You are on page 1of 2

SHEV & Ventilation

JET-TOP-Light Flap
as SHEV exhaust unit for effective
smoke and heat exhaust

or applicable as pure natural


ventilation unit

Application:
product overview

JET-TOP-Light Flap consisting of:


1 Natural Ventilation:
- manually
- PVC-ventilation frame - electrical activated (230V / 24V)
- PC-multiwall sheet - pneumatically 300 - 500 mm stroke length
-surrounding aluminum covering frame

Technical datas of the glazing


- PC-SDP 10 opal (1700g):
T L: 60 %, U-value: 3,1 W / m²K

- PC-SDP 10 opal (2000g):


T L: 50 %, U-value: 3,0 W / m²K

- PC-S4P 10 opal:
T L: 55 %, U-value: 2,4 W / m²K JET-TOP-Light Flap for natural ventilation

- PC-S7P 16 opal:
T L: 54 %, U-value: 1,7 W / m²K
2 Smoke Exhaust Function
- up to 180 x 250 cm unit size

T L: light transmission value


- certified according DIN EN 12101-2
U-value: heat transmission coefficient - Aa max = 3,375 m²

Fire Behavior Classification


- PC-SDP 10 opal (1700g):
B1, hardly flammable

- PC-SDP 10 opal (2000g):


B1, hardly flammable

- PC-S4P 10 opal:
brochure no. 1.5.1.1

B2, non burning drippy


Smoke Exhaust Unit: JET-TOP Light Flap after
- PC-S7P 16 opal:
activation in end position open with spoilers for
B-s1 d0 according EN 13501-1
optimization of the aerodynamic coefficient
hardly flammable, non burning
drippy
Industrial Construction   Architecture   SHEV-Technology & Customer Service

delivery program of the JET-TOP-Light Flap

system Firejet Rasant 170 °

with RAK 30 / 40 / 45 / 50 with AK 30 / 40 / 50 with RS 30 / 40 with RS 30 / 40


order size upstand upstand upstand + spoiler below
(RAK-geometry) (AK-geometry) (RS-geometry) upstand ED

without without with


spoiler WLF with spoiler WLF spoiler WLF with with
cm x cm
minimum spoiler WLF minimum maximum spoiler WLF spoiler WLF
Aa-value Aa-value Aa-value Aa-value Aa-value Aa-value

100 x 100 0,650 0,700 0,600 - 0,750 0,926


100 x 150 0,900 1,125 0,900 0,975 1,050 1,424
100 x 200 1,200 1,500 1,200 1,300 1,400 1,855
100 x 250 1,500 1,875 1,500 1,630 1,750 2,286
120 x 120 0,864 1,080 0,864 0,936 1,008 1,367
120 x 150 1,080 1,350 1,080 1,170 1,260 1,671
120 x 180 1,188 1,620 1,188 1,404 1,512 1,975
120 x 240 1,584 2,160 1,584 2,016 1,872 2,582
125 x 125 0,940 1,170 0,940 1,010 1,094 1,470
125 x 250 1,719 2,344 1,719 2,188 2,031 2,783
150 x 150 1,350 1,688 1,350 1,463 1,463 2,042
150 x 180 1,620 2,025 1,620 1,890 1,755 2,414
150 x 210 1,890 2,363 1,890 2,205 2,048 2,785
150 x 240 1,980 2,700 1,980 2,520 2,340 3,156

Valid from date of issue until reissue. Updated: June 2009. Misprints, mistakes and technical changings excepted.
150 x 250 2,063 2,813 2,063 2,625 2,438 3,280
180 x 180 1,782 2,430 1,782 2,268 - -
180 x 240 2,376 3,240 2,376 3,024 - -
180 x 250 2,475 3,375 2,475 3,150 - -
Aa-values in m (aerodynamic effective surface) according DIN EN 12101-2
2

Samples for JET-upstand-designs

ED-Spoiler
for better
Aa-Values

JET-METAL-AK Type RAK, 40 JET-Steel-Aluminium- JET-METAL-Upstand type


cm high, with JET-OPTIMAL- Integrated-AK Type AK RS, 40 cm high, with JET-
Roof Connection-System 40 cm high, connection OPTIMALRoof Connection-
Connection example: high example: bituminous roof System, Connection
polymer roof sheeting sheeting, 1st layer example: high polymer roof
sheeting

JET Tageslicht & RWA GmbH


Certified in com-

VdS
pliance with
Weidehorst 28 Tel. +49 (0) 5744 / 503-0 www.jet-group.info DIN EN ISO

D- 32609 Hüllhorst Fax +49 (0) 5744 / 503-40 email@jet-group.info 9001


VdS-approved manufacturer for
LIGHT DOMES ~ ROOF LIGHTS ~ SHEV ~ SPECIAL GLASS AND GRILLODUR® ~ SURFACE VENTILATORS smoke and heat exhaust systems