May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 1


Focus Controller

• Overview of Capabilities • Base Load Switching


• Focus Hardware • Leak Detection
• Focus Interface • Software Updates
• Parameters • Modules
• Faults

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 2


Focus Basics

General Capabilities
All Ratio Capabilities, Plus:
• Control of 1-4 Compressors via Integrated ModBus
• Control of VFD Setpoint in SF Machines

• Efficiency Display
• Leak Detection Mode
• Clock/Sequencer Function
• More User-Friendly Interface
• Two Remote-Switchable Pressure Profiles
• Multiple Add-On Modules to Expand Capabilities Further

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 3


Focus Basics

Focus Hardware

Focus TAN
Display Module

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 4


Focus Basics

Focus Hardware
Focus Base Module

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 5


Focus Basics

Focus Hardware
Additional Modules

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 6


Focus Controller

Focus Interface

Net/Line Pressure Air End


Temperature

Compressor Status

Press Right Arrow for Next Screen

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 7


Focus Controller

Focus Interface
Sump/System
Net/Line Pressure Pressure

Compressor Status

Press Right Arrow for Next Screen

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 8


Focus Controller

Focus Interface

Hours Until Motor


Servicing Due
Load Cycles Until
Separator
Servicing Due
Hours Until
Compressor
Servicing Due Battery Voltage
>2.8v is Normal

Press Right Arrow for Next Screen

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 9


Focus Controller

Focus Interface

Total Hours Efficiency

Idle Hours
Load Cycles

Up Arrow for Leakage Monitor Right Arrow for Next Screen

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 10


Focus Controller

Focus Interface

ModBus Status

Release Type

Key Switch Status

Auto Restart
After Power Loss
Delay

Press Right Arrow for Next Screen

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 11


Focus Controller

Focus Interface

Pressure Range

Net Pressure Timer Status

Sequencer Status

Press Right Arrow for Next Screen

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 12


Focus Controller

Focus Interface

Hold Enter to
Change Date/Time

Press Right Arrow for Next Screen

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 13


Focus Controller

Focus Interface

Software Version

Press Enter for Press Right Arrow


Code Entry for Main Screen

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 14


Focus Controller

Focus Interface

Use Navi Keys to


Enter Access Code

Press Enter

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 15


Focus Controller

Focus Interface

Parameter Access

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 16


Focus Controller

Focus Interface
Parameter Access

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 17


Focus Controller

Focus Parameters

Parameter List in Functional Description

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 18


Focus Controller

Focus Faults

Fault Table

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 19


FOCUS base load switch (BLS)

FOCUS base load switch

- Integrated BLS for up to 4 machines (via RS485 / optional relay module)


- Modular expendability (max. 5 additional modules)

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 20


Focus Controller

Base Load Switching

RS485 RS485 RS485

BLS is Intended to Sequence/Cycle 4 Machines of the Same or Similar Size

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 21


Focus Controller

Base Load Switching


Wiring

51 GND

52 RS485 +

53 RS485 -

120ohm Termination Resistor Jumper

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 22


FOCUS base load switch (BLS)

Base load switch only by RS 485


3 3 3

+ RS485 Interface + RS485 Interface

FOCUS RATIO FOCUS RATIO

Bus address Bus address Bus address Bus address


“0” “2” “3” “4”
MASTER SLAVE SLAVE SLAVE
May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 23
FOCUS base load switch (BLS)

Base load switch only by contact (Relay module)

Contact

2
2

2
Output release Output release Output release

Other
FOCUS RATIO BASIC
brand
+ 3x Relay
module

Relay address Relay address Relay address


“2” “3” “4”
SLAVE SLAVE SLAVE
May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 24
FOCUS base load switch (BLS)

Base load switch with combination of contact and RS 485

Contact

2
3

2
RS 485
Output release Output release

Autotronic Other
FOCUS FOCUS
brand
+ 2x Relay
module

Bus address Bus address Relay address Relay address


“0” “2” “3” “4”
MASTER SLAVE SLAVE SLAVE
May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 25
Example parameters for base load switch

9.7 bar C1
9.6 bar C 2 Pressure switch points
9.5 bar C 3 BLS

9.0 bar Pressure switch points


8.7 bar C 1 compressors
8.5 bar C2
8.3 bar C3
8.0 bar
- The cut in and cut off pressures of the compressors must be above the values of the BLS
- The machine switching points of the machines should be cascaded
- A differential pressure between pressure transducers of machines and BLS must be
- considered during adjustment of machine pressure settings
May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 26
Example parameters for base load switch

Cut in and cut off characteristic of the BLS

9.0 bar
• • Priority 1
Priority 2
Priority 1 • Priority 3
• • Priority 4
Priority 2
• Priority 3
• Priority 4
8.0 bar •

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 27


Example parameters for base load switch

Example with only bus-compatible controllers


3 3 3

RS485

+ RS485 Interface + RS485 Interface

FOCUS FOCUS RATIO RATIO

- The RATIO controller must be equipped with the RS 485 BUS Interface
- The machines need to be connected from controller to controller
- Connection sequence in any direction is possible - the Bus address defines the Compressor
- At great cable length a resistor (120 Ω) must be set on both ends of the line
- The pressure control must be active on all „Slave-Machines“ (Bridge on X2:18/19)
May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 28
Example parameters for base load switch

BLS
(Priority change based on hours)
by only RS485 connection with FOCUS

Requirements:
- 4 Machines connected (2x FOCUS and 2x RATIO)
- all machines on the same or similar size
- 7 hours changeover
- Pressure range of installation 8bar - 9bar

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 29


Example parameters for base load switch
RS485

3
3

3
FOCUS +Interface +Interface

FOCUS RATIO RATIO

MASTER SLAVE SLAVE SLAVE

Parameter settings of FOCUS “Master” machine


P012 9.0bar Cut off pressure Operating range of
P013 8.0bar Cut in pressure base load switch
P050 0 Modbus address MASTER = „ 0 „
P051 9600 Modbus baud rate MASTER = SLAVE
P052 8E1 Modbus communication parameter MASTER = SLAVE
P070 4 Number of connected machines
P071 7hrs base-change cycle in hours

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 30


Example parameters for base load switch
RS485

3
3
FOCUS +Interface +Interface

FOCUS RATIO RATIO

SLAVE

Parameter settings of FOCUS “Slave” machine


P012 9.3bar Cut off pressure Operating range for
P013 8.3bar Cut in pressure failure of BLS
P050 2 Modbus address SLAVE = „ 2 „
P051 9600 Modbus baud rate MASTER = SLAVE
P052 8E1 Modbus communication parameter MASTER = SLAVE
P063 2 External release via Bus MASTER controls SLAVE

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 31


Example parameters for base load switch
RS485

3
3
+ RS485 Interface

RATIO +Interface

FOCUS FOCUS RATIO

SLAVE

Parameter settings of RATIO “Slave” machine


CODE 9.5bar Cut off pressure Operating range for
360 8.5bar Cut in pressure failure of BLS
CODE 3 Modbus address SLAVE = „ 3 „
830 96 Modbus baud rate MASTER = SLAVE
8E1 Modbus communication parameter MASTER = SLAVE
CODE 2 External release via Bus MASTER controls SLAVE
210

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 32


Example parameters for base load switch
RS485

3
3

3
+ RS485 Interface

+Interface RATIO
FOCUS FOCUS RATIO

SLAVE

Parameter settings of RATIO “Slave” machine


CODE 9.7bar Cut off pressure Operating range for
360 8.7bar Cut in pressure failure of BLS
CODE 4 Modbus address SLAVE = „ 4 „
830 96 Modbus baud rate MASTER = SLAVE
8E1 Modbus communication parameter MASTER = SLAVE
CODE 2 External release via Bus MASTER controls SLAVE
210

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 33


Example parameters for base load switch
RS485

3
3

3
+ RS485 Interface + RS485 Interface

FOCUS FOCUS RATIO RATIO

P012 9.0bar P012 9.3bar Code 360 Code 360


P013 8.0bar P013 8.3bar 9.5bar / 8.5bar 9.7bar / 8.7bar
P050 0 P050 2 Code 830 Code 830
P051 9600 P051 9600 3 / 96 / 8E1 4 / 96 / 8E1
P052 8E1 P052 8E1 Code 210 Code 210
P070 4 P063 2 2 2
P071 7hrs

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 34


Example parameters for base load switch

BLS
(Priority change based on hours)
by only relay module connection with FOCUS

Requirements:
- 4 machines connected (1x FOCUS, 1x RATIO, 1x BASIC
and 1x Other brand controller)
- all machines on the same or similar size
- 23 hours changeover
- Pressure range of installation 8bar - 9bar
May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 35
Example parameters for base load switch

Signal line
Contact

2
2
Output release Output release Output release

FOCUS RATIO BASIC Other


+ 3x Relay brand
module

- The FOCUS Master machine must be equipped with the relay modules for the
- connected compressors
- Every single relay module has to be connected to the output release of the machines
- Every single relay module must be configured with it’s own rotary switch
- The cable length should not be longer then 50m
May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 36
Example parameters for base load switch

Contact

2
2
FOCUS
RATIO BASIC Other
brand

MASTER
Parameter settings of FOCUS “Master” machine
P012 9.0bar Cut off pressure Operating range of
P013 8.0bar Cut in pressure base load switch
P070 4 Number of connected machines
P071 23hrs base-change cycle in hours

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 37


Example parameters for base load switch

Contact

2
RATIO
FOCUS BASIC Other
brand

SLAVE
Parameter settings of RATIO “Slave” machine
CODE 9.3bar Cut off pressure Operating range for
360 8.3bar Cut in pressure failure of BLS
CODE 1 External release via contact MASTER controls SLAVE
210

The Relay module in the switch cabinet of the “master machine”, has to be configured to „2“.

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 38


Example parameters for base load switch

Contact

2
2
BASIC
FOCUS RATIO Other
brand

SLAVE
Parameter settings of BASIC “Slave” machine
CODE 9.5bar Cut off pressure Operating range for
360 8.5bar Cut in pressure failure of BLS
CODE 1 External release via contact MASTER controls SLAVE
210

The Relay module in the switch cabinet of the “master machine”, has to be configured to „3“.

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 39


Example parameters for base load switch

Contact

2
2
2
Other
FOCUS RATIO BASIC
brand

SLAVE
Parameter settings of other brand “Slave” machine
9.7bar Cut off pressure Operating range for
8.7bar Cut in pressure failure of BLS
External release via contact MASTER controls SLAVE

The Relay module in the switch cabinet of the “master machine”, has to be configured to „4“.

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 40


Example parameters for base load switch

Signal line
Contact

2
2
Output release Output release Output release

FOCUS RATIO BASIC Other


+ 3x Relay brand
module

P012 9.0bar Code 360: Code 360: Pressure settings:


P013 8.0bar 9.3bar / 8.3bar 9.5bar / 8.5bar 9.7bar / 8.7bar
P070 4 Code 210: Code 210: Output release:
P071 23hrs 1 1 active

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 41


Example parameters for base load switch

Contact

2
2
Output release Output release Output release

FOCUS RATIO BASIC Other


+ 3x Relay brand
module

Settings of rotary
switches of relay
modules

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 42


Example parameters for base load switch

BLS
(Clock switch based priority change)
by combination of contact and RS485
with FOCUS
Requirements:
- 4 machines connected ( 1x FOCUS 55 kW, 1x FOCUS 37 kW,
- 1x Autotronic 22 kW und 1x “other brand” 37 kW
- Working time: 6.00Uhr to 19.30Uhr

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 43


Example parameters for base load switch

BLS
(Clock switch based priority change)
by combination of contact and RS485
with FOCUS
- Pressure range of installation 10.5bar - 11.5bar
- The 55 kW machine is frequency controlled
- The 55 kW compressor is base load machine
- Both 37 kW compressors are peak load machines
- The 22 kW compressor is a reserve machine

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 44


Example parameters for base load switch

Contact
RS485

2
3
Output release Output release

FOCUS FOCUS Autotronic Other


+ 2x Relay brand
module

- The FOCUS machines are connected from controller to controller


- The FOCUS must be equipped with two relay modules
- Every single relay module must be configured with it’s own rotary switch
- Every single relay module has to be connected to the output release of the machines
- The cable length should not be longer then 50m from relay module to machine controller
- On great cable length resistor terminator (120 Ω) has to be set on the end of the bus
- The pressure control must be active on all „Slave-Machines“ (Bridge on X2:18/19)
May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 45
Example parameters for base load switch

Contact
RS485

2
3
FOCUS
FOCUS FOCUS Auto-
BASIC Other
tronic brand

MASTER
Parameter settings of FOCUS “Master” machine
P012 11.5bar Cut off pressure Operating range of
P013 10,5bar Cut in pressure base load switch
P050 0 Modbus address MASTER = „ 0 „
P051 9600 Modbus baud rate MASTER = SLAVE
P052 8E1 Modbus communication parameter MASTER = SLAVE
P070 4 Number of connected machines
P071 0hrs base-change cycle = “0” deactivates BLS based on hours

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 46


Example parameters for base load switch

Contact
RS485

2
3
FOCUS
FOCUS FOCUS Auto-
BASIC Other
tronic brand

MASTER
Clock switch settings of FOCUS “Master” machine
Canal A A Channel
Channel Canal C C Channel
Canal I I Channel
Canal K K
MO 6:00 DI 6:00
TU 6:00 FR 6:00 FR 16:00
1243 1423
1423 1423 3241
Canal D D • • • Canal
Canal B B Channel
Channel Channel
J J Channel
Canal K K
MO 19:30 TU DI 19:30
19:30 FR 11:00 FR 16:00
3241 3421 1243 0000
May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 47
Example parameters for base load switch

3
Contact
RS485

2
FOCUS
FOCUS Auto-
BASIC Other
tronic brand

SLAVE
Parameter settings of FOCUS “Slave” machine
P012 11.5bar Cut off pressure Operating range for
P013 10,5bar Cut in pressure failure of BLS
P050 2 Modbus address MASTER = „ 2 „
P051 9600 Modbus baud rate MASTER = SLAVE
P052 8E1 Modbus communication parameter MASTER = SLAVE
P063 2 External release via bus MASTER controls SLAVE

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 48


Example parameters for base load switch

Contact

2
RS485

2
3
Auto-
Other
FOCUS FOCUS
tronic brand

SLAVE
Parameter settings of Autotronic “Slave” machine
PS- 12bar Cut off pressure Operating range for
set. 11bar Cut in pressure failure of BLS
Contact to External release via Contact MASTER controls SLAVE
pressure switch

The Relay module in the switch cabinet of the “master machine”, has to be configured to „3“.

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 49


Example parameters for base load switch

Contact

2
RS485

2
3
Other
FOCUS FOCUS Auto-
BASIC brand
tronic

SLAVE
Parameter settings of other brand “Slave” machine
12.2bar Cut off pressure Operating range for
11.2bar Cut in pressure failure of BLS
External release via Contact MASTER controls SLAVE

The Relay module in the switch cabinet of the “master machine”, has to be configured to „4“.

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 50


Example parameters for base load switch

Contact
RS485

2
3

2
Output release Output release

FOCUS FOCUS Autotronic Other


+ 2x Relay brand
module

P012 11.5bar P012 11.8bar Pressure switch Pressure settings:


P013 10.5bar P013 10.8bar 12bar / 11bar 12.2bar / 11.2bar
P050 0 P050 2 Contact to Output release:
P051 9600 P051 9600 pressure switch active
P052 8E1 P052 8E1
P070 4 P063 2
P071 0hrs

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 51


Example parameters for base load switch

Contact
RS485

2
3

2
Output release Output release

FOCUS FOCUS Autotronic Other


+ 2x Relay brand
module

Settings of rotary
switches of relay
modules

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 52


Focus Controller

Leak Detection (>v1.15 Only)

Single Measurement Hours of Run Time


Used Only for Leaks

Continuous
Measurement

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 53


Focus Controller

Leak Detection (v1.15 Only)

Conditions:
• All Plant Usage Must be Off
• Compressors Must be Enabled / Green
• These conditions must remain for 6 hours

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 54


Focus Controller

Leak Detection (v1.15 Only)

Starting a Test:
1. Navigate to the Leak Detection Screen
2. Hold Enter for 2 secs, until “Le” starts flashing, then release Enter
3. Hold Enter for another 2 secs to initiate a 6hr test
4. After 6 hours, values will appear showing calculated wasted run
hours
5. The system will monitor in 6hr intervals, and will update the values if
a lower load period is detected

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 55


Focus Controller

Leak Detection (v1.15 Only)

Faults:
• 9999 = Power Failure
• 9990 = Loss of “Ready” Status

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 56


Focus Controller

Software Updates
Potential Damage to Focus Controller and PC

Follow Directions Exactly

NEVER Disconnect Flashing Cables With the


Focus Energized

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 57


Focus Controller

Software Updates
• Focus Flashing Device
and Serial Cable
Boge P/Ns:
659003101 & 681004805

• CS Manager +

• Laptop w/ Serial Port

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 58


Focus Controller

Software Updates
Remove Power from the Focus –
the Screen Must Turn Off

Breaker 4F is Sufficient

Main Panel Disconnect is Safest

The E-Stop Will Not Power Down


the Focus

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 59


Focus Controller

Software Updates

Connect Flash Device


Ground to Term 32

Connect the Flash Device


Cable to the Software
Update Port and the
Serial Cable to your PC

Disconnect the Digital


Outputs

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 60


Focus Controller

Software Updates

Disconnect the
Transformer Ground

Power On the Focus


Controller

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 61


Focus Controller

1. Restrict Selection 4 5
2. Identify
3. Ensure “Type” Turns
Green – Indicates Comm
4. Select Correct Program
and Version 2 1
5. Write to Flash
3

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 62


Focus Controller

Red Indicates a Comm


Problem

Check Cables, Port


Settings, and Power

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 63


Focus Controller

Software Updates
Wait for Flashing to Finish

Ignore Any Faults

De-energize the Focus

Wait 10 Seconds

May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 64


Focus Controller

Software Updates
After Waiting 10 Seconds:

1. Disconnect the Flash


Cable from the Focus Base
2. Connect the Flash Cable to
the Focus TAN
3. Energize the Focus and
Repeat the CSM+ Process
4. De-Energize
5. Wait 10 Seconds
6. Disconnect All Flash
Cables, Reconnect
Transformer Ground
May 2011 Advanced Training © BOGE KOMPRESSOREN 03.11.2011 65