for various conditions of submerged steam coil application. 'U' values for
steam pressures between 2 bar g and 6 bar g should be found by interpolation of the data in the table.
The range of figures shown in Table 2.10.1 demonstrates the difficulty in providing definitive 'U' values.
Customary figures at the higher end of the scale will apply to installations that are supplied with clean dry
steam, small coils and good condensate drainage. The lower end is more applicable to poor quality steam,
long coils and poor condensate drainage.
The recommended overall heat transfer coefficients will apply to typical conditions and installations. These
recommended rates are empirically derived, and will generally ensure that a generous safety margin applies to
the coil sizing.
In the case of fluids other than water, the heat transfer coefficient will vary even more widely due to the way in
which viscosity varies with temperature. However, the values shown in Table 2.10.2 will serve as a guide for
some commonly encountered substances, while Table 2.10.3 gives typical surface areas of pipes per metre
length.
Example 2.10.1
Continuing from Example 2.9.1 determine:
Part 1. The average steam mass flowrate during start-up. (Mean heat load = 367 kW)
Part 4. The maximum steam mass flowrate with the recommended heat transfer area.
Steam pressure onto the control valve = 2.6 bar g (3.6 bar a).
A stainless steel steam coil provides heat.
Heat transfer coefficient from steam/coil/liquid, U = 650 W/m2°C
Critical pressure drop (CPD) will occur across the control valve during start-up, therefore the minimum steam
pressure in the heating coil should be taken as 58% of upstream absolute pressure. An explanation of this is
given in Block 5.
Part 4 The maximum steam mass flowrate with the recommended heat transfer area
Maximum heat transfer (and hence steam demand) will occur when the temperature difference between the
steam and the process fluid is at its maximum, and should take into consideration the extra pipe area allowed
for fouling.
It may be difficult to accommodate this length of large bore heating pipe to install in a 3 m נ3 m tank.
One solution would be to run a bank of parallel pipes between steam and condensate manifolds, set at
different heights to encourage condensate to run to the lower (condensate) manifold. The drain line must fall
from the bottom of the condensate manifold down to the steam trap (or pump-trap). See Figure 2.10.1 for a
suggested layout.
In the application, the steam and condensate headers would each be 2.8 m long. As the condensate manifold
is holding condensate, the heat from it will be small compared to the steam manifold and this can be ignored in
the calculation.
The steam manifold should be 100 mm diameter as determined by the previous velocity calculation. This will
provide a heating area of:
Consequently 7 m2 - 1 m2 = 6 m2 of heat transfer area is still required, and must be provided by the connecting
pipes.
On the basis of proportionality of heat transfer area, the steam header will condense:
This leaves 86% of the 850 kg/h = 731 kg/h of steam which must pass through the 18 connecting pipes and
also into the lower (condensate) manifold.
However, where there is no danger of corrosion, lifts over the tank structure should be avoided, and the steam
inlet and outlet connections may be taken through the tank side. The presence of any lift will result in
waterlogging of a proportion of the coil length, and possibly waterhammer, noise and leaking pipework.
Steam heating coils should generally have a gradual fall from the inlet to the outlet to ensure that condensate
runs toward the outlet and does not collect in the bottom of the coil.
Where a lift is unavoidable, it should be designed to include a seal arrangement at the bottom of the lift and a
small bore dip pipe, as shown in Figure 2.10.2.
Fig. 2.10.2 Tank with a
rising discharge pipe
The seal arrangement allows a small amount of condensate to collect to act as a water seal, and prevents the
occurrence of steam locking. Without this seal, steam can pass over any condensate collecting in the bottom of
the pipe, and close the steam trap at the top of the riser.
The condensate level would then rise and form a temporary water seal, locking the steam between the bottom
of the riser and the steam trap. The steam trap remains closed until the locked steam condenses, during which
time the coil continues to waterlog.
When the locked steam condenses and the steam trap opens, a slug of water is discharged up the riser. As
soon as the water seal is broken, steam will enter the rising pipe and close the trap, while the broken column of
water falls back to lie at the bottom of the heating coil.
The small bore dip pipe will only allow a very small volume of steam to become locked in the riser. It enables
the water column to be easily maintained without steam bubbling through it, ensuring there is a steady and
continuous condensate flow to the outlet.
When the seal is ultimately broken, a smaller volume of water will return to the heating coil than with an
unrestricted large bore riser, but as the water seal arrangement requires a smaller volume of condensate to
form a water seal, it will immediately re-form.
If the process involves articles being dipped into the liquid, it may not be convenient to install the coil at the
bottom of the tank - it may be damaged by the objects being immersed in the solution. Also, during certain
processes, heavy deposits will settle at the bottom of the tank and can quickly cover the heating surface,
inhibiting heat transfer.
For these reasons side hung coils are often used in the electroplating industry. In such cases serpentine or
plate-type coils are arranged down the side of a tank, as shown in Figure 2.10.3. These coils should also have
a fall to the bottom with a water seal and a small bore dip-pipe. This arrangement has the advantage that it is
often easier to install, and also easier to remove for periodic cleaning if required.
Fig. 2.10.3 Side hung coils
If articles are to be dipped into the tank, it may not be possible to use any sort of agitator to induce forced
convection and prevent temperature gradients occurring throughout the tank. Whether bottom or side coils are
used, it is essential that they are arranged with adequate coverage so that the heat is distributed evenly
throughout the bulk of the liquid.
The diameter of the coil should provide sufficient length of coil for good distribution. A short length of coil with a
large diameter may not provide adequate temperature distribution. However a very long continuous length of
coil may experience a temperature gradient due to the pressure drop from end to end, resulting in uneven
heating of the liquid.
Whilst the next two headings, 'Sizing the control valve' and 'The condensate removal device' are
included in this Tutorial, the new reader should refer to later Blocks and Tutorials in The Learning
Centre for full and comprehensive information, before attempting sizing and selection of equipment.
The coil has been sized on mean heat transfer values. However, it may be better to size the control valve to
supply the maximum (start-up) load. With large coils in tanks, this will help to maintain a degree of steam
pressure throughout the length of the coil when the steam is turned on, helping to push condensate through
the coil to the steam trapping device. If the control valve were sized on mean values, steam pressure in the coil
at start-up will tend to be lower and the coil may flood.
Using one valve
Continuing with Example 2.10.1 the maximum steam load is 850 kg/h and the coil is designed to deliver this at
a pressure of 1.1 bar g. A steam valve sizing chart would show that a K v of about 20 is required to pass 850
kg/h of steam with a pressure of 2.6 bar g at the inlet of the control valve, and Critical Pressure Drop (CPD)
across the valve. (Tutorial 6.4 will show how the valve size can be determined by calculation).
A DN40 control valve with a larger Kvs of 25 would therefore need to be selected for the application.
If one valve is to be used, this valve must ensure the maximum heat load is catered for, while maintaining the
required steam pressure in the coil to assist the drainage of condensate from it at start-up. However, for
reasons previously explained, two valves may be better.
The running load is 52 kW and with the coil running at 1.1 bar g, the running steam load:
The steam valve sizing chart shows a Kv of 2 is required to pass 85 kg/h with 3.6 bar upstream, operating at
critical pressure drop.
A DN15 KE type valve (Kvs = 4) and a DN25 piston actuated valve (Kvs = 18.6) operating together will cater for
the start-up load. When approaching the control temperature, the larger valve would be set to shut down,
allowing the smaller valve to give good control.
1. Pass 850 kg/h of condensate with 1.1 bar g in the coil, i.e. the full-load condition.
2. Pass the condensate load when steam pressure in the coil equals the condensate backpressure, i.e.
the stall load condition.
If the steam trap is only sized on the first condition, it is possible that it may not pass the stall load (the
condition where the product approaches its required temperature and the control valve modulates to reduce
steam pressure). The stall load may be considerable. With respect to non-flow type applications such as tanks,
this may not be too serious from a thermal viewpoint because the contents of the tank will almost be at the
required temperature, and have a huge reservoir of heat.
Any reduction in heat transfer at this part of the heating process may therefore have little immediate effect on
the tank contents.
However, condensate will back up into the coil and waterhammer will occur, along with its associated
symptoms and mechanical stresses. Tank coils in large circular tanks tend to be of robust construction, and
are often able to withstand such stresses. Problems can however occur in rectangular tanks (which tend to be
smaller), where vibration in the coil will have more of an effect on the tank structure. Here, the energy
dissipated by the waterhammer causes vibration, which can be detrimental to the life of the coil, the tank, and
the steam trap, as well as creating unpleasant noise.
With respect to flow-type applications such as plate heat exchangers, a failure to consider the stall condition
will usually have serious implications. This is mainly due to the small volume in the heat exchanger.
For heat exchangers, any unwanted reduction in the heating surface area, such as that caused by condensate
backing up into the steam space, can affect the flow of heat through the heating surface. This can cause the
control system to become erratic and unstable, and processes requiring stable or accurate control can suffer
with poor performance.
If heat exchangers are oversized, sufficient heating surface may remain when condensate backs up into the
steam space, and reduction of thermal performance may not always occur. However, with heat exchangers not
designed to cope with the effects of waterlogging, this can lead to corrosion of the heating surface, inevitably
reducing the service life of the exchanger. Waterlogging can, in some applications, be costly. Consider a
waterlogging air heater frost coil. Cold air at 4°C flowing at 3 m/s can soon freeze condensate locked in the
coils, resulting in premature and unwarranted failure. Proper drainage of condensate is essential to maintain
the service life of any heat exchanger and air heater.
Steam traps are devices which modulate to allow varying amounts of condensate to drain from applications
under varying conditions. Float traps are steam traps designed to modulate and release condensate close to
steam temperature, offering maximum plant performance, maximum plant life, and maximum return on plant
investment.
When stall conditions occur, and a steam trap cannot be used, an automatic pump-trap or pump and trap in
combination will ensure correct condensate drainage at all times, thus maximising the thermal capability and
lifetime costs of the plant.
Steam jackets
The most commonly used type of steam jacket consists simply of an outer cylinder surrounding the vessel, as
shown in Figure 2.10.4. Steam circulates in the outer jacket, and condenses on the wall of the vessel. Jacketed
vessels may also be lagged, or may contain an internal air space surrounding the jacket. This is to ensure that
as little steam as possible condenses on the outer jacket wall, and that the heat is transferred inwards to the
vessel.
Fig. 2.10.4 A
conventional jacketed vessel
The heat transfer area (the vessel wall surface area), can be calculated in the same manner as with a steam
coil, using Equation 2.5.3 and the overall heat transfer coefficients provided in Table 2.10.4.
Although steam jackets may generally be less thermally efficient than submerged coils, due to radiation losses
to the surroundings, they do allow space for the vessels to be agitated so that heat transfer is promoted. The U
values listed in Table 2.10.4. are for moderate non-proximity agitation.
Commonly the vessel walls are made from stainless steel or glass lined carbon steel. The glass lining will offer
an additional corrosion resistant layer. The size of the steam jacket space will depend on the size of the vessel,
but typically the width may be between 50 mm and 300 mm.
Top