You are on page 1of 76

com_T104_profile_us.

book Page 1 Tuesday, February 19, 2013 3:17 PM

Preface

Contents

SIPROTEC Characteristic of the IEC 60870-5-104 Module 1


Communication Module
Configuration in DIGSI 4 2
IEC 60870-5-104
Scaling and Thresholds for Transmission 3
Communication Profile
Time Synchronization 4
IEC 60870-5-104 Diagnosis for EN100+ 5
Redundancy IEC 60870-5-104 6
Technical Data 7
Index

Edition: Feb. 2013


C53000-L2040-C370-2
com_T104_profile_us.book Page 2 Tuesday, February 19, 2013 3:17 PM

NOTE
For your own safety, please observe the warnings and safety instructions contained in this document.

Disclaimer of Liability Copyright

This document has been subjected to rigorous technical review Copyright © Siemens AG 2013. All rights reserved.
before being published. It is revised at regular intervals, and any The disclosure, duplication, distribution and editing of this
modifications and amendments are included in the subsequent document, or utilization and communication of the content are not
issues. The content of this document has been compiled for permitted, unless authorized in writing. All rights, including rights
information purposes only. Although Siemens AG has made best created by patent grant or registration of a utility model or a design,
efforts to keep the document as precise and up-to-date as possible, are reserved.
Siemens AG shall not assume any liability for defects and damage
which result through use of the information contained herein.
Registered Trademarks
This content does not form part of a contract or of business
relations; nor does it change these. All obligations of Siemens AG SIMATIC®, SIMATIC NET®, SIPROTEC®, DIGSI®, SICAM®,
are stated in the relevant contractual agreements. SIMEAS®, SINAUT® , OSCOP®, and DAKON® are registered
trademarks of SIEMENS AG. An unauthorized use is illegal.
Siemens AG reserves the right to revise this document from time to
time. All other designations in this document can be trademarks whose
use by third parties for their own purposes can infringe the rights of
the owner.
Document Release: C53000-L2040-C370-2
Edition: 02.2013
Product version: V1.00
com_T104_profile_us.book Page 3 Tuesday, February 19, 2013 3:17 PM

Preface

Purpose of this manual

This manual describes the communication profile of the SIPROTEC Communication Module with IEC 60870-
5-104.

Target group

Protection engineers, commissioning engineers, persons who are involved in setting, testing and service of
protection, automation, and control devices, as well as operation personnel in electrical plants and power sta-
tions.

Scope of validity of this manual

This manual is valid for the SIPROTEC Communication Module with IEC 60870-5-104.

Further support

Should further information be desired or should particular problems arise which are not covered sufficiently for
the purchaser's purpose, the matter should be referred to the local Siemens representative.

Hotline

Our Customer Support Center provides around-the-clock support.

Phone: +49 (180) 524-8437


Fax: +49 (180) 524-2471
Internet: http://www.siprotec.com
e-mail: support.ic@siemens.com

Training courses

If you are interested in our current training program, please contact our training center:

Siemens AG
Siemens Power Academy TD

Humboldtstr. 59

D-90459 Nuremberg
Germany

Phone: +49 (911) 433-7415


Fax: +49 (911) 433-5482
e-mail: poweracademy.ic-sg@siemens.com
Internet: www.siemens.com/poweracademy

SIPROTEC, Communication Module, Communication Profile 3


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 4 Tuesday, February 19, 2013 3:17 PM

Preface

Notes On Safety

This document is not a complete index of all safety measures required for operation of the equipment (module,
device). However, it comprises important information that must be noted for purposes of personal safety, as
well as in order to avoid material damage. Information is highlighted and illustrated as follows according to the
degree of danger:

DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.

✧ Comply with all instructions, in order to avoid death or severe injuries

WARNING
WARNING means that death or severe injury can result if the measures specified are not taken.

✧ Comply with all instructions, in order to avoid death or severe injuries.

CAUTION
CAUTION means that medium-severe or slight injuries can result if the measures specified are not taken.

✧ Comply with all instructions, in order to avoid medium-severe or slight injuries.

NOTICE
NOTICE means that material damage can result if the measures specified are not taken.

✧ Comply with all instructions, in order to avoid material damage.

NOTE
Important information about the product, product handling, or a certain section of the documentation, which
must be given particular attention.

4 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 5 Tuesday, February 19, 2013 3:17 PM

Preface

Qualified Personnel

Commissioning and operation of the equipment (module, device) described in this manual must be performed
by qualified personnel only. As used in the safety notes contained in this manual, qualified personnel are those
persons who are authorized to commission, release, ground and tag devices, systems, and electrical circuits
in accordance with safety standards.

Use as Prescribed

The equipment (device, module) must not be used for any other purposes than those described in the
Catalog and the Technical Description. If it is used together with third-party devices and components, these
must be recommended or approved by Siemens.

Correct and safe operation of the product requires adequate transportation, storage, installation, and
mounting as well as appropriate use and maintenance.

During the operation of electrical equipment, it is unavoidable that certain parts of this equipment will carry dan-
gerous voltages. Severe injury or damage to property can occur if the appropriate measures are not taken:
• Before making any connections at all, ground the equipment at the PE terminal.
• Hazardous voltages can be present on all switching components connected to the power supply.
• Even after the supply voltage has been disconnected, hazardous voltages can still be present in the equip-
ment (capacitor storage).
• Equipment with current transformer circuits must not be operated while open.
• The limit values indicated in the manual or the operating instructions must not be exceeded; this also
refers to testing and commissioning

SIPROTEC, Communication Module, Communication Profile 5


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 6 Tuesday, February 19, 2013 3:17 PM

Preface

6 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 7 Tuesday, February 19, 2013 3:17 PM

Contents

Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1 Characteristic of the IEC 60870-5-104 Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9


1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.2 Identification of Module and Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.3 Supported IEC 60870-5-104 Object Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.4 Table of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.5 Buffered Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1.6 File Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.6.1 Reading of Fault Records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.6.2 Reading of Parameter File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1.7 Further Ethernet Services and Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1.7.1 Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1.7.2 IEC 60870-5-104 with IEC 61850 and GOOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

2 Configuration in DIGSI 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.1 Inserting and Adjusting of a New Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.2 Setting the Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
2.3 Customization of the Allocations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

3 Scaling and Thresholds for Transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53


3.1 Measured Value Scaling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
3.2 Measured Value Threshold Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
3.3 Counter Value Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

4 Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4.2 Time Synchronization with IEC 60870-5-104 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

5 IEC 60870-5-104 Diagnosis for EN100+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63


5.1 HTML Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.2 SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.3 IEC 60870-5-104 Error Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

6 Redundancy IEC 60870-5-104. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71


6.1 General Introduction and Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
6.2 Configuration in DIGSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

7 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
7.1 Technical Data of EN100+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

SIPROTEC, Communication Module, Communication Profile 7


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 8 Tuesday, February 19, 2013 3:17 PM

Contents

Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

8 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 9 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module

1.1 General 10

1.2 Identification of Module and Firmware 12

1.3 Supported IEC 60870-5-104 Object Types 14

1.4 Table of Parameters 17

1.5 Buffered Events 19

1.5 Buffered Events 19

1.6 File Transfer 20

1.7 Further Ethernet Services and Protocols 27

SIPROTEC, Communication Module, Communication Profile 9


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 10 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.1 General

1.1 General
With the EN100+ module firmware IEC 60870-5-104 from version V1.00, the Ethernet-based IEC 60870-5-
104 protocol is implemented in addition to other transmission protocols (e.g. IEC 61850 and GOOSE, see
chapter 1.7) in the 100 Mbit Ethernet module EN100+.

NOTE
Refer to your device manual to find out whether the device you are using supports the IEC 60870-5-104 pro-
tocol.The protocol is available for the electrical and optical module.

The required settings are made by using the DIGSI 4 parameterization software from version 4.87.

NOTE
For the configuration of IEC 60870-5-104 a DIGSI 4 package is required with IEC 61850 station configurator.

Detailed information on the EN100+ module and the IEC 61850 engineering is given in the manuals:
• German edition: Handbuch Ethernetmodul EN100+, Bestellnr. C53000-G1100-C167-x
• US-english edition: Manual Ethernet Module EN100+, order no. C53000-G1140-C167-x

Abbreviations are used in the following text:


• for 100-MBit Ethernet module EN100+: EN100+
• for IEC 60870-5-104 over the internet protocol suite: IEC 60870-5-104

10 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 11 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.1 General

Application

Figure 1-1 shows an application example of the SIPROTEC devices with IEC 60870-5-104 and GOOSE in an
installation where IEC 60870-5-104 is used for communication to a substation controller and GOOSE for inter-
device data exchange.

Fig. 1-1 Application Communication Example

Bus Mapping Documents

You can download the bus mapping document for each device type at the following address:
http://siemens.siprotec.de/download_neu/index_e.htm

The bus mapping documents describe the data objects available via IEC 60870-5-104.

Example: Manual SIPROTEC Feeder Automation Controller 7SC80, order number C53000-L2040-C353

Accessories

EN100+ supports electrical and optical interface in different variants. Please refer to Chapter 3.1 Getting Start-
ed in Commissioning in the Device in the manual of SIPROTEC4 Ethernet Module EN100 for IEC 61850 with
electrical/optical 100 MBit Interface, for the technical specification of the cables needed for electrical or optical
connection.

To order these cables, please refer to SIPROTEC price list available from your Siemens representative or sup-
port hotline.

SIPROTEC, Communication Module, Communication Profile 11


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 12 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.2 Identification of Module and Firmware

1.2 Identification of Module and Firmware

Modulinfo Menu

Available on HMI display or via WebMonitor:

✧ Select Enter → Test/Diagnosis → Modulinfo → Port F


This shows e.g. module type, communication protocol, network settings

Fig. 1-2 Modulinfo


Module type:
• EN100_E+ - EN100+ module with electrical Ethernet interface
• EN100_O+ - EN100+ module with fiber-optical Ethernet interface
Communication protocol:
• IEC61850 - IEC61850/GOOSE
• IEC 60870-5-104 - IEC 60870-5-104 with IEC61850/GOOSE option (see chapter 1.7.2)

MLFB/Version Menu

Available on HMI display or via WebMonitor:

✧ Select Enter → Settings → Setup/Extras → MLFB/Version, then scroll down twice


This shows the version number of the firmware on EN100+ module

12 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 13 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.2 Identification of Module and Firmware

Fig. 1-3 MLFB/Version

NOTE
Always the firmware identifcation IEC61850 is shown here, also when IEC 60870-5-104 firmware is loaded.

HTML Page of the EN100+ Module

Refer to chapter 5.1.


• If IEC 60870-5-104 firmware is loaded then the menu IEC 60870-5-104 is available in the navigation pane.
• The firmware version is shown on the bottom of the homepage.

SIPROTEC, Communication Module, Communication Profile 13


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 14 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.3 Supported IEC 60870-5-104 Object Types

1.3 Supported IEC 60870-5-104 Object Types

Table 1-1 IEC 60870-5-104 Object Types

COT( Cause Of Transmission )

TI No. Type 1 2 3 4 5 6 7 8 9 10 11 12 13 20 37 Description


Identification to to
36 41

<1> M_SP_NA_1 X X X Single-point


information

<3> M_DP_NA_1 X X X Double-point infor-


mation

<5> M_ST_NA_1 X X X X Step position infor-


mation

<7> M_BO_NA_1 X Bitstring of 32 bit

<13> M_ME_NC_1 X X X Measured value,


short floating point
value

<15> M_IT_NA_1 X Integrated totals

<30> M_SP_TB_1 X X X Single-point infor-


mation with time tag
CP56Time2a

<31> M_DP_TB_1 X X X Double-point infor-


mation with time tag
CP56Time2a

<32> M_ST_TB_1 X X X Step position infor-


mation with time tag
CP56Time2a

<36> M_ME_TF_1 X Measured value,


short floating point
value with time tag
CP56Time2a

<37> M_IT_TB_1 X Integrated totals


with time tag
CP56Time2a

<38> M_EP_TD_1 X Event of protection


equipment with time
tag CP56Time2a

<45> C_SC_NA_1 X X X X X Single command

<46> C_DC_NA_1 X X X X X Double command

14 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 15 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.3 Supported IEC 60870-5-104 Object Types

Table 1-1 IEC 60870-5-104 Object Types (cont.)

COT( Cause Of Transmission )

TI No. Type 1 2 3 4 5 6 7 8 9 10 11 12 13 20 37 Description


Identification to to
36 41

<47> C_RC_NA_1 X X X X X Regulating step


command

<70> M_EI_NA_1 X End of initialization

<100> C_IC_NA_1 X X X Interrogation


command

<101> C_CI_NA_1 X X X Counter interroga-


tion command

<102> C_RD_NA_1 X Read command

<103> C_CS_NA_1 X X X Clock synchroniza-


tion command
(option see 7.6)

<105> C_RP_NA_1 X X Reset process


command

<122> F_SC_NA_1 X X Call directory, select


file, call file, call
section

<124> F_AF_NA_1 X Ack file, ack section

<126> F_DR_TA_1 X X Directory {blank or


X, only available in
monitor (standard)
direction}

SIPROTEC, Communication Module, Communication Profile 15


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 16 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.3 Supported IEC 60870-5-104 Object Types

Table 1-2 IEC 60870-5-104-Specific Parameters

COT Number Description

1 Periodic, cycilic
2 Background scan
3 Spontaneous
4 Initialized
5 Request or requested
6 Activation
7 Activation confirmation
8 Deactivation
9 Deactivation confirmation
10 Activation termination
11 Return info caused by a remote cmd
12 Return info caused by a local cmd
13 File transfer
20 to 36 Interrogated by group <number>
37 to 41 Request by group <n> counter request
44 Unknown type identification
45 Unknown cause of transmission
46 Unknown common address of ASDU
47 Unknown information object address

16 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 17 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.4 Table of Parameters

1.4 Table of Parameters


The following IEC 60870-5-104-specific configuration parameters are available in the SIPROTEC device (i.e.
in the IEC 60870-5-104 mapping file, see chapter 2).

Table 1-3 IEC 60870-5-104-Specific Parameters

Parameter Default Setting Description


Setting Range

OutstationAddress 1 1 to 250 IEC 60870-5-104 station address of


the device

MasterAddress1 0.0.0.0, 0.0.0.0 to Addresses of the IEC 60870-5-104


0.0.0.0 255.255.255.254 masters
MasterAddress2

TcpPortNumber1 2404, 1000 to 65535 The TCP ports to listen on


TcpPortNumber2 2405 TcpPortNumber1=2404
TcpPortNumber2=2405

Enable104TimeSynch 0 0,1 Determines whether the IEC 60870-


0 = device does not ex- 5-104 outstation expect and evalu-
pect time synchronization ates time synchronization from IEC
from IEC 60870-5-104 60870-5-104 master
master
1 = device expect time
synchronization from IEC
60870-5-104 master

EnableRedundancy 0 0,1 Determines whether the IEC 60870-


0 = no redundancy 5-104 outstation supports the redun-
1 = redundancy support- dancy
ed

t1AckPeriod_1/2 15 1 to 255 (in seconds) Determines the Time-out of send or


test APDUs for connection with the
master 1 or master 2

t2SFramePeriod_1/2 10 1 to 255 (in seconds) Determines the Time-out for ac-


knowledges in case of no data mes-
sages(t2 < t1) for connection with the
master 1 or master 2

t3TestPeriod_1/2 20 1 to 255 (in seconds) Determines the Time-out for sending


test frames in case of a long idle
state for connection with the master
1 or master 2

TransMeasurements 0 0,1,2,3 Choice of the measured values


0 = not assigned transmission (in addition to events)
1 = cyclic
2 = general interrogation
3 = cyclic and general in-
terrogation

SIPROTEC, Communication Module, Communication Profile 17


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 18 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.4 Table of Parameters

Table 1-3 IEC 60870-5-104-Specific Parameters (cont.)

Parameter Default Setting Description


Setting Range

CyclicTime 60 0, 1 to 65535 (in seconds) Time for sending cyclical data (in
0 = swiched off seconds) only valid if transmission of
measuremens is cyclic or cyclic and
general interrogation

MeasureTimeStamp 1 0, 1 Determines wether the measured


0 = no time stamp value events are sent with time
1 = with time stamp stamp or not

MeasureDelay 1000 0, 1 to 10000 (in miliisec- Determines the delay time when
onds) sending spontaneous measure-
0 = no delay ments (in milliseconds)

NOTE
The settings above are valid for all TCP connections in the same way; they are not configurable individually per
TCP connection or connected IEC 60870-5-104 master.

During startup of the Ethernet module it is checked whether all IEC 60870-5-104 parameters are configured in
their valid ranges given in table 1-4 and table 1-3. If a parameter value is detected outside the valid range, an
error log entry is issued on the EN100+ module and the parameter is set to its default value (see figure 5-2).

18 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 19 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.5 Buffered Events

1.5 Buffered Events


When a SOE(Sequence of Event) happened, this event will be transmitted to the master, if the transmission is
successful this event will be cleared up in the buffer, otherwise the event will be stored in the buffer and wait
for the next transmission try. The max event entries are 100 items for each type of indication including SP (Sin-
gle Point indication), DP (Double Point indication) and Counter Value. The latest event will replace the oldest
one when buffered event reaches maximum amount.

SIPROTEC, Communication Module, Communication Profile 19


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 20 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.6 File Transfer

1.6 File Transfer

1.6.1 Reading of Fault Records


Fault records from the device can be read using the file transfer feature of IEC 60870-5-104. The fault records
are converted on the EN100+ module to Comtrade format.

For reading a fault record, the following steps must be executed:

NOTE
ASE2000 version 2 is used as IEC 60870-5-104 test master for the examples.

Open the directory file of available fault records which are available using IEC 60870-5-104 TI122(call directo-
ry), COT 5 (request), e.g.:

✧ The IEC 60870-5-104 outstation responds with IEC 60870-5-104 TI126, COT5 (response).

✧ If no fault records are available, the returned object is zero, otherwise it is different from zero, e.g.

With this response, a file handle is returned Object:11010001).

✧ In the IEC 60870-5-104 master the file selection after directory read could look like this:

20 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 21 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.6 File Transfer

Fig. 1-4 Select File Name on Remote Device to Read

NOTE
The file named with 11xxxxxx can be saved as a *.dat file, and the file named with 12xxxxxx can be saved as
a *.cfg file. The file named with 13xxxxxx can be saved as a *.txt file.

SIPROTEC, Communication Module, Communication Profile 21


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 22 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.6 File Transfer

✧ Read the file(s) of interest, e.g. the file "11010001":


Read file use TI 122 COT 13 SCQ 01 to request and use TI 120 COT 13 to response:

22 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 23 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.6 File Transfer

Read section use TI122 COT 13 SCQ 02 to request and use TI 121 COT 13 to response:

SIPROTEC, Communication Module, Communication Profile 23


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 24 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.6 File Transfer

Call section use TI 122 COT 13 SCQ 06 to request and use TI 125 COT 13 to response:

When one section is transmitted, the outstation will send last section TI 123 COT 13 to the master:

24 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 25 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.6 File Transfer

Then, the master can call the next section as the same.
When all the sections are transmitted, the master will send ACK TI 124 COT 13 to the outstation.

The read file now is available in the IEC 60870-5-104 master and the next file can be read.

After that, the fault record Comtrade file can be evaluated, e.g. with the "SIGRA 4 - Fault Evaluation
Software" from Siemens.

1.6.2 Reading of Parameter File


Parameter file from the device can be read using the file transfer feature of IEC 60870-5-104 as well. The op-
eration is nearly the same as reading of fault record file. Please refer to chapter 1.7.1.

SIPROTEC, Communication Module, Communication Profile 25


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 26 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.6 File Transfer

The file looks like figure 1-5:

Fig. 1-5 Parameter File

The following table gives a reference for understanding the parameter file.

Table 1-4 Reference for Parameter File

Unit ID Description
1 Dimensionless
5 A (amperer)
23 °C (degree centigrade)
29 V (volt)
33 Hz ((hertz))
61 VA
62 W (watt)
63 var
72 Wh
73 varh
Multipier ID Description
3 k (kilo)
6 M (mega)

26 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 27 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.7 Further Ethernet Services and Protocols

1.7 Further Ethernet Services and Protocols


The following additional services and protocols are supported on the EN100+ module. With DIGSI 4 these ser-
vices can be switched ON or OFF. Unused services shall be switched OFF for security reason.

1.7.1 Services
• Module homepage (HTTP)
• Firmware upgrade (HTTP)
• DIGSI 4 over EN100+
• SNMP V2 (see chapter 5.2)
• IEC 61850 and GOOSE
• SNTP (see chapter 4.2)

For more information, please refer to the following manual:


Ethernet Module EN100+ for IEC 61850 with electrical/optical 100 Mbit Interface,
Order number C53000-G1140-C167

NOTE
In order to make sure the GOOSE service runs smoothly, it is recommended that the maximum GOOSE set-
tings from sending or receiving sides are less than 100.

1.7.2 IEC 60870-5-104 with IEC 61850 and GOOSE


The communication IEC 60870-5-104 with IEC 61850 and GOOSE is represented in the following figure:

SIPROTEC, Communication Module, Communication Profile 27


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 28 Tuesday, February 19, 2013 3:17 PM

1 Characteristic of the IEC 60870-5-104 Module


1.7 Further Ethernet Services and Protocols

Fig. 1-6 IEC 60870-5-104 with IEC 61850 and GOOSE

IEC61850: 2 process clients maximum in the system

GOOSE: Publisher: 12 GOOSE applications/dataset maximum per device, with 120 data objects in total
Subscriber: 100 GOOSE dataset per device, with 1000 data objects in total

Set minimum monitoring >= 10 ms (use standard settings of communication profile PriorityLow in GOOSE pa-
rameters of the IEC 61850 System Configurator)

The above mentioned recommendations are not fixed, the system allows configuring more GOOSE applica-
tions and more data objects as source and destination. Higher GOOSE load may lead to delayed transmission.
Please test and verify the needed transmission times for indications in your specified application.

28 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 31 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4

2.1 Inserting and Adjusting of a New Project 32

2.2 Setting the Interfaces 38

2.3 Customization of the Allocations 40

SIPROTEC, Communication Module, Communication Profile 31


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 32 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project

2.1 Inserting and Adjusting of a New Project

NOTE
In order to configure the IEC 60870-5-104 protocol, the device functions must be parameterized correctly. For
detailed information in this context, please see chapter 1.1 (Prerequisites at DIGSI 4) of the DIGSI 4 manual.

NOTE
The following configuration is shown for the 7SC80.

✧ Open DIGSI Manager.

✧ Click File → New...

Fig. 2-1 New Project Dialog

32 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 33 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project

✧ Enter a name for the new project (7SC80_XX in the example) and select the storage location (path).
Next click OK.

Fig. 2-2 DIGSI Manager with a New Project

✧ Right-click Folder and open the Device Catalog via Insert New Object → SIPROTEC device.

Fig. 2-3 DIGSI Manager with an Object Selected

SIPROTEC, Communication Module, Communication Profile 33


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 34 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project

✧ Select the desired device in the Device Catalog (7SC feeder automation/7SC802/V4.0 in the example)
and copy the object into the Folder of the DIGSI Manager window via Drag&Drop.

Fig. 2-4 Device Catalog

The MLFB tab of Properties - SIPROTEC device dialog opens (see figure 2-5 ).

✧ Configure the order number (MLFB) of your device in the Properties - SIPROTEC device dialog and
press the OK button.

Fig. 2-5 Configuring the Order Number (MLFB)

✧ If you have retrofitted the device or if you want to install the IEC 60870-5-104 protocol afterwards, you
have to activate the IEC 60870-5-104 protocol on the tab Communication modules → List item 11. Port

34 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 35 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project

F (Communication Interface) → Selection L:.. → Additional Information dialog.

Fig. 2-6 Activating the IEC 60870-5-104 Protocol

✧ Click the OK button.

✧ Right-click Folder and insert an IEC61850 station via Insert New Object → IEC61850 station.
An IEC61850 station is inserted in DIGSI Manager
.

Fig. 2-7 Inserting an IEC61850 Station

✧ In DIGSI Manager, right-click IEC61850 station and select the Object properties… menu item.

✧ Select a device from the Available IEC61850 devices in the Properties - IEC61850 station dialog →
Communicator tab and click Add.
The selected device is moved from the Available IEC61850 devices window into the IEC61850 station
communicator window.

SIPROTEC, Communication Module, Communication Profile 35


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 36 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project

Fig. 2-8 Select Device into IEC61850 Station Communicator

✧ Click the OK button.

✧ Double-click the SIPROTEC device in DIGSI Manager.


The Open device dialog opens.

✧ Activate the option Offline in the Connection type section and confirm with OK.

Fig. 2-9 Opening the SIPROTEC Device

36 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 37 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project

After initialization the following window opens:

Fig. 2-10 Select Functions

SIPROTEC, Communication Module, Communication Profile 37


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 38 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.2 Setting the Interfaces

2.2 Setting the Interfaces


✧ Double-click the function Settings.
The following windows opens.

Fig. 2-11 Settings

✧ Double-click the function Interfaces.


The Interface Settings dialog opens.

✧ Select the Additional protocols at device tab.

Fig. 2-12 Mapping File Selection and Module-specific Settings

38 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 39 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.2 Setting the Interfaces

List Box Mapping File

If no mapping file is currently assigned to the SIPROTEC device then the following entries are available in the
list box “Mapping file”:

Table 2-1 Selection without Module-specific Settings

Selection Meaning

<none> No mapping file is assigned to the device.

IEC60870-5-104 standard mapping 3-1 Selection of a mapping file 3-1 to 3-n (n = device type dependent
to number of standard mappings).
IEC60870-5-104 standard mapping 3-n

The following entries can be selected at an already existing mapping file assignment:

Table 2-2 Selection with Module-specific Settings

Selection Meaning

<none> No mapping file is assigned to the device.

<see module-specific settings> This selection indicates the device will use the current content in
the edit area “Module-specific settings”, which can have the
updated bus specific parameters upon specific requirement.

IEC60870-5-104 standard mapping 3-1 New Selection of a mapping file 3-1 to 3-n
to (n = device type dependent number of standard
IEC60870-5-104 standard mapping 3-n mappings). All bus specific parameters are reset to
default values.

If the mapping file assignment was changed for a SIPROTEC device, then this is in general connected with a
change of the routing of the SIPROTEC objects to the system interface.
Please, check after choice of a new mapping file the allocations to column Destination or Source in the DIGSI
configuration matrix.

NOTE
The mapping file is factory-set, but you can adapt it to your device configuration.

To activate and change the protocol IEC 60870-5-104 , proceed as follows:

✧ Activate the mapping file IEC 60870-5-104 standard mapping 3-1 in the list box Mapping file.
✧ If necessary, change the entries in the Module-specific settings edit area according to your device
configuration.

✧ Click the OK button.

NOTE
Please, edit only the numbers in the rows which do not start with “//” and note the semicolons at the end of the
line.

Editing anything else in the Module-specific settings may cause an error when closing the Interface Settings
dialog.

SIPROTEC, Communication Module, Communication Profile 39


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 40 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

2.3 Customization of the Allocations


✧ Double-click the function Masking I/O (Configuration Matrix) in the dialog Settings acc. to Figure 2-11.
The windows Setting Masking I/O opens:

Fig. 2-13 DIGSI 4 Configuration Matrix with Columns for System Interface Routing

NOTE
Another port instead of port F can be displayed as Source and Destination of the system interface, for exam-
ple, port B for SIPROTEC 4 devices.

NOTE
If you do not want to display all columns and rows in the configuration matrix for the setting of the system in-
terface or for your information, you can minimize these columns and rows by double-clicking the corresponding
button. If you want to enter values to the minimized columns, you can maximize these columns again by dou-
ble-clicking the corresponding button.

✧ Move the cursor in the columns Source and Destination over port F and determine the column assigned
to IEC 60870-5-104 (marked in red in Figure 2-13).
The used protocol is displayed (text in a yellow box) if you stop for a short while on the letter F.

✧ If necessary, adapt the default routing in the configuration matrix to your SIPROTEC device/installation as
follows. If you do not want to change anything in the DIGSI routing matrix, continue with the section Time
Synchronization.

✧ If you want to delete all default routings to set new default routings, right-click the corresponding port F
or the system interface S in Source or Destination. Then, click the query Delete configurations at Port
F or Delete configurations at System Interface.
A dialog appears with the information that a deletion is not possible or with the confirmation about how
many entries can be deleted or cannot be deleted. Confirm this information with OK:

40 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 41 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

Fig. 2-14 Indications for Deletion

The identification whether an information is routed on system interface (IEC 60870-5-104) is shown in the col-
umns Source and Destination, port F, system interface S in the DIGSI configuration matrix.

A cross ('X') in this column indicates the associated information as "routed on system interface"
(see Figure 2-13).

Source System Interface

The SIPROTEC object can be controlled via IEC 60870-5-104. This is possible for the following information
types (column Type in configuration matrix):
• IntSP Internal single-point indication (tagging)
• IntDP Internal double-point indication (tagging)
• SC/DC Single control/Double control without feedback from process
• SF/DF Single control/Double control with feedback from process

Destination System Interface

The value of the SIPROTEC object is transmitted to the IEC 60870-5-104 master. This is possible for the fol-
lowing information types:
• SP Single-point indication
• DP Double-point indication
• Out Output annunciation
• IntSP Internal single-point indication (tagging)
• IntDP Internal double-point indication (tagging)
• MV Measured value
• MVMV Power meter (metered measurand, source is a measured value)
• PMV Pulse (metered measurand, source is a pulsed binary input)

SIPROTEC, Communication Module, Communication Profile 41


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 42 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

To add or remove an information to Source or Destination of system interface set/reset the cross ('X') in the
associated column of the DIGSI configuration matrix (pop-up menu when pressing the right mouse button).

Fig. 2-15 Pop-up Menu in Column Destination F/S

NOTE
• The maximum number ( see Table 2-3) of routable objects of an information type varies according to the
chosen mapping file. If e.g. a measured value not routed in the mapping file per default shall be transferred
via IEC 60870-5-104, then first a measured value already routed has to be removed from system interface
so that the position gets available in the IEC 60870-5-104 message.
• The maximum number of user defined objects mapping to IEC 61850 system interface is recommended
not more than 100. Otherwise, it may cause the MMS disabled.
• An error message (see Figure 2-16) is shown if all routing possibilities of an information type are occupied
and if it is nevertheless tried to route an information of this type.

Table 2-3 The Maximum Number

Info Types Maximum Comments


Number

Measured Values 59 Include 5 user defined values

Counter Value 12 Include 5 user defined values

Single Point 108 Include 14 user defined values

Double Point 5 Include 2 user defined values

Step Position 5 5 user defined values

Single Commands 9 Include 4 user defined commands

Double Commands 5 Include 2 user defined commands

Step Position Commands 5 5 user defined commands

Fig. 2-16 Error Message

42 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 43 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

Adding an Allocation

Adding an allocation requires (in addition to the identification in the system interface column of the DIGSI con-
figuration matrix) the selection of the position of the information in the IEC 60870-5-104 message as well as
the definition of scaling values for measured values (scaling of measured values see chapter 3 Scaling and
Thresholds for Transmission).

Therefore after adding the allocation, the Object properties dialog window which is used to define the mes-
sage position of the information is opened automatically (property sheets for source: Protocol info - Source F;
property sheets for destination: Protocol info - Destination F and Measured value - Destination F).

Fig. 2-17 Definition of the Position of an Information in the IEC 60870-5-104 Message

NOTE
• The information type of double commands for routing as Source system interface depends on the infor-
mation type of the associated checkback indication.
Only double commands with a double-point indication as checkback indication can be routed to the
positions in the IEC 60870-5-104 message which are reserved for double commands according to the bus
mapping.

Double commands with a single-point indication as checkback indication or without checkback indication
are treated via IEC 60870-5-104 like single commands and must be routed to the positions reserved for
single commands.

• Commands without checkback indication can not be routed to Destination of system interface. Reading
the state of these command types is not possible via IEC 60870-5-104.

Change of an Existing Allocation

If the information already routed on system interface shall get another (empty) position in the IEC 60870-5-104
message, then the Object properties dialog (see Figure 2-17) has to be selected (Properties ... in the pop-
up menu when pressing the right mouse button in one of the columns Display text, Long text or Type of the

SIPROTEC, Communication Module, Communication Profile 43


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 44 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

DIGSI configuration matrix in the row which is associated to the information).

Fig. 2-18 Change of an Existing Allocation

Depending on the information type the following parameters are to select in the property sheet
Protocol info - Source F, Protocol info - Destination F or Measured value - Destination F of the Object
properties dialog:

Table 2-4 Protocol Info Source

Parameter Comments Info Types

Obj Address The index indicates the address of this object. IntSP, IntDP, SC/DC,
SF/DF
Flags Command properties (Latch ON/OFF, ... - depending on the
object info type)

Table 2-5 Protocol Info Destination

Parameter Comments Info Types

Obj Address The index indicates the address of this object. SP, DP, Out, IntSP,
IntDP, MV, MVMV, PMV

Type The index indicates the types that this object can be mapped SP,IntSP,Out
to.

44 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 45 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

Measurement Conversion

Before transmission of a measured value via IEC 60870-5-104 a measurement conversion (scaling) must be
executed in the SIPROTEC device.

Scaling

Scaling of a measured value to the format for the transmission via IEC 60870-5-104 means the definition of:
• Type
• Scaling factor
• Zero offset

Type

Decision, whether the measured value is transmitted as percentage value or whether a conversion shall take
place into primary or secondary value before (depending on the measured value not all of these three possibil-
ities are available, e.g. no secondary values for power values).

Threshold value

Changes of measured values are transmitted using IEC 60870-5-104 object 32 (Analog Change Event) only if
the accumulated change differences of the 16-bit analog input exceed the threshold value.

Scaling factor

The measured value in the SIPROTEC device (floating-point format) is multiplied by the scaling factor before
transformation to an integer value. With that it is possible to transfer fractional digits by multiplication by a mul-
tiple of 10 in the integer value.

Zero offset

The Zero offset is added to the result of the multiplication of the measured value in the SIPROTEC device (float-
ing-point format) by the scaling factor.

The measured value in the integer format for transmission via IEC 60870-5-104 is calculated summarizing ac-
cording to the following formula:
Measured valueInteger = Measured valueFloat * Scaling factor + Zero offset

in which "Measured valueFloat" is a percentage value or, if necessary, changed into primary value or secondary
value before (according to the definition of type).

SIPROTEC, Communication Module, Communication Profile 45


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 46 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

Time Synchronization

✧ If the device requires time synchronization with NTP or IEC 60870-5-104, double-click Time
Synchronization.
The Time Synchronization & Time Format dialog opens.

✧ Select Ethernet NTP as the source in the field Source of time synchronization and set the desired
parameters.

Fig. 2-19 Setting theTime Synchronization

✧ Confirm with OK.

✧ Close the SIPROTEC device and confirm that you want to save the modified data.

✧ Close the Report window.

✧ Double-click IEC61850 station in DIGSI Manager.


The DIGSI system configurator opens with the IEC61850 station application and Subnet1.

46 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 47 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

Fig. 2-20 DIGSI System Configurator - Subnet

✧ If necessary, change the name for Subnet1 in the Properties window (right window) and the parameters
(e.g. IP start address, Subnet mask, Standard gateway).

✧ Click the SIPROTEC device and change its parameters in the Properties window (right window) (e.g. IP
address, Subnet mask, Standard gateway).

Fig. 2-21 DIGSI System Configurator - SIPROTEC Device

✧ Close the DIGSI system configurator and confirm saving the IEC61850 station settings with OK.

SIPROTEC, Communication Module, Communication Profile 47


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 48 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

The following steps only have to be carried out if time synchronization via NTP or IEC 60870-5-104 is required;
in case of time synchronization via NTP with a second redundant NTP server, these steps have to be carried
out for two NTP servers:
− Right-click Folder and open the Import device dialog via Insert New Object → Other IEC61850
communicator.
− Search for the file sntp.icd in the DIGSI 4 folder and click OK.
(Example (x = hard drive directory): x:\DIGSI4\Utilities\IEC61850\ICD\sntp.icd)
TEMPLATE is inserted in the DIGSI Manager window.
− Rename TEMPLATE to NTP Server.
− In DIGSI Manager, right-click IEC61850 station and select the menu item Object properties...
− Select a device from the Available IEC61850 devices in the Properties - IEC61850 station dialog
→ Communicator tab and click Add.
The selected device is moved from the Available IEC61850 devices window into the IEC61850
station communicator window and click OK.
− Double-click on IEC61850 station in DIGSI Manager.
The DIGSI system configurator opens with the IEC61850 station application.

− Drag & Drop the NTP server entered under New devices (1) into the Subnet1 folder.

Fig. 2-22 Integrating the NTP Server in Subnet1

− Click on NTP server and enter the IP address under Parameter in the Properties window (right
window). If necessary, change subsequently the Subnet mask and the Standard gateway.
− Close the DIGSI system configurator and confirm saving the IEC 61850 station settings with OK.

Please refer to chapter 4 Time Synchronization .

Parameterizing the Device Functions

✧ Open the SIPROTEC device from the DIGSI 4 user interface.

48 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 49 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

✧ Enter all desired settings (see Figure 2-11).

NOTE
These settings, e.g. protection settings, CFC charts and routing to binary inputs/outputs or LEDs, are described
in the DIGSI 4 manual.

✧ Save the parameter set and subsequently close the device on the DIGSI 4 user interface.

Update the Parameter Sets of IEC 61850

NOTE
To activate the modified parameters, you have to update the parameter set after each time you have changed
the settings in DIGSI Manager.

✧ In DIGSI Manager, right-click IEC61850 station and select the menu item Object properties...

✧ In the Properties - IEC61850 station dialog box select the Update tab and update the parameter set
using the Update all parameter sets button.

✧ Close the Report window and the Properties - IEC61850 station dialog box.

Initializing the SIPROTEC Device

NOTE
The SIPROTEC device only has to be initialized once when a new device has been added.

✧ Right-click the SIPROTEC device in DIGSI Manager.

✧ Click Initialize device.... in the menu that opens.

Fig. 2-23 Click Initialize Device in the Menu

SIPROTEC, Communication Module, Communication Profile 49


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 50 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

✧ Adapt again the device settings in DIGSI 4 or the IEC 60870-5-104 settings in the mapping file if
necessary.

✧ To transmit the device settings modified in DIGSI Manager to the SIPROTEC device, right-click the
SIPROTEC device.

✧ Click DIGSI -> Device... in the menu that opens.

Fig. 2-24 Click DIGSI -> Device in the Menu

50 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 51 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

✧ Select the Connection type and the device in the Transfer the parameter set dialog.

Fig. 2-25 Select the Connection type

Fig. 2-26 Transfer the parameter set

SIPROTEC, Communication Module, Communication Profile 51


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 52 Tuesday, February 19, 2013 3:17 PM

2 Configuration in DIGSI 4
2.3 Customization of the Allocations

52 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 53 Tuesday, February 19, 2013 3:17 PM

3 Scaling and Thresholds for Transmission

3.1 Measured Value Scaling 54

3.2 Measured Value Threshold Processing 56

3.3 Counter Value Scaling 57

SIPROTEC, Communication Module, Communication Profile 53


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 54 Tuesday, February 19, 2013 3:17 PM

3 Scaling and Thresholds for Transmission


3.1 Measured Value Scaling

3.1 Measured Value Scaling


Depending on the rated values of the primary equipment of the installation (Vrated, Irated), the scaling of the
measured values has to be adapted in order to ensure a correct transmission of these values in integer format
( 32767) including implicit fractional digits.

Example with rated current: 120 A

Primary current values in SIPROTEC are then displayed in A.

For transmission with implicit one fractional digit a scaling factor of 10 must be used:

120 A then is transmitted as: 120 * 10 = 1200

Example with rated current: 1500 A

Primary current values in SIPROTEC are then displayed in kA.

For transmission with implicit 3 fractional digit a scaling factor of 1000 must be used:

1.5 kA then is transmitted as: 1.5 * 1000 = 1500

In addition to the scaling factor it has to be determined whether the measured value shall be transmitted as
primary value, secondary value or percentage value (i.e. the measured value type).

NOTE
By default, only primary values are used with IEC 60870-5-104.

For the scaling of a measured value, a scaling index in the conversion table has to be selected which is a com-
bination of scaling value, threshold value and measured value type as shown in the following table with the de-
fault entries:

Table 3-1 Conversion Table for Measured Values with Default Entries

Scaling Index Scaling Factor Measured Value Threshold Value By Default Used for
Type (in%)

0 10 Primary value 5 AC currents

1 100 Primary value 3 AC voltages

2 100 Primary value 10 Power

3 1000 Primary value 5 Power factor

4 100 Primary value 0.1 Frequency

5 10 Primary value 2 DC voltages

6 10 Primary value 2 Temperatures

7 100 Primary value 10 -

54 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 55 Tuesday, February 19, 2013 3:17 PM

3 Scaling and Thresholds for Transmission


3.1 Measured Value Scaling

Table 3-1 Conversion Table for Measured Values with Default Entries (cont.)

Scaling Index Scaling Factor Measured Value Threshold Value By Default Used for
Type (in%)

8 100 Percentage value 10 -

9 100 Percentage value 10 -

10 10 Secondary value 10 -

11 100 Secondary value 10 -

The scaling index also determines the threshold value for measured values.

Threshold value: Changes of measured values are transmitted using object 32 (Analog Change Event) only if
the accumulated change differences of the 16-bit Analog Input exceed the threshold value.

SIPROTEC, Communication Module, Communication Profile 55


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 56 Tuesday, February 19, 2013 3:17 PM

3 Scaling and Thresholds for Transmission


3.2 Measured Value Threshold Processing

3.2 Measured Value Threshold Processing


Threshold processing is executed based on a combined fixed and integrated threshold method and based on
relative thresholds related to the last transmitted value.

Relative thresholds related to the last transmitted value


The threshold values are given in percent.

The absolute size of the threshold value in units of the measured value depends on the value last
transmitted to the master and is smaller for smaller values than for larger values.

NOTE
This is independent if the last value has been transmitted by a change event or by a value request from the IEC
60870-5-104 master, e.g. for General Interrogation.

Example for Configured Threshold Value: 10 %

Last transmitted value: 100 V

Current threshold in units: 10 V

If the last transmitted value was zero, a measured value change is transmitted immediately.

56 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 57 Tuesday, February 19, 2013 3:17 PM

3 Scaling and Thresholds for Transmission


3.3 Counter Value Scaling

3.3 Counter Value Scaling

Scaling

The scaling of the metered measurands, which are derived from measured values, refers to:
60,000 impulses per hour for V = Vprim and I = Iprim

Vprim = Full Scale Voltage


(parameter address = 1101)
Iprim = Full Scale Current
(parameter address = 1102)

Example
The following is configured in the parameter set:
Iprim = 1000 A and Vprim = 400.0 kV

60,000 impulses correspond so that:


1 h * 1000 A * 400 kV * 3 = 692.82 MWh

NOTE
• The type of the update (cyclic, with or without deletion) and the update interval must be programmed for
the metered measurands with the parametrization software DIGSI 4.
• The scaling of the metered measurands at binary inputs Wp(puls) and Wq(puls) depends on the externally
connected pulse generator.

SIPROTEC, Communication Module, Communication Profile 57


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 58 Tuesday, February 19, 2013 3:17 PM

3 Scaling and Thresholds for Transmission


3.3 Counter Value Scaling

58 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 59 Tuesday, February 19, 2013 3:17 PM

4 Time Synchronization

4.1 General 60

4.2 Time Synchronization with IEC 60870-5-104 60

SIPROTEC, Communication Module, Communication Profile 59


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 60 Tuesday, February 19, 2013 3:17 PM

4 Time Synchronization
4.1 General

4.1 General
During operation, SIPROTEC devices need the date and time for all time-relevant processes. The time syn-
chronization is required to guarantee a uniform time basis for the communication with other devices and time
stamping of the process data.

Chapter 2 describes the configuration of the time synchronization with IEC 60870-5-104 .

4.2 Time Synchronization with IEC 60870-5-104


IEC 60870-5-104 offers an own time synchronization from the master to the outstations.

During configuration of the SIPROTEC device in DIGSI 4, set the time synchronization parameters for time syn-
chronization via IEC 60870-5-104 in same manner as for NTP (see figure 2-20 ):
• Source of time synchronization: Ethernet NTP
• Further time synchronization parameters (see figure 4-1 )

Fig. 4-1 IEC 60870-5-104 Synchronization Parameters

The following IEC 60870-5-104-specific parameters are relevant for time synchronization via :

Table 4-1 IEC 60870-5-104-specific Parameters

Parameter Description

Enable104TimeSynch Determines whether the IEC 60870-5-104 outstation expects and evaluates time
synchronization from IEC 60870-5-104 master.

NOTE
For time synchronization with NTP or IEC 60870-5-104, at least one NTP server must be configured in the IEC
61850 System Configurator (see figure 2-22)

60 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 61 Tuesday, February 19, 2013 3:17 PM

4 Time Synchronization
4.2 Time Synchronization with IEC 60870-5-104

If IEC 60870-5-104 time synchronization is enabled, the IEC60870-5-104 master shall perform time synchro-
nization to the outstation periodically every 55 s to 61 s, because the time control algorithm in the SIPROTEC
devices is based on a cyclical synchronization within this time period.

The accuracy of the time synchronization via IEC60870-5-104 protocol is 10 ms when time telegrams are being
received continuously in the interval stated above.

If two masters are connected to the device, the connecting one will be the time master.

The IEC 60870-5-104-specific parameter Enable T104 Time Synch determines whether NTP or IEC60870-5-
104 is used for time synchronization:

Table 4-2 Time Synchronization Sources

Source Time NTP Server is Setting Result


Synchronization Configured in Enable
Selection in DIGSI 4 Station Configurator T104TimeSynch

Ethernet NTP Yes = 0: NTP is used Device is synchronized from


NTP (no time requests with
IIN1.4 to a IEC 60870-5-104
master and time telegrams
from IEC60870-5-104
master are rejected)

= 1: IEC60870-5-104 is Device is synchronized from


used IEC60870-5-104

Ethernet NTP No Not relevant No time synchronization


(no time requests with IIN1.4
to a IEC 60870-5-104
master and time telegrams
from IEC60870-5-104
master are rejected)

Other than Not relevant Device is synchronized from


Ethernet NTP the selected source (no time
(e.g. IRIG B, GPS) requests with IIN1.4 to a IEC
60870-5-104 master and
time telegrams from
IEC60870-5-104 master are
rejected)

IEC 60870-5-104 time objects contain the number of milliseconds from the IEC60870-5-104 time epoch, which
is defined as 1970-01-01 00:00:00.000 UTC. Before transmitting internally from the EN100+ to the SIPROTEC
device, the local time correction factor that is configured for NTP time synchronization (and which contains the
time zone and daylight saving time factors, see figure 2-19) is added;

SIPROTEC, Communication Module, Communication Profile 61


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 62 Tuesday, February 19, 2013 3:17 PM

4 Time Synchronization
4.2 Time Synchronization with IEC 60870-5-104

62 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 63 Tuesday, February 19, 2013 3:17 PM

5 IEC 60870-5-104 Diagnosis for EN100+

5.1 HTML Page 64

5.2 SNMP 68

5.3 IEC 60870-5-104 Error Indication 69

SIPROTEC, Communication Module, Communication Profile 63


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 64 Tuesday, February 19, 2013 3:17 PM

5 IEC 60870-5-104 Diagnosis for EN100+


5.1 HTML Page

5.1 HTML Page


EN100+ has a homepage which you can open by entering the IP address of the device.

To open the HTML page, proceed as follows:

✧ Enter the IP address of the device in the browser according to the following rule:
http://IP address/home
Example: http://192.168.0.186/home
The EN100+ homepage opens.

Fig. 5-1 EN100+ Homepage

✧ In the navigation pane (menu on the left), click the entry IEC60870-5-104.
The IEC 60870-5-104 diagnosis page opens.

64 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 65 Tuesday, February 19, 2013 3:17 PM

5 IEC 60870-5-104 Diagnosis for EN100+


5.1 HTML Page

Fig. 5-2 IEC 60870-5-104 Diagnosis HTML Page

This page offers statistic data that are useful for communication diagnosis (e.g. telegram and error counters as
well as the IP of the connected IEC 60870-5-104 master). Additionally, the main protocol-specific settings made
during IEC 60870-5-104 configuration in the mapping file are shown and an overview is given with which para-
meters IEC 60870-5-104 is running on the module.

The parameters displayed on the diagnosis page correspond to the IEC 60870-5-104-specific parameters
(see table 1-3) and the IEC 60870-5-104 networking parameters (see table 1-4).

Additional Remarks to Links

Clear statistics (link) Clicking this link resets all statistic values (telegram and error
counters) to zero.

SIPROTEC, Communication Module, Communication Profile 65


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 66 Tuesday, February 19, 2013 3:17 PM

5 IEC 60870-5-104 Diagnosis for EN100+


5.1 HTML Page

Update statistics (link) The HTML page is not updated automatically. Click this link to up-
date the statistic values (all values will then be read again from the
EN100+ module)

Additional Remarks to Statistics and Parameters

Connected It is shown whether a IEC 60870-5-104 client is connected to this IEC


60870-5-104 server - “yes” or “no”- and additionally if time synchro-
nization via IEC 60870-5-104 is executed, the text “Time synch.”
shows which client acts as time master.

IEC 60870-5-104 Client IP address:Port

IP address and TCP port number of the client which is currently con-
nected to the server or was last connected to the server.

Enable IEC 60870-5-104 time synchronization

- no: Enable IEC 60870-5-104 time synchronization = no


- yes: Enable IEC 60870-5-104 time synchronization = yes and
NTP server is configured
- (yes): Enable IEC 60870-5-104 time synchronization = yes but
no NTP server is configured

66 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 67 Tuesday, February 19, 2013 3:17 PM

5 IEC 60870-5-104 Diagnosis for EN100+


5.1 HTML Page

NOTE
The entry Connection / Security log in the navigation pane (see figure 5-1) is also relevant for IEC 60870-5-
104.

The following events are entered:


• Establishing a new connection with a client (IEC 60870-5-104 master)
• Closing a connection
• Rejecting a connection (unknown IP address or server already connected)

Fig. 5-3 EN100+ Module - Connection/Security Log

SIPROTEC, Communication Module, Communication Profile 67


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 68 Tuesday, February 19, 2013 3:17 PM

5 IEC 60870-5-104 Diagnosis for EN100+


5.2 SNMP

5.2 SNMP
All statistic data shown in the IEC 60870-5-104 diagnosis HTML page (see figure 5-2) are also available via
SNMP. A special MIB file with the name “SipT104.mib” exists for this purpose and is delivered together with the
other MIB files for the EN100+ module. The “SipT104.mib” is contained in the “IEC61850 SNMP MIB V1.XX”.

MIB files package for SIPROTEC devices with EN100+ can be downloaded from:
http://siemens.siprotec.de/download_neu/index_e.htm → All Documents for Communication →
IEC 61850 - General information and descriptions → Tools and MIB-Files

68 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 69 Tuesday, February 19, 2013 3:17 PM

5 IEC 60870-5-104 Diagnosis for EN100+


5.3 IEC 60870-5-104 Error Indication

5.3 IEC 60870-5-104 Error Indication

Display in DIGSI 4

For the IEC 60870-5-104 error indication the SysIntErr (Error System Interface) indication in the device is
used. In the DIGSI Configuration Matrix this indication is available in the Protocol group.

Fig. 5-4 IEC 60870-5-104 Error Indication - Group Protocol in DIGSI 4

The following table shows the values and causes of the IEC 60870-5-104 error indication:

Table 5-1 Indication SysIntErr in DIGSI 4

Indication After Startup/ Change ON to OFF Change OFF to ON


Restart

SysIntErr ON Changes to OFF when a client Changes to ON when no clients are


is connected to the IEC 60870- connected to the IEC 60870-
5-104 servers with its config- 5-104 servers more.
ured TCP port numbers.

SIPROTEC, Communication Module, Communication Profile 69


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 70 Tuesday, February 19, 2013 3:17 PM

5 IEC 60870-5-104 Diagnosis for EN100+


5.3 IEC 60870-5-104 Error Indication

Display in DIGSI 4 for EN100+

Further general EN100+ indications show the startup state of the EN100+ module as well as Ethernet link sta-
tus information:

Fig. 5-5 IEC 60870-5-104 Error Indication - EN100+

Table 5-2 Indication SysIntErr from EN100+

Indication After Startup/ Change ON to OFF Change OFF to ON


Restart

Failure Modul ON Module is ready to work, startup Device or module reset/restart


sequence via DPR successfully
processed

Fail Ch1 ON Ethernet link on Ch1/Ch2 is es- Ethernet link on Ch1/Ch2 is lost
tablished
Fail Ch2 ON

70 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 71 Tuesday, February 19, 2013 3:17 PM

6 Redundancy IEC 60870-5-104

6.1 General Introduction and Requirements 72

6.2 Configuration in DIGSI 73

SIPROTEC, Communication Module, Communication Profile 71


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 72 Tuesday, February 19, 2013 3:17 PM

6 Redundancy IEC 60870-5-104


6.1 General Introduction and Requirements

6.1 General Introduction and Requirements

Redundant communication in a system using IEC 60870-5-104 can be achieved by providing the possibility to
establish more than one logical connections between two stations.

The station that performs the connection establishment is in either case referred to as the controlling station
(station A) in the subsequent description, while the partner station is referred to as the controlled station (station
B).

The following general rules apply to this clause concerning redundant connections:

1) The controlling and controlled station shall be able to handle multiple (N) logical connections.

2) The N logical connections represent one redundancy group.

3) Only one logical connection is in the started state and sending/receiving user data at a time for one redun-
dancy group.

4) The controlling station decides which one of the N connections is in started state.

5) All logical connections of a redundancy group shall be supervised by test frames as described in 60870-5-
104 Ed_2_57_812e_FDIS 5.2.

6) A redundancy group shall rely upon only one process image (database/event buffer).

72 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 73 Tuesday, February 19, 2013 3:17 PM

6 Redundancy IEC 60870-5-104


6.2 Configuration in DIGSI

6.2 Configuration in DIGSI

During configuration of the SIPROTEC device in DIGSI 4, 3 parameters need setting in mapping file (see figure
6-1):

Fig. 6-1 IEC 60870-5-104 redundancy setting

The following IEC 60870-5-104-specific parameters are relevant for redundancy via :

Table 6-1 IEC 60870-5-104-specific Parameters

Parameter Parameter

EnableRedundancy Determines whether the IEC 60870-5-104 outstation


support the redundancy.

TcpPortNumber Determines the TCP ports to listen on

MasterIPAddress List of IP address to accept connections from masters

SIPROTEC, Communication Module, Communication Profile 73


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 74 Tuesday, February 19, 2013 3:17 PM

6 Redundancy IEC 60870-5-104


6.2 Configuration in DIGSI

Table 6-2 IEC 60870-5-104 redundancy description

Redundancy IP address setting Action


Disable/ Enable

Master1 IP address *.*.*.* (by default) Any IEC 60870-5-104 master can com-
municate with the device. After the con-
Master2 IP address *.*.*.* (by default) nection of master1is interrupted, the
master2 can communicate with the
device without device restarts.

Master1 IP address *.*.*.* (by default) Only master2 can communicate with the
device
IEC 60870-5-104 Master2 IP address 192.168.0.12 (e.g)
redundancy
Disable (Only
Master1 IP address 192.168.0.11(e.g) Only master1 can communicate with the
port number 2404
device
is available
Master2 IP address *.*.*.* (by default)

Master1 IP address 192.168.0.11 (e.g) Both of them can communicate with the
device.But only one can communicate
Master2 IP address 192.168.0.12 (e.g) with the device at one time. After the con-
nection is interrupted, the device does
not need to restart.

Master1 IP address *.*.*.*(by default) Any IEC 60870-5-104 master can com-
municate with the device. If the first
Master2 IP address *.*.*.*(by default) master communicates with the device via
port2404/2405, the next one can only
communicate via another port 2405/
2404.

Master1 IP address *.*.*.*(by default) The two scenarios are forbidden to con-
IEC 60870-5-104 figure in DIGSI. If the customer makes a
redundancy Master2 IP address 192.168.0.12 (e.g) defect to configure like this. The redun-
Enable (port dancy will be switched off. That means no
number 2404 and redundancy. Only the master with fixed ip
Master1 IP address 192.168.0.11 (e.g)
2405 are all avail- address can communicate via port 2404.
able) Port 2405 is unavailable.
Master2 IP address *.*.*.* (by default)

Master1 IP address 192.168.0.11 (e.g) Only these two masters can communi-
cate with the device.If the first master
Master2 IP address 192.168.0.12 (e.g) communicates with the device via
port2404/2405, the next one can only
communicate via another port 2405/2404

74 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 75 Tuesday, February 19, 2013 3:17 PM

7 Technical Data

7.1 Technical Data of EN100+ 76

SIPROTEC, Communication Module, Communication Profile 75


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 76 Tuesday, February 19, 2013 3:17 PM

7 Technical Data
7.1 Technical Data of EN100+

7.1 Technical Data of EN100+


The following manuals contain a detailed list of the technical data of the EN100+:
• German edition: Handbuch Ethernetmodul EN100+, Bestellnr. C53000-G1100-C167-10
• US-english edition: Manual Ethernet Module EN100+, order no. C53000-G1140-C167-10

Since EN100+ modules are installed in SIPROTECT 4 devices, both the technical data of the EN100+ and the
technical data of the SIPROTEC 4 device can apply.

76 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 77 Tuesday, February 19, 2013 3:17 PM

Index

A Thresholds for Transmission 53


Application 11 Time Synchronization 59
Time Synchronization with IEC 60870-5-104 60

B
Buffered Events 19 U
Bus Mapping Documents 11 Update the Parameter Sets of IEC 61850 49

C
Configuration in DIGSI 4 31
Counter Value Scaling 57

E
Ethernet Services and Protocols 27

F
File Transfer 20
File Transfer/Reading of Fault Records 20

H
HTML Page 64

I
IEC 60870-5-104 Diagnosis for EN100+ Module 63
IEC 60870-5-104 with IEC 61850 and GOOSE 27
Initializing the SIPROTEC 4 device 49

M
Measured Value Scaling 54
Measured Value Threshold Processing 56

P
Parameterizing the device functions 48
Parameters 17

R
Reading of Fault Records 20
Redundant IEC 60870-5-104 71

S
Scaling for Transmission 53
SNMP 68

T
Technical Data of EN100+ 76

SIPROTEC, Communication Module, Communication Profile 77


C53000-L2040-C370-2, Edition 02.2013
com_T104_profile_us.book Page 78 Tuesday, February 19, 2013 3:17 PM

Index

78 SIPROTEC, Communication Module, Communication Profile


C53000-L2040-C370-2, Edition 02.2013

You might also like