REPORT
of
• PROPOSED
RESIDENTIAL
DEVELOPMENT
• AT PLOT: 3161
• CAD. ZONE F01
KUBWA DISTRICT
• FCT-ABUJA
• CLIENT:
• AIHSA IBRAHIM SERTI
GEOTECHNIC OFFICE:
EXT. A35, EFAB MALL COMPLEX,
AREA 11, GARKI,
FCT-ABUJA
JULY, 2018
Sub-Soil
Investigation REPORT
of
PROPOSED RESIDENTIAL
DEVELOPMENT
AT PLOT 3161, CADASTRAL ZONE F01
KUBWA DISTRICT
FCT-ABUJA
CLIENT:
AISHA IBRAHIM SERTI
GEOTECHNIC OFFICE:
EXT. A35, EFAB MALL COMPLEX,
AREA 11, GARKI,
FCT-ABUJA
JULY, 2018
CONTENTS
Page
INTRODUCTION
In order to guard against shear failures and unacceptable settlement due to
loading, it is desirable to determine the sub-soil geotechnical properties of
a site for use in the safe and economic design of appropriate foundation
for the intended structure. The slight or absolute horizontal to vertical
variation in the engineering properties of soil brought about sub-soil
investigation prior to engineering project.
This soil investigation and exploration were conducted on the site for the
PROPOSED RESIDENTIAL DEVELOPMENT AT PLOT 3161, CADASTRAL ZONE F01,
KUBWA DISTRICT, FCT- ABUJA.
SCOPE OF WORK
The scope of this work involves conducting Five [5] number of dynamic
cone penetration test and Three [3] trial pits, to deduce the necessary
engineering
FIELD WORK
The instruments consist of 14kg mass dropped from the height 600mm
with the driving cone of 90o, 5cm², the resistance of penetration (N), or
number of blows was used to measure the state of parking and angle of
shearing resistance (O0) and approximate allowable bearing capacity in
KN/m².
The in-situ strength test involves counting the number of blows using a
weight of 14kg that drive a rod with cone into the ground. The equipment
was manually operated.
The said site topographically, is gentle slope terrain. Top soil yet to be
excavated and NO part of SITE have existing building in it as at the time of
our soil investigation. Ground water was not encounter in the course of
digging of trial pits. Seasonal variation in ground water levels may occur
within the possible development of perched water table just at the aquifer
wet season. The soil on the site is of Reddish Lateritic soil layer and
Reddish-Brown lateritic.
The site is located at Plot 3161, Cadastral Zone F01, Kubwa District in the
Federal Capital Territory, Abuja and north central of Nigeria on the
Longitude 9°10ʺE.It has two major seasons, Dry and Rainy season with
annual rainfall between1890-2500mm.The rainfall reaches its peak in
mid-August and September while the temperature ranges between 20° and
less during the harmattarn to 38° in the dry season and strong wind
pattern from north-east during the harmattarn and onset of raining
season.
LABORATORY INVESTIGATION
The samples collected on the site were transported to our soil mechanic
Laboratory for analysis in which the relevant test toward achieving the
primary aim of conducting the soil investigation was done on selected
samples recovered from the trial pits/DCP Test to establish the
characteristics of the various strata and derived parameters required for
foundation design. The test includes; Density Test, Classification Test
(Grain Size Analysis), Water Content Determination, Atterberge Limit Test
and Undrained Shear Box Test, to deduce the cohesiveness of the soil.
Consolidation test was conducted on the undisturbed sample to determine
the settlement analysis. All test procedures were in accordance with B.S
1377 part 9, 1975.
ATTERBERG LIMITS
TEST ANALYSIS
BULK DENSITY
g = 10m/sec².
Volume of sample
For Instance;
TP1,
B.D = 1715
1021 =1.68g/cc
1000 = 16.8KN/m².
TP2,
B.D = 1736
1000 =17.0KN/m².
TP3,
B.D = 1817
1000 =17.8KN/m².
TP1 VALUES
A safe factor of 3 was used in computing the safe bearing capacity pressures.
= 422.2/3 = 140.7KN/m².
TP2 VALUES
A safe factor of 3 was used in computing the safe bearing capacity pressures.
= 413.6/3 = 137.9KN/m².
TP3 VALUES
C= Cohesion = 32KN/m², Ø = 7º
A safe factor of 3 was used in computing the safe bearing capacity pressures.
= 325.2/3 = 108.4KN/m².
Soil stress analysis for elastic theory indicate that the increase in vertical
stress bellow the centre of a strip foundation of width B is approximately
20% of the foundation pressure at depth 3B and1.5B for square footing. In
practice, this depth is known as depth of influence and essential to
determine the soil condition within the depth for any foundation, therefore,
DCP was used to probing the soil to this depth.
When depth of penetration is less than 10m, a factor called rod ratio is
normally applied to take care of the rod skin friction.
(N X 0.7)
Note that, the chart for upper 1m is different from the chart subsequent
depth.
TABLE 1
DCPT
0.5 67 - 96 88 57
1.0 107 67 126 136 110
1.5 144 107 154 148 152
2.0 160 146 184 172 165
2.5 212 203 217 190 172
3.0 385 220 240 200 180
3.5 403 385 255 224 200
4.0 423 418 352 352 352
4.5 444 - 396 396 396
5.0 - - 409 427 409
5.5 - - 427 - 420
6.0 - - - - -
Sieve analysis was carried out on some selected samples. The result
confirmed the very stiff silty Lateritic nature of the soil between
63.5% - 76.0% size fractions pass sieve no. 200.
SHEAR STRENGTH
Shear Box Test Cohesion ranges between (c) 25 to 32KN/m² with angle of
internal friction rages between 7º to 14º.
The average cohesion and angle of internal friction used for computation
of ultimate bearing capacity is C 29 AND 10º respectively.
PERMEABILITY TEST
Ho =Initial head
Hi=Final head
K = (0.5×2.5 ∕ 21600×78.57)ln(100÷4)
K =2.48×10×6⁻ⁱ ⁰ m/s.
Between the depth of 0.0-2.5 based on the increase in the effective vertical
pressure induced by the loads from structure. Conventional settlement
relationship containing of volume compressibility (Mv) was used in the
analysis.
TP1.
Qa=200KN/m²
Lc=0.09
∆r=4qLr
SC (mm) =Mv∆rH
= 4×200×0.08×0.52×1.8
= 66mm.
CV= K/Mv × W
= 0.014m/year.
TP2.
Mv=0.51
Qa=200KN/m²
H= 1.8m
Lc=0.07
∆r=4qLr
Cv= K/Mv x w
= 0.017m/year.
DIFFERENTIAL SETTLEMENTANALYSIS
TABLE 2
2
(%) 5.0MM 2.0MM 0.425MM 0.075MM LL (%) P1 (%) C KN/m Q QULT QALT
(GEG)
DCP 01 - -
0.5M 211 67
1.0M 321 107
TP 01 - -
1.5M 16.8 2.6 23.3 - 93.4 91.6 68.4 43 21 30 10 432 144 SILTY –SOIL
2.0M 480 160 A-7-5
2.5M 636 212
3.0M 1155 385
3.5M 1206 403
4.0M 1266 423
4.5M 1332 444
DCP 02 - -
0.5M - -
1.0M 211 67
1.5M 321 107
2.0M 438 146
2.5M 609 203
3.0M 660 220
3.5M 1155 385
4.0M 1254 418
4.5M 1320 440
DCP 03 - -
0,5M 288 96
1.0M 378 126
1.5M 462 154
2.0M 600 184
2.5M 552 217
3.0M 720 240 -
3.5M 765 255
4.0M 1056 352
4.5M 1188 396
5.0M 1227 409
5.5M 1181 427
DCP 04 - -
0.5M 254 88
TP 01 - - -
1.0M 17.0 2.6 23.9 91.7 85.5 71.4 80.0 60 20 25 14 408 136 LATERITIC-SILTY
1.5M 444 148 CLAY. A -7-6
2.0M 516 172
2.5M 570 190
3.0M 600 200
3.5M 672 224
4.0M 1056 352
4.5M 1188 396
5.0M 1181 427
DCP 05 - -
0.5M 171 57 -
TP 01 - - LATERITIC-SILTY
1.0M 17.8 2.6 26.4 - 98.1 91.8 76.0 72 24 32 7 330 110 SOIL A -7-6
1.5M 456 152
2.0M 495 165
2.5M 516 172
3.0M 540 180
3.5M 600 200
4.0M 1052 352
4.5M 1188 396
5.0M 1227 409
5.5M 1260 420
Dynamic Cone Penetration (DCP) test was the main in-situ test performed
on the site and was carried out at the land surface.
Trial pits were dug to collect both disturbed and undisturbed samples,
sieve analysis, shear and specific gravity and atterberg limit test and the
Oedometer/settlement were carried out on the sample (Test results are
attached herewith).
The result of Dynamic Cone Penetration (DCP) revealed that the subsoil in
the site area is very good at deep depth.
The grain size distribution pattern of the soil shows that the soil is
homogeneous from place to place. Generally, the subsoil consists of Silty
clay and Stiff clay of A-7-5 and A-7-6 soil classification respectively.
The result of laboratory test and analysis show that, generally, the natural
moisture content (NMC) increase with depth there is difference in % of
NMC, ranges from 23.3-26.4% while the plastic index is very high with
values range from 40-48%, linear shrinkage is 0.8cm-1.4cm and for
particle size distribution analysis test, the ranges of passing 0.07mm sieve
size is 64%-76%.
The specific gravity of material is between 2.60 and the field allowable
bearing capacity is 153.2KN/m² at 2.0-2.5m depth while laboratory is
129.0KN/m².
The safe bearing capacity to work out the dimension of the footing at
tolerable and uniform settlement using C=29, Ø =10º. And average density
of 1.80g/cm³ with safety factor of 3.0 in Terzaghi equation
Qu=1.3CNc+¥ (Nq) +0.4¥BNy.
The most probable allowable bearing capacity achieve on the site Dynamic
61.6kN/m² @ 0.5M
109.2kN/m² @ 1.0 M
141.0kN/m² @ 1.5M
165.4kN/m² @ 2.0M
198.8KN/m² @ 2.5M
245.0kN/m² @ 3.0M
293.4kN/m² @ 3.5M
379.4kN/m² @ 4.0M
The type and depth of foundation was guided by the soil properties, type
of structure to be supported and its influence on the soil, angle of
cohesion geologically, evaluation, water table and the net allowable
bearing capacity.
In view of the above data, and since the working load was not known, we
suggest that, RAFT FOUNDATION/UNDERGROUND BEAM is recommended
at the depth 1.5m-2.0m from the ground surface and 1.5x1.5m
foundation footing in view of the wider width peculiar to raft foundation is
considered adequate as footing for such structure (Five slabs) on this
NOTE:
Compiled by
Kola
08056969171
TABLE 3
MOISTURE CONTENT DETERMINATION
OPERATOR: ABDULAHI DATE: JULY, 2018 SAMPLE NO: TP 01 TO TP 03
TEST TP 01 TP 02 TP 03
Container No.(g) 3 36 33 30 3 36
Wt of tare (g) 42 40 43 43 42 42
Wt of water (g) 11 9 15 13 11 13
DCP 1
TP 1
DCP 2
TP 2
DCP 3
DCP 4
TP 3
DCP 5
KEY
TP ------------------
DCP ------------------ 19
SUB-SOIL INVESTIGATION ON PROPOSED DEVELOPMENT @ PLOT 3161, CAD. ZONE F01, KUBWA DISTRICT, FCT-ABUJA
2
V E RTICA L P RE S S URE KN/ M
2 .5
2 .0
VOID RATIO
1 .5
0 .5
2
V E RT ICA L P RE S S URE K N/M
2.5
2.0
VOID RATIO
1.5
0.5
CALIBERATION PARAMETER
Zc = 0 Qa = 400KN/m2
UPPER 1M
BLOWS Zc (cm) Qc(KN/m2) Qu(KN/m2) Qa(KN/m2)
50/N 0.5 378 1945 720
1.0 352 1810 670
1.5 337 1730 640
2.0 284 1460 540
2.5 263 1350 500
3.0 236 1215 450
3.5 184 945 350
4.5 131 675 250
5.0 116 594 220
5.5 105 540 200
6.0 95 486 180
6.5 84 432 160
7.0 79 405 150
7.5 74 379 140
8.0 68 351 130
8.5 63 324 120
9.0 58 297 110
9.5 53 270 100
10.0 47 243 90
11.0 42 216 80
12.5 37 189 70
14.0 32 162 60
15.0 29 149 55
25.0 - - 0
CALIBERATION PARAMETER
Zc = 0 Qa = 400KN/m2
SUBSEQUENT DEPTH
BLOWS Zc (cm) Qn(KN/m2) Qu(KN/m2) Qa(KN/m2)
0.5 341 1765 650
1.0 313 1607 595
1.5 300 1539 570
2.0 252 1296 480
2.5 234 1202 445
3.0 210 1080 400
3.5 200 1026 380
4.0 126 648 240
4.5 105 540 200
5.0 92 473 175
5.5 84 432 160
6.0 76 392 145
6.5 68 351 130
7.0 63 324 120
7.5 58 297 110
8.0 55 284 105
8.5 50 257 95
9.0 47 243 90
9.5 42 216 80
10.0 37 189 70
10.5
11.0 34 176 65
12.5 30 150 55
14.0 26 135 50
15.0 24 120 45
25.0 - - 0
DEPTH (M)
26.00 2.74 423
4.00
- -
5.00
5.50
6.00
6.50
7.00
7.50
0 50 100 150 200 250 300 350 400 450 500 550 300 300
Qa (KN/m2)
DYNAMIC CONE PENETRATION
PROPOSED RESIDENTIAL DEVELOPMENT 10 KG
AT PLOT 3161, CADASTRAL ZONE F01 Extrapolated values of the cone Penetration from the table
KUBWA DISTRICT , FCT-ABUJA. Zc = 50/(0.7 × N)
Where N = No of blows per 10cm
DCP 2
Depth (m) Zc Qa (KN/m2) The table below shows the extrapolated values of the allowable bearing capacity
of the said site as enumerated below.
0.00
0.00 0.00 0.00
DEPTH (M)
21.00 3.40 385 3.50
4.50
5.00
5.50
6.00
6.50
7.00
7.50
0 50 100 150 200 250 300 350 400 450 500 550 300 300
Qa (KN/m2)
DYNAMIC CONE PENETRATION
PROPOSED RESIDENTIAL DEVELOPMENT 10 KG
AT PLOT 3161, CADASTRAL ZONE F01 Extrapolated values of the cone Penetration from the table
KUBWA DISTRICT , FCT-ABUJA. Zc = 50/(0.7 × N)
Where N = No of blows per 10cm
DCP 3
Depth (m) Zc Qa (KN/m2) The table below shows the extrapolated values of the allowable bearing capacity
of the said site as enumerated below.
0.00 0.00 0.00 0.00
DEPTH (M)
19.00 2.98 352
4.00
6.00
6.50
7.00
7.50
0 50 100 150 200 250 300 350 400 450 500 550 300 300
Qa (KN/m2)
DYNAMIC CONE PENETRATION
PROPOSED RESIDENTIAL DEVELOPMENT 10 KG
AT PLOT 3161, CADASTRAL ZONE F01 Extrapolated values of the cone Penetration from the table
KUBWA DISTRICT , FCT-ABUJA. Zc = 50/(0.7 × N)
Where N = No of blows per 10cm
DCP 4
Depth (m) Zc Qa (KN/m2) The table below shows the extrapolated values of the allowable bearing capacity
of the said site as enumerated below.
0.00 0.00 0.00 0.00
DEPTH (M)
20 3.6 352
4.00
5.50
6.00
6.50
7.00
7.50
0 50 100 150 200 250 300 350 400 450 500 550 300 300
Qa (KN/m2)
DYNAMIC CONE PENETRATION
PROPOSED RESIDENTIAL DEVELOPMENT 10 KG
AT PLOT 3161, CADASTRAL ZONE F01 Extrapolated values of the cone Penetration from the table
KUBWA DISTRICT , FCT-ABUJA. Zc = 50/(0.7 × N)
Where N = No of blows per 10cm
DCP 5
Depth (m) Zc Qa (KN/m2) The table below shows the extrapolated values of the allowable bearing capacity
of the said site as enumerated below.
0.00 0.00 0.00 0.00
DEPTH (M)
19.00 2.98 352
4.00
6.00
6.50
7.00
7.50
0 50 100 150 200 250 300 350 400 450 500 550 300 300
Qa (KN/m2)
SUB-SOIL INVESTIGATION ON PROPOSED DEVELOPMENT @ PLOT 1813, CAD. ZONE B13, GADUWA DISTRICT, FCT-ABUJA
SIEVE ANALYSIS OF SOIL (WET/DRY SIEVING)
CONTACT
LOCATION
3 IN. 75 mm
2 IN. 50 mm 4500
1 IN. 25 mm 2500
3
/4 IN. 20 mm 2000
1
/2 IN. 12.5 mm 1500
3
/8 IN. 10 mm 1000
1
/4 IN. 6.3 mm 750
3
/8 IN. 5 mm 500
TOTAL
LOCATION
3 IN. 75 mm
2 IN. 50 mm 4500
1 IN. 25 mm 2500
3
/4 IN. 20 mm - - 100.0 2000
1
/2 IN. 12.5 mm 18 3.7 93.3 1500
3
/8 IN. 10 mm 24 5.0 95.0 1000
1
/4 IN. 6.3 mm 35 7.2 92.8 750
3
/8 IN. 5 mm 40 8.3 91.7 500
18 IN 3.35 mm - - - 300
TOTAL
LOCATION
3 IN. 75 mm
2 IN. 50 mm 4500
1 IN. 25 mm 2500
3
/4 IN. 20 mm 2000
1
/2 IN. 12.5 mm 1500
3
/8 IN. 10 mm 1000
1
/4 IN. 6.3 mm 750
3
/8 IN. 5 mm 500
TOTAL
¼
3/8
½
¾
1
5
1/8
3/16
3
52
1
2
2½
-3
7
-4
-2
25
36
72
14
300
1¼
18
-1
200
10
150
100
1½
90 90 90
80 80 80
70 70 70
60 60 60
50 50 50
40 40 40
30 30 30
20 20 20
10 10 10
0
6 0.002 0.02 0.06 0.2 0.6 2.0 6.0
20 60 300
Particle Size (mm)
2½
¼
3/8
¾
3/16
IN CM PER SECONDS
1/8
1¼
52
7
14
25
1½
36
18
10
72
1
300
200
150
-2
100
-1
-3
-4
0 1
0
90 90 9
0
80 80 8
0
70 70 7
0
60 60 6
0
50 50 5
0
40 40 4
0
30 30 3
0
20 20 2
0
10 10 1
0
0
0
0.2 0.6 2.0 6.0 20 60 300
.0006 0.002 0.02 0.06
Particle Size (mm)
¼
3/8
1
½
¾
1
52
5
1/8
3/16
3
2
2½
-3
-4
-2
7
25
36
72
300
14
-1
18
1¼
200
150
10
100
1½
100
90 90 90
80 80 80
70 70 70
60 60 60
50 50 50
40 40 40
30 30 30
20 20 20
10 10 10
0
06 0.002 0.02 0.06 0.2 0.6 2.0 6.0
20 60 300
Particle Size (mm)
TABLE 5
LOCATION: PLOT 3161, CAD. ZONE F01, KUBWA DISTRICT, FCT-ABUJA DESCRIPTION: TP1, TP2 & TP3. DIAMETER: 60mm
SAMPLE WT.OF AREA OF VOLUME BULK SWELL MOISTURE LATERAL NORMAL NORMAL DIAL LOAD SHEAR
NO. SAMPLE SAMPLE OF DENSITY (%) CONTENT STRAIN WEIGHT STRESS GUAGE (KN) STRESS
(KG) (MM2) SAMPLE (KG/m3) (%) (%) (KG) (KN/m2) (KN/m2)
(CM3)
TP 1 A 0.1667 0.0028 0.1924 1684 - 23.9 10% 18.4 50 4.7 0.1170 38
B 0.1667 0.0028 0.1924 1684 - 23.9 10% 36.8 100 5.2 0.1294 42
C 0.1667 0.0028 0.1924 1684 - 23.9 10% 73.6 200 6.9 0.1725 56
D 0.1667 0.0028 0.1924 1684 - 23.9 10% 147.2 400 10.6 0.2649 86
PROJECT NAME: PROPOSED RESIDENTIAL DEV, PLOT 3161, CAD. ZON F01, KUBWA DISTRICT, FCT-ABUJA
38 42 56 86
SHEAR STRESS
CHECK : 1= C + 6tan∅
38 47 65 101
COHESION = 30 Ø = 10 DEGREES
200
SHEAR STRESS KN/m2
150
100
50
50 200 400
100
PROJECT NAME: PROPOSED RESIDENTIAL DEV, PLOT 3161, CAD. ZON F01, KUBWA DISTRICT, FCT-ABUJA
38 46 65 104
SHEAR STRESS
CHECK : 1= C + 6tan∅
38 50 75 125
COHESION = 26 Ø = 14 DEGREES
200
SHEAR STRESS KN/m2
150
100
50
50 200 400
100
PROJECT NAME: PROPOSED RESIDENTIAL DEV, PLOT 3161, CAD. ZON F01, KUBWA DISTRICT, FCT-ABUJA
SHEAR STRESS
39 40 51 72
CHECK : 1= C + 6tan∅
38 44 56 81
COHESION = 32 Ø = 7 DEGREES
200
SHEAR STRESS KN/m2
150
100
50
50 200 400
100
SAMPLE No.: 01 DEPTH : 0 -1.5m JOB No.: OPERATOR: ABBEY DATE: JULY, 2018
PLASTIC LIMIT
TYPE OF TEST LIQUID LIMIT TEST (L.L) TEST (P.L)
Test No. 1 2 3 4 5 6 7
No. of blows 12 20 16
Container No. 04 09 13 02 06
Wt. of Wet soil + container (gm) 70.5 66.4 63.6 48.3 48.0
Wt. of dry soil + container (gm) 57.1 55.8 55.4 46.7 46.2
50
80
FLOW CURVE
40
60
MO IS TU RE CO N TE NT
30
40
20 20
0 5 10 15 20 25 30 35 40 45 50
NUMBER OF BLOWS
SUMMARY
SAMPLE No.: 02 DEPTH : 0 -2.0m JOB No.: OPERATOR : ABBEY DATE: JULY, 2018
PLASTIC LIMIT
TYPE OF TEST LIQUID LIMIT TEST (L.L) TEST (P.L)
Test No. 1 2 3 4 5 6 7
No. of blows 11 22 31
Container No. 7 5 8 01 03
Wt. of Wet soil + container (gm) 75.1 67.0 62.0 46.9 46.9
Wt. of dry soil + container (gm) 60.9 56.4 54.0 45.5 45.5
50
80
FLOW CURVE
40
60
MO IS TU RE CO N TE NT
30
40
20 20
0 5 10 15 20 25 30 35 40 45 50
NUMBER OF BLOWS
SUMMARY
SAMPLE No.: 03 DEPTH : 0 -2.0m JOB No.: OPERATOR : ABBEY DATE: JULY, 2018
PLASTIC LIMIT
TYPE OF TEST LIQUID LIMIT TEST (L.L) TEST (P.L)
Test No. 1 2 3 4 5 6 7
No. of blows 12 21 32
Container No. 17 21 23 11 10
Wt. of Wet soil + container (gm) 79.2 71.3 67.3 47.6 46.8
Wt. of dry soil + container (gm) 63.0 58.9 57.3 45.8 44.9
50
80
FLOW CURVE
40
60
MO IS TU RE CO N TE NT
30
40
20 20
0 5 10 15 20 25 30 35 40 45 50
NUMBER OF BLOWS
SUMMARY
REMOVAL OF ROD 45
DCPT BORED - HOLES 46