Geometrical Description
Exchanger Geometry
Unit : : m
Length of Exchanger (L) : 7.16
Upper Exchanger Diameter (UD) : 0.00
Lower Exchanger Diameter (LD) : 1.07
Height from Pier top to Upper Exchanger Central Line (H) : 2.51
Spacing between Exchanger (S) : 0.00
Soil Depth (SD) : 0.76
Height from Base to Pier top (B) : 1.98
Footing Geometry
Unit : m
Channel/Sliding End Geometry
Length of Left Footing : 2.44
Maximum Length of Footing : 3.30
Minimum width of footing : 1.68
Maximum Width of footing : 8.00
03/08/2019
Heat Exchanger Foundation Design Page 2 of 16
------------------------------------------------------
Design Parameters
Cover and Soil Properties
Pier Clear Cover : 0.05 m
Footing Clear Cover : 0.07 m
Unit Weight of Soil : 15.71 kN/m3
Soil Bearing Capacity : 263.00 kN/m2
Soil Bearing Capacity Type : Gross Bearing Capacity
Soil Surcharge : 0.00 MPa
------------------------------------------------------
Load Description
Primary Load
Force Unit : kN
Empty Load : -284.69
Operating Load : -391.44
Test Load : -391.44
Live Load : 0.00
Erection Load : -284.69
Erection Load : -20.55
Thermal Load : 0.00
Bundle Pull Force : 84.00
Moment Unit : kNm
Empty Moment : 0.00
03/08/2019
Heat Exchanger Foundation Design Page 3 of 16
Load distributionPercentage
Shell End Percent : 40.00 %
Channel End Percent : 60.00 %
Wind Load
Shear Force : Fx : 2.220 kN
Shear Force : Fz : 11.390 kN
Moment : Mx : 0.000 kNm
Moment : Mz : 0.000 kNm
Seismic Load
Empty Load Case:
Shear Force : Fx : 54.800 kN
Shear Force : Fz : 33.720 kN
Moment : Mx : 0.000 kNm
Moment : Mz : 0.000 kNm
Load Combination
Allowable Stress Design Factors (Service Loads)
Seismic Seismic Bundle
LC SWF SBF Empty Operating Test Live Erection Miscellaneous Wind X Wind Z Thermal
X Z Pull
5033 1.00 1.00 1.00 . . . . 0.60 . . . . 1.00 .
------------------------------------------------------
------------------------------------------------------
Channel/Sliding End
03/08/2019
Heat Exchanger Foundation Design Page 4 of 16
As two isolated footings are identically grouped, so for detail drawing, the maximum dimensions/reinforcements are taken into
consideration(as below).
Design Calculations
Footing Size
Initial Length (Lo) = 2.44 m
2
Min. area required from bearing pressure, Amin = = 1.287 m
2
Area from initial length and width, Ao = = 4.10 m
03/08/2019
Heat Exchanger Foundation Design Page 5 of 16
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of negative pressure
will be set to zero and the pressure will be redistributed to remaining corners.
Load
Along X- Along Z- About X- About Z-
Case Resultant
Direction Direction Direction Direction
No.
Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - X Direction
Critical Load Case for Sliding along X-Direction : 1
03/08/2019
Heat Exchanger Foundation Design Page 6 of 16
Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - Z Direction
Critical Load Case for Sliding along Z-Direction : 0
Critical Load Case And The Governing Factor Of Safety For Sliding Along Resultant Direction
Critical Load Case for Sliding along Resultant Direction : 1
Shear Calculation
Punching Shear Check
03/08/2019
Heat Exchanger Foundation Design Page 7 of 16
Check that 0.75 * Vc > Vux where Vux is the shear force for the critical load cases at a distance d from the face of the pier caused by
bending about the X axis.
Along Z Direction
Check that 0.75 * Vc > Vuz where Vuz is the shear force for the critical load cases at a distance d from the face of the pier caused by
bending about the Z axis.
03/08/2019
Heat Exchanger Foundation Design Page 8 of 16
Calculate the flexural reinforcement along the X direction of the footing. Find the area of steel required, A, as per Section 3.8 of
Reinforced Concrete Design (5th ed.) by Salmon and Wang (Ref. 1)
The strength values of steel and concrete used in the formulae are in ksi
Required = 0.00000
Since = OK
Find suitable bar arrangement between minimum and maximum rebar sizes
03/08/2019
Heat Exchanger Foundation Design Page 9 of 16
Because the number of bars is rounded up, make sure new reinforcement ratio < max
Total reinforcement area, As_total = Nbar * (Area of one bar) = 0.00 mm2
d = D - Ccover - 0.5 * (db) = 0.00 m
Calculate the flexural reinforcement along the Z direction of the footing. Find the area of steel required, A, as per Section 3.8 of
Reinforced Concrete Design (5th ed.) by Salmon and Wang (Ref. 1)
The strength values of steel and concrete used in the formulae are in ksi
Required = = 0.00000
Since = = OK
03/08/2019
Heat Exchanger Foundation Design Page 10 of 16
Find suitable bar arrangement between minimum and maximum rebar sizes
Because the number of bars is rounded up, make sure new reinforcement ratio < max
Cd = max (Diameter of one bar, 1.0" (25.4mm), Min. User Spacing) = 0.000mm
Shell/Fixed End
Design Calculations
Footing Size
Initial Length (Lo) = 2.44 m
2
Min. area required from bearing pressure, Amin = = 2.182 m
2
Area from initial length and width, Ao = = 4.10 m
03/08/2019
Heat Exchanger Foundation Design Page 11 of 16
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of negative pressure
will be set to zero and the pressure will be redistributed to remaining corners.
03/08/2019
Heat Exchanger Foundation Design Page 12 of 16
Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - X Direction
Critical Load Case for Sliding along X-Direction : 1
Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - Z Direction
Critical Load Case for Sliding along Z-Direction : 0
Critical Load Case And The Governing Factor Of Safety For Sliding Along Resultant Direction
Critical Load Case for Sliding along Resultant Direction : 1
Shear Calculation
Punching Shear Check
03/08/2019
Heat Exchanger Foundation Design Page 13 of 16
Check that 0.75 * Vc > Vux where Vux is the shear force for the critical load cases at a distance d from the face of the pier caused by
bending about the X axis.
Along Z Direction
03/08/2019
Heat Exchanger Foundation Design Page 14 of 16
Check that 0.75 * Vc > Vuz where Vuz is the shear force for the critical load cases at a distance d from the face of the pier caused by
bending about the Z axis.
Calculate the flexural reinforcement along the X direction of the footing. Find the area of steel required, A, as per Section 3.8 of
Reinforced Concrete Design (5th ed.) by Salmon and Wang (Ref. 1)
The strength values of steel and concrete used in the formulae are in ksi
03/08/2019
Heat Exchanger Foundation Design Page 15 of 16
Required = 0.00000
Since = OK
Find suitable bar arrangement between minimum and maximum rebar sizes
Because the number of bars is rounded up, make sure new reinforcement ratio < max
Total reinforcement area, As_total = Nbar * (Area of one bar) = 0.00 mm2
d = D - Ccover - 0.5 * (db) = 0.00 m
Calculate the flexural reinforcement along the Z direction of the footing. Find the area of steel required, A, as per Section 3.8 of
Reinforced Concrete Design (5th ed.) by Salmon and Wang (Ref. 1)
The strength values of steel and concrete used in the formulae are in ksi
03/08/2019
Heat Exchanger Foundation Design Page 16 of 16
Required = = 0.00000
Since = = OK
Find suitable bar arrangement between minimum and maximum rebar sizes
Because the number of bars is rounded up, make sure new reinforcement ratio < max
Cd = max (Diameter of one bar, 1.0" (25.4mm), Min. User Spacing) = 0.000mm