dF = Ids x B
Forces are
proportional to the
square of the current
(instantaneous
F∝ I *B
values)
= F∝ I2
B∝ I
Short circuit integrity
Inner Outer
winding winding
Fmean
Buckling
Characteristic failure mode
for inner winding
Short circuit integrity
Collapse of a cylinder
shaped winding from evenly
distributed external force
B B Fax Fax
Short circuit integrity
B B Fax Fax
Short circuit integrity
Consequently, large
axial forces will be
developed
B B Fax Fax
Short circuit integrity
Tilting of conductors
Short circuit integrity
Strict Manufacturing
Procedures and Tolerances
IREQ High-Power
Test Station in
ABB GSU transformer
Varennes - Canada: 775 MVA – 24/230±2x2.5%
Arrangement for the
short-circuit withstand kV - 60 Hz,
test
200
150
100
50
0
1997 2000 2001 2002 2005 2007 2008 2011 2012
16
20 initially not OK
number of transformers
number of transformers
initially not OK
16 initially OK 12
initially OK
12
8
8
4
4
0 0
25-50 50-100 100-200 >200 20-100 100-200 200-300 300-400 >400
MVA (rated) kV (rated)
No common root-cause
Short circuit tests: Verification Criteria