TRANSFORMERS DISTRIBUTION AGE SP185 PT. PLN (PERSERO)
AREA UP3 KEBON JERUK
Rizky Pangestu (201671097)
Under the guidance of Nurmiati Pasra, ST., MT.
ABSTRACT
Transformer is an important equipment in the electric power system, especially in
the distribution of electrical energy. The transformer must be maintained so that it can last long according to the age that it should. Transformer age will be reduced due to overloading, high loading can cause an increase in hotspot temperatures and can damage insulation. An increase in hotspot temperature that exceeds the reference standard of 98 ° C will cause the transformer shrinkage life value to be higher so that the remaining life of the transformer will decrease. Based on SPLN D3.002-1.2007 and standard IEEE Guide for loading mineral oil-immersed Transformers and step voltage regulator C57.91-2011 the life of the transformer is set for 20.55 years (7500.75 days). Distribution transformer used ONAN type cooler. From the results of calculations on the distribution transformer, the value of the age loss for the transformer on the sp185 substation is 0.12752332 hours for 5 days or 0.0000701%. So that the transformer has the highest loading only on March 24, 2019, the life of the transformer can reach 2028.6 and 9.6 years remain.
Keywords: distribution transformer, load, transformer life