M-PACT New

Air Circuit Breaker 400-4000A


GE
GE is a diversified organization covering a myriad of market segments, including infrastructure, finance and media.
From energy, water, transportation and health to access to money and information, GE serves customers in more than
100 countries and employs more than 300,000 people worldwide.

The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light Company in 1878.
In 1892, a merger of Edison General Electric Company and Thomson-Houston Electric Company created the General
Electric Company. GE is the only company listed in the Dow Jones Industrial Index today that was also included in the
original index in 1896.

Industrial Solutions
GE Industrial Solutions, a division of GE Energy Management, is a global leading provider in power distribution, offering a
wide range of products which include medium and low voltage power distribution equipment and components, and
motor & control systems that are safe, reliable and offer high performance. Its innovative solutions can improve energy
efficiency and environmental impact in power plants, power grids, oil & gas, mining, data center, overseas EPC,
industrial manufacturing, rail transportation, commercial buildings, residential houses, renewable energy and many
other industries.

GE is one of the worldwide partners of the Olympic Games. In 2008, GE assisted


Beijing with this tremendous event, which was unprecedented in scale and
first-class in its use of science and technology, offering a series of innovative
solutions and products for around 400 Olympic infrastructure projects, covering
fields in electricity distribution, lighting, security, water processing, benefiting
some 37 Olympic venues and 168 commercial buildings. GE also brought its
experiences to the 2010 Expo in Shanghai, Asia Games in Guangzhou,
Vancouver Olympic Games and continued through to the London 2012 Olympic
Games.

2010 World's Most Innovative Companies

2011 World’s Most Admired Companies

2009 World’s Most Respected Companies

2011 Best Global Brand

2008 World’s Most Respected Companies 2007 World’s Best R&D Companies
M-PACT
Air Circuit Breaker
400-4000A
Technical overview
Air circuit breakers 400A-4000A

Technical overview A
A.4 Fixed Circuit Breaker
A.6 Withdrawable Circuit Breaker
A.7 Characteristics
A.9 State of the Art Electronic Trip Units
A.11
A.19
Time Current Curves
M-PACT Accessories
Order codes B

Wiring diagrams
Dimensional drawings C

A.2
B
A

C
Technical overview

A.3
M-PACT
Notes
Fixed Circuit Breaker
Rated from 400 to 4000A the M-PACT circuit
Specification
A
breaker has been designed to meet the most
stringent demands in fault detection and safe M-PACT air circuit breakers comply with the following
interruption thereof. specifications for Low Voltage Switchgear:
• IEC 60947-1
Available in 2 frame sizes: • IEC 60947-2
- frame size 1 ranging from 400 to 2500A • IEC 60947-3
- frame size 2 ranging from 800 to 4000A • Utilisation category B B
The range has been developed to be aesthetically
and technically co-ordinated with other protective
devices within the GE Power Controls industrial
product ranges. Approvals
The breaker range has a common height and depth and KEMA certification in accordance with IEC 60947-2
is available in both fixed pattern and drawout versions CCC certification in accordance with GB14048-2
CCS certification in accordance with China Certification of shipping
C
which can be manually or electrically operated.
Designed to offer multiple mains connection options it
also comes with a wide range of easy-to-install
accessories.

3 performance ranges*
A -50 kA (Icu)
D -65 kA (Icu)
H1, H2 -80 kA (Icu)
*Ratings shown at 415V AC
2 compact frame sizes
Frame size 1 - 400 to 2500A
Frame size 2 - 800 to 4000A
Fixed pattern and withdrawable versions
3 or 4 pole configuration
Front and rear access connections (horizontal/vertical)
Devices provided with or without protection relay
Manual or electrical operation
Common height and depth dimensions
Built-in safety features e.g. safety shutters
Wide range of protection settings offering full selectivity
Combinations of earth fault protection A D H1,H2
Easy-to-install accessories, common to entire range
Simple and efficient servicing on site

A.4
M-PACT

Fixed circuit breaker Power Supply


All M-PACT fixed pattern air circuit breakers incorporate a stored All stated short circuit ratings are certified with incoming
energy mechanism. The spring can be charged either manually supply connection made to either upper or lower terminals.
or electrically via a motor operator that is automatically
activated after the closing operation.
IP43 front panel and door escutcheon seals are standard
features with IP20 protected secondary isolating contacts. For
enhanced protection, an optional
Technical overview

3 4 5 6
IP54 door panel is also available.

7
8
9
A 10

11

B 1
12

• Trip-free operating mechanism


• Positive 'ON/OFF' contact indication 1. Motorised spring charging unit (optional)
• Mechanical/electrical anti-pumping device 2. M-PRO Protection Relay (optional)
• Charging spring status indication (optional) 3. Secondary contacts
C •

Ergonomic manual spring charging handle
Field-mountable range of accessories
4. Shunt trip (optional)
5. Closing coil (optional)
• Auxiliary switches 5 NO and 3 NC, 10A 250V (standard) 6. Undervoltage release (optional)
• Mechanical Trip Alarm switch (1NO) (optional) 7. Manual charging handle
• Padlockable push-button cover 8. ON/OFF push-buttons
• Mechanical cable interlocking (optional) 9. Push-button padlockable covers
• Termination: rear, horizontal or front access (optional) 10. Positive contact indication
• Electrical clearances according to IEC60947-2 11. Charging spring status indication
• Front access of secondary terminals for simple connection 12. Mounting plate

Installation
Fixed pattern M-PACT can be fastened into any suitable
switchboard or cubicle arrangement using four M8 bolts.
Clearance is only required above the unit for the removal and
inspection of the arc chutes (see dimensional drawings for
mounting details and recommended clearance distances).
An earthing point is provided on either side of the circuit breaker.

A.5
Withdrawable circuit breaker Power Supply

Withdrawable circuit breaker


Pre-mounted into a self-contained 'cassette', this versatile All stated short circuit ratings are certified with incoming
circuit breaker can be inserted or withdrawn via sliding rails supply connection made to either upper or lower terminals.
using a racking drive mechanism controlled by a racking
handle. 4
It provides three set positions:
Disconnected / Test / Connected.
Any attempt to withdraw the unit whilst in service will
automatically trip the breaker, either by the racking position
safety mechanism or by the insertion of the racking handle. It
can be racked to the dis-connected position with the cubicle
door closed or open.

11
A

B
• Insulated, earthed steel shutters to isolate the main 3
contact zone
• Front access padlocking for safety shutters
• Secure padlocking in the "Disconnect" position
• Clearly visible operational position indication 2
• Carriage position switch (optional)
• Termination: Flat copper palms (standard) with captive M10 C
fixing nuts
• 'T' terminal adaptors for horizontal/vertical connection 1
(optional)
• Front access connections (optional) 10
• Automatic disconnect of secondary circuits
• Lifting lugs for ease of removing the circuit breaker from
the cassette 9
8 7 6
• Front access of secondary terminals for simple connection
• Cassette side mounting fixing parts (optional)

1. Carriage position switch (optional)


2. Extension rail
Installation 3. Earthed steel safety shutter
Circuit breakers are delivered pre-mounted in the 4. Secondary terminals
cassette (standard) 5. 2 way cable interlock mechanism (optional)
Versatile fixing arrangements allow mounting onto any 6. Racking handle (storage)
switchboard or cubicle using four M8 bolts (see dimensional 7. Padlocking for safety shutters
drawings for mounting details and recommended clearance 8. Insertion hole for racking handle
distances) 9. Padlocking in the DISCONNECTED position
Earthing point situated on the right hand side of cassette 10. Operational position indication
(front view) 11. Key interlock (optional)

A.6
M-PACT

Characteristics
Performance Data
Characteristic Symbol Units
Rated current (40℃) 400 800 1000 1250
Endurance (number of operating cycles)
Mechanical (with maintenance) 20000 20000 20000 20000
Mechanical (without maintenance) 10000 10000 10000 10000
Electrical (at rated current) 5000 5000 5000 5000
Technical overview

Rated service voltage (50/60 Hz) Ue V 690 690 690 690


Rated insulation voltage (50/60 Hz) Ui V 1000 1000 1000 1000
Rated impulse withstand voltage Uimp V 8000 8000 8000 8000

Number of poles 3&4 3&4 3&4 3&4


Rating of 4th pole 100% 100% 100% 100%
ACB type A D A D H1 H2 A D H1 H2 A D H1 H2
Frame size 1 1 1 1 2 2 1 1 2 2 1 1 2 2

Rated ultimate short-circuit Icu kA (rms) 220V 50 65 50 65 80 80 50 65 80 80 50 65 80 80


breaking capacity 415V 50 65 50 65 80 80 50 65 80 80 50 65 80 80
500V 50 65 50 65 65 80 50 65 65 80 50 65 65 80
600V 50 50 50 50 50 65 50 50 50 65 50 50 50 65
690V 40 40 40 40 40 60 40 40 40 60 40 40 40 60

Rated service short-circuit Ics kA (rms) 220V 50 65 50 65 80 80 50 65 80 80 50 65 80 80


breaking capacity 415V 50 65 50 65 80 80 50 65 80 80 50 65 80 80
500V 50 65 50 65 65 80 50 65 65 80 50 65 65 80

A 600V
690V
50
40
50
40
50
40
50
40
50
40
65
60
50
40
50
40
50
40
65
60
50
40
50
40
50
40
65
60

Rated short time withstand current


1 second Icw 415/690VAc kA (rms) 50 65/50 50 65/50 65 80 50 65/50 65 80 50 65/50 65 80
3 seconds Icw kA (rms) 40 50 40 50 50 50 40 50 50 50 40 50 50 50
Rated short-circuit making capacity Icm kA (peak) 415V 105 143 105 143 176 176 105 143 176 176 105 143 176 176
500V 105 143 105 143 143 176 105 143 143 176 105 143 143 176
600V 105 105 105 105 105 143 105 105 105 143 105 105 105 143
B Power dissipation at In (Fixed breaker) Watts
690V 84
15
84
10
84
63
84
43
84
23
105
20
84
106
84
68
84
36
105
32
84
175
84
105
84
60
105
53
Power dissipation at In (Withdrawable) Watts 30 21 127 86 49 43 211 135 77 68 351 211 128 113

Design and specifications are subject to changes without notice.

Selectivity Temperature Deratings


C
The following table shows the conditions to satisfy full Free Air(1)
selectivity between UP-STREAM and DOWN-STREAM devices. The M-PACT ACBs may operate at higher ambient
Up-stream: M-PACT temperatures than 40oC in certain installation conditions. In
Down-stream: M-PACT this case the current rating in Amperes should be reduced as
S T d e l a y 5 0 m s m i n i m u m b e t we e n u p - s t re a m a n d indicated below.
downstream ACB Multiplication coefficient between LT-
ratings≥1,56
Amblent Current Rating (A)
Temperature 800 1000 1250 1600 2000 2500 3200 4000
Down-stream 50℃ 800 1000 1250 1600 2000 2450 3200 3727
60℃ 800 1000 1250 1445 2000 2232 3200 3367
- 400 800 1000 1250 1600 2000 2500 3200 4000
65℃ 800 1000 1250 1364 2000 2092 3019 3175
400 - - - - - - - - -
70℃ 800 1000 1250 1280 1970 1970 2831 2978
800 Full - - - - - - - -
1000 Full - - - - - - - -
1250 Full Full - - - - - - -
Up-stream

The figures specified apply to withdrawable ACB's with flat face vertical
1600 Full Full Full - - - - - - copper connections
2000 Full Full Full Full - - - - - (1) Protection degree IP00.For use in enclosures with interior temperatures
2500 Full Full Full Full Full Full - - - of 40℃ to 70℃ the relevant IP values can be applied.
3200 Full Full Full Full Full Full - - -
4000 Full Full Full Full Full 2000 Full - -

A.7
1600 2000 2500 3200 4000

20000 20000 20000 20000 20000


10000 10000 10000 10000 10000
5000 5000 5000 5000 5000
690 690 690 690 690
1000 1000 1000 1000 1000
8000 8000 8000 8000 8000

Characteristics
3&4 3&4 3&4 3&4 3&4
100% 100% 100% 100% 100%
A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2
1 1 2 2 1 1 2 2 1 1 2 2 2 2 2 2 2 2 2 2

50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80
50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80
50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80
50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65
40 40 40 60 40 40 40 60 40 40 40 60 40 40 40 60 40 40 40 60

50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80
50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80
50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80
50
40
50
40
50
40
50
60
50
40
50
40
50
40
65
60
50
40
50
40
50
40
65
60
50
40
50
40
50
40
65
60
50
40
50
40
50
40
65
60 A

50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80
40 50 50 50 40 50 50 50 40 50 50 50 40 50 50 50 40 50 50 50
105 143 176 176 105 143 176 176 105 143 176 176 105 143 176 176 105 143 176 176
105 143 143 176 105 143 143 176 105 143 143 176 105 143 143 176 105 143 143 176
105 105 105 143 105 105 105 143 105 105 105 143 105 105 105 143 105 105 105 143
84
284
84
196
84
98
105
86
84
224
84
224
84
163
105
143
84
351
84
351
84
255
105
223
84
418
84
418
84
418
105
366
84
571
84
571
84
571
105
571
B
574 392 209 184 490 490 347 306 765 765 542 478 888 888 888 783 1224 1224 1224 1224

Catalog NO.Configuration Recommended Minimum Copper Size


In accordance with IEC 60947-2 C
MP A 3 1 F 16 04-400A, 08-800A Rating (A) Copper / phase
10-1000A, 12-1250A 400 2 x 50 x 5
Ratings: 16-1600A, 20-2000A 800 2 x 50 x 5
25-2500A, 32-3200A
40-4000A 1000 2 x 60 x 5
1250 2 x 100 x 5
Installation: F-fixed W-withdrawable 1600 2 x 100 x 5
Type: 1-Frame1 2-Frame2 2000 3 x 100 x 5
Pole: 3-3P 2500 4 x 100 x 5
4-4P* 3200 4 x 100 x 10
Breaking Capacity: A, D, H1, H2 4000 4 x 100 x 10 + 1 x 100 x 5

M-PACT

Dimensions in mm Weights (kg)


Frame Rating (1) (2) A range D range H range
Poles Type Height Width Depth
Size (A) Fixed pattern ACB Frame 3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
1 400 to 2500 3 Withdrawable 440 329 422 400 to 1600A 1 39 49 39 49 / /
Fixed 430 342 352 2000 to 2500A 1 43 54 43 54 / /
4 Withdrawable 440 429 422
800 to 3200A 2 53 68 53 68 53 68
Fixed 430 442 352
2 800 to 4000 3 Withdrawable 440 419 424 4000A 2 53 68 53 68 53 68
Fixed 430 432 352
4 Withdrawable 440 549 424 Withdrawable ACB Frame 3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
Fixed 430 562 352 400 to 1600A 1 68 79 68 79 / /
2000 to 2500A 1 74 85 74 85 / /
(1) Height is from mounting surface to highest part of the ACB. 800 to 3200A 2 90 109 90 109 90 109
(2) Depth is from the cubicle door to the back of terminals. 4000A 2 113 128 113 128 113 128
* For a 4P unit with a neutral, please specify on the selection form if it is required
on the LHS or RHS (viewed from the front), the default value is netural on the right.
* Letter 'L' & 'R' only for type selection, not shown on nameplate.
A.8
M-PACT

State of the Art Electronic Trip Units


• A line offering a new range of electronic trip units designed to extend and/or upgrade the
functionality offered by the existing M-PACT Plus air circuit breaker.
• Two types are available. The simple and effective MPRO-27 and the MPRO-50 offering extended
functionality .
Technical overview

• Each has a LCD screen with ammeter and a menu driven setting interface, allowing a simple and
accurate setting of all parameters.
• This global line of electronic trip units uses the most recent technology to offer each user an
unique combination of selectivity speed and functionality.

Plug'n Play MPRO-27 & MPRO-50


Electronic trip units are normally supplied The basic MPRO-27 type has been designed to replace the existing MPRO-
factory fitted. However spares are available 17 and MPRO-18 plus units offering an extended functionality and a
that can be simply plugged into breakers standard ammeter.
installed in the field.
A
The MPRO-50 type replaces the existing MPRO-30 and MPRO-40 designs
Each trip unit then needs to be adjusted to covering an extended functionality with protection devices as fuse links,
the required settings. If the installation is not overload protection and reduced instantaneous (RELT). Each MPRO-50
powered up the installed battery pack or the comes with a simple to connect 4 wire modbus communciation option.
seperately available test kit with Power Pack
B can be used as alternate power source.
Main Adjustment Options

• LT-LTD protection
Each device has an overload setting range of 0.4 to 1 times In and
offer a choice of 22 time bands designed for use with circuit breakers.
C A second set of 22 time bands shaped to match the time current
curves of fuses is available on the MPRO-50 type.

• ST-STD protection
A timed delayed short circuit protection are installed with a current
setting of 2 to 12 times the set LT current value. The short circuit
protection time can be set, at one of 17 bands ranging from 90
milliseconds to 1 second.
Optionaly this device can be set to one of three I2t curves.

• I-protection
A switchable and selective instantaneous protection with a setting
range of 2 to 15 times the breaker rating that is programmed to wait
one half cycle until the downstream device has reacted.

• Other protection features


A host of other protection devices are available including: Ground
Fault sum and Ground Fault source return (allowing UEF, SEF & REF)
and a reduced instantaneous device. The reduced instanataneous
device allows the user to conditionally programme the breaker to trip
faster and at lower short circuit settings than it would on the standard
instantaneuos device.
This RELT device allows the user to reduce the short circuit current
level and its time span, thus reducing the amount of electrical energy
A.9 in the direct vicinity of the breaker.
State of the Art Electronic Trip Units
Trip Unit MPRO-27 MPRO-50
Setting Interface
LCD screen allowing access to 4 distinct menu's X X
Touch pad adjustments X X
Multilingual X X
Adjustable manual or automatic RESET option X X
Long Time or Overload Current Protection
13 current settings Ir 1, 0.95, 0.9. 0,85, 0.8, 0.75, 0.7, 0.65, 0.6, 0.55, 0.5, 0.45 & 0.4 x breaker rating In X X
22 thermal protection (C type) time bands available ranging from class 0.5 to 40 (bands at 7.2 x Ir) X X
22 I2t protection (F type {fuse} ) time bands available - X
Neutral protection 0-50%-63%-100% X X
Possibility to switch OFF - X
Cooling function and thermal memory X X
Short Time Short-Circuit Current Protection
Setting range from 1.5 to 12 x Ir (LT setting) X X
Steps of 0.5 (a total of 22 settings) X X
Possibility to switch OFF - X
17 time delay settings (STDB) ranging from 30 to 940 milliseconds delay setting result in
X X
a 90 to 1000 milliseconds
Clearance times to IEC 40979-1 and IEC 60364
3 I2t Protection time bands available
Instantaneous Short-Circuit Current
• Standard
Ii setting range from 2 to 15 x breaker rating In X X
Steps of 0.5 (a total of 28 settings) X X
Possibility to switch OFF X X
Selective execution X X
Fixed instantaneous or HSIOC protection X X A
• Reduced
Ii setting range from 1.5 to 15 x Ie (primary setting) - X
Steps of 0.5 (a total of 29 settings) - X
Possibility to switch OFF - X
Remote and local ON and OFF with position indication signal - X
Ground or Earth Fault Protection
Setting range from 0.1 to 1 x In (breaker rating) (1) •(1) •(1) B
Steps of 0.01 (a total of 92 settings) • •
Possibility to switch OFF • •
14 time delay settings (GFDB) ranging from 50 to 840 milliseconds delay setting resulting in a 110 to
• •
900 milliseconds
Clearance times to IEC 40979-1 and IEC 60364 • •
3 I2t protection time bands available • •
1 I4t protection time bands available
Residual principle (UEF application possible)




C
Source ground return principle - •
UEF, REF and SEF applications possible - •
Combinations of UEF, REF and SEF applications possible - •
Other Functions
Current measurement (L1, L2, L3, N) X X
Trip target (trip reason indication) X X
Trip info (magnitude / phase) X X
Trip counter X X
Event logger (trip events) X X
General inputs (4 availble) - X
General relay outputs (4 available) - X
Relay based on current level (load shedding) - X
Good & bad health indicator - X
Watchdog - X
Communication 2 way - X
Modbus - X
24V DC auxiliary power supply X X
Test kit with power support function • •

(1) A 24V auxiliary power supply is required.


Key
X = Present
• = Optional
- = Not possible

A.10
M-PACT

Time Current Curves


Example of Full Time Current Curve
Time Current Curve
The MPRO Electronic trip unit has many sophisticated setting features and an extremely broad
setting range. On request we can provide complete Time Current Curves covering all installed
protection devices.

The curves can be produced for any current setting within the range of the installed protection
Technical overview

devices, for one or for a combination of two breakers.


Please contact your local GE Sales Office for more information.

MPRO Electr onic Trip Unit

10000
Time Current Curve
2h Breaker In= 2500A
----------------------------------
LT - Protection device
Set at Ie= 2400A
Ir at 0,9 =2160A
Band C-10
1000
ST - Protection device
A LT Band Set at 6x Ir of 2160A
Ist=12960A
Band STDB 10

I - Protection device
Set at 12 x Ie of 2400A
Ii = 28800A
100
GF - Protection device
Set at 0,6 x Ie of 2500A
B (Ig = 1500A)
Band GFDB 6
I²t ON & OFF

10
GF Band

C
1 ST Band

0,1 I Band
Tripping Time in Seconds (s)

0,01
HSIOC Band

Green & Light Blue Line = Full Clearing time


Red Line & Dark Blue Line = Non Tripping time
0,001
1000 10000 100000

x Current in Amps (Strom in Ampere) 7,2 x

A.11
Time Current Curves (cold state)
LT Protection Device
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10000 10000
2h
LT set at Breaker Rating In - Time Current Curve 2h
LT set at Breaker Rating In - Time Current Curve
Setting Range Setting Range
LT-Protection Device LT-Protection Device

Time Current Curves


Ie= 0.975, 0.9625, 0.95, 0.45 or 0.4 x In Ie= 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
Ir= 0.4 - 1 x Ie in steps of 0.25 - Band C-06 Ir= 0.4 - 1 x Ie in steps of 0.25 - Band C-02
Total Setting Range 0,2 - 1 x In Total Setting Range 0,2 - 1 x In
- Band C-11 - Band C-07
- Band C-16 - Band C-12
- Band C-22 - Band C-17
1000 1000

100 100

ST protection - OFF ST protection - OFF


10 I protection set to 15 x Ie(1) 10 I protection set to 15 x Ie(1)

A
Tripping Time In Seconds (s)
Tripping Time In Seconds (s)

1 1

0,1
1,00 10,00 100,00
0,1
1,00 10,00 100,00
B
x Breaker Rating In 7,2x x Breaker Rating In 7,2x

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10000 10000
2h
LT set at Breaker Rating In - Time Current Curve 2h LT set at Breaker Rating In - Time Current Curve
Setting Range Setting Range
Ie= 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
LT-Protection Device LT-Protection Device
Ie= 0.975, 0.9625, 0.95, 0.45 or 0.4 x In

C
Ir= 0.4 - 1 x Ie in steps of 0.25 - Band C-03 Ir= 0.4 - 1 x Ie in steps of 0.25 - Band C-04
Total Setting Range 0,2 - 1 x In
- Band C-08 Total Setting Range 0,2 - 1 x In
- Band C-09
- Band C-13 - Band C-14
- Band C-19 - Band C-20
1000 1000

100 100

ST protection - OFF ST protection - OFF


10 I protection set to 15 x Ie(1) 10 I protection set to 15 x Ie(1)
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

1 1

0,1 0,1
1,00 10,00 100,00 1,00 10,00 100,00
x Breaker Rating In 7,2x x Breaker Rating In 7,2x
A.12
M-PACT

Time Current Curves (cold state)


LT & STDB Protection Device
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10000 10000
2h LT set at Breaker Rating In - Time Current Curve 2h LT set at Breaker Rating In - Time Current Curve
Setting Range Setting Range
Ie= 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
LT-Protection Device Ie= 0.975, 0.9625, 0.95, 0.45 or 0.4 x In LT-Protection Device
Ir= 0.4 - 1 x Ie in steps of 0.25 - Band C-05 Ir= 0.4 - 1 x Ie in steps of 0.25 - Band C-01
Technical overview

Total Setting Range 0,2 - 1 x In Total Setting Range 0,2 - 1 x In


- Band C-10 - Band C-18
- Band C-15
- Band C-21
1000 1000

100 100

ST protection - OFF ST protection - OFF


10 I protection set to 15 x Ie(1) 10 I protection set to 15 x Ie(1)

A
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

1 1

B 0,1
1,00 10,00 100,00
0,1
1,00 10,00 100,00
x Breaker Rating In 7,2x x Breaker Rating In 7,2x

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve - 10 - Time Current Curve
ST-Protection Device ST-Protection Device
I 2t - OFF- I 2t - OFF-

C ST set on breaker rating In


- Band STDB 01
- Band STDB 03 ST set on breaker rating In
- Band STDB 02
- Band STDB 04
Setting Range Setting Range
1,5 to 12 x Ir in steps of 0,5
- Band STDB 05 1,5 to 12 x Ir in steps of 0,5
- Band STDB 06
- Band STDB 07 - Band STDB 08
- Band STDB 09 - Band STDB 19
17
17 - Band STDB 11 - Band STDB 12
1 1 16
15
15 - Band STDB 13 16 - Band STDB 14
0,8 0,8 14
13 - Band STDB 15 14 - Band STDB 16
0,6 13 0,6
- Band STDB 17 12
11 12
0,4 11 0,4 10
9
10 8
9 7
8
0,2 7 0,2 6
5

6 4
5 3
0,1 2
1 0,1

4
3
2
1 Green Line = Full Clearing Time Green Line = Full Clearing Time
Red Line = Non Tripping Time Red Line = Non Tripping Time

0,01
Tripping Time In Seconds (s)

0,01
Tripping Time In Seconds (s)

I protection set to 15 x Ie(1) I protection set to 15 x Ie(1)

0,001 0,001
1,00 10,00 100,00 1,00 10,00 100,00
x Breaker Rating In x Breaker Rating In
A.13
Time Current Curves (cold state)
ST Protection Device
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve 10 - Time Current Curve
ST- Protection Device ST- Protection Device

Time Current Curves


I 2t ON “Iow” I 2t ON “Iow”
- Band STDB 01 - Band STDB 02
ST set at Breaker Rating In - Band STDB 03 ST set at Breaker Rating In - Band STDB 04
Setting Range Setting Range
1,5 to 12 × Ir in steps of 0,5 - Band STDB 05 1,5 to 12 × Ir in steps of 0,5 - Band STDB 06
- Band STDB 07 - Band STDB 08
- Band STDB 09 - Band STDB 10
17 - Band STDB 11 - Band STDB 12
1 17 16
15
15 - Band STDB 13 16 - Band STDB 14
0,8 0,8 14
13 - Band STDB 15 14 - Band STDB 16
0,6 13 0,6
- Band STDB 17 12
11 12
0,4 11 0,4 10
9
9 7 10 8
8
0,2 7 0,2 6
5
6
5 3 4
0,1 1 0,1 2

4
3
2
1 Green Iine = Full Clearing time Green Iine = Full Clearing time
Red Line = Non Tripping time Red Line = Non Tripping time

A
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

00,1 00,1

I protection set to 15×Ie (1) I protection set to 15×Ie (1)

0,01
1,00 10,00 100,00
0,01
1,00 10,00 100,00
B
x Breaker rating In x Breaker rating In

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve 10 - Time Current Curve
ST set at Breaker Rating In ST set at Breaker Rating In
ST- Protection Device ST- Protection Device
Setting Range Setting Range
1,5 to 12 × Ir in steps of 0,5 1,5 to 12 × Ir in steps of 0,5
I 2t ON “med” I 2t ON “med”
-
-
Band STDB 01
Band STDB 03
-
-
Band STDB 02
Band STDB 04
C
- Band STDB 05 - Band STDB 06
- Band STDB 07 - Band STDB 08
- Band STDB 09 - Band STDB 10
17 - Band STDB 11 - Band STDB 12
1 17 1 16
15 - Band STDB 13 16 - Band STDB 14
0,8 15 0,8 14
13 - Band STDB 15 14 - Band STDB 16
0,6 13 0,6
- Band STDB 17 12
11 12
0,4 11
0,4 10
9
10 8
9 7
8
0,2 7 0,2 6
5
6
5 3 4
0,1 1 0,1 2

4
3

1 2
Green Iine = Full Clearing time Green Iine = Full Clearing time
Red Line = Non Tripping time Red Line = Non Tripping time
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

00,1 00,1

I protection set to 15×Ie (1) I protection set to 15×Ie (1)

0,01 0,01
1,00 10,00 100,00 1,00 10,00 100,00

x Breaker rating In x Breaker rating In


A.14
M-PACT

Time Current Curves (cold state)


ST, I and Hi Protection Device
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve 10 - Time Current Curve
ST set at Breaker Rating In ST- Protection Device ST set at Breaker Rating In ST- Protection Device
Setting Range Setting Range
1,5 to 12 × Ir in steps of 0,5 I 2t ON “max” 1,5 to 12 × Ir in steps of 0,5 I 2t ON “max”
- Band STDB 01 - Band STDB 02
Technical overview

- Band STDB 03 - Band STDB 04


- Band STDB 05 - Band STDB 06
- Band STDB 07 - Band STDB 08
- Band STDB 09 - Band STDB 10
17 - Band STDB 11 - Band STDB 12
1 17 16 16
15
15 - Band STDB 13 - Band STDB 14
0,8 0,8 14
13 - Band STDB 15 14 - Band STDB 16
0,6 13 0,6
- Band STDB 17 12
11 12
0,4 0,4 10
11
9
10 8
9 7
8
0,2 7 0,2 6
5
6 4 2 4 2
5 3 1 3 1
0,1 0,1

Green Iine = Full Clearing time Green Iine = Full Clearing time
Red Line = Non Tripping time Red Line = Non Tripping time

A
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

0,01 0,01

I protection set to 15×Ie (1) I protection set to 15×Ie (1)

B 0,01
1,00 10,00 100,00
0,01
1,00 10,00 100,00

x Breaker rating In x Breaker rating In

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
1 1
- Time Current Curve - Time Current Curve
I set on breaker rating In I - Protection Device I set on breaker rating In HI - Protection Device
HI Setting Range RELT - Protection Device HI Setting Range RELT - Protection Device

C
2 to 15 × Ie in steps of 0,5 2 to 15 × Ie in steps of 0,5

HSIOC device HSIOC device


0,1 0,1

Green Iine = Full Clearing time Green Iine = Full Clearing time
Red Line = Non Tripping time Red Line = Non Tripping time

0,01 0,01
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

I set on breaker rating In I set on breaker rating In


RELT Setting Range RELT Setting Range
1,5 to 15 × Ie in steps of 0,5 1,5 to 15 × Ie in steps of 0,5

0,001 0,001
1,00 10,00 100,00 1,00 10,00 100,00

x Breaker rating In x Breaker rating In


A.15
Time Current Curves (cold state)
HSIOC & GF Protection Device
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
1 1
- Time Current Curve - Time Current Curve
HSIOC - Protection Device HSIOC - Protection Device

Time Current Curves


I Setting On I - Present & ON I - PRESENT OFF
sei at 15kA ST Ser at 12,5kA
STDB 1

100kA
85kA
65kA
0,1 0,1 50kA

Green Iine = Full Clearing time


Red Line = Non Tripping time

Green Iine = Full Clearing time


Red Line = Non Tripping time

0,01 0,01

A
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

50 kA
65 kA

85 kA

100 kA

0,01
1000 10000 100000 10000,00
0,01
1000 10000 100000 10000,00
B
Amps Amps

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve 10 - Time Current Curve
GF- Protection Device GF- Protection Device
I 2t -OFF- I 2t -OFF-
-
-
Band GFDB
Band GFDB
01
03
-
-
Band GFDB
Band GFDB
02
04
C
- Band GFDB 05 - Band GFDB 06
- Band GFDB 07 - Band GFDB 08
GF set on breaker rating In - Band GFDB 09 GF set on breaker rating In - Band GFDB 10
Setting Range Setting Range
0,1 to 1 × In in steps of 0,01 - Band GFDB 11 0,1 to 1 × In in steps of 0,01 - Band GFDB 12
- Band GFDB 13 - Band GFDB 14

14 14
13
0,8 13 0,8
12
11 12
0,6 0,6
11
10
9 10
0,4 0,4
9 8
7
8 6
7 5
6
0,2 0,2 4
5
3

4
2
3 1
0,1 0,1
Green Iine = Full Clearing time
Red Line = Non Tripping time
2
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

Green Iine = Full Clearing time


Red Line = Non Tripping time

0,01 0,01
0,10 1,00 10,00 0,10 1,00 10,00

x Breaker rating In x Breaker rating In


A.16
M-PACT

Time Current Curves (cold state)


GF Protection Device
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve 10 - Time Current Curve
GF set on breaker rating In GF- Protection Device GF set on breaker rating In GF- Protection Device
Setting Range Setting Range
0,1 to 1 × In in steps of 0,01 I 2t “low” -ON- 0,1 to 1 × In in steps of 0,01 I 2t “low” -ON-
- Band GFDB 01 - Band GFDB 02
Technical overview

- Band GFDB 03 - Band GFDB 04


- Band GFDB 05 - Band GFDB 06
- Band GFDB 07 - Band GFDB 08
- Band GFDB 09 - Band GFDB 10
- Band GFDB 11 - Band GFDB 12
- Band GFDB 13 - Band GFDB 14

1 14
13 14
0,8 13 0,8 12
11 12
0,6 11 0,6
10
9 10
0,4 0,4
9 8
7
8 6
7 5
6
0,2 5 0,2 4
3

4 2
3 1
0,1 0,1
Green Iine = Full Clearing time

A
Green Iine = Full Clearing time Red Line = Non Tripping time
Red Line = Non Tripping time 2
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

B 0,01
0,10 1,00 10,00
0,01
0,10 1,00 10,00

x Breaker rating In x Breaker rating In

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve 10 - Time Current Curve
GF set on breaker rating In GF- Protection Device GF set on breaker rating Inv GF- Protection Device
Setting Range Setting Range
I 2t “med” -ON-
C
0,1 to 1 × In in steps of 0,01 0,1 to 1 × In in steps of 0,01 I 2t “med” -ON-
- Band GFDB 01 - Band GFDB 02
- Band GFDB 03 - Band GFDB 04
- Band GFDB 05 - Band GFDB 06
- Band GFDB 07 - Band GFDB 08
- Band GFDB 09 - Band GFDB 10
- Band GFDB 11 - Band GFDB 12
- Band GFDB 13 - Band GFDB 14

1 1 14
13 14
0,8 13 0,8 12
11 12
0,6 11 0,6
10
9 10
0,4 0,4
9 8
7
8 6
7 5
6
0,2 0,2 4
5
3

4 2
3 1
0,1 0,1
Green Iine = Full Clearing time
Green Iine = Full Clearing time Red Line = Non Tripping time
Red Line = Non Tripping time 2
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

0,01 0,01
0,10 1,00 10,00 0,10 1,00 10,00

x Breaker rating In x Breaker rating In


A.17
Time Current Curves (cold state)
GF Protection Device
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 GF set on breaker rating In - Time Current Curve GF set on breaker rating In - Time Current Curve
Setting Range GF- Protection Device Setting Range GF- Protection Device
0,1 to 1 × In in steps of 0,01 0,1 to 1 × In in steps of 0,01

Time Current Curves


I 2t “max” -ON- I 2t “max” -ON-
- Band GFDB 01 - Band GFDB 02
- Band GFDB 03 - Band GFDB 04
- Band GFDB 05 - Band GFDB 06
- Band GFDB 07 - Band GFDB 08
- Band GFDB 09 - Band GFDB 10
- Band GFDB 11 - Band GFDB 12
- Band GFDB 13 - Band GFDB 14

1 1 14
13 14
0,8 13 0,8 12
11 12
0,6 11 0,6
10
9 10
0,4 0,4
9 8
7
8 6
7 5
6
4
0,2 5 0,2
3

4 2
3 1
0,1 0,1
Green Iine = Full Clearing time

A
Green Iine = Full Clearing time Red Line = Non Tripping time
Red Line = Non Tripping time 2
Tripping Time In Seconds (s)

Tripping Time In Seconds (s)

0,01
0,10 1,00 10,00
0,01
0,10 1,00 10,00
B
x Breaker rating In x Breaker rating In

A.18
M-PACT

M-PACT Accessories Shunt trip


A wide range of optional accessories have been developed that
are compatible with all M-PACT air circuit breakers, regardless
of nominal rating or frame size. Each one incorporates 'easy-fit'
design features for quick installation, either in the factory or by
the user on site.
Technical overview

Motorised spring charging unit

Energisation, locally or remote, will instantaneously activate the


circuit breaker mechanism, ensuring rapid disconnection of the
main contacts.
In addition, a series connected auxiliary switch ensures
automatic isolation whenever the circuit breaker is open.
Shunt trip releases also have a wide operational voltage range,
and they include the same easy-fit, clip-on/plug-in connectors as
the closing coil above.

The unique motor/gearbox unit is specially designed to operate


with the full range of M-PACT breakers.
It is easily fitted with just two bolts. In the event of circuit breaker
A closure, this unit will automatically recharge the spring in Undervoltage release
readiness for instant reclosure should the need arise.
High speed recharging ensures that the springs are fully charged
within approximately three seconds following a release.
As an optional feature, a "springs charged" contact is available
for the motor unit.

B
Circuit breaker closing coil

Instantaneously releases the circuit breaker trip mechanism


should the supply voltage dip below the pre-set value.
Simple to install, these devices have the same easy-fit features
as previously described.
Note: This is a 'no-volt/ no-close device. The circuit breaker
cannot be closed (manually or electrically) unless the
undervoltage release coil is energised.
Time delay undervoltage release Similar to the above, but this
electronic device prevents nuisance tripping of the circuit breaker
if circuit interruption is not desirable when supply voltage drop is
only transient. Fixed time delay 3 sec ±1sec.
The closing coil is an easy-to-fit, clip-on unit, with simple plug-
in connectors. This permits either local or remote release of the
spring charged closing mechanism by electrical operation.
An additional anti-pumping safety feature also ensures that the
electrical closing signal must be released before further closure is Auxiliary trip combination
attempted, and a cut-off is instigat-ed should a closing signal be
maintained. The M-PACT circuit breaker can be equipped with the following
Because each coil operates within a wide voltage range, the auxiliary trips or releases 1 x Shunt trip + 1 x Closing coil + 1 x
number of individually rated coils required is drastically reduced. Undervoltage release or 1 time delay Undervoltage release

A.19
Auxiliary switches Cassette main terminal adaptors
The M-PACT circuit breaker is equipped with 5 NO and 3 NC
auxiliary switches as standard. Maximum number of contacts is 8,
for alternative configurations please contact for availability.

Mechanical operation counter

M-PACT Accessories
Combinations of rear and front access connections possible for
Easily fitted, this useful accessory may be specified for use with entire range. Tested and approved from 50 to 80kA.
either manual or motor charged M-PACT circuit breakers.
It is clearly visible through the front panel, and the counter
provides an accurate record of the cumulative number of A
complete breaker closing operations.

Key interlock facility


B

To simplify main busbar or cable termination, M-Pact provides a


full range for rear and/or front access connection.
Bolt-on adaptor kits can be fitted easily to suit either horizontal
or vertical connections.

Ready-to-fit interlocking device: Ronis, for installation between


separate circuit breakers, available in kit form.
This valuable safeguard ensures that a circuit breaker cannot be
closed unless the dedicated key has been inserted and secured
within the lock.

Lock and key types

Ronis: Type 1104B lock with standard key, 1/4" turn rotation to
trap the key, compulsory spindle size.

A.20
M-PACT

Carriage position switch 2/3 way cable mechanical


interlocks
Technical overview

Available as an optional device for mounting within the base


of the cassette, this switch provides six single pole changeover
contacts for local or remote electrical indication of the circuit
Available for fixed and withdrawable circuit breakers. These units
A breaker status: Connected, Test and Disconnected.
The Disconnected position is indicated only when minimum
enable the direct interlocking of M-PACT circuit breakers, either
mounted side-by- side or stacked. The interlocking mechanisms
isolating distances between contacts on both the main and
are connected by a specially designed cable in '1 from 3' OR
auxiliary circuits have been achieved.
'2 from 3' configuration, and any mix of current ratings / pole
This option is in addition to the mechanical indicators which are
configurations can be accommodated.
fitted as standard.
Standard cable lengths available: 1.6, 2.0, 3.0 metres. (Please
When installed, the carriage switch is IP2X protected and includes
contact our technical customer service department if longer
wiring to a terminal block located on the left-hand side of the
B cassette.
lengths are required.)

Note: The carriage position switch is optional and is suitable


for withdrawable circuit breakers only.

C Cluster contacts

These are the main isolating contacts which are fitted to the rear
terminals on the moving portion of the withdrawable unit.
As part of standard inspection and maintenance procedures,
cluster contacts have been designed to be easily and quickly
removed and replaced using universal cluster pliers.

A.21
Interlocks
Mechanical interlocks can be fitted to the following electrical systems and can link 2 or 3 circuit breakers of any
rating or number of poles, Fixed or Withdrawable.

Typical circuit Interlock configuration Possible combinations

M-PACT Accessories
Type A
Interlocking between 2 circuit breakers
B1 B2
B1 normal power supply
B2 generator (emergency) supply 0 0
I 0
0 I

Circuit breaker B1 can only close if B2 is open


Circuit breaker B2 can only close if B1 is open

Type B
Interlocking between 3 circuit breakers

3 power supplies (generator or


B1 B2 B3
transformers) feeding the same
busbar but parallel operation is prevented. 0 0 0

Available upon request.


I
0
0
I
0
0
A
0 0 I

Only 1 from 3 breakers can be closed

Type C
Interlocking between 3 circuit breakers B
2 bus sections can be powered by a B1 B2 B3
single transformer (bus coupler 0 0 0
closed) or by both transformers I 0 0
(bus coupler open). 0 I 0
0 0 I
Available upon request.
I 0 I

C
0 I I
I I 0
Any 2 from 3 circuit breakers can be closed
Any 1 from 3 circuit breakers can be closed

A.22
M-PACT

Circuit breaker insertion interlock Circuit breaker handling truck


Specifically designed for use with the M-PACT range, this
dedicated handling truck is a useful accessory when faced
with the task of inserting or removing the circuit breaker from
its panel, or when transporting the unit should it be outside its
cassette. Installers will also find it particularly valuable for top-
tier mounted circuit breakers.
Technical overview

By incorporating this optional security interlock device into a


system, it prevents the inadvertent insertion of an incorrectly
rated withdrawable circuit breaker into a cassette.

Cassette interlock
A

Available for withdrawable circuit breaker s only, this


sophisticated interlock system secures the circuit breaker in the
C disconnected position by means of a Ronis key.
When the key is removed, the safety shutters are automatically
locked in position, thus preventing access to the contacts and
also ensuring that the racking mechanism is not operable. For
lock and key details refer to key interlock facility section (p. A.21)

Sealed
door panel
escutcheon
An optional IP54 complete front door
panel is available should a higher
degree of protection be necessary.

A.23
Plug-in Portable Test Unit (PTU) Auxiliary Power Unit (APU)

M-PACT Accessories
Specially designed for reliable testing of the MCR and HSISC
protection systems on each phase, by means of tertiary
injection. Can be powered by 2 x 9 V batteries or main power
lead. Available to be fitted within the circuit breaker cubicle, an
APU ensures that M-PRO receives independent and
continuous
power at all times. The APU accepts any input supply
voltage within 380VAC, 110V, 220V AC/DC. Maximum
input current is 0.5 A. 1m length cable (twisted pair) should
be used to connect auxiliary supply and MPRO protection
relay. A

Accessories Performance Data B


Operating Voltage (V) Rating
Device AC DC Operating range (Amps resistive)
250 - 10
Auxiliary & carriage switch 125 - 5
250 - 0.25
220-250 220-250

Motor operator
110-130
380-440
110-130
48, 60 0.85 to 1.1 times
AC-50VA
DC-50W C
24-30 rated voltage
220-250 220-250
110-130 110-130 AC-300VA
Closing coil
380-440 48 0.85 to 1.1 times DC-250W
24-30 rated voltage
220-250 220-250
110-130 110-130 AC-300VA
Shunt trip
380-440 48 0.70 to 1.1 times DC-250W
24-30 rated voltage
380-440 110-130 -
Instantanious Undervoltage Inrush power consumption 300VA
220-250 48 -
release Holding power consumption 20VA
110-130 24-30 -
Auxiliary power unit 110, 220, 380 110, 220 - -

A.24
Order codes
M-PACT

A Technical overview

B Order codes
B.2 Specify on the order
B.3 Breaker ordering code
B.5 M-PACT Air Circuit Breaker - Type A - 50kA
B.7 M-PACT Air Circuit Breaker - Type D - 65kA
B.9 M-PACT Air Circuit Breaker - Type H1,H2 - 80kA
B.11 Factory Mounted Trip Units
C B.12 Spare Trip Units

Wiring diagrams
Dimensional drawings

B.1
1. Customer Name 2. Project Name 3. Quanitity
Specify on the Order

Code MP □ □ □ □ □ □ -□ □ □ □ □ □ □ □ Voltage (Ue) □ 415V □ 690V

1. Device □ TypeA 50kA □ TypeD 65kA □ TypeH1 80kA □ TypeH2 80kA

2. Rating □ 400A □ 630A □ 800A □ 1000A □ 1250A □ 1600A

Specify on the Order


□ 2000A □ 2500A □ 3200A □ 4000A

3. Number of Poles □ 3 Pole □ 4Pole Left Neutral □ 4Pole Right Neutral * Viewed from front of breaker.

4. System □ 3 phase 3 wire □ 3 phase 4 wire

5. Frequency □ 50Hz □ 60Hz

6. Type Connections Top&Bottom

□ Fix □ Front □ Horizontal □ Vertical

□ Withdrawable □ Front □ Horizontal □ Vertical

□ Moving portion only

□ Cassette only □ Front □ Horizontal □ Vertical

7. Protection □ Non automatic □ MPRO 27 □ MPRO 27 WITH GF □ MPRO 50L □ MPRO 50H
□ Mechanical Operation Counter □ Mechanical Trip Alarm Switch (1NO) A
8. Optional Features □ Portable Test Unit Auxillary Power Unit □ 110V AC/DC □ 220V AC/DC
Auxillary Contactor □ 5NC+3NC □ 4NC+4NC
9. Control Voltage MOP CC ST UV UVTD

24/30V DC □ □ □

48V DC □ □ □ □ □
B
60V DC □

110/130V DC □ □ □ □

110/130V AC □ □ □ □

220/250V DC □ □ □

220/250V AC □ □ □ □ □ C
380/440V AC □ □ □ □ □

Charging contact signal is default with charging motor

10. Carriage switch □ Factory fitted □ Loose kit

11. Interlocks Door interlock □ left Door interlock (Hinge in left) □ Right door interlock(Hinge in right)

□ Ronis Cassette Key interlock

□ Ronis Breaker Key interlock □ Lock A □ Lock B □ Lock C □ Lock D

□ Circuit breaker misinsertion interlock

Cable Interlock □ Type A 2 way □ Type B 1 from 3 way

□ Type C 2 from 3 way

Cable Length required (in centimeters)

□ 160 □ 200 □ 300

12. Miscellaneous □ IP54 Door panel □ ACB Lifting Truck

13. Special requirements (please Specify any improtant instructions)

B.2
M-PACT
Breaker ordering code

M P A 3 1 F 0 8
Order codes

Poles
3 3 poles
Rating
4 4 poles
08 800A
Frame 10 1000A
1 Frame 1
12 1250A
A 2 Frame 2
Type 16 1600A
Breaking Capacity

A 50kA F Fixed 20 2000A

D 65kA W Withdrawable 25 2500A

H 80kA M Cassette 32 3200A


B C Moving Part 40 4000A
H2 80kA

others Acc
C 000 standard without any option
002 Earth Fault Protection(UEF)
006 Neutral protection
015 Ronis Key breaker Interlock (factory fitted)
016 Mechanical Trip alarm Switch (1n/o)
049 Carriage switch
025 UEF+Mechanical Trip alarm Switch (1n/o)+Ronis Key breaker Interlock (factory fitted)
028 Mechanical Trip alarm Switch (1n/o) + Carriage switch +UEF
029 Ronis Key breaker Interlock (factory fitted)+UEF
047 UEF+Mechanical Trip alarm Switch (1n/o)+Mechanical operations counter
104 UEF+Mechanical Trip alarm Switch (1n/o)+Carriage switch
107 UEF+Mechanical Trip alarm Switch (1n/o)
111 Mechanical Trip alarm Switch (1n/o)+Ronis Key breaker Interlock

For more option codes please ref to sheet "optional" or contact our local office.

B.3
N 4 4 4 0 X X X

Breaker ordering code


others Acc

MPro Shunt

0 Non-Auto 0 No
N Mpro 27 1 24/30V DC
V Mpro50L 2 48V DC
W Mpro50H 3 110/130V DC/AC A
4 220/250V DC/AC
Motor Operator 5 380/400V AC
0 No
1 24/30V DC
Undervoltage B
2 48V DC 0 No

3 110/130V DC/AC 1 48V DC

4 220/250V DC/AC 2 110/130V AC


3 220/250V AC C
4 380/440V AC
Closing coil
5 30/48V DC - delay
0 No
6 220/250V AC - delay
1 24/30V DC
7 380/440V AC - delay
2 48V DC
3 110/130V DC/AC
4 220/250V DC/AC
Note: The following parts are supplied default with
the breaker
1. Auxiliary power supply of 24V DC
2. IP30 Door flange
3. Connection bars are default with drawout breaker.
4. Auxilary contacts 5NC + 3NO
5. The 4th RC sensor with 3P breaker & GF option
6. Saftey shutter

B.4
M-PACT

M-PACT Air Circuit Breaker - TYPE A - 50kA


Basic circuit breaker manually operated, 5 NO and 3 NC auxiliary switches.
Withdrawable pattern - basic circuit breaker and cassette with flat copper terminals
rear connected.
Fixed pattern - basic circuit breaker with rear terminals horizontal.

Withdrawable and Fixed Pattern


Withdrawable Fixed Pattern
Frame size Rating (A) Poles Cat. no. Cat. no.
1 400 3 MPA31W04 MPA31F04
4 MPA41W04 MPA41F04
Order codes

1 800 3 MPA31W08 MPA31F08


4 MPA41W08 MPA41F08
1 1000 3 MPA31W10 MPA31F10
4 MPA41W10 MPA41F10
1 1250 3 MPA31W12 MPA31F12
4 MPA41W12 MPA41F12
1 1600 3 MPA31W16 MPA31F16
4 MPA41W16 MPA41F16
1 2000 3 MPA31W20 MPA31F20
4 MPA41W20 MPA41F20
1 2500 3 MPA31W25 MPA31F25
4 MPA41W25 MPA41F25
2 3200 3 MPA32W32 MPA32F32

A 2 4000
4
3
MPA42W32
MPA32W40
MPA42F32
MPA32F40
4 MPA42W40 MPA42F40

Installation: Units rated < 1600A have reduced copper section.


Refer to engineered drawings in section C.

Rear 'T' Connections (for cassette only)


B Pequired
Frame size Rating (A) Poles Quantity Cat. no. Cat. no.
1 400 to 1600 3 6 RT1HOR Horizontal
4 8 RT1HOR Horizontal
1 400 to 1600 3 6 RT1VER Vertical
4 8 RT1VER Vertical
1 2000 & 2500 3 6 RT1UNI Universal
4 8 RT1UNI Universal
C 2 3200 3
4
6
8
RT2UNI
RT2UNI
Universal
Universal
2 4000 3 Standard N/A Vertical
4 Standard N/A Vertical

Front Access Connections


Withdrawable
TOP connections BOTTOM connections
Frame size Rating (A) Poles Cat. no. Cat. no.
1 400 to 1600 3 FA31WA16T FA31WA16B
4 FA41WA16T FA41WA16B
1 2000 to 2500 3 FA31WA25T FA31WA25B
4 FA41WA25T FA41WA25B
2 3200 3 FA32WA32T FA32WA32B
4 FA42WA32T FA42WA32B
2 4000 3 FA32WA40T FA32WA40B
4 FA42WA40T FA42WA40B

B.5
Air Circuit Breaker - TYPE A - 50kA
Front Access Connections
Fixed Type
TOP connections BOTTOM connections
Frame size Rating (A) Poles Cat. no. Cat. no.
1 400 to 1600 3 FA31FA16T FA31FA16B
4 FA41FA16T FA41FA16B
1 2000 to 2500 3 FA31FA25T FA31FA25B
4 FA41FA25T FA41FA25B
2 3200 3 FA32FA32T FA32FA32B
4 FA42FA32T FA42FA32B
2 4000 3 FA32FA40T FA32FA40B
4 FA42FA40T FA42FA40B

Cassette only
Basic cassette with flat copper terminals rear connected.
Frame size Rating (A) Poles Cat. no.
1 400 to 1600 3 MPA31C16
4 MPA41C16
1 2000 to 2500 3 MPA31C25
4 MPA41C25
2 3200 3 MPA32C32

2 4000
4
3
MPA42C32
MPA32C40
A
4 MPA42C40

Moving Portion only B


Basic circuit breaker manually operated,
5 NO and 3 NC auxiliary switches and cluster contacts.
Frame size Rating (A) Poles Cat. no.
1 400 3 MPA31M04
4 MPA41M04
1 800 3 MPA31M08

1 1000
4
3
MPA41M08
MPA31M10
C
4 MPA41M10
1 1250 3 MPA31M12
4 MPA41M12
1 1600 3 MPA31M16
4 MPA41M16
1 2000 3 MPA31M20
4 MPA41M20
1 2500 3 MPA31M25
4 MPA41M25
2 3200 3 MPA32M32
4 MPA42M32
2 4000 3 MPA32M40
4 MPA42M40

B.6
M-PACT

M-PACT Air Circuit Breaker - TYPE D - 65kA


Basic circuit breaker manually operated, 5 NO and 3 NC auxiliary switches.
Withdrawable pattern - basic circuit breaker and cassette with flat copper terminals
rear connected.
Fixed pattern - basic circuit breaker with rear terminals horizontal.

Withdrawable and Fixed Pattern


Withdrawable Fixed Pattern
Frame size Rating (A) Poles Cat. no. Cat. no.
1 400 3 MPD31W04 MPD31F04
4 MPD41W04 MPD41F04
Order codes

1 800 3 MPD31W08 MPD31F08


4 MPD41W08 MPD41F08
1 1000 3 MPD31W10 MPD31F10
4 MPD41W10 MPD41F10
1 1250 3 MPD31W12 MPD31F12
4 MPD41W12 MPD41F12
1 1600 3 MPD31W16 MPD31F16
4 MPD41W16 MPD41F16
1 2000 3 MPD31W20 MPD31F20
4 MPD41W20 MPD41F20
1 2500 3 MPD31W25 MPD31F25
4 MPD41W25 MPD41F25
2 3200 3 MPD32W32 MPD32F32

A 2 4000
4
3
MPD42W32
MPD32W40
MPD42F32
MPD32F40
4 MPD42W40 MPD42F40

Rear 'T' Connections (for cassette only)


B Pequired
Frame size Rating (A) Poles Quantity Cat. no. Cat. no.
1 400 to 1600 3 6 RT1UOR Universal
4 8 RT1UOR Universal
2 3200 3 6 RT2UNI Universal
4 8 RT2UNI Universal
2 4000 3 Standard N/A Vertical
4 Standard N/A Vertical
C

Front Access Connections


Withdrawable
TOP connections BOTTOM connections
Frame size Rating (A) Poles Cat. no. Cat. no.
1 400 to 1600 3 FA31WA16T FA31WA16B
4 FA41WA16T FA41WA16B
1 2000 to 2500 3 FA31WA25T FA31WA25B
4 FA41WA25T FA41WA25B
2 3200 3 FA32WA32T FA32WA32B
4 FA42WA32T FA42WA32B
2 4000 3 FA32WA40T FA32WA40B
4 FA42WA40T FA42WA40B

B.7
Air Circuit Breaker - TYPE D - 65kA
Front Access Connections
Fixed Type
TOP connections BOTTOM connections
Frame size Rating (A) Poles Cat. no. Cat. no.
1 400 to 1600 3 FA31FD16T FA31FD16B
4 FA41FD16T FA41FD16B
1 2000 to 2500 3 FA31FD25T FA31FD25B
4 FA41FD25T FA41FD25B
2 3200 3 FA32FD32T FA32FD32B
4 FA42FD32T FA42FD32B
2 4000 3 FA32FD40T FA32FD40B
4 FA42FD40T FA42FD40B

Cassette only
Basic cassette with flat copper terminals rear connected.
Frame size Rating (A) Poles Cat. no.
1 400 to 1600 3 MPD31C25
4 MPD41C25
2 3200 3 MPD32C32
4 MPD42C32
2 4000 3 MPD32C40
4 MPD42C40
A

Moving Portion only


Basic circuit breaker manually operated,
B
5 NO and 3 NC auxiliary switches and cluster contacts.
Frame size Rating (A) Poles Cat. no.
1 400 3 MPD31M04
4 MPD41M04
1 800 3 MPD31M08
4 MPD41M08
1 1000 3
4
MPD31M10
MPD41M10 C
1 1250 3 MPD31M12
4 MPD41M12
1 1600 3 MPD31M16
4 MPD41M16
1 2000 3 MPD31M20
4 MPD41M20
1 2500 3 MPD31M25
4 MPD41M25
2 3200 3 MPD32M32
4 MPD42M32
2 4000 3 MPD32M40
4 MPD42M40

B.8
M-PACT

M-PACT Air Circuit Breaker - TYPE H1,H2 - 80kA


Basic circuit breaker manually operated, 5 NO and 3 NC auxiliary switches.
Withdrawable pattern - basic circuit breaker and cassette with flat copper terminals
rear connected.
Fixed pattern - basic circuit breaker with rear terminals horizontal.

Withdrawable and Fixed Pattern


Frame Withdrawable Fixed Pattern Withdrawable Fixed Pattern
Rating (A) Poles
size Cat. no. Cat. no. Cat. no. Cat. no.
2 800 3 MPH32W08 MPH32F08 MPH232W08 MPH232F08
4 MPH42W08 MPH42F08 MPH242W08 MPH242F08
Order codes

2 1000 3 MPH32W10 MPH32F10 MPH232W10 MPH232F10


4 MPH42W10 MPH42F10 MPH242W10 MPH242F10
2 1250 3 MPH42W12 MPH32F12 MPH232W12 MPH232F12
4 MPH42W12 MPH42F12 MPH242W12 MPH242F12
2 1600 3 MPH32W16 MPH32F16 MPH232W16 MPH232F16
4 MPH42W16 MPH42F16 MPH242W16 MPH242F16
2 2000 3 MPH32W20 MPH32F20 MPH232W20 MPH232F20
4 MPH42W20 MPH42F20 MPH242W20 MPH242F20
2 2500 3 MPH32W25 MPH32F25 MPH232W25 MPH232F25
4 MPH42W25 MPH42F25 MPH242W25 MPH242F25

A 2 3200 3
4
MPH32W32
MPH42W32
MPH32F32
MPH42F32
MPH232W32
MPH242W32
MPH232F32
MPH242F32
2 4000 3 MPH32W40 MPH32F40 MPH232W40 MPH232F40
4 MPH42W40 MPH42F40 MPH242W40 MPH242F40

Rear 'T' Connections (for cassette only)


Frame Required
B size
Rating (A) Poles
Quantity
Cat. no.

2 800 - 3200 3 6 RT2UNI


4 8 RT2UNI
2 4000 3 Standard N/A
4 Standard N/A

C Front Access Connections


Withdrawable
TOP connections BOTTOM connections
Frame size Rating (A) Poles Cat. no. Cat. no.
2 800 - 3200 3 FA42WH32T FA32WH32B
4 FA42WH32T FA42WH32B
2 4000 3 FA32WH40T FA42WH40B
4 FA42WH40T FA42WH40B

Front Access Connections


Fixed Type
TOP connections BOTTOM connections
Frame size Rating (A) Poles Cat. no. Cat. no.
2 800 - 3200 3 FA32FH32T FA32FH32B
4 FA42FH32T FA42FH32B
2 4000 3 FA32FH40T FA32FH40B
4 FA42FH40T FA42FH40B

B.9
Air Circuit Breaker - TYPE H1,H2 - 80kA
Cassette only
Basic cassette with flat copper terminals rear connected.

Frame size Rating (A) Poles Cat. no.


2 800 - 3200 3 MPH32C32
4 MPH42C32
2 4000 3 MPH32C40
4 MPH42C40

Moving Portion only


Basic circuit breaker manually operated,
5 NO and 3 NC auxiliary switches and cluster contacts.
Frame size Rating (A) Poles Cat. no. Cat. no.
2 800 3 MPH32M08 MPH232M08
4 MPH42M08 MPH242M08 A
2 1000 3 MPH32M10 MPH232M10
4 MPH42M10 MPH242M10
2 1250 3 MPH32M12 MPH232M12
4 MPH42M12 MPH242M12
2 1600 3 MPH32M16 MPH232M16
4 MPH42M16 MPH242M16
2 2000 3 MPH32M20 MPH232M20 B
4 MPH42M20 MPH242M20
2 2500 3 MPH32M25 MPH232M25
4 MPH42M25 MPH242M25
2 3200 3 MPH32M32 MPH232M32
4 MPH42M32 MPH242M32
2 4000 3 MPH32M40 MPH232M40
4 MPH42M40 MPH242M40 C

B.10
M-PACT

Factory Mounted Trip Units

MPRO-27
Basic functionality Functionality and application Cat. No.
MPRO-27 trip unit For Frame 1 GL100M3-SF

LT-C 0.4-1 x In = Ir For Frame 2 GL200M3-SF


LTDB
ST I2t ON or OFF
STDB
Order codes

Extended functionality
MPRO-27 trip unit For Frame 1 GL100M5-SF

LT-C 0.4-1 x In = Ir For Frame 2 GL200M5-SF


LTDB
ST I2t ON or OFF
STDB
GF sum. I2t ON or OFF
GFDB

A MPRO-50
MPRO-50L For Frame 1 GH100M7-6SF
LT band choice (LT-C or LT-F)
LT-C 0.4-1 x In = Ir Dual GF protection (Res./SUM or CT)
-ORLT- Relt Instantaneous &
Basic functionality
F 0.4-1 x In = Ir Modbus Communiction
ST
STD
B GF sum. I2t ON or OFF For Frame 2 GH200M7-6SF
-AND/ORGF LT band choice (LT-C or LT-F)
CR I2t ON or OFF Dual GF protection (Res./SUM or CT)
GFDB Relt Instantaneous &
I Modbus Communiction
RELT
Input supply 24V AC(1)

C MPRO-50H For Frame 1 GQ100M7-6SF


LT band choice (LT-C or LT-F)
LT-C 0.4-1 x In = Ir Dual GF protection (Res./SUM or CT)
Extended functionality
-ORLT- Relt Instantaneous &
F 0.4-1 x In = Ir Modbus Communiction
ST
STD
GF sum. I2t ON or OFF For Frame 2 GQ200M7-6SF
-AND/ORGF LT band choice (LT-C or LT-F)
CR I2t ON or OFF Dual GF protection (Res./SUM or CT)
GFDB Relt Instantaneous &
I Modbus Communiction
RELT
Input supply 110-130V DC
or 110-250V AC(1)

Accessories
Designation
Digital test kit GTUTK20

(1) relay output available voltage rate.MPRO50L= 24V AC,MPRO50H=110-250V AC


The MPRO27/50 trip units are not offered individually, they must be order with a complete breaker.
For spares and service purposes, please contact your local GE Energy Industrial Solutions service department you will be required to provide a valid serial number.
B.11
Spare Trip Units

Withdrawable and Fixed Pattern


Range Voltage Cat. no. Order Code
Shunt trip (ST) 24/30 V DC ST30 B40006554
48 V DC ST48 B40006555
110/130 V AC/DC ST130 B40006401
220/250 V AC/DC ST250 B40006500
380/440 V AC ST440 B40006497

Spare Trip Units


Motor operator (MOP) 24/30 V DC MOP30 B40029600
48 V DC MOP48 B40029601
110/130 V AC/DC MOP130 B40033630
220/250 V AC/DC MOP250 B40032398
380/440 V AC MOP440A B90000018
Closing coil (CC) 24/30 V DC CC30 B40006556
48 V DC CC48 B40006557
110/130 V AC/DC CC130 B40006402
220/250 V AC/DC CC250 B40006498
300/440 V AC CC440 B90000018
Undervoltage release (UV) 48 V DC UV48 B40027558
110/130 V AC UV130A B40027559
110/130 V DC UV130D B40027570
220/250 V AC UV250 B40033628

Undervoltage release time delayed (UVTD)


380/440 V
48 V
AC
DC
UV440
UVTD48
B40006578
B40027571 A
220/250 V AC UVTD250 B40006576
The UVTD already involved UV and time delay relay. 380/440 V AC UVTD440 B40006580
250 V AC/DC CSWFF B40011377
Spring charged signal (1 x N/O) SCC

Offered with spring charging motor

Mechanical Accessories
2 way Interlocking Type A 1 from 3 wayInterlocking Type B
Frame Type Poles Cable Frame Type Poles Cable
size Cat. no. Ref. no. size Cat. no. Ref. no.
1 Withdrawable 3 2WCI3PW 406342 1 Withdrawable 3 B13WCI3PW 406350 C
1 4 2WCI4PW 406343 1 4 B13WCI4PW 406351
2 3 2WCI3PW 405459 2 3 B13WCIF23PW 405475
2 4 2WCI4PW 405461 2 4 B13WCIF24PW 405477
1 Fixed 3 2WCI3PF 406340 1 Fixed 3 B13WCI3PF 406348
1 4 2WCI4PF 406341 1 4 B13WCI4PF 406349
2 3 2WCI3PF 405463 2 3 B13WCIF23PF 405479
2 4 2WCI4PF 405465 2 4 B13WCIF24PF 405481

2 from 3 way Interlocking Type C


Frame Type Poles Cable
size Cat. no. Ref. no.
1 Withdrawable 3 C23WCI3PW 406358
1 4 C23WCI4PW 406359
2 3 C23WCIF23PW 405491
2 4 C23WCIF24PW 405493
1 Fixed 3 C23WCI3PF 406356
1 4 C23WCI4PF 406357
2 3 C23WCIF23PF 405495
2 4 C23WCIF24PF 405497
Please refer to page A.23 for available cable configurations.

Cable for interlocks


Item Cat. no. Ref. no.
cable, 100cm 100BCMCI 405531
cable, 160cm 160BCMCI 405532
cable, 200cm 200BCMCI 405533
cable, 300cm 300BCMCI 405611

Longer length required , contact local GE Office please.


B.12
M-PACT

Interlocks Miscellaneous
Item Cat. no. Order Code Item Cat. no. Order Code
Mechanical Operations Counter MOC B40006511
left Door interlock (Hinge in left) DILHS B40006546
Ronis Key breaker Interlock⑴ RONLOK B40006515 Right door interlock(Hinge in right) DIRHS B40006504
Ronis Key Cassette Interlock(factory fitted) RONCASFF B40011378 Mis-Insertion Device ACBMID B40006503
IP54 Door IP54DOOR B40006507
Lifting Truck ACBLIFT B40006832
Mechanical Trip Alarm Switch MPROMAC B40006573

(1) There are 4 lock type available (A, B, C, D).


Please put A, B, C, D back on B40006515 when you order Ronis individually.
Order codes

Frame 1, 2
Spare parts
Neutral (4th) Rogowski coil
Current transformer with mounting kit(1)
with mounting kit(2)

Current transformer Rogowski coil(2)


Frame size Rating (A) Cat. No. Order Code Cat. No. Order Code

A 1
2
800 ELCT8001
ELCT8002
RCMK8001
RCMK8002
1 1000 ELCT10001 RCMK10001
2 ELCT10002 RCMK10002
1 1250 ELCT12501 RCMK12501
2 ELCT12502 RCMK12502
1 1600 ELCT16001 RCMK16001
2 ELCT16002 RCMK16002
1 2000 ELCT20001 RCMK20001
B 2 ELCT20002 RCMK20002
1 2500 ELCT25001 RCMK25001
2 ELCT25002 RCMK25002
2 3200 ELCT32002 RCMK32002
2 4000 ELCT40002 RCMK40002

(1) The earth CT leg is used for GF CT function which offered by MPOR50. But it is not default with MPOR50 as standard parts.
Please contact with GE local office,if you have any inquire.
C (2) Rogowski coils are provided with twisted pair cables of (max. length 2m).
The 4th Rogowski coil for GF protection comes default with 3 pole breakers. If you need a separate 4th Rogowski coil please
contact your local GE Energy Industrial Solutions office.

B.13
Air circuit breakers 400A-4000A

Technical overview A

Order codes B

Wiring Diagrams
Dimensional drawings C
C.2 Mpro 27 & 50 Connection Scheme
C.6 Dimensional drawings

C.1
M-PACT
Wiring Diagrams
Mpro 27 & 50 Connection Scheme

A9 A8 B5 B6
Dimensional drawings

N-RC N-RC 24V+ 24V-


- +
+24-
N VDC

Connection scheme
Wiring diagrams

Electronic Trip Unit


MPRO 27
B3 B4 A15 A14 A8 A7 A6 A5 A4 A3 A2 A1 B5 B6

Interposing CT

EL CT N-RC N-RC Relay O/P1 Relay O/P2 Relay O/P3 Relay O/P4 24V+ 24V-
- +
N
+24-
N VDC

Connection scheme

A
Communication
Input 1 - 4
Electronic Trip Unit
MPRO 50 C 1 2 3 4
SCR RX- RX+ TX- TX+

A13 A12 A11 A10 A9 A16 A20 A19 A18 A17

OFF
B OFF ON

C9

C11

C13

C15
B11

B13

B15
(+VE)
(+VE)

C1

C3

C5

C7
B9

B1
B7

C A A B B B A A A A A

C
AL ML

D
UVR
M ST CC UVTD
(-VE)

(-VE)

C10

C12

C14

C16
B12

B16
B10

B14
B2

C6

C8
C4
B8

C2
LP7

LP5

LP6
LP4

Breaker accessories

C.2
Dimensional drawings
Mounting hole - Fixed Type
Frame 1 - ¢ 9.2mm , Recommend bolt M8 x 4.
Frame 2 - ¢ 11.2mm , Recommend bolt M10 x 4.

Horizontal, rear access connection


Fixed pattern
Type A-3 pole- Frame size 1, In=400A to 1600A

Dimensional drawings
Minimum space to earth metal
and for arc chute removal
Centre line of operating panel
Insulated metal or insulated
sheet ( customer supplied )

Centre line of
operating panel
A

100 to door

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.
B

Type A-4 pole- Frame size 1, In=400A to 1600A

Minimum space to earth metal


and for arc chute removal
Centre line of operating panel
Insulated metal or insulated
sheet ( customer supplied )

Centre line of
operating panel

100 to door

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.3
M-PACT

Horizontal, rear access connection


Fixed pattern
Type D-3 pole- Frame size 1, In=400A to 1600A
Dimensional drawings
Wiring diagrams

Minimum space to earth metal


and for arc chute removal Insulated metal or insulated
sheet ( customer supplied )
Centre line of operating panel

Centre line of
operating panel

100 to door

B Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

Type D-4 pole- Frame size 1, In=400A to 1600A

Minimum space to earth metal


and for arc chute removal Insulated metal or insulated
Centre line of operating panel sheet ( customer supplied )

Centre line of
operating panel

100 to door

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.
C.4
Horizontal, rear access connection
Fixed pattern
Type A, D-3 pole- Frame size 1, In=2000A to 2500A

Dimensional drawings
Minimum space to earth metal
and for arc chute removal Insulated metal or insulated
Centre line of operating panel sheet ( customer supplied )

Centre line of
operating panel
A

100 to door

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.
B

Type A, D-4 pole- Frame size 1, In=2000A to 2500A

Minimum space to earth metal Insulated metal or insulated


and for arc chute removal sheet ( customer supplied )
Centre line of operating panel

Centre line of
operating panel

100 to door

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.5
M-PACT

Horizontal, rear access connection


Fixed pattern
Type A, D-3 pole- Frame size 2, In=3200A to 4000A
Type H-3 pole- Frame size 2, In=800A to 4000A
Dimensional drawings
Wiring diagrams

Minimum space to earth metal Insulated metal or insulated


and for arc chute removal sheet ( customer supplied )
Centre line of operating panel

Centre line of

A operating panel

100 to door

B Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

Type A, D-4 pole- Frame size 2, In=3200A to 4000A


Type H-4 pole- Frame size 2, In=800A to 4000A

Insulated metal or insulated


Minimum space to earth metal sheet ( customer supplied )
and for arc chute removal
Centre line of operating panel

Centre line of
operating panel

100 to door

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.
C.6
Rear access connection
Withdrawable pattern
Type A-3 pole- Frame size 1, In=400A to 1600A

Dimensional drawings
to door Minimum clearance
to cassette side

Ventilation

Centre line of
operating panel

Centre line of operating panel


35 Test
50 Disconnected
Connected A
275 Fully withdrawn

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

B
Type A-4 pole- Frame size 1, In=400A to 1600A

to door C

Minimum clearance
to cassette side

Ventilation

Centre line of
operating panel

35 Test Connected
Centre line of operating panel
50 Disconnected

275 Fully withdrawn

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.7
M-PACT

Rear access connection


Withdrawable pattern
Type A-3 pole- Frame size 1, In=2000A & 2500A
Type D-3 pole- Frame size 1, In=400A to 2500A
Dimensional drawings

to door Minimum clearance


to cassette side
Wiring diagrams

Ventilation

Centre line of
operating panel

Centre line of operating panel 35 Test Connected


50 Disconnected
A 275 Fully withdrawn

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

B
Type A-4 pole- Frame size 1, In=2000A & 2500A
Type D-4 pole- Frame size 1, In=400A to 2500A

C
to door
Minimum clearance
to cassette side
Ventilation

Centre line of
operating panel

Centre line of operating panel 35 Test Connected


50 Disconnected
275 Fully withdrawn

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.8
Rear access connection
Withdrawable pattern
Type A, D-3 pole- Frame size 2, In=3200A

Dimensional drawings
Type H-3 pole- Frame size 2, In=800A to 3200A

to door
Minimum clearance to cassette side

Ventilation
Center line of
operating panel

Center line of 35 Test Connected


operating panel 50 Disconnected
275 Fully withdrawn
A

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

B
Type A, D-4 pole- Frame size 2, In=3200A
Type H-4 pole- Frame size 2, In=800A to 3200A

to door
Minimum clearance to cassette side
C
Ventilation

Center line of
operating panel

Center line of 35 Test Connected


operating panel
50 Disconnected
275 Fully withdrawn

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.9
M-PACT

Rear access connection


Withdrawable pattern

Type A, D,H - 3 pole - Frame size 2, ln=4000A


Dimensional drawings

Must not be removed


or fitted horizontally
Wiring diagrams

Minimum clearance to cassette side

to door

Ventilation
Center line of
operating panel

Center line of
operating panel 35 Test Connected

A 50 Disconnected
275 Fully withdrawn

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

B
Type A, D,H - 4 pole - Frame size 2, ln=4000A

Must not be removed


or fitted horizontally
Minimum clearance to cassette side
C
to door

Ventilation

Center line of
operating panel

Center line of 35 Test Connected


operating panel 50 Disconnected
275 Fully withdrawn

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.10
Front access connection
Fixed pattern

Type A, D - 3 pole - Frame size 1, ln = 400A to 1600A

Dimensional drawings
Minimum space to earth metal
Minimum clearance and for arc chute removal
to breaker side Insulated metal
or insulated sheet
(customer supplied)

Center line of
operating panel

100 to door

Center line of
operating panel
A

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

B
Type A, D - 4 pole - Frame size 1, ln = 400A to 1600A

Minimum space to earth metal

Minimum clearance
and for arc chute removal
Insulated metal
C
to breaker side or insulated sheet
(customer supplied)

Center line of
operating panel

100 to door

Center line of
operating panel

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.11
M-PACT

Front access connection


Fixed pattern

Type A, D - 3 pole - Frame size 1, ln = 2000A to 2500A


Dimensional drawings

Minimum clearance Minimum space to earth metal


to breaker side and for arc chute removal
Wiring diagrams

Insulated metal
or insulated sheet
(customer supplied)

Center line of
operating panel

100 to door

A
Center line of
operating panel

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

B
Type A, D - 4 pole - Frame size 1, ln = 2000A to 2500A

Minimum space to earth metal


and for arc chute removal
C Minimum clearance Insulated metal
to breaker side or insulated sheet
(customer supplied)

Center line of
operating panel

100 to door

Center line of
operating panel

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.12
Front access connection
Fixed pattern

Type A, D - 3 pole - Frame size 2, ln = 3200A to 4000A

Front access connection


Type H - 3 pole - Frame size 2, ln = 800A to 4000A

Minimum space to earth metal


Minimum clearance
and for arc chute removal
to breaker side Insulated metal
or insulated sheet
(customer supplied)

Center line of
operating panel

100 to door

Center line of
operating panel
A

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

B
Type A, D - 4 pole - Frame size 2, ln = 3200A to 4000A
Type H - 4 pole - Frame size 2, ln = 800A to 4000A

Minimum clearance Minimum space to earth metal


C
to breaker side and for arc chute removal
Insulated metal
or insulated sheet
(customer supplied)

Center line of
operating panel

100 to door

Center line of
operating panel

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.13
M-PACT

Front access connection


Withdrawable pattern

Type A, D - 3 pole - Frame size 1, ln = 400A to 1600A


Dimensional drawings

Plqlpxp#fohdudqfh
wr#euhdnhu#vlgh

to door
Wiring diagrams

Fhqwhu#olqh#ri
rshudwlqj#sdqho

Connected
A Disconnected
Fhqwhu#olqh#ri Test
rshudwlqj#sdqho

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

B
Type A, D - 4 pole - Frame size 1, ln = 400A to 1600A

C Minimum clearance to cassette side


to door

Center line of
operating panel

Connected
Disconnected
Center line of Test
operating panel

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.14
Front access connection
Withdrawable pattern

Type A, D - 3 pole - Frame size 1, ln = 2000A to 2500A

Front access connection


Minimum clearance to cassette side

to door
Center line of
operating panel

Connected

Test
Disconnected A
Center line of
operating panel

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.
B
Type A, D - 4 pole - Frame size 1, ln = 2000A to 2500A

Minimum clearance to cassette side


C
to door

Center line of
operating panel

Connected
Disconnected
Center line of Test
operating panel

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.15
M-PACT

Front access connection


Fixed pattern

Type A, D - 3 pole - Frame size 2, ln = 3200A to 4000A


Type H - 3 pole - Frame size 2, ln = 800A to 4000A
Dimensional drawings

Minimum clearance to cassette side

to door
Wiring diagrams

Center line of
operating panel

Connected

Test Disconnected

Center line of
operating panel
A
Copperwork must be supported within 200 mm of breaker
connections-busbars or cables. All connections to be tightened to 50Nm.

B
Type A, D - 4 pole - Frame size 2, ln = 3200A to 4000A
Type H - 4 pole - Frame size 2, ln = 800A to 4000A

C Minimum clearance to cassette side


to door

Center line of
operating panel

Connected
Disconnected
Test
Center line of
operating panel

Copperwork must be supported within 200 mm of breaker


connections-busbars or cables. All connections to be tightened to 50Nm.

C.16
Adaptor connections

Rear Adapter Vertical Connection Rear Adapter Horizontal Connection

Front access connection


Type A - Frame 1 - ln = 400A to 1600A (max) Type A - Frame 1 - ln = 400A to 1600A (max)

B
Rear Adapter Vertical / Horizontal Connection

Type D - Frame 1 - ln = 400A to 2500A (max) Type A,D,H - Frame 2 - ln = 800A to3200A (max)

C.17
M-PACT

Copper connections - Front access (Fixed and/or withdrawable)

Type A - Frame 1 - ln = 400A to 2500A (max) Type A,D - Frame 2 - ln = 3200A to 4000A (max)
Type D - Frame 1 - ln = 400A to 2500A (max) Type H - Frame 2 - ln = 800A to 4000A (max)
Dimensional drawings
Wiring diagrams

B Copper connections - Rear access (withdrawable)

Type A,D,H - Frame 2 - ln = 4000A IP54 Door (Withdrawable unit only - Frame 1&2 only)

C.18
Cassette mounting details

Type A,D - Frame 1 - ln = 400A to 2500A (max)

Adaptor connections
Terminals

Ventilation in base of cassette


(leave unobstructed)
A
A

A Centre line of A
operating panel

3 pole 4 pole

3 pole 4 pole

3 pole 4 pole B

Type A,D - Frame 2 - ln = 3200A to 4000A (max)


Type H - Frame 2 - ln = 800A to 4000A (max)

Terminals
C

Ventilation in base of cassette


(leave unobstructed)
A A

Centre line of
A A
operating panel

3 pole 4 pole

3 pole 4 pole

A. recommend installtion mounting cut


C.19
M-PACT

Door cut-outs
Fixed pattern
Dimensional drawings
Wiring diagrams

Door

281
270.2 Door
19 131

5.4
16 off M3 x 6
self tapping screw
Escutcheon

M-PACT breaker Escutcheon


seal

28

378
178
358

ACB facia

ACB facia
centre line of ACB

A mounting hole

175
100
175 100

5.4
Frame 1 = 42.5 263
40 13 Frame 2 = 102.5

Withdrawable pattern

Door

16 off M3 x 6
self tapping screw
Escutcheon

M-PACT breaker Escutcheon


seal

ACB facia
benchmark of
breaker left side

benchmark of
Frame 1: Max.2500A=40
breaker button side
Frame 2: Max.4000A=100

C.20
2-Way cable interlocking

Fixed pattern - Front/rear access

Frame 1-3P = 322


Frame 1-4P = 422
Frame 2-3P = 410

900 Max vertical base to base


Frame 2-4P = 540

Door cut-outs
A

Min.bend radius 120 Min.bend radius 120

Withdrawable pattern - Front/rear access

C
Frame 1-3P = 329
Frame 1-4P = 429
Frame 2-3P = 419
Frame 2-4P = 549
900 Max vertical base to base

Min.
Min. clearance
clearance below
below cassette
cassette

Min.bend radius 120 Min.bend radius 120

C.21
M-PACT

3-Way cable interlocking

Fixed pattern - Front/rear access


Dimensional drawings

1250 MAX
F13P=322
55 F14P=422 55
Wiring diagrams

55
F23P=410
F24P=540

900 MAX. VERTICAL


BASE TO BASE
140 MIN
A these 2 cabel length must exceed 3M

Withdrawable pattern - Front/rear access


B 1250 MAX
F13P=329
F14P=429
55 55
F23P=419

900 Max vertical base to base


F24P=549

30
40 MIN. CLEARENCE
BELOW CASETTE

these 2 cabel length must exceed 3M

C.22
GE
Industrial Solutions

Greater China
Shanghai Taiwan
4F, Building 2, CTP, No.1 Hua Tuo Rd. 6F, No. 8, Min Sheng E. Rd., Sec. 3,
Zhang Jiang Hi-Tech Park Taipei 10480
Shanghai, China 201203 T : +886 2 2183 7000
T : +86 21 3877 7888 F : +886 2 2516 6829
F : +86 21 3877 7600

South East Asia


Malaysia Philippines Indonesia
Level 6, 1 Sentral, 8F Net Cube Building, 30th Street BRI II Tower, 27th floor
Jalan Travers, Kuala Lumpur Sentral Corner 3rd Avenue, Crescent West Park Jl. Jend. Sudirman No. 44-46
Kuala Lumpur, Malaysia 50470 Global City Taguig 1634 Jakarta 10210
T : +603 2273 9788 T : +63 2 877 7000 T: +62 21 573 0430
F : +603 2273 7988 F : +63 2 846 0629 F: +62 21 574 7089

Thailand Vietnam Singapore


25th floor, CRC Tower, All Seasons Place Saigon Centre, Unit 1, Floor 7 240 Tanjong Pagar Road
87/2 Wireless Road, Lumpini Le Loi Boulevard, District 1 #06-00 GE Tower
Pathumwan, Bangkok 10330 HoChiMinh City Singapore 088540
T : +66 2 648 0240 T : +84 8 3914 6700 T : +65 6326 3718
F : +66 2 648 0200 F : +84 8 3827 8229 F : +65 6326 3015

ANZ
Australia New Zealand
125-127 Long Street Level 1, 8 Tangihua Street
Smithfield, Sydney, NSW 2164 Auckland, North Island
T : +61 2 8788 6911 T : +64 9 353 6706
F : +61 2 8788 7224 F : +64 9 353 6707

North Asia
Japan Korea
11F, Akasaka Park Bldg.,5-2-20 3rd Floor, GE Tower, 71-3,
Akasaka, Minato-ku Cheongdam-dong, Gangnam-gu
Tokyo 107-6111 Seoul, Korea 135-100
T : +81 3 3588 5288 T : +82 2 6201 4501
F : +81 3 3585 3010 F : +82 2 6201 4344

For more information, please visit


www.geindustrial.com