Professional Documents
Culture Documents
MODEL YK (STYLE G)
R-134a or R-513A
Issue Date:
April 15, 2019
FORM 160.75-N1
ISSUE DATE: 04/15/2019
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During rigging, installation, operation, maintenance, death to themselves and people at the site.
or service, individuals may be exposed to certain com-
ponents or conditions including, but not limited to: This document is intended for use by owner-authorized
heavy objects, refrigerants, materials under pressure, rigging, installation, and operating/service personnel. It
rotating components, and both high and low voltage. is expected that these individuals possess independent
Each of these items has the potential, if misused or training that will enable them to perform their assigned
handled improperly, to cause bodily injury or death. It tasks properly and safely. It is essential that, prior to
is the obligation and responsibility of rigging, instal- performing any task on this equipment, this individual
lation, and operating/service personnel to identify and shall have read and understood the on-product labels,
recognize these inherent hazards, protect themselves, this document and any referenced materials. This in-
and proceed safely in completing their tasks. Failure dividual shall also be familiar with and comply with
to comply with any of these requirements could result all applicable industry and governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
External wiring, unless specified as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specifications and must be performed only by a qualified
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2 JOHNSON CONTROLS
FORM 160.75-N1
ISSUE DATE: 04/15/2019
ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
Installation Checklist/Start-Up Request 160.75-CL1
Unit Start-Up Checklist 160.75-CL2
Installation and Reassembly - Unit 160.75-N3
Installation - MV VSD - 2300 VAC – 6600 VAC 160.00-N6
Installation - MV VSD - 10 kV – 13.8 kV 160.00-N8
Wiring Diagrams - Field Connections - Unit-Mounted SSS, MV SSS, or Remote Mounted MV SSS, MV EMS 160.75-PW1
Wiring Diagrams - Field Connections - Remote Mounted MV SSS 160.75-PW2
Wiring Diagrams - Field Connections - Remote Mounted MV VSD 160.75-PW3
Wiring Diagrams - Field Connections - LV VSD 160.54-PW6
Wiring Diagrams - OptiView Control Center and EMS 160.75-PW5
Wiring Diagrams - OptiView Control Center and EMS with the LTC I/O Board 160.75-PW7
Wiring Diagrams - OptiView Control Center and SSS, LV VSD, MV VSD 160.75-PW6
Wiring Diagrams - OptiView Control Center and SSS, LV VSD, MV VSD with the LTC I/O Board 160.75-PW8
Wiring Diagrams - Field Control Modifications 160.75-PW4
Unit Operation and Maintenance 160.75-O1
Operation OptiView Panel 160.54-O1
Operation - Variable Speed Drive - TM Model 160.00-O1
Operation and Maintenance - Solid State Starter (Mod "B") 160.00-O2
Operation - Variable Speed Drive - VSD and LVD Model 160.00-O4
Operation - Variable Speed Drive - HYP Model 160.00-O10
Operation - Floor Mounted MV SSS, Manufactured Before 2007 160.00-O5
Operation - Floor Mounted MV SSS, Manufactured After 2007 160.00-O5.1
Operation - Unit Mounted MV SSS 160.00-O7
Operation - MV VSD - 2300 VAC – 6600 VAC 160.00-O6
Operation - MV VSD - 10 kV – 13.8 kV 160.00-O8
Service Policy - Shipping Damage Claims 50-15-NM
JOHNSON CONTROLS 3
FORM 160.75-N1
ISSUE DATE: 04/15/2019
NOMENCLATURE
YK KC K4 H9 – CY G
MOTOR CODE
POWER SUPPLY
– for 60 Hz
5 for 50 Hz
COMPRESSOR CODE*
CONDENSER CODE*
EVAPORATOR CODE*
* Refer to YK Engineering Guide (Form 160.75-EG1)
MODEL* for Shell/Motor/Compressor combinations.
4 JOHNSON CONTROLS
FORM 160.75-N1
ISSUE DATE: 04/15/2019
TABLE OF CONTENTS
SECTION 1 - INTRODUCTION..................................................................................................................................7
General.............................................................................................................................................................. 7
Field Assembled Units Only.............................................................................................................................. 7
Shipment........................................................................................................................................................... 8
Inspection – Damage – Shortage...................................................................................................................... 9
Chiller Data Plate.............................................................................................................................................. 9
Long-Term Storage..................................................................................................................................................9
Rigging............................................................................................................................................................ 12
Location........................................................................................................................................................... 13
Motors............................................................................................................................................................. 13
Foundation...................................................................................................................................................... 13
Clearance........................................................................................................................................................ 13
SECTION 2 - INSTALLATION.................................................................................................................................17
Rigging Unit to Final Location......................................................................................................................... 17
Locating and Installing Isolator Pads............................................................................................................... 17
Checking the Isolation Pad Deflection............................................................................................................. 17
Leveling the Unit.............................................................................................................................................. 17
Installing Optional Spring Isolators.................................................................................................................. 17
Piping Connections......................................................................................................................................... 17
Evaporator and Condenser Water Piping........................................................................................................ 18
Unit Piping....................................................................................................................................................... 19
Refrigerant Relief Piping................................................................................................................................. 20
Control Panel Positioning................................................................................................................................ 21
Control Wiring.................................................................................................................................................. 21
Power Wiring................................................................................................................................................... 21
Oil Pump – 3 Phase Starter............................................................................................................................. 21
Insulation......................................................................................................................................................... 22
Installation Check – Request for Start-Up Service..........................................................................................23
P and Q Compressor Units (Standard)........................................................................................................... 25
P and Q Compressor Units (Metric)................................................................................................................ 26
H Compressor Units (Standard)...................................................................................................................... 27
H Compressor Units (Metric)........................................................................................................................... 28
K Compressor Units (Standard)...................................................................................................................... 29
K Compressor Units (METRIC)....................................................................................................................... 30
Evaporator Compact Waterboxes - Ft-In (mm)............................................................................................... 31
Condenser Compact Waterboxes - Ft-In (mm)............................................................................................... 32
Evaporators – Compact Waterboxes – A through L Evaporators - Ft-In (mm).............................................. 33
Evaporators – Compact Waterboxes – M through Z Evaporators - Ft-In (mm)............................................. 34
Condenser – Compact Waterboxes – Standard - Ft-In (mm)........................................................................ 35
Condenser – Heat Recovery Compact Waterboxes – Standard - Ft-In (mm)............................................... 37
Evaporator – Nozzle Arrangements – Standard - Ft-In (mm)........................................................................ 38
Condenser – Nozzle Arrangements – Standard - Ft-In (mm)........................................................................ 39
Evaporator Marine Waterbox Nozzle Arrangements - Ft-In (mm)................................................................... 40
Condenser Marine Waterbox Nozzle Arrangements - Ft-In (mm)................................................................... 41
Condensers Marine Waterboxes Heat Recovery Units - Main (Tower) Circuit Only....................................... 42
JOHNSON CONTROLS 5
FORM 160.75-N1
ISSUE DATE: 04/15/2019
LIST OF FIGURES
LIST OF TABLES
6 JOHNSON CONTROLS
FORM 160.75-N1
ISSUE DATE: 04/15/2019
SECTION 1 - INTRODUCTION 1
GENERAL
This manual describes the installation of a YORK YK The services of a Johnson Controls representative will
Mod "G" Centrifugal Chiller. This unit can be shipped be furnished to check the installation, supervise the
as a single factory assembled, piped, wired package, initial start-up and operation of all chillers installed
requiring a minimum of field labor to make chilled within the Continental United States.
water connections, condenser water connections, re- The Johnson Controls Warranty may be
frigerant atmospheric relief connections, and electri- voided if the following restrictions are not
cal power connections. Refrigerant and oil charges are adhered to:
shipped separately unless optional condenser isolation
valves are ordered.
Chillers can also be shipped dismantled when required 1. No valves or connections should be opened under
by rigging conditions, but generally it is more econom- any circumstances because such action will result
ical to enlarge access openings to accommodate the in loss of the factory nitrogen charge.
factory assembled unit. Chillers shipped dismantled
MUST be field assembled under the supervision of a 2. Do not dismantle or open the chiller for any rea-
Johnson Controls representative, but otherwise instal- son except under the supervision of a Johnson
lation will be as described in this instruction. Controls representative.
3. When units are shipped dismantled, notify the
FIELD ASSEMBLED UNITS ONLY nearest Johnson Controls office in ample time for
Use Installation and Reassembly - Unit (Form 160.75- a Johnson Controls representative to supervise
N3) in conjunction with this installation instruction. This rigging the unit to its operating position and the
instruction will be furnished with all units that are to be assembly of components.
field assembled. 4. Do not make final power supply connections to
the compressor motor or control center.
COMPRESSOR
CONTROL
CENTER
MOTOR
CONDENSER
LD15222
EVAPORATOR
JOHNSON CONTROLS 7
FORM 160.75-N1
Section 1 - INTRODUCTION
ISSUE DATE: 04/15/2019
5. Do not charge the compressor with oil. • Compressor/motor assembly removed from
shells and skidded. Evaporator/condenser is
6. Do not charge the unit with refrigerant.
not skidded.
7. Do not attempt to start the system.
• All wiring integral with compressor is left on
8. Do not run hot water (110°F / 43°C max) or steam it, and all conduit is left on shell. All open-
through the evaporator or condenser at any time. ings on compressor, oil separator, and shell
are closed and charged with dry nitrogen (2
SHIPMENT psig to 3 psig) (115/122 kPa).
The chiller may be ordered and shipped in any of the • Miscellaneous packaging of control center,
following forms: tubing, water temperature controls, wiring,
Form 1 – Factory Assembled Unit, complete with mo- oil, isolators, solid state starter (option), etc.;
tor, refrigerant, and oil charges. refrigerant charge shipped separately.
Units shipped dismantled MUST be re-
• The motor/compressor assembly mounted, assembled by, or under the supervision of,
with all necessary interconnecting piping a Johnson Controls representative. Refer
assembled. OptiView™ Control Center is to Installation and Reassembly - Unit
mounted on the unit. Complete unit fac- (Form 160.75-N3)
tory leak tested, evacuated and charged with
R-134a.
Form 7 – S
plit Shells – Shipped as three major assem-
An optional Solid State Starter or Variable blies. Unit first factory assembled, refriger-
Speed Drive can be factory mounted and ant piped, wired and leak tested; then dis-
wired. mantled for shipment.
• Miscellaneous material – Four (4) vibration • Compressor/motor assembly removed from
isolation pads (or optional spring isolators shells and skidded.
and brackets). K7 units will be shipped with
• Evaporator and condenser shells are sepa-
8 Vibration Isolation Pads.
rated at tube sheets and are not skidded. Re-
Form 2 – Factory Assembled Unit, complete with mo- frigerant lines between shells are flanged and
tor (refrigerant and oil charges shipped sepa- capped, requiring no welding.
rately).
• All wiring integral with compressor is left
• The motor/compressor assembly mounted, on it. All wiring harnesses on shells are re-
with all necessary interconnecting piping moved. All openings on compressor and
assembled. OptiView™ Control Center is shells are closed and charged with dry nitro-
mounted on the unit. Complete unit fac- gen (2 to 3 psig) (115/122 kPa).
tory leak tested, evacuated and charged with
• Miscellaneous packaging of control center,
holding charge of nitrogen.
tubing, water temperature controls, wiring,
An optional Solid State Starter or Variable oil isolators, solid state starter (option), etc.;
Speed Drive can be factory mounted and refrigerant charge shipped separately.
wired. Units shipped dismantled MUST be re-
assembled by, or under the supervision of,
• Miscellaneous material – Four (4) vibration
a Johnson Controls representative. Refer
isolation pads (or optional spring isolators).
to Installation and Reassembly - Unit
K7 units will be shipped with 8 Vibration
(Form 160.75-N3)
Isolation Pads.
Form 3 – D
riveline Separate From Shells – Shipped as When more than one chiller is involved, the major
two major assemblies. Unit first factory assem- parts of each unit will be marked to prevent mixing
bled, refrigerant piped, wired and leak tested; of assemblies. (Piping and Wiring Drawings to be fur-
then dismantled for shipment. nished by Johnson Controls)
8 JOHNSON CONTROLS
FORM 160.75-N1
Section 1 - INTRODUCTION
ISSUE DATE: 04/15/2019
All wiring integral with compressor is left on it, and all To protect the waterbox of pressure vessels from rust-
conduit is left on shell. ing, the tube side (water side) has been purged and
charged with nitrogen to a positive pressure of 5 psig
Miscellaneous packaging of tubing, water temperature to 7 psig.
controls, wiring, isolators, etc. The unit is shipped with
refrigerant charge. See Figure 2. Do not break the seal or remove closures until ready
for set up. Relieve pressure as per the following proce-
dure (see Figure 3 on page 10).
65°
Min. Failure to follow the following procedures
will cause severe personal injury or death
65°
Min. to operators themselves or people on-site.
It is the obligation and responsibility of
Lifting operators to identify and recognize the
Holes
inherent hazards of material under pres-
sure and to protect themselves.
Lifting
Holes
LD16730
Figure 2 - VARIABLE SPEED DRIVE RIGGING
JOHNSON CONTROLS 9
FORM 160.75-N1
Section 1 - INTRODUCTION
ISSUE DATE: 04/15/2019
5
4
3
ITEM DESCRIPTION
8 1 Tag Warning Dennison 8E
9 2 Gauge Press 2 Dia 0-30
3 Tag GlvSt Wire Speed
4 Bush Pipe 3/4 - 14 NPTE X
5 Valve, Transducer 1/4 NPTE X
6 Flange Cover
7 Gasket
Nozzle without flanges 8 Victaulic Coupling
(Lines 4 in. through 12 in.) 9 Sealing Cap
8
10 JOHNSON CONTROLS
FORM 160.75-N1
Section 1 - INTRODUCTION
ISSUE DATE: 04/15/2019
JOHNSON CONTROLS 11
FORM 160.75-N1
Section 1 - INTRODUCTION
ISSUE DATE: 04/15/2019
LD19197
Rigging and lifting should only be done by a professional rigger in accordance with a written rig-
ging and lifting plan. The most appropriate rigging and lifting method will depend on job specific
factors, such as the rigging equipment available and site needs. Therefore, a professional rigger
must determine the rigging and lifting method to be used, and it is beyond the scope of this manual
to specify rigging and lifting details.
RIGGING
The complete standard chiller is shipped without skids. Do not lift the unit with slings around
(When optional skids are used it may be necessary to motor/compressor assembly or by means
remove the skids so riggers skates can be used under of eyebolts in the tapped holes of the
the unit end sheets to reduce overall height.) compressor motor assembly. Do not turn
a unit on its side for rigging. Do not rig
Each unit has four (4) lifting holes (two in each end) vertically.
in the end sheets which should be used to lift the unit.
Care should be taken at all times during rigging and The rigging and operating weights and overall dimen-
handling of the chiller to avoid damage to the unit and sions are given on page 25 through page 46 as a
its external connections. Lift only using holes shown in guide in determining the clearances required for rig-
Figure 4 on page 13. ging. Add 6" (15 cm) to overall height for optional
skidded unit.
12 JOHNSON CONTROLS
FORM 160.75-N1
Section 1 - INTRODUCTION
ISSUE DATE: 04/15/2019
LD19569
Figure 4 - RIGGING
LOCATION MOTORS
YORK Chillers are furnished with vibration isola- The YK open motor is air cooled. Check state, local,
tor mounts for basement or ground level installations. and other codes for ventilation requirements.
Units may be located on upper floor levels providing
the floor is capable of supporting the total unit operat- FOUNDATION
ing weight and optional spring isolators are used. A level floor, mounting pad or foundation must be pro-
Sufficient clearance to facilitate normal vided by others, capable of supporting the operating
service and maintenance work must be weight of the unit.
provided all around and above the unit
and particularly space provided at either CLEARANCE
end to permit cleaning or replacement Clearances should be adhered to as follows:
of evaporator and condenser tubes – see
Clearance. A doorway or other sufficiently • Rear and above unit – 2 ft (61 cm).
large opening properly located may be • Front of unit – 3 ft (91 cm).
used. The chiller should be located in an
indoor location where temperatures range • Tube Removal – 14 ft.* (4.3 m) (either end)
from 40°F to 110°F (4.4°C to 43.3°C). * 16 ft (4.9 meters) on shell codes Q-Q, N-N, R-R, X-T and X-X.
** 18 ft (5.5 meters) on shell code S-S, S-V, Z-Z.
*** 22 ft (6.7 meters) on shell code W-W.
JOHNSON CONTROLS 13
FORM 160.75-N1
Section 1 - INTRODUCTION
ISSUE DATE: 04/15/2019
DIA.
END SHEET HOLE END SHEET
DIA.
HOLE
LD12638a LD12639a
UNIT WEIGHT UP TO 16,365 Lbs (7,423 Kgs) UNIT WEIGHT 16,366 - 28,835 Lbs (7,424 - 13,080 Kgs)
SHELL
SHELL
See Detail A
See Detail A
LD12640a LD12641a
UNIT WEIGHT 28,836 - 53,530 Lbs (13,081 - 24,281 Kgs) UNIT WEIGHT 53,531 - 100,464 Lbs (24,283 - 45,559 Kgs)
SHELL SHELL
DIA.
END SHEET DIA.
END SHEET
HOLE HOLE
9"
(229)
5"
(127) Mounting 3/8”
Bracket (10)
9"
(229)
LD19571a
LD12642a
LD19578
14 JOHNSON CONTROLS
FORM 160.75-N1
Section 1 - INTRODUCTION
ISSUE DATE: 04/15/2019
SHELL SHELL
END END
5 1/2” 1 3/8” 5 1/2” 1 3/8” SHEET
(35) SHEET
(140) (35)
(140) CAP
CAP
SCREW SCREW
ADJUSTING ADJUSTING
BOLT BOLT
1 1
(25” (25”
) )
(17 7” (15 6”
7” 8) 2)
(1 6”
)
8)
52
(17
4-SPRING ISOLATORS 4-SPRING ISOLATORS
LD19572 LD19573
UNIT WEIGHT UNIT WEIGHT
10,000 to 19,563 19,564 Lbs UP TO 35,009 Lbs
(4,536 to 8,873 Kgs) (8,874 Kgs UP TO 15,880 Kgs)
END SHELL
SHELL
SHEET
END
SHEET
6-
5 1/2" 1
(1 /4" CAP
59
(140) ) SCREW
CAP ADJUSTING
SCREW BOLT
ADJUSTING
BOLT
(22 9” 9” 29)
9) (2
JOHNSON CONTROLS 15
FORM 160.75-N1
Section 1 - INTRODUCTION
ISSUE DATE: 04/15/2019
/4"
5 1 3)
16 (13
1/
(41 4"
6- 3)
1
(1 /4" CAP
59
)
SCREW
CAP
ADJUSTING SCREW
BOLT
ADJUSTING
BOLT
12-SPRING ISOLATORS
3-SPRING ISOLATORS
LD19580 LD19581
UNIT WEIGHT UNIT WEIGHT
89,341 Lbs UP TO 115,000 Lbs 115,000 Lbs. UP TO 190,000 Lbs
(40,526 Kgs UP TO 52,163 Kgs) (52,163 Kgs UP TO 86,183 Kgs)
16 JOHNSON CONTROLS
FORM 160.75-N1
ISSUE DATE: 04/15/2019
SECTION 2 - INSTALLATION
CHECKING THE ISOLATION PAD DEFLECTION After the unit is leveled (and wedged in place for op-
tional spring isolators) the piping connections may be
All isolation pads should be checked for the proper de- made; chilled water, condenser water and refrigerant
flection while checking to see if the unit is level. Each relief. The piping should be arranged with offsets for
pad should be deflected approximately 0.10 inches flexibility, and adequately supported and braced inde-
(2.5 mm) to 0.20 inches (5 mm). If an isolation pad is pendently of the unit to avoid strain on the unit and
under-deflected, shims should be placed between the vibration transmission. Hangers must allow for align-
unit tube sheet and the top of the pad to equally deflect ment of pipe. Isolators (by others) in the piping and
all pads. hangers are highly desirable, and may be required by
specifications, in order to effectively utilize the vibra-
LEVELING THE UNIT
tion isolation characteristics of the vibration isolation
The longitudinal alignment of the unit should be mounts of the unit.
checked by placing a level on the top center of the
evaporator shell under the compressor/motor assem- Check for piping alignment – Upon completion of
bly. Transverse alignment should be checked by plac- piping, a connection in each line as close to the unit
ing a level on top of the shell end sheets. as possible should be opened, by removing the flange
JOHNSON CONTROLS 17
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
bolts or coupling and checked for piping alignment. If flow path for the starter heat exchanger to regulate cooling
any of the bolts are bound in their holes, or if the con- above the equipment room dewpoint for applications using
nection springs are out of alignment, the misalignment cooling sources other than evaporative air-exchange meth-
must be corrected by properly supporting the piping or ods, such as wells, bodies of water, and chilled water. The
by applying heat to anneal the pipe. temperature control valve should be the type to open on in-
If the piping is annealed to relieve stress, creasing drive coolant temperature, fail-closed, and set for a
the inside of the pipe must be cleaned of temperature above dewpoint. It can be requested as factory-
scale before it is finally bolted in place. supplied on a chiller order by special quotation.
Chilled Water
Foreign objects which could lodge in, or block flow
through, the evaporator and condenser tubes must be
EVAPORATOR AND CONDENSER WATER
kept out of the water circuit. All water piping must be
PIPING
cleaned or flushed before being connected to the chiller
The evaporator and condenser liquid heads of chiller pumps, or other equipment.
have nozzles which are grooved, suitable for welding
150 psig DWP flanges or the use of flexible couplings. Permanent strainers (supplied by others) are required
Factory mounted flanges are optional. in both the evaporator and condenser water circuits to
protect the chiller as well as the pumps, tower spray
The nozzles and water pass arrangements are furnished in ac- nozzles, chilled water coils and controls, etc. The
cordance with the job requirements (refer to Product Draw- strainer must be installed in the entering chilled water
ings) furnished with the job. Standard units are designed for line, directly upstream of the chiller.
150 psig DWP on the water side. If job requirements are for
greater than 150 psig DWP, check the unit data plate before Water piping circuits should be arranged so that the
applying pressure to evaporator or condenser to determine if pumps discharge through the chiller, and should be
the chiller has provisions for the required DWP. controlled as necessary to maintain essentially constant
chilled and condenser water flows through the unit at
Inlet and outlet connections are identified by labels
all load conditions.
placed adjacent to each nozzle.
The coolant temperature inside any JCI-supplied liquid- If pumps discharge through the chiller, the strainer
cooled motor starter must be maintained above the dewpoint may be located upstream from pumps to protect both
temperature in the equipment room to prevent condensing pump and chiller. (Piping between strainer, pump and
water vapor inside the starter cabinet. Therefore, an addi- chiller must be very carefully cleaned before start-up.)
tional temperature-controlled throttle valve is needed in the If pumps are remotely installed from chiller, strainers
should be located directly upstream of the chiller.
COOLING
TOWER
CONTROLLED COOLING
TOWER BYPASS VALVE
(IF NECESSARY) C = COMPRESSOR
STRAINER M = MOTOR
CONDENSER
FLOW SWITCH
COOLING TOWER COOLING
PUMP UNIT
EVAPORATOR
COOLING UNIT
CODEPAK STRAINER
CHILLED WATER PUMP
LD08529
Figure 8 - SCHEMATIC OF A TYPICAL PIPING ARRANGEMENT
18 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
JOHNSON CONTROLS 19
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
VENT TO ATMOSPHERE
CONDENSATION
TRAP
CONDENSER
DUAL RELIEF SEE NOTE
VALVES
EVAPORATOR
20 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
JOHNSON CONTROLS 21
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
CONDENSER
CONDENSER
EVAPORATOR
EVAPORATOR
2” Liquid
Level Indicator
Refigerant from
Oil Cooler to Cooler
Input Drain
Liquid Line and
Hot Gas
Connection Tape Insulation Charging
around flanges to
allow for removal
22 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
YK MOD G COMBINATIONS
COMPRESSOR EVAPORATOR CONDENSER MOTOR CODES
CODES CODES CODES 60 HZ 50 HZ
Q3 AP to AS AP to AS
CP to CS CP to CS CF-CT 5CC-5CO
Q3, Q4
DP to DS DP to DS EF-ET 5EC-5EO
Q4 EP to ET EP to ET
CP to CS CP to CS
Q5
DP to DS DP to DS CH-CT 5CE-5CO
EP to ET EP to ET EH-ET 5EE-5EO
Q5, Q6, Q7
FQ to FT FQ to FT
EP to ET EP to ET CU-CY 5CP-5CU
P7
FQ to FT FQ to FT EU-EY 5EP-5EU
P8 GQ to GS EV to EX
HQ to HS FV to FX CH-CZ 5CE-5CU
P8, P9 JP to JS JP to JS EH-EZ 5EE-5EU
LQ to LS LQ to LS
KP to KS, K2 to K4 KP to KS, K2 to K4 CN-CA 5CK-5CW
H9
MQ to MS, M2 to M4 MP to MS, M2 to M4 EN-EA 5EK-5EW
K1 KT to KX, K5 to K7 KP to KS, K2 to K4
MQ to MS, M2 to M4 MP to MS, M2 to M4
CS-DC 5CN-5DC
NQ to NS, N2 to N4 NP to NS, N2 to N4
K1, K2 ES-FC 5EN-5FB
PQ to PS, P2 to P4 PQ to PS, P2 to P4
QQ to QS, Q2 to Q4 QQ to QS, Q2 to Q4
NQ to NS, N2 to N4 NP to NS, N2 to N4
DA-DJ 5DA-5DH
K3 QQ to QV, Q2 to Q4 QQ to QS, Q2 to Q4
FA-FD 5FA-5FB
RQ, RS, RN, R3, R5, R7 RQ, RR, RS, R2, R3, R4
RP, RR, RT, R2, R4, R6 RQ, RR, RS, R2, R3, R4, R5
SQ, SR, SS, S2, S3, S4
SQ, SS, SV, S3, S5, S7 DA-DJ 5DA-5DJ
K4 VP, VQ, VR, VS, V2, V3, V4, V5
FA-FD 5FA-5FB
TP, TQ, TR, TS, T2, T3, T4, T5
XQ, XR, XS, X2, X3, X4
XQ, XR, XS, X2, X3, X4
WP, WR, WT, W1, W2, W4, W6 WQ, WR, WS, W1, W2, W3, W4
K7 DD-DL 5DD-5DL
ZQ, ZR, ZS, Z1, Z2, Z3, Z4 ZQ, ZR, ZS, Z1, Z2, Z3, Z4
JOHNSON CONTROLS 23
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
24 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
LD07134
JOHNSON CONTROLS 25
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
LD07134
Q3 COMPRESSOR
ADDITIONAL OPERATING HEIGHT CLEARANCE
EVAPORATOR – CONDENSER SHELL CODES
Type of Chiller Mounting M A–A C–C D–D
Neoprene Pad Isolators 45 A 1,549 1,676 1,676
Spring Isolators 25mm Deflection 25 B 2,134 2,229 2,229
Direct Mount 19 C 394 445 445
D 381 394 394
P7, Q7 COMPRESSOR E 3,658 3,658 4,877
EVAPORATOR – CONDENSER SHELL CODES
E–E E–I F–F Q4 COMPRESSOR
A 1,880 2,178 1,880 EVAPORATOR – CONDENSER SHELL CODE
B 2,299 2,642 2,299 C–C C–B D–D E–E
C 495 495 495 A 1,676 1,949 1,676 2,134
D 445 594 445 B 2,197 2,423 2,197 2,350
E 3,658 3,658 4,877 C 445 445 445 495
D 394 530 394 445
P8 COMPRESSOR E 3,658 3,658 4,877 3,658
EVAPORATOR – CONDENSER SHELL CODES
E–E F–F G–G H–H Q5 COMPRESSOR
A 2,108 2,108 2,299 2,299 EVAPORATOR – CONDENSER SHELL CODES
B 3,200 3,200 3,327 3,327 C–C D–D E–E F–F
C 610 610 641 641 A 1,676 1,676 2,134 2,134
D 445 445 508 508 B 2,403 2,403 2,578 2,578
E 3,658 4,877 3,658 4,877 C 445 445 495 495
D 394 394 445 445
P9 COMPRESSOR E 3,658 4,877 3,658 4,877
EVAPORATOR – CONDENSER SHELL CODES
H–F J–J L–L Q6 COMPRESSOR
A 2,108 2,299 2,299 EVAPORATOR – CONDENSER SHELL CODES
B 3,124 3,264 3,264 E–E F–F
C 610 641 641 A 2,134 2,134
D 445 508 508 B 2,515 2,515
E 4,877 3,658 4,877 C 495 495
D 445 445
NOTES: E 3,658 4,877
1. All dimensions are approximate.
2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length.
3. Water nozzles can be located on either end of unit. Add 13 mm (1/2 inch) to nozzle length for flanges connections.
4. To determine overall height, add 22 mm (7/8 inch) for isolators.
5. Use of motors with motor hoods may increase overall unit dimensions.
26 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
LD07135
H9 COMPRESSORS
EVAPORATOR – CONDENSER SHELL CODES
I-K & K–K K–O M–M
A 7'-6 1/2" 8'-9 1/4" 8'-7"
B 10'-4" 10'-7 5/8" 10'-10 1/2"
C 2'-1 1/4" 2'-1 1/4" 2'-4 1/2"
D 1'-8" 2'-3 3/8" 1'-11"
E 14'-0" 14'-0" 14'-0"
NOTES:
1. All dimensions are approximate.
2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length.
3. Water nozzles can be located on either end of unit. Add 1/2" (13 mm) to nozzle length for flanges connections.
4. To determine overall height, add 7/8" (22 mm) for isolators.
5. Use of motors with motor hoods may increase overall unit dimensions.
JOHNSON CONTROLS 27
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
178
LD03886
H9 COMPRESSORS
EVAPORATOR – COND. SHELL CODES
I-K & K–K K–O M–M
A 2,299 2,673 2,616
B 3,150 3,242 3,315
C 641 641 724
D 508 695 584
E 4,267 4,267 4,267
NOTES:
1. All dimensions are approximate.
2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length.
3. Water nozzles can be located on either end of unit. Add 13 mm (1/2 inch) to nozzle length for flanges connections.
4. To determine overall height, add 22 mm (7/8 inch) for isolators.
5. Use of motors with motor hoods may increase overall unit dimensions.
28 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
LD07136
NOTES:
1. All dimensions are approximate.
2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length.
3. Water nozzles can be located on either end of unit. Add 1/2" (13 mm) to nozzle length for flanges connections.
4. To determine overall height, add 7/8" (22 mm) for isolators.
5. Use of motors with motor hoods may increase overall unit dimensions.
JOHNSON CONTROLS 29
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
LD07139
NOTES:
1. All dimensions are approximate.
2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length.
3. Water nozzles can be located on either end of unit. Add 13 mm (1/2 inch) to nozzle length for flanges connections.
4. To determine overall height, add 22 mm ( 7/8 inch) for isolators.
5. Use of motors with motor hoods may increase overall unit dimensions.
30 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
F F 2
G
F
F F
LD07619
JOHNSON CONTROLS 31
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
F F
G
F
TWO
F PASS CONDENSERS, SHELL CODES F
DIMENSIONS A C,D E,F J,K,L M,N P,Q R,S T,V,W X,Z
1'-1 7/8" 1'-1 7/8" 1'-3" 1'-4" 1'-2 7/8" 1'-4 7/8" 1'-7 3/8" 1'-7 1/2" 1'-9 3/4"
H
(352) (352) (381) (406) (378) (429) (492) (495) (552)
0'-5 7/8" 0'-6 1/2" 0'-7" 0'-7 1/2" 0'-7 3/4" 0'-9 1/2" 0'-11 3/4" 0'-11" 1'-1 7/8"
J F (178)
(149) (165) (191) (197) (241) F (298) (279) (352)
DOUBLE BUNDLE HEAT RECOVERY CONDENSERS, SHELL CODES
B I O U Y
DIMENSIONS TOWER HEATING TOWER HEATING TOWER HEATING TOWER HEATING TOWER HEATING
1'-6 1/2" 1'-5" 1'-7 1/2" 1'-4 3/4" 1'-9 1/2" 1'-6" 1'-10 1/4" 1'-8" 2'-4 3/4" 1'-10 1/2"
H
(470) (432) (495) (425) (546) (457) (565) (508) (730) (572)
0'-10 1/2" 0'-9" F 1/2" 0'-8 3/4"
0'-11 1'-1 1/2" 0'-10" 1'-2 1/4"
F 1'-0" 1'-8 3/4" 1'-2 1/2"
J
(267) (229) (292) (222) (343) (254) (362) (305) (527) (368)
LD07619a
32 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
FRONT 1-PASS
OF
UNIT
NOZZLE
2
ARRANGEMENTS
A H NUMBER OF EVAPORATOR
PASSES IN OUT
AA AA
A H
1
H A
M C C M
COMPRESSOR END FLOOR LINE MOTOR END
FRONT 2-PASS
OF
UNIT
NOZZLE
B J ARRANGEMENTS
C K NUMBER OF EVAPORATOR
DD DD
BB BB
PASSES IN OUT
C B
2
K J
M C C M
COMPRESSOR END FLOOR LINE MOTOR END
FRONT 3-PASS
OF
UNIT
NOZZLE
F N
ARRANGEMENTS
DD G P DD NUMBER OF EVAPORATOR
BB BB
PASSES IN OUT
G N
3
M C C M
P F
COMPRESSOR END FLOOR LINE MOTOR END LD07598a LD07598a
JOHNSON CONTROLS 33
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
SHELL 1 PASS
CODES IN OUT
AA HH
M–Z
HH AA
SHELL 2 PASS
CODES IN OUT
CC BB
M,N,P,Q
KK JJ
SHELL 2 PASS
CODES IN OUT
DD CC
R,S,W, EE BB
X and Z LL KK
MM JJ
SHELL 3 PASS
CODES IN OUT
GG NN
M–Z
PP FF
LD07173c
34 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
2
NOZZLE
ARRANGEMENTS
NUMBER CONDENSER
OF PASSES IN OUT
P Q
1
Q P
NOZZLE
ARRANGEMENTS
NUMBER CONDENSER
OF PASSES IN OUT
R S
2
T U
NOZZLE
ARRANGEMENTS
NUMBER CONDENSER
OF PASSES IN OUT
V Y
3
X W
LD07131a
JOHNSON CONTROLS 35
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
NOZZLE
L R ARRANGEMENTS
NUMBER CONDENSER
OF PASSES IN OUT
PP QG
1
QQ PP
L R NOZZLE
ARRANGEMENTS
NUMBER CONDENSER
OF PASSES IN OUT
RR SS
2
TT UU
L R NOZZLE
ARRANGEMENTS
NUMBER CONDENSER
OF PASSES IN OUT
VV YY
3
XX WW
LD07131d
36 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
Front
D of Unit D
1 PASS 2
Heat Heat
NOZZLE
Heat
Recovery
Recovery
EE FF Heat
Recovery
Recovery
ARRANGEMENTS
L IN OUT
Cooling Cooling
Cooling
Tower P Q Cooling
Tower HEAT EE FF
Tower Tower
K
RECOVERY FF EE
C C
L L COOLING P Q
M TOWER Q P
Compressor End Motor End
2 PASS
I Front I NOZZLE
I of Unit I
ARRANGEMENTS
IN OUT
Heat Heat
Heat
Recovery AA BB CC DD Heat
Recovery AA BB
Recovery Recovery
HEAT BB AA
Cooling
L
Cooling RECOVERY CC DD
Cooling
Tower
Tower
R S T U Cooling
Tower
Tower
DD CC
C K
C
R S
L L COOLING S R
M D D TOWER T U
Compressor End Motor End U T
Front
D of Unit D 2 PASS
NOZZLE
Heat Heat ARRANGEMENTS
Heat
Recovery GG HH Heat
Recovery
Recovery Recovery IN OUT
L
Cooling
HEAT GG HH
Cooling
Cooling
Tower V Y Cooling
Tower RECOVERY HH GG
Tower Tower
C K COOLING V Y
L C
L TOWER Y V
M
Compressor End Motor End
LD07131c
JOHNSON CONTROLS 37
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
EVAPORATOR
1-PASS
IN OUT
1 6
6 1
EVAPORATOR
2-PASS
IN OUT
2 3
7 8
F
EVAPORATOR
3-PASS (2-PASS RETURN HEAD)
IN OUT
5 10 LD01342c
9 4
38 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
CONDENSER
2-PASS
IN OUT
12 13 TUBE TUBE
SHEET SHEET
17 18
CONDENSER (2-PASS
3-PASS RETURN HEAD)
IN OUT
LD07177
15 20
19 14
JOHNSON CONTROLS 39
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
LD07175a
LD07175a
40 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
LD07178a
LD07178a
MARINE WATER BOXES – 150 PSI ROUND
NOZZLE PIPE SIZE
CONDENSER IN (MM) NUMBER OF 1-PASS 2-PASS 3-PASS
SHELL CODE PASSES
1 2 3 D S5 S5 T5 U S5 T5 U
10" 6" 6" 1'-3" 3'-11" 3'-11" 1'-8" 1'-3 3/8" 3'-11" 1'-8" 1'-3 3/8"
A
(254) (152) (152) (381) (1,194) (1,194) (508) (391) (1,194) (508) (391)
12" 8" 6" 1'-3 1/2" 4'-3" 4'-3" 1'-8" 1'-6 1/2" 4'-3" 1'-8" 1'-6 1/2"
C,D
(305) (203) (152) (394) (1,295) (1,295) (508) (470) (1295) (508) (470)
14" 10" 8" 1'-5 1/2" 4'-7" 4'-7" 1'-10" 1'-9" 4'-7" 1'-10" 1'-9"
E,F
(356) (254) (203) (445) (1,397) (1,397) (559) (533) (1,397) (559) (533)
16" 10" 10" 1'-8" 5'-1" 5'-1" 1'-9" 1'-9 1/2" 5'-1" 1'-9" 1'-9 1/2"
J,K,L
(406) (254) (254) (508) (1,549) (1,549) (533) (546) (1,549) (533) (546)
20" 14" 10" 1'-11" 5'-9 7/8" 5'-9 7/8" 2'-4" 2'-1 1/2" 5'-9 7/8" 2'-4" 2'-1 1/2"
M,N
(508) (356) (254) (584) (1,775) (1,775) (711) (648) (1,775) (711) (648)
20" 16" 14" 2'-1 1/4" 6'-2 3/8" 6'-2 3/8" 2'-4 1/2" 2'-5 1/2" 6'-2 3/8" 2'-4 1/2" 2'-5 1/2"
P,Q
(508) (406) (356) (641) (1,889) (1,889_ (724) (749) (1,889) (724) (749)
20" 18" 14" 2'-3 1/2" 6'-7" 6'-7" 2'-6 1/2" 2'-8 1/2" 6'-7" 2'-6 1/2" 2'-8 1/2"
R,S
(508) (457) (356) (699) (2007) (2007) (775) (825) (2007) (775) (826)
24" 18" 16" 2'-5 1/2" 6'-10 1/4" 6'-10 1/4" 2'-6" 2'-10" 6'-10 1/4" 2'-6" 2'-10"
T,V,W
(610) (457) (406) (749) (2,089) (2,089) (762) (864) (2,089) (762) (864)
24" 20" 16" 2'-8" 7'-2" 7'-2" 2'-7 3/4" 2'-11 1/2" 7'-2" 2'-7 3/4" 2'-11 1/2"
X,Z
(610) (508) (406) (813) ( 2184) ( 2184) ( 806) (902) (2184 ) (806) (902)
JOHNSON CONTROLS 41
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
CONDENSERS MARINE WATERBOXES HEAT RECOVERY UNITS - MAIN (TOWER) CIRCUIT ONLY
Front
D of U nit D
M U U M
11 16
V Front Front V
S S
D CL of U nit CL D D of U nit D
M U U M
13 V Front Front V 18
D of U nit D D of U nit D
12 17
S S
T CL CL CL CL T
T T
M U M M U M
13 C om pressor End M otor End C om pressor End M otor End 18
LD18181
12 17
S CONDENSER 3-PASS
COOLING WATER S
CL CL CL
T
T NOZZLECL T
Front IN OUT Front T
OPTIONS
of U nit of U nit
M UD V M M V DU M
12 13
C om pressor End 2 PASS
M otor End C om pressor End M otor End
17 18
3-PASS
Front 20 14 Front
of U nit of U nit
D V V D
15 19
S S S
T CL CL CL CL T
T T
M U D M M D U M
C om pressor End M otor End 20 C om pressor End
14 M otor End
15 19
S S S
T CL CL CL CL T
T T
M U D M M D U M
C om pressor End M otor End C om pressor End M otor End LD18181
15 20
3 PASS
19 14
42 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
CONDENSERS MARINE WATERBOXES HEAT RECOVERY UNITS - MAIN (TOWER) CIRCUIT ONLY
2 PASS
1 2 3 D S T U V
10" 8" 6" 1'-8 7/8" 2'-3 7/16" 1'-1 15/16" 2'-4 3/4" 2'-7 1/8"
B
(254) (203) (152) (530) (697) (338) (730) (790)
14" 10" 8" 1'-11 3/8" 2'-4 1/2" 1'-1" 2'-5 1/8" 2'-10 5/8"
I
(355) (254) (203) (593) (723) (330) (740) (879)
16" 12" 10" 2'-3 3/8" 2'-7 1/8" 1'-1 3/8" 2'-10 1/4" 3'-4 1/2"
O
(406) (305) (254) (695) (790) (339) (870) (1029)
18" 14" 10" 2'-4 1/2" 3'-6 9/16" 1'-11 3/16" 3'-1 7/8" 3'-7 1/2"
U
(457) (355) (254) (723) (1081) (589) (962) (1105)
24" 20" 16" 3'-4" 4'-2 5/16" 1'-10 5/16" 4'-4 3/4" 4'-11 11/16"
Y
(610) (508) (406) (1016) (1278) (582) (1340) (1516)
3 PASS
1 2 3 D S T U V
10" 8" 6" 1'-8 7/8" 2'-4 1/2" 1'-5 1/2" 2'-6 3/4" 2'-6 3/4"
B
(254) (203) (152) (530) (723) (444) (780) (780)
14" 10" 8" 1'-11 3/8" 2'-5 1/2" 1'-6 3/8" 2'-9 1/8" 2'-9 1/8"
I
(355) (254) (203) (593) (749) (466) (841) (841)
16" 12" 10" 2'-3 3/8" 2'-8 3/8" 1'-7 5/8" 3'-1 7/8" 3'-1 7/8"
O
(406) (305) (254) (695) (822) (498) (962) (962)
18" 14" 10" 2'-4 1/2" 3'-8 3/16" 2'-5 15/16" 3'-0 11/16" 3'-3"
U
(457) (355) (254) (723) (1122) (760) (932) (991)
24" 20" 16" 3'-4" 4'-4 5/16" 2'-7 7/16" 4'-2 1/16" 4'-6 13/16"
Y
(610) (508) (406) (1016) (1328) (798) (1271) (1392)
JOHNSON CONTROLS 43
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
Table 2 - APPROXIMATE UNIT WEIGHT INCLUDING MOTOR FOR FLOODED EVAPORATOR UNITS -
LB (KG)
SHIPPING ESTIMATE
OPERATING WEIGHT
SHELLS COMPRESSOR WEIGHT REFRIGERANT
LBS (KGS)
LBS (KGS) CHARGE LBS (KGS)
A-A Q3 13,100 (5,942) 15,000 (6,804) 810 (367)
C-B Q4 18,023 (8,175) 22,323 (10,126) 1,525 (692)
C-C Q3, Q4 14,920 (6,768) 17,940 (8,138) 1,240 (562)
C-C Q5 15,330 (6,954) 18,350 (8,324) 1,240 (562)
D-D Q3, Q4 17,215 (7,809) 21,100 (9,571) 1,680 (762)
D-D Q5 17,625 (7,995) 21,510 (9,757) 1,680 (762)
E-E Q3, Q4 17,950 (8,142) 22,160 (10,052) 1,710 (776)
E-E Q5,Q6,Q7,P7 18,360 (8,328) 22,570 (10,238) 1,710 (776)
E-I Q7 23,567 (10,690) 29,384 (13,328) 1,805 (819)
F-F Q5,Q6,Q7,P7 18,720 (8,491) 23,880 (10,832) 2,175 (987)
G-E P8 20,300 (9,208) 24,200 (10,977) 1,990 (903)
H-F P8,P9 23,100 (10,478) 28,000 (12,701) 2,610 (1,184)
J-J P8,P9 24,000 (10,886) 29,100 (13,200) 2,550 (1,157)
L-L P8,P9 27,400 (12,429) 33,900 (15,377) 3,165 (1,436)
K-K H9 28,530 (12,941) 36,000 (16,329) 2,925 (1,327)
K-K K1 31,100 (14,107) 36,200 (16,420) 3,248 (1,473)
K-O H9 34,483 (15,641) 44,776 (20,310) 3,260 (1,479)
M-M H9 34,200(15,513) 43,600 (19,777) 3,665 (1,662)
M-M K1,K2 38,300 (17,373) 47,100 (21,364) 3,665 (1,662)
M-U K2 45,178 (20,493) 58,017 (26,316) 3,540 (1,606)
N-N K1,K2 28,530 (18,549) 50,800 (23,043) 4,225 (1,916)
N-N K3 48,000 (21,773) 54,100 (24,540) 4,225 (1,916)
P-P K1,K2 41,500 (18,824) 51,900 (23,542) 3,855 (1,749)
Q-Q K1,K2 45,300 (20,548) 56,800 (25,764) 4,255 (1,930)
Q-Q K3 46,000 (20,865) 60,200 (27,307) 4,255 (1,930)
R-R K3 52,800 (23,950) 70,300 (31,888) 4,660 (2,114)
R-R K4 53,000 (24,041) 70,600 (32,034) 4,785 (2,170)
S-S K4 59,000 (26,672) 76,300 (34,609) 4,940 (2,241)
S-V K4 60,100 (27,261) 81,300 (36,877) 5,500 (2,495)
X-T K4 59,200 (26,853) 80,000 (36,288) 5,125 (2,325)
X-X K4 66,000 (29,937) 87,000 (39,463) 5,625 (2,551)
W-W K7 79,500 (36,061) 104,000 (47,174) 6,900 (3,130)
Z-Y K7 95,300 (43,196) 123,015 (55,799) 6,555 (2,973)
Z-Z K7 80,500 (36,515) 105,000 (47,628) 6,275 (2,846)
NOTE: Refrigerant charge quantity and weights will vary based on tube count, configuration, and chiller performance. Use for reference only.
Refer to YORKworks Performance Page or chiller nameplate for actual charge requirement.
44 JOHNSON CONTROLS
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
Table 3 - APPROXIMATE UNIT WEIGHT INCLUDING MOTOR FOR HYBRID FALLING FILM EVAPORATOR
UNITS - LB (KG)
SHIPPING WEIGHT OPERATING WEIGHT EST. REFRIGERANT
SHELLS COMPRESSOR
LBS. (KGS) LBS. (KGS) CHARGE LBS. (KGS)
2
A-A Q3 12,850 (5584) 14,419 (6266) 695 (302)
C-C Q3, Q4 14,570 (6331) 16,848 (7321) 875 (380)
C-C Q5 15,000 (6518) 17,278 (7508) 875 (380)
D-D Q4 17,000 (7387) 20,051 (8713) 1,180 (513)
D-D Q5 17,410 (7565) 20,461 (8891) 1,180 (513)
E-E Q5, Q6, Q7, P7 18,700 (8126) 21,700 (9429) 1,120 (487)
F-F Q5, Q6, Q7, P7 19,220 (8352) 23,142 (10056) 1,415 (615)
G-E P8, P9 20,640 (8969) 24,036 (10445) 1,320 (574)
H-F P8, P9 23,540 (10229) 28,083 (12203) 1,775 (771)
I-K H9 28,849 (12536) 34,078 (14808) 1,820 (791)
K-K H9 28,850 (12536) 34,079 (14809) 1,820 (791)
I-K K1 31,350 (13623) 35,145 (15272) 1,820 (791)
M-M K1, K2 34,520 (15000) 46,055 (20013) 2,300 (999)
N-N K1, K2 41,273 (17935) 49,605 (21555) 2,650 (1152)
N-N K3 48,380 (21023) 52,905 (22989) 2,650 (1152)
P-P K1, K2 41,950 (18229) 51,595 (22420) 3,100 (1347)
Q-Q K1, K2 45,800 (19902) 56,545 (24571) 3,500 (1521)
Q-Q K3 46,500 (20206) 59,945 (26048) 3,500 (1521)
NOTE: Refrigerant charge quantity and weights will vary based on tube count, configuration, and chiller performance. Use for reference only.
Refer to YORKworks Performance Page or chiller nameplate for actual charge requirement.
JOHNSON CONTROLS 45
FORM 160.75-N1
Section 2 - Installation
ISSUE DATE: 04/15/2019
46 JOHNSON CONTROLS
FORM 160.75-N1
ISSUE DATE: 04/15/2019
TEMPERATURE
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 7.22°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range
JOHNSON CONTROLS 47
5000 Renaissance Drive, New Freedom, Pennsylvania USA 17349 1-800-524-1330 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2019 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 160.75-N1 (419)
Issue Date: April 15, 2019
Supersedes: 160.75-N1 (1217)