Professional Documents
Culture Documents
Caso Space
Caso Space
Abstract: This paper summarizes the different activities undertaken in order to identify the main causes of the collapse of the Space
Building, a 27-story reinforced concrete framed building in Medellín, Colombia. Site investigations, field and laboratory tests, and a detailed
Downloaded from ascelibrary.org by 190.93.159.100 on 07/20/18. Copyright ASCE. For personal use only; all rights reserved.
analytical work including structural analysis under different considerations were carried out. The main cause of the collapse was associated
with the deficient structural capacities of the columns of the building in relation to the dead and service loads imposed at the time of the
collapse. The occurrence of high differential settlements, the high compressive stresses in main columns, the repair works that were carried
out minutes before the collapse, and the probable shear failure of beams and compressive failure of partitions walls during repair works were
identified as probable secondary causes and detonating factors of the building collapse. The authors of this investigation considered that if the
building had been designed adequately using the Colombian building design codes available at that time, it would not have collapsed, even if
most of the aforementioned detonating events had occurred. DOI: 10.1061/(ASCE)CF.1943-5509.0001148. © 2018 American Society of
Civil Engineers.
Introduction differences between actual and design loads; (2) inadequate floor
system thickness; (3) insufficient reinforcement; (4) overloads at
Collapses of reinforced concrete residential buildings because of the foundation level; (5) concrete strengths smaller than the mini-
gravitational loads have caused not only devastating life and eco- mum specified; (6) dimensions of structural elements lower than
nomic losses, but are also an important detriment to the engineering those specified; and (7) vertical elements with excessive concrete
profession’s reputation. Therefore, it is important that the engineer- cover. It was concluded that the building failed by creep attributable
ing community not only study the causes of collapses but also
to design flaws and errors in the construction process.
document each case in order to learn from the mistakes and avoid
In October 2004, in an area near the Zumrut building, the failure
them happening again. One of the most tragic cases reported in the
of two basement columns of the Altinbasak residential building
literature was the collapse of the Zumrut residential apartment
was also reported (Kaltakci et al. 2007). The causes of this event
building, located in the city of Konya in Turkey. This 9-story re-
were similar to those found in the Zumrut building. Another case
inforced concrete building collapsed on February 2, 2004, causing
the death of 92 people. In this case, the investigators found the fol- reported in the literature corresponds to the collapse of the Lian Yak
lowing building problems (Kaltakci et al. 2013): (1) important Building in Singapore on March 15, 1986, which caused the death
of 33 people. The sudden collapse of this building was mainly
1
Associate Professor, Dept. of Civil and Environmental Engineering, attributed to the underestimation of dead loads during the design
Universidad de los Andes, Bogotá 111711, Colombia (corresponding process, which led to an inadequate design of structural elements,
author). E-mail: lyamin@uniandes.edu.co especially columns (Standing Committee on Structural Safety
2
Associate Professor, Dept. of Civil and Environmental Engineering, 1987; National Geographic Channel 2005).
Universidad de los Andes, Bogotá 111711, Colombia. E-mail: jcorreal@ In October 2013, the media reported the collapse of the Space
uniandes.edu.co Building located in Medellín, Colombia (García et al. 2014).
3
Associate Professor, Dept. of Civil and Environmental Engineering,
Universidad de los Andes, Bogotá 111711, Colombia. E-mail: jureyes@
Although the building was conceived and designed as a unit, it was
uniandes.edu.co constructed by stages. The 27-story stage (the last of the six stages)
4
Associate Professor, Dept. of Civil and Environmental Engineering, was completed by the end of April 2013. Six months later, one of
Universidad de los Andes, Bogotá 111711, Colombia. E-mail: framirez@ the columns on the fourth level of this stage failed. The city of
uniandes.edu.co Medellín authorities [Disaster Risk Management Administrative
5
Instructor, Dept. of Civil and Environmental Engineering, Universidad Department (DAGRD)] decided to evacuate Stage 6 of the building.
de los Andes, Bogotá 111711, Colombia. E-mail: jr.rincon3391@
Meanwhile, the construction company started repairing works.
uniandes.edu.co
6
Research Assistant, Dept. of Civil and Environmental Engineering, On October 12, 2013, at 8:20 p.m. and with no apparent cause,
Universidad de los Andes, Bogotá 111711, Colombia. E-mail: ai Stage 6 suddenly collapsed, killing 12 people; the largest part of the
.hurtado77@uniandes.edu.co building (Stages 1–5), occupied at that moment, did not collapsed.
7
Research Assistant, Dept. of Civil and Environmental Engineering, This paper presents the results of a comprehensive research con-
Universidad de los Andes, Bogotá 111711, Colombia. E-mail: jf ducted to establish the main causes of the collapse of this building,
.dorado285@uniandes.edu.co including a general description of the building, main construction
Note. This manuscript was submitted on April 25, 2017; approved on
October 17, 2017; published online on February 16, 2018. Discussion per-
deficiencies reported, results of field and laboratory investigations,
iod open until July 16, 2018; separate discussions must be submitted for analyses of compliance with building code requirements, and
individual papers. This paper is part of the Journal of Performance of the computational modeling conducted to understand the causes of
Constructed Facilities, © ASCE, ISSN 0887-3828. collapse.
X E H K N Q T
Level
23
19
17
15
13
11
-4
K L M N
J O
I P
Column R3
H
Q
G 6.60 m Column S3
R
7.17 m
F S S1
T
U
E Stage 4
Column R5
D
Column S5
C
B
X 3 4 5
1 2
Fig. 2. Typical plan including axes nomenclature; critical columns are highlighted
N° 2 @0.15 m 4 N°5
N°2 @ 0.15 m Differential Settlements in Several Columns
N° 2 @0.15 m
1.80 m
1.50 m 6 N°4 34 N°5
1.00 m
(Fig. 2), presented a total deflection on the order of 80 mm in
October, 2013 (6 months after the end of construction). This col-
N° 2 @0.30 m N° 2 @0.30 m N° 2 @0.30 m
umn had evidenced signs of distress in February 2013 (2 months
before the end of construction) at the fifth story. Other columns
4 N°5
presented simultaneously settlements in the order of 40–60 mm.
4 N°5 0.20 m 8 N°6
At this time, the construction firm and the designer decided
0.20 m to reinforce the foundation of Column R3 with two additional
0.20 m
piles firmly connected to the original pile. Some months later,
Downloaded from ascelibrary.org by 190.93.159.100 on 07/20/18. Copyright ASCE. For personal use only; all rights reserved.
(a) (b) (c) on October 11, 2013, just 1 day before the building collapse,
Column S3 evidenced signs of compression failure. According
Fig. 3. Cross section for (a) typical columns; (b) x-axis columns; to current building design codes (AIS 2010; ACI 2014) the maxi-
(c) columns at basement of Stage 6 mum allowable differential settlement between columns for this
building was approximately 8 mm, 1/10 the maximum registered.
However, the NSR-98 did not specify provisions about this issue.
After a detailed revision of the construction reports, it was found
of 0.20 × 0.50 m in the longitudinal direction and 0.40 × 0.30 m in that difficulties during the geotechnical excavations and the pres-
the radial direction of the building. The thickness of the slab varied ence of pressurized ground water made it impossible to complete
from 0.06 or 0.10 m depending on the building stage to 0.40 m the increased diameter size (bell-shaped) specified in the design for
[Fig. 4(c)]. The foundation of the building was composed of 0.40 × the bottom part of the pile in Axis R3. In addition, the same con-
0.40 m grade beams and cast-in-place concrete belled piles with struction difficulties prevented the construction firm from reaching
typical shaft diameter of 1.20 m, and bell diameters varying from the specified depth of foundation for this pile. To verify this situa-
1.90 to 3.0 m. The piles included reinforcement up to a depth of tion, in the framework of the present paper, an excavation was
4 m; below that depth, they were built using cyclopean concrete. conducted adjacent to Pile R3. Visual inspections confirmed that
The foundation did not consider pile caps, as shown in Fig. 5. Pile R3 did not have the bell-shaped point specified in the design,
and the foundation depth was approximately 15 m instead of the
20 m specified in the geotechnical report. As it is well known,
Construction Deficiencies differential settlements generate an important redistribution of in-
ternal stresses in beams and columns adjacent to the critical zones.
A series of construction deficiencies and problems were identified In particular, because of the interconnection between structural el-
during the field investigation activities. The most relevant were ements, the axial loads in columns that evidence the highest settle-
the differential settlements observed during construction, the solu- ments tend to reduce significantly, whereas axial loads in neighbor
tions adopted by the construction firm in order to correct the high columns tend to increase proportionally, probably generating im-
vertical deflections of the slabs, and the inadequate reaction of the portant overloads; in addition, beams connecting columns present
1.50 m 1.50 m
7.00 m
B B
Floor slab
(thickness equal to 0.06 m) (b)
7.5 m
Radial beam
(0.40m × 0.30m)
0.06 m or 0.10 m
0.40 m depending on the stage
longitudinal beam
0.30 m
(0.40 m × 0.30 m)
(c)
Fig. 4. Details in floor system: (a) floor slab; (b) Section A radial cross section; (c) Section B longitudinal cross section
N°3 @0.30 m
0.40 m
Pile
1.20 m
1.50 m
Bell
1.10 m
Concrete pile, 21 MPa
Foundation beam
11 N°6, L=4,0 m
B
Downloaded from ascelibrary.org by 190.93.159.100 on 07/20/18. Copyright ASCE. For personal use only; all rights reserved.
1.20 m
1.50 m
(a) (b)
Fig. 5. Column-pile connection for typical columns: (a) plan view; (b) Section B
occupation
20 by owners, tions, and others. The construction logbooks reported deflections
30 04/03/2013
ranging from 5 to 20 cm in the central zone of typical two-way
40 Distress in slabs (clear span of approximately 8 m). Initially, in order to correct
R3 column, Differential
50 02/26/2013 Differential settlement these high deflections, the contractor ordered a concrete fill to level
S5-S3= 5 mm
60 Foundation settlement the floor surface. A mixture of mortar and polystyrene spheres was
retrofit, R3-S3= 54 mm
70 08/21/2013 used for this purpose. From the debris of the collapsed structure,
One day prior samples of this lightweight mortar were recovered to conduct
80 to colapse.
10/11/2013 density tests, which reported specific weight values from 14 to
90
18 kN=m3 . Later, the construction firm decided to increase the
Fig. 6. Differential settlement during construction and postconstruction minimum thickness of floor slabs in the central zone from an initial
value of 6 cm to a thickness of 10 cm. Considering the advance
of the construction of Stage 6, this modification was only imple-
mented above the sixth floor. However, the proposed solution
Table 1. Space Building Collapse: Chronology Events
was not effective, and mortar filling was also reported in the upper
stories. In general, the estimated overload caused by these floor
Date Event fillings ranged from 0.6 to 1.0 kN=m2 . No evidence was found of
February 2006 Stage 1 of construction started any verification or revision of the design as a consequence of the
March 1, 2011 Stage 6 of construction started change in slab thickness or generated overloads.
February 2, 2013 Allowable differential settlement were
exceeded with high values in one pile
(pile located under Column R3) Damage in Main Columns
February 20, 2013 Evidence of distress in Column R3 column at
fifth level As explained before, some columns evidenced signs of distress
April 10, 2013 Residents were allowed to use Stage 6 8 months before the collapse of the building. The first report was
August 2013 Construction of foundation retrofit in R3 piles on Column R3, which showed loss in concrete cover and partial
October 11, 2013 Structural failure in Column S3 buckling of one longitudinal bar near the upper joint at the fifth-
October 12, 2013 Building collapse story level. On October 11, 2013, the second important event was
reported in Column S3 at the fourth level (adjacent to Column R3).
Figs. 7(a and b) illustrate the compression failure observed in the
column just 1 day before the collapse of the building. The column
a considerable increase in the shear forces and moments at connect- evidenced a clear diagonal crack, loss of concrete section, buckling
ing joints. Fig. 6 illustrates the total and the differential settlements of all longitudinal bars, and tension failure of stirrups in the central
measured in some of the critical columns of Stage 6. Table 1 sum- part of the column. Total vertical displacement of approximately
marizes the chronology of the main events reported during the 85 mm and horizontal displacement of approximately 30 mm were
construction phase related to differential settlements and signs of measured. From the photographs, it is clear that concrete masonry
distresses in critical columns. partition walls were playing an important role in the prevention of
Fig. 7. Photography of compression failure of Column S3: (a) front view; (b) lateral view; (c) pancaked floor slabs just after Stage 6 collapse
[(a and b) images courtesy of DAGRD]
Collapse Event
Six months after the end of construction, on October 12, 2013, at Fig. 8. Demolition of the remaining structure (Stages 1–4) decided by
8:20 p.m. and with no apparent external cause, the 27-story Stage 6 the city authorities (image courtesy of DAGRD)
of the Space Building suddenly collapsed, killing 12 people. Most
of the fatality victims were workers who were trying to repair
Column S3 at the fourth level. Surprisingly, Stages 1–5 of the build-
ing did not collapse. Fig. 7(c) illustrates the final pancake-type ar- as columns and structural walls was also verified. The verticality of
rangement of the collapsed floor slabs, indicating a vertical collapse the elements was evaluated by means of plumbing laser levels, and
mechanism with no important horizontal load participation. only 3 out of 53 inspected elements exhibited deviations between
A detailed field investigation was made immediately after the ends of approximately 0.27°. Location, size, and depth of reinforc-
collapse. Several important structural damages were observed ing bars in the structural elements (beams, columns, and concrete
in Stage 5, particularly in the columns shared with the collapsed walls) were determined in more than 200 points using a Ferroscan.
Stage 6 at the basement level. Considering the high risk of collapse Some results were verified by visual inspection once exposing
for the rest of the building, the authorities decided to immediately the reinforcement in some critical zones. Results indicated that the
evacuate the rest of the building. Some weeks later, after an initial location and size of the reinforcement bars were reasonably con-
assessment, the demolition of Stage 5 was ordered by the city sistent with that specified in the construction drawings for most
authorities using controlled quantities of explosive to prevent fur- structural elements.
ther damage to the remaining part of the building and adjoining
constructions. Later on, after the final structural risk assessment
Construction Materials Quality Control
process of the remaining stages, the city authorities decided to
demolish the complete structure (Fig. 8). During the construction process, a material quality-control program
was followed. According to the information provided by the con-
struction company, a total of 92 tension tests were performed on
Field Investigation reinforcing bars and 24 tension tests were performed on welded
wire fabrics. Out of the 92 rebar tests, only four bars exhibited a
A complete field inspection was performed after the collapse of yield strength slightly below approximately 92.5% of the minimum
Stage 6. Initial activities included geometric and dimensional ver- specified (fy ¼ 420 MPa). In addition, a total of 539 compressive-
ifications using the design drawings available. Differences between strength test results were obtained from logbooks for specified con-
geometric field measurements and design drawings specifications crete strength of 21 MPa. A total of 27 tests indicated values of fc0
were negligible. The plumbing of vertical structural elements such lower that the specified value by more than 3.5 MPa. In addition,
31.0 31.0
27.0 27.0
23.0 23.0
19.0 19.0
15.0 15.0
01/07/2007 20/07/2009 09/08/2011 28/08/2013 01/07/2007 20/07/2009 09/08/2011 28/08/2013
(a) Date [dd/mm/yyyy] (b) Date [dd/mm/yyyy]
Downloaded from ascelibrary.org by 190.93.159.100 on 07/20/18. Copyright ASCE. For personal use only; all rights reserved.
35.0 35.0
31.0 31.0
27.0 27.0
23.0 23.0
19.0 19.0
15.0 15.0
01/07/2007 20/07/2009 09/08/2011 28/08/2013 01/07/2007 20/07/2009 09/08/2011 28/08/2013
(c) Date [dd/mm/yyyy] (d) Date [dd/mm/yyyy]
Fig. 9. Construction quality control in concrete strength: (a) foundations; (b) slabs; (c) concrete walls; (d) columns
109 arithmetic averages of three consecutive strengths had Table 2. Drill Cores Extracted in the Building
results below the specified fc0 . For the case of 35 MPa concrete, Element Stage 1 Stage 2 Stage 3 Stage 4 Stage 5 Stage 6 Total
21 tests results were available, wherein all of the individual results
were above (f c0 − 3.5) MPa and nine arithmetic averages were Columns 17 9 15 11 5 4 61
Beams 0 0 0 0 0 6 6
below fc0.
Floor slabs 1 0 0 1 0 2 4
In order to check the concrete strength of those batches falling Concrete wallsa 2 3 1 2 0 2 10
below the required values, additional tests were performed at Total cores 20 12 16 14 5 14 81
56 days. For 21-MPa concrete, the test results show that, 12 indi- a
vidual results (approximately 2%) and 35 arithmetic averages Concrete walls exist only in the elevator area.
(approximately 12%) fell below the specified strength. For 35-MPa
concrete, no individual results and three arithmetic averages failed
to meet the required strengths. According to the evidence provided discarded, resulting in a total of 66 concrete drilled cores available
by the construction company, the structural engineer of the project for testing. The cores were extracted from different places and
considered the previous results acceptable and no further action structural elements as listed in Table 2. The mean of all the results
was decided. Fig. 9 summarizes all results available for the different was above 85% of the requires concrete strength, but seven
construction phases including concrete strength results and testing cores had a strength below 75% of the specified fc0 , as shown
dates. The lower limit indicated in Fig. 9 corresponds to 17.5 MPa, in Fig. 10. Additionally, four masonry prisms were taken from
which corresponds to f c0 − 3.5 MPa. partition walls to measure their engineering properties. Laboratory
tests reported mean values of compressive strength and elastic
modulus (both for gross area) of approximately 7 and 3.6 GPa,
Field Sampling and Testing
respectively.
During the field inspection after the collapse event, a total of 23
reinforcing bar samples of different diameters were recovered from
various structural elements. Tensile test results showed that all Computational Modeling
samples but one met the specified yield strength of 420 MPa;
however, the modulus of elasticity results always fell below the ex-
Model Description
pected value of 200 GPa, with an average value of approximately
182 GPa. A total of 81 concrete drilled cores were taken in the Linear analyses of the building were implemented using the
field. Some of the samples were not suitable for testing and were SAP2000 computer program. The model included documented
35
25
20
15
10
0
N15G3S1
N16H5N1
N08C3N3
N01X1S2
N06B1N1
N07B4N2
N07B4N2b
N08C3N3b
N09FA1N4
N11D5N6
N13C3N9
N14F5S2
N17F5N2
N17F5N2b
N18E3N3
N18E3N3b
N20H5N6
N21FA2N7
N22F5N8
N23FA2N10
N24H5N12
N26J5N2
N27K3N3
N28FA3N4B
N29I3N7
N29I3N7b
N31K3N9
N31K3N9b
N32I3N13
N34K5N15
N34K5N15b
N35L3S2
N36M3S1
N37L5N1b
N38L5N5
N39M3N6
N40FA4N7
N41FA4N10
N42L5N9
N43M3N12
N44L5N17
N45N5N9
N46F5N11
N46F5N11b
N47O3N12
N48O5N15
N49P5N17
N57FAT6a
N50DEN1
N51O3N18
N56VET6b
N58VET6a
N59CET6a
N60VET6a
N61PET6b
N61CET6a
Downloaded from ascelibrary.org by 190.93.159.100 on 07/20/18. Copyright ASCE. For personal use only; all rights reserved.
Nombre
f'c lab test f'c esperado
Specified f'c 0.75f'c
0.75 f'c
modifications of the structure during its construction, such as Table 3. Considered Material Properties
larger dimensions, larger thickness of some slabs, and supplemental
Strength Elastic modulus
slab thickness for floor leveling. The computer model shown
Material (MPa) (MPa)
in Fig. 11 has the following features: (1) columns are modeled us-
ing frame elements; (2) girders, slabs, and walls are modeled using Concrete (columns) 21.0 21,538
shell elements to account for the two-way load transmission, the Concrete (columns below the 35.0 27,805
first story of Stage 6)
variable thickness of the slab [Fig. 4(c)], and in-plane stiffness
Concrete (beams) 21.0 21,538
of the horizontal diaphragm; (3) all elements are located at the Steel reinforcement 420.0 2,00,000
precise axis location in order to guarantee the consideration of real Masonry walls (gross area) 7.0 3,600
eccentricities between beam and column axes; (4) the structural
contribution of masonry partitions is modeled by adding vertical
springs connecting beams from consecutive stories (this feature is nonstructural components. Live load corresponds to the actual live
only used on Model 4); (5) columns are assumed to be fixed at the load existing in the building at the time of the collapse; in average,
base; (6) geometric nonlinear effects are considered by a standard this load was estimated in 0.11 kN=m2 for Stage 6 and 0.35 kN=m2
P-delta formulation; and (7) analyses used cracked sections with for the other stages. This difference was attributable to the occu-
the effective stiffness ratios obtained from Section C.10.10.4.1 of pancy level of Stage 6, which at the time of the collapse was ap-
NSR-10 [or Section 6.6.3.1.1 of ACI 318-14 (ACI 1998)]. proximately 30% (16 out of 53 apartments were occupied). The
Material properties used in the analyses are given in Table 3. combination of 1.0 × actual dead load þ 1.0 × existing live load
These properties were confirmed with laboratory tests, as explained is subsequently referred to as the real load at the time of the col-
in the “Field Investigation” section. Dead loads included columns, lapse. In order to include in the simulations the sequence of events
walls, slabs, beams, partitions, and flooring. These weights were described in the “Construction Deficiencies” section, the following
carefully calculated using actual dimensions of the structural and models were prepared:
(3.6 GPa) obtained from the lab tests described in the “Field in Fig. 13, the axial load demanded in Columns R3 and S3 is very
Sampling and Testing” section, Ag is the gross area of the parti- close or slightly exceeds the estimated capacity. From the results of
tions (0.28 m2 ), and h is the wall height (2.40 m). The calculated this model, it is clear that the projected columns did not meet mini-
axial stiffness is 420 MN=m. Based on the laboratory results, mum safety factors provided by NSR-10 (or ACI 318-14).
the vertical strength of the walls is approximately 1,000 kN. Fig. 13 shows the nominal axial load-bending moment interac-
The following subsections present the results for each one of the tion diagram (using ϕ ¼ 1.00 and fc0 ¼ 21 MPa for columns above
aforementioned models. The axis nomenclature mentioned in the Level 2, or fc0 ¼ 35 MPa for columns below Level 2) for Columns
text and figures is presented in the typical plan view of Fig. 2. R3 and S3, highlighting their demands from Model 1 with solid
circles. The minimum specified strength was used in this figure
to have a unique capacity surface. It is evident that many demands
Results of Model 1
are out of the diagram (over the compression failure zone), confirm-
As explained previously, this model would represent the ideal ing that the columns are inadequate to sustain the loads of this
conditions for the end of construction situation without any defi- model. Demand-capacity shear ratios for the columns are very
ciencies (no differential settlements or any other problem). In low; therefore, the axial load/shear force interaction was not con-
Fig. 12, solid lines indicate the heightwise variation of axial load sidered relevant for this paper.
on the critical columns of Stage 6 (highlighted in Fig. 2) attribut- As commonly reported in the literature (Iravani and MacGregor
able to real dead plus live load (as explained before in the 1998), in elements subjected to sustained high axial loads, creep
“Model Description” section); the dashed lines and gray contours causes an increase in the axial compressive strain resulting in
-15000
-5000
5000
0 1000 2000 3000 4000 0 1000 2000 3000 4000
(a) (b)
Downloaded from ascelibrary.org by 190.93.159.100 on 07/20/18. Copyright ASCE. For personal use only; all rights reserved.
-20000
-15000
Axial Load (kN)
-10000
-5000
5000
0 1000 2000 3000 4000 0 1000 2000 3000 4000
(c) Bending moment (kN·m) (d) Bending moment (kN·m)
Fig. 13. Axial load-bending moment interaction diagram for critical columns: (a) Column R-3 above Level 2; (b) Column S-3 above Level 2;
(c) Column R-3 below Level 2; (d) Column S-3 below Level 2
long-term deformations. This deformations are proportional to the significant reduction of the axial load in Column R3 (which had
acting stress for columns subjected to axial stresses below 0.40f c0 ; presented signs of distress 2 months before the end of construction)
however, if the axial stress is larger than 0.70fc0 , creep deformations and a major increment of the axial loads on Column S3 (which had
become nonlinear and may lead to premature cracking and failure presented compression failure on October 11, 2013, just 1 day
of the component (Richart 1933; Rüsch 1960; ACI 1992). Fig. 14 before the collapse of Stage 6) and Column R5.
shows in three different gray intensities areas of axial loads corre-
sponding to stresses from zero to 0.40f c0 , from 0.40f c0 to 0.70fc0 , Results of Model 3
and larger than 0.70fc0 . The solid line indicates the axial loads of the
most critical columns of Stage 6. Columns R3 and S3 (highlighted Model 3 represents the new stress distribution once the compressive
in Fig. 2) in the lower stories present axial stresses larger than failure of Column S3 at the fourth level occurred. Fig. 16 presents
0.70f c0 , implying that in the short term, creep effects may induce the new axial load distribution in critical columns in Axes 3 and 5
(according to Fig. 2), respectively. The compressive failure of
a fragile failure of the critical columns of the building. The structure
Column S3 generated a load redistribution instantaneously to
was at risk of collapse even if the foundation had not suffered any
columns in Axes R5 and S5, indicating that Column R5 could
differential settlements.
have been the next in the collapse sequence. The sequential failure
of Column R5 and others main elements would have led to the
Results of Model 2 complete collapse of the building sometime after the compressive
failure of Column S3.
The objective of this model is to estimate the stress distribution in
the main structural elements after the occurrence of the differential
settlements reported on October 11, 2013, just before the compres- Results of Model 4
sive failure of Column S3. Fig. 15 presents the heightwise variation The analysis of the available information and the testimonies of the
of axial load on the critical columns of Stage 6 compared with their occupants of the building suggest that the masonry partitions
respective capacities. These results confirm that the differential set- played an important role in the structural stability after the com-
tlements generated an internal redistribution of loads that led to a pressive failure of Column S3. The construction details on the other
Fig. 14. Axial loads and creep effects in critical columns of Stage 6; gray intensities represents the axial loads corresponding to stresses from zero to
0.40fc0 , from 0.40fc0 to 0.70f c0 , and larger than 0.70f c0 ; solid line indicates the axial loads
Fig. 15. Axial loads in critical columns of Stage 6 considering differential settlements
Fig. 16. Axial loads in critical columns of Stage 6 after failure of Column S3
hand, clearly indicate that some of the partitions were connecting with the construction drawings, and the few material tests that did
uninterrupted several floor slabs along the height of the building; not satisfied the specified requirements were hardly relevant factors
this detail was included in Model 4, as explained in the “Model for the collapse. Therefore, the causes of the collapse are probably
Description” section. Fig. 17 represents the probable axial load se- mostly related to the design, construction, and early behavior of the
quence in critical partition walls (those located near Column R3). building and its foundation.
Steps 1–3 correspond to the equivalent analysis presented with As described before, the results of computer Model 1 demon-
Models 1–3, but using the new stiffness distribution of Model 4. strated that Columns R3 and S3 of Stage 6 did not have enough
The analysis of the evolution of events reported in the building gen- capacity to withstand the real vertical loads. This fact and the
erated successive increases in axial loads on critical masonry parti- excessive vertical deflections of the slabs indicate that there were
tions up to the point of reaching the axial load capacity estimated for major design flaws that should have contributed to the progressive
such elements (on the order of 1,000 kN each, presented in dashed failure of the building. During construction, the overload caused by
lines in the figure). Walls located on the fourth and sixth levels for the mortar leveling of slabs and settlement of Pile R3 caused the
Axis 5, were probably subjected at axial loads greater than their local failure at fifth story of the corresponding column. Just at
capacities, just after the compressive failure of Column S3. The the end of construction, the total real vertical load did not reach the
model was also used to analyze the evolution in the critical shear capacity of the columns. Then, differential settlements (R3–S3)
forces in critical beams connecting Columns R3 and S3 with the rest increased the vertical load on Column S3 and caused its compres-
of the building (Fig. 18). The analysis shows that after the series of sive failure on October 11. According to the computer simulation
events reported in the building, it is highly probable the occurrence (Model 3), the failure of Column S3 generated a redistribution of
of shear failure in several of the critical beams connecting Columns loads, leading to a critical condition for Columns R5 and S5, the
R3 and S3. The unfactored shear capacity of such beams was esti- masonry partitions, and some critical beams as well. The building
mated on the order of 80–100 kN (shown in gray in the figure) collapse was temporary prevented by the action of the masonry par-
whereas the estimated demands, instants before the collapse of titions. Once the demand exceeded the capacity of the partition
the building, are in some cases higher than 100 kN. walls, failure of Columns R5 and S5 should have been the follow-
ing event in the progressive failure of the building. At this stage,
no redistribution of forces was possible and, therefore, the sudden
Causes of Collapse complete collapse of Stage 6 was just a matter of time.
Based on the information gathered in this paper as well
In addition to the field investigation and computational modeling, as the forensic analyses performed, the main cause of the collapse
the occurrences of external events that may have affected the sta- was the lack of structural capacity of the columns (cross-section
bility of the building were investigated. It was determined that area, reinforcement ratios, and details) to withstand gravity loads.
events such as local soil instability, wind overloads, earthquakes, It was determined that the axial load capacity provided by
internal explosions, etc., did not occur in the hours or days before columns of the Stage 6 of the Space Building was approximately
the collapse. In addition, there were no geometrical inconsistencies 40% of the load capacity specified by NSR-10 or ACI 318-14.
Level 7
750 750 750
500 500 500
250 250 250
0 0 0
-250 -250 -250
1 2 3 1 2 3 1 2 3
Steps Steps Steps
1500 1500 1500
R axis R axis R axis
1250 S axis 1250 S axis 1250 S axis
Fig. 17. Axial loads in masonry walls for Stages 1–3, with walls in R and S axes
Fig. 18. Shear forces in longitudinal beams located next to Columns R3 and S3
Additionally, the following deficiencies during the construction (5) compression failure of partition walls because of the overload
process may have boosted the initiation of the progressive failure: by slabs deflections and the failure of the surrounding columns.
(1) high differential settlements measured during the construction
period and high redistribution of internal loads and eccentricities
generated by these differential settlements; (2) high compressive Conclusions
stresses in main columns, which produced long-term compressive
creep and ultimately a compressive fragile failure; (3) repair works As a result of the field investigation, analysis of information, and
that were conducted after the failure of Column S3; (4) shear failure interpretation of computational models results, the authors con-
of beams attributable to the overload by slabs deflections and cluded that the main cause of the collapse was the deficient struc-
redistribution of load because previous column failures; and tural capacities of the main columns of the building. In particular,