Aux Boiler Datasheet for FD Fan and Motor (Including Outline Drawing)

DP16004-YT01-90QH-111012

SHAFT POWER CALCULATION:

STATIC PRESSURE(P) OF TEST BLOCK = 710 mm WG

VOLUME FLOW RATE (V) OF TEST BLOCK = 87222 m3/hr =24.34 m3/Sec

CONSIDERING THE ABOVE PRESSURE AND FLOW OF TEST BLOCK WE GET,

FAN STATIC EFFICIENCY (ƞ)=80.1%=0.801

SHAFT POWER(KW) =[ PRESSURE(mm WG)*FLOW (m3/Sec)] / [102*EFFICIENCY]

[WHERE 102 IS A CONSTANT FACTOR]

BY USING THE ABOVE EQUATION WE CAN GET THE SHAFT POWER WHICH IS 211.5 KW.

Rev. 3
OBRA “C” (2x660 MW) THERMAL POWER EXTENSION PROJECT Page 9 of 11