You are on page 1of 40

Atlas Copco Stationary Air Compressors

GA5 - GA7 - GA10

Instruction Book

Important
1. This book applies exclusively to GA5 - GA7 - GA10 from following serial number onwards:

AII-119 500

2. This book must be used together with the "User manual for Elektronikon regulator for GA5 up to GA75"

This instruction book meets the requirements for instructions specified by the machinery directive
89/392/EEC and is valid for CE as well as non-CE labelled machines

No. 2920 1386 00

Registration code: APC G5-10/'98 / 38 / 999

1998-09 Web-site: http://www.atlascopco-compressors.com

*2920138600*
Instruction book

This instruction book describes how to handle the machines to ensure safe operation, optimum efficiency and long service life.

Read this book before putting the machine into operation to ensure correct handling, operation and proper maintenance from the
beginning. The maintenance schedule comprises measures for keeping the machine in good condition.

Keep the book available for the operator and make sure that the machine is operated and that maintenance is carried out according
to the instructions. Record all operating data, maintenance performed, etc. in an operator's logbook available from Atlas Copco.
Follow all relevant safety precautions, including those mentioned on the cover of this book.
Repairs must be carried out by trained personnel from Atlas Copco who can be contacted for any further information.

In all correspondence always mention the type and the serial number, shown on the data plate.

For all data not mentioned in the text, see sections "Preventive maintenance schedule" and "Principal data".
The company reserves the right to make changes without prior notice.

Contents
Page Page
1 Leading particulars . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3.4.5 Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
1.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . 3 3.5 For GA Standard Pack . . . . . . . . . . . . . . . . . . . . . 26
1.1.1 Compressor variants . . . . . . . . . . . . . . . . . . 3 3.5.1 Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
1.1.2 Main options-special versions . . . . . . . . . . . 4 3.5.2 During operation . . . . . . . . . . . . . . . . . . . . 26
1.1.3 Air flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3.5.3 Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1.1.4 Oil system . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3.6 Taking out of operation at end of compressor
1.1.5 Cooling and condensate drain systems . . . . 4 service life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1.2 Unloading/loading system . . . . . . . . . . . . . . . . . . . 4
1.2.1 Unloading . . . . . . . . . . . . . . . . . . . . . . . . . . 4 4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1.2.2 Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4.1 Drive motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1.3 Elektronikon regulator for GA Pack / 4.2 Preventive maintenance schedule for the
Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.3.1 Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4.3 Oil specifications . . . . . . . . . . . . . . . . . . . . . . . . . 30
1.3.2 Control panel . . . . . . . . . . . . . . . . . . . . . . . 11 4.3.1 Atlas Copco Roto-injectfluid . . . . . . . . . . 30
1.3.3 Function keys . . . . . . . . . . . . . . . . . . . . . . . 12 4.3.2 Mineral oil . . . . . . . . . . . . . . . . . . . . . . . . . 30
1.3.4 Menu-driven control programs . . . . . . . . . 12 4.4 Oil change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1.4 Regulator for GA Standard Pack . . . . . . . . . . . . . 13 4.5 Oil filter change . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1.4.1 Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . 13 4.6 Storage after installation . . . . . . . . . . . . . . . . . . . . 30
1.4.2 Control panel . . . . . . . . . . . . . . . . . . . . . . . 16 4.7 Service kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1.5 Air dryer on GA Full-feature . . . . . . . . . . . . . . . . 16 5 Adjustments and servicing procedures. . . . . . . . . . . 31
1.5.1 Compressed air circuit . . . . . . . . . . . . . . . . 16
5.1 Air filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1.5.2 Refrigerant circuit . . . . . . . . . . . . . . . . . . . 16
5.2 Coolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 5.3 Safety valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.1 Dimension drawings . . . . . . . . . . . . . . . . . . . . . . . 17 5.4 Safety devices of dryer on GA Full-feature . . . . . 31
2.2 Installation proposal . . . . . . . . . . . . . . . . . . . . . . . 18 5.5 Load/unload pressure switch on
2.3 Electric cable size . . . . . . . . . . . . . . . . . . . . . . . . . 22 GA Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . 31
2.4 Electrical connections . . . . . . . . . . . . . . . . . . . . . . 22 5.6 Temperature shut-down switch on
2.5 Pictographs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 GA Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . 32
5.7 Belt set exchange . . . . . . . . . . . . . . . . . . . . . . . . . 32
3 Operating instructions . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1 Before initial start-up . . . . . . . . . . . . . . . . . . . . . . 24 6 Problem solving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.1.1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7 Principal data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.1.2 User manual . . . . . . . . . . . . . . . . . . . . . . . . 24
7.1 Readings on display or gauges . . . . . . . . . . . . . . . 35
3.1.3 Outdoor/altitude operation . . . . . . . . . . . . 24 7.2 Settings of overload relay and fuses . . . . . . . . . . . 36
3.1.4 Remote compressor status indication
7.3 Settings of fan control switch (GA Full-feature) . 37
for GA Pack/Full-feature . . . . . . . . . . . . . . 24
7.4 Compressor specifications . . . . . . . . . . . . . . . . . . 37
3.1.5 Remote control for GA Pack/Full-feature . 24 7.4.1 Reference conditions . . . . . . . . . . . . . . . . . 37
3.1.6 Remote pressure sensing for GA Pack /
7.4.2 Limitations . . . . . . . . . . . . . . . . . . . . . . . . . 37
Full-feature . . . . . . . . . . . . . . . . . . . . . . . . 24
7.4.3 GA5 Pack . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.2 Initial start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 7.4.4 GA5 Full-feature . . . . . . . . . . . . . . . . . . . . 38
3.3 Before starting . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
7.4.5 GA7 Pack . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.4 For GA Pack / Full-feature . . . . . . . . . . . . . . . . . . 25
7.4.6 GA7 Full-feature . . . . . . . . . . . . . . . . . . . . 39
3.4.1 Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 7.4.7 GA10 Pack . . . . . . . . . . . . . . . . . . . . . . . . 39
3.4.2 During operation . . . . . . . . . . . . . . . . . . . . 25
7.4.8 GA10 Full-feature . . . . . . . . . . . . . . . . . . . 40
3.4.3 Checking the display . . . . . . . . . . . . . . . . . 25
7.5 Conversion list of SI units into US/British units . 40
3.4.4 Manual control . . . . . . . . . . . . . . . . . . . . . 26

2 2920 1386 00
Instruction book

1 Leading particulars

1.1 General description

GA are stationary, single-stage, oil-injected screw compressors GA Pack


driven by an electric motor. The compressors are air-cooled. GA Pack are enclosed in a sound-insulated bodywork. The
compressors are controlled by the Atlas Copco Elektronikon®
regulator. This electronic control module (E1) is fitted to the
1.1.1 Compressor variants (Fig. 1) door of the front panel. The Elektronikon regulator reduces
the power consumption and it allows the operator to easily
GA Standard Pack program and monitor the compressor. The control panel
GA Standard Pack are enclosed in a sound-insulated bodywork. includes the start, stop and emergency stop buttons.
The control panel (1) is fitted to the door at the front side. It
includes the start button and the stop/emergency stop button. An electric cabinet comprising the motor starter is located
behind this panel.
The relay-controlled regulator and the motor starter are located
in an electric cabinet behind the door. The compressors are provided with an automatic condensate
drain system.

E1
AV 1

2
2

50411F

50412F Dm Da

AV. Air outlet valve E1. Elektronikon regulator, GA Pack/Full-feature


Da. Automatic condensate drain outlet 1. Control panel, GA Standard Pack
Dm. Manual condensate drain valve 2. Service panel
Fig. 1. Front views

2920 1386 00 3
Instruction book

GA Full-feature The oil system is provided with a by-pass valve (BV). When
GA Full-feature are GA Pack compressors, additionally the oil temperature is below 65°C for GA5-7 or below 40°C
provided with an air dryer integrated in the bodywork. The for GA10, there is no oil flow to the oil cooler (Co). Air pressure
dryer removes moisture from the compressed air by cooling forces the oil from air receiver/oil separator (AR) through oil
the air to near freezing point and automatically draining the filter (OF) to compressor element (E) and the lubrication points.
condensate. See section 1.5. Oil cooler (Co) is by-passed. At approx. 80°C for GA5-7 or
approx. 55°C for GA10, all oil flows through the oil cooler.

1.1.2 Main options - special versions


1.1.5 Cooling and condensate drain systems
Full- Pack Standard (Figs. 4)
feature Pack
The cooling system comprises air cooler (Ca) and oil cooler
(Co). The cooling air is generated by fan (FN).
Integrated oil/water
separator (OSD) . . . . . . . 0 0 1) A condensate trap (MT) is provided in the air outlet system 3).
High ambient version The trap is equipped with a valve for automatic condensate
(up to 50°C) . . . . . . . . . . NA 0 0 draining during operation (Da-Fig. 1) and a manually operated
Lifting device . . . . . . . . . 0 0 0 valve for draining after stopping the compressor (Dm-Fig. 1).
Bodywork heating . . . . . 0 0 0
Rain protection . . . . . . . . 0 0 0
Heavy-duty filter . . . . . . 0 0 0
Modulating control 1.2 Unloading/loading system
regulator 2) . . . . . . . . . . . 0 0 0
Integrated condensate
separator (WSD) . . . . . . . S S 0 1.2.1 Unloading (Fig. 4b)
Integrated dryer . . . . . . . S 0 NA
Main power isolating If the air consumption is less than the air output of the
switch . . . . . . . . . . . . . . . 0 0 0 compressor, the net pressure increases. When the net pressure
Electronic drain . . . . . . . 0 0 0 reaches the unloading pressure, solenoid valve (Y1) is de-
Dryer by-pass . . . . . . . . . 0 NA NA energized. The plunger of the valve returns by spring force:
Relay expansion box . . . 0 0 NA
Unit on air receiver . . . . . 0 0 0 1. The control pressure present in the chambers of loading
Tropical thermostat plunger (LP) and unloading valve (UV) is vented to
(75-90°C) . . . . . . . . . . . . 0 0 0 atmosphere via solenoid valve (Y1).
2. Loading plunger (LP) moves upwards and causes inlet valve
(IV) to close the air inlet opening.
0 = optional S = standard NA = not available 3. Unloading valve (UV) is opened by receiver pressure. The
pressure from air receiver (AR) is released towards unloader
(UA).
4. The pressure is stabilized at a low value. A small amount
1.1.3 Air flow (Figs. 4) of air is kept drawn in through valve (BV1) and is blown to
the unloader.
Air drawn through filter (AF) and open inlet valve (IV) into
compressor element (E) is compressed. Compressed air and Air output is stopped (0 %), the compressor runs unloaded.
oil flow into air receiver/oil separator (AR). The air is
discharged through outlet valve (AV) via minimum pressure
valve (Vp), air cooler (Ca) and condensate trap (MT).

1.1.4 Oil system (Figs. 4)

In air receiver/oil separator (AR), most of the oil is removed


1) If an oil/water separator is desired, an integrated separator must
from the air/oil mixture centrifugally. The balance is removed be applied.
by oil separator element (OS). The oil collects in the lower 2) Not for GA5.
part of air receiver/oil separator (AR), which serves as oil tank. 3) Available as an option for GA Standard Pack.

4 2920 1386 00
Instruction book

OF 1 AR. Air receiver/oil separator


DP. Oil drain plug
FC. Oil filler plug
Gl. Oil level gauge
M1. Drive motor
OF. Oil filter
OS. Oil separator element
1. Dryer
2. Arrow, motor rotation direction

Fig. 2. GA Full-feature

50413F

FC M1 AR DP OS Gl 2 PSR19 Ca/Co OF

AR. Air receiver/oil separator


Ca. Air cooler
Co. Oil cooler
DP. Oil drain plug
FC. Oil filler plug
Gl. Oil level gauge
M1. Drive motor
OF. Oil filter
OS. Oil separator element 50414F
PSR19. Load/unload switch
FC M1 AR DP OS Gl
Fig. 3. GA Standard Pack

2920 1386 00 5
Instruction book

Fig. 4a. GA5/7/10 Full-feature during loading

6 2920 1386 00
Instruction book

Fig. 4b. GA5/7/10 Pack during unloading

AF. Air filter Gl. Oil level gauge 2. Flexible, blow-off air or control air
AR. Air receiver/oil separator IV. Inlet valve 3. Belts
AV. Air outlet valve LP. Loading plunger
BV. Oil cooler by-pass valve MT. Air cooler moisture trap On Full-feature also:
BV1. By-pass valve M1. Drive motor M1. Refrigerant compressor
CV. Check valve OF. Oil filter M2. Motor, condenser fan
Ca. Air cooler OS. Oil separator element S3. Condenser fan control switch
Co. Oil cooler PT20. Pressure sensor, air outlet TT90. Temperature sensor, dewpoint
Da. Automatic condensate drain SV. Safety valve 5. Air/air heat exchanger
outlet TT11. Temperature sensor, 6. Filter
Dm. Manual condensate drain valve compressor element outlet 7. Capillary tube
DP. Oil drain plug UA. Unloader 8. Fan, condenser
E. Compressor element UV. Unloading valve 9. Condenser
E1. Elektronikon regulator Y1. Loading solenoid valve 10. Hot gas by-pass valve
FC. Oil filler plug 1. Flexible, oil scavenge 11. Air/refrigerant heat exchanger
FN. Fan, coolers (evaporator)
Figs. 4. Air-oil and unloading-loading systems

2920 1386 00 7
Instruction book

1.2.2 Loading (Fig. 4a)


K11
When the net pressure decreases to the loading pressure,
solenoid valve (Y1) is energized. The plunger of solenoid valve
(Y1) moves against spring force: T2
1X1
1. Control pressure is fed from air receiver (AR) via solenoid
valve (Y1) to loading plunger (LP) and unloading valve
(UV).
2. Unloading valve (UV) closes the air blow-off opening.
Loading plunger (LP) moves downwards and causes inlet T1 F4/5/6
valve (IV) to open fully.

Air output is resumed (100 %), the compressor runs loaded.


F2
F1
1.3 Elektronikon regulator for GA Pack /
K22
Full-feature

The control system consists of an electronic regulator and a K23


control panel.
F21 K21

1.3.1 Regulator (E1-Fig. 1)


50415F
Automatic control of the compressor
See Fig. 6 for denomination of components
The regulator maintains the net pressure between programmable
limits by automatically loading and unloading the compressor. Fig. 5. Electric cabinet, GA Pack / Full-feature (typical
A number of programmable settings, e.g. the unloading and example)
loading pressures, the minimum stop time and the maximum
number of motor starts are taken into account.

SENSORS/SOLENOID VALVES/ ELECTRIC CABINET K01. Blocking relay


ELECTRONIC DRAIN F1/F8. Fuses K02. Auxiliary relay, star contactor
B1. Electronically-controlled con- F21. Overload relay, drive motor K03. Auxiliary relay, delta contactor
densate drain (type Bekomat) 1) K11. Auxiliary contactor for dryer 2) K04. Auxiliary relay, loading/
PT20. Pressure sensor, air outlet K21. Line contactor unloading
TT11. Temperature sensor, compressor K22. Star contactor K05. Auxiliary relay, high/low air
element outlet K23. Delta contactor pressure
TT90. Temperature sensor, dewpoint 2) T1/T3.Transformers K10. Auxiliary relay, dryer
Y1. Loading solenoid valve 1X1. Terminal strip O. Stop button
S3. Emergency stop button
MOTORS CONTROL MODULE (E1)
M1. Drive motor I. Start button DRYER ON FULL-FEATURE (A1)

1) Available as an option
2) Only for Full-feature compressors

Fig. 6. Electrical diagram, GA Pack / Full-feature 50 Hz with star-delta starter

8 2920 1386 00
Instruction book

2920 1386 00 9
Instruction book

The regulator stops the compressor whenever possible to reduce Protecting the compressor
the power consumption and restarts it automatically when the
net pressure decreases. In case the expected stopping period is Shut-down
too short, the compressor is kept running to prevent too-short If the compressor element outlet temperature exceeds the
standstill periods. programmed shut-down level, the compressor will be stopped.
This will be indicated on display (4-Fig. 8). The compressor
Warning A number of time-based automatic start/stop will also be stopped in case of overload of drive motor (M1).
commands may be programmed. 1) Take into
account that a start command will be executed (if Shut-down warning
programmed and activated), even after manually If the compressor element outlet temperature exceeds a
stopping the compressor. programmed value below the shut-down level, this will also be
indicated to warn the operator before the shut-down level is
reached.

Monitoring components subject to service

The regulator continuously monitors the oil, oil filter, oil


separator and air filter.

Service warning
Each input is compared to programmed limits. If these limits
are exceeded, a message will appear on display (4-Fig. 8) to
warn the operator to replace the indicated component.

Automatic restart after voltage failure

For compressors leaving the factory, this function is made


inactive. If desired, the function can be activated. Consult
Atlas Copco.

Warning If activated and provided the module was in the


automatic operation mode, the compressor will
automatically restart if the supply voltage to the
module is restored within a programmed time
period.

The power recovery time (the period within which


the voltage must be restored to have an automatic
restart) can be set between 1 and 254 seconds or
to symbol 00!. If the power recovery time is set
to 00!, the compressor will always restart after a
voltage failure, no matter how long it takes to
restore the voltage.

F0. Fuses (customer's installation)


M1. Refrigerant compressor
M2. Motor, condenser fan
S3. Condenser fan control switch
1) See User manual for Elektronikon regulator, section "Timer
Fig. 7 Electrical diagram, dryer on GA Full-feature submenu".

10 2920 1386 00
Instruction book

1.3.2 Control panel (Fig. 8)

Ref. Designation Function Ref. Designation Function

1 Automatic Indicates that the regulator is auto- 4 Display Indicates messages concerning the
operation LED matically controlling the compressor operating condition, a
compressor: the compressor is service need or a fault. Consult
loaded, unloaded, stopped and section 3.4 and the User manual
restarted depending on the air for Elektronikon regulator,
consumption and the limitations sections "Main display", "Main
programmed in the regulator. menu", "Status data submenu" and
"Service submenu".
2 Voltage on LED Indicates that the voltage is
switched on. 5 Function keys Keys to control and program the
compressor. See section 1.3.3.
3 General alarm LED Is alight if a service warning or
shut-down warning condition 6 Scroll keys Keys to scroll through the display.
exists or if a sensor is out of order.
Blinks if a shut-down condition 7 Tabulator key Key to go to the next field of the
exists, if a sensor is out of order display.
or after an emergency stop.
Consult the User manual for 8 Start button Push button to start the
Elektronikon regulator, section compressor. LED (1) lights up
"Status data submenu". indicating that the regulator is
operative (in automatic operation).
The LED goes out after unloading
the compressor manually.

1 2 11 4 6

10 7
3 9

12
5 S3. Emergency stop button
1. LED, automatic operation
2. LED, voltage on
3. LED, general alarm
4. Display
5. Function keys
6. Scroll keys
7. Tabulator key
8. Start button
9. Stop button
10. Pictograph, automatic operation
11. Pictograph, voltage on
50418F
12. Pictograph, alarm
S3
Fig. 8. Control panel, GA Pack / Full-feature

2920 1386 00 11
Instruction book

Ref. Designation Function Abbre- Desig- Function


viation nation

9 Stop button Push button to stop the


compressor. LED (1) goes out. Add Add To add compressor start/stop commands
The compressor will stop after (day/hour)
running in unloaded condition for Canc Cancel To cancel a programmed setting when
30 seconds. programming parameters
Del Delete To delete compressor start/stop
S3 Emergency Push button to stop the compressor commands
stop button immediately in case of emergency. Lim Limits To show limits for a programmable setting
See section 3.4.5. List List To list programmed start/stop commands
(day/hour)
Load Load To load the compressor manually
Pictographs Main Main To return from a menu to the main display
10 Automatic operation (Fig. 9)
11 Voltage on Menu Menu Starting from the main display (Fig. 9),
12 Alarm to initiate the main menu (Fig. 10) which
gives access to submenus
Starting from a submenu, to return to the
1.3.3 Function keys (5-Fig. 8) main menu (Fig. 10)
Mod Modify To modify programmable settings
The keys are used: More More To have a quick look at the compressor
- To manually load/unload the compressor status
- To call up or to program settings Prog Program To program modified settings
- To reset a motor overload, shut-down or service message, Rset Reset To reset a timer or message
or an emergency stop Rtrn Return To return to a previously shown option or
- To have access to all data collected by the regulator menu
Slct Select To select a submenu or to read more
The functions of the keys vary depending on the displayed menu. details of a selection shown on the display
The actual function is abbreviated and indicated on the bottom Unld Unload To unload the compressor manually
line of the display just above the relevant key. The most
common abbreviations are listed below.

1.3.4 Menu-driven control programs

To facilitate programming and controlling the compressor,


menu-driven programs are implemented in the electronic
Delivery air module.
bar 7.0
Auto loaded The User manual for Elektronikon regulator for GA5 up to
Menu More Unld GA75 deals elaborately with all regulator functions.
F1 F2 F3
Program/ Description
Fig. 9. Example of the main display Function

MAIN DISPLAY Shows in short the operation status of the


compressor. It is the gateway to all
Status data
functions. See Fig. 9.

Main Slct
More Allows a quick look at the actual status
F1 F2 F3 of the compressor. See section 3.4.

Fig. 10. Example of a main menu Load/Unld To manually load/unload the compressor

12 2920 1386 00
Instruction book

Program/ Description 1.4 Regulator for GA Standard Pack


Function

1.4.1 Regulator (Fig. 11)


MAIN MENU See Fig. 10. It is the gateway to following
menus: The regulator loads, unloads, stops and restarts the compressor
according to the air consumption, and protects the compressor
Status data Calling up the status of the compressor and motor from overloads. The unloading and loading pressures
protection functions (service warning, are the opening and closing pressures respectively of switch
shut-down and shut-down warning). (PSR19-Fig. 3). See section 5.5.
Resetting of a shut-down and motor
overload. See section 1.3.1. Star/delta switch-over / Delayed motor stopping
A time relay (K24) is provided:
Measured data Calling up actually measured values and - for delayed motor stopping: the frequency of automatic
the status of the motor overload motor starts is limited by stopping the motor only after a
protection. set time of 5 minutes of uninterrupted unloaded operation;
if the net pressure drops to the loading pressure within the
Hours Calling up the running hours, loading set unloading time, the compressor will be loaded without
hours, regulator hours and number of stopping
motor starts. - to switch over from star to delta connection 10 seconds after
starting
Service Calling up and resetting the service
messages for the oil, oil filter, oil Compressor temperature shut-down switch (TSHH11)
separator, air filter. The switch prevents damage resulting from too high a
temperature at the outlet of the compressor element. See section
Test Allows a display test. 5.6.

Modify settings Modifying the settings for regulation (e.g.


loading and unloading pressures), for
protection (e.g. temperature shut-down
level) and for service (e.g. for the oil).
1X1
Timer Programming automatic compressor start/
stop commands.

Configuration Programming the time, date, display


F2
language, units, motor start mode and date
format. T1
F1
Saved data Calling up the saved data: last shut-down,
last emergency stop, longest load, longest K24
unload.
K22

K23

Selecting a menu
When the voltage is switched on, the MAIN DISPLAY (Fig. 9) K21
is shown automatically. The other menus are selected by
pressing one of function keys (5-Fig. 8). Pushing the key F21
<<Menu>> initiates the MAIN MENU (Fig. 10), giving access
to most other functions via submenus; the submenus can be
selected by pressing the key <<Slct>> (select).
50419F

Whenever displayed on the bottom line of the screen, press the


key <<Menu>> to return from a submenu to the MAIN MENU.
See Figs. 12 for denomination of components
Whenever displayed, press the key <<Main>> to return from a
menu to the MAIN DISPLAY.
Fig. 11. Electric cabinet, GA Standard Pack (typical example)

2920 1386 00 13
Instruction book

Fig. 12a. Standard Pack with transformer

F1/3. Fuses
F21. Overload relay, drive motor
H1. Automatic operation lamp
K1. Blocking relay
K21. Line contactor
K22. Star contactor
K23. Delta contactor
K24. Time relay for star/delta switch-over (10 seconds)
and for delayed motor stopping (5 min)
M1. Drive motor
PSR19. Load/unload pressure switch
P1. Hourmeter indicating total motor running time
S1. Start button

14 2920 1386 00
Instruction book

Fig. 12b. Standard Pack without transformer

S3. Button to stop compressor after 30 seconds unloading or to stop it


immediately (emergency)
S4. Switch to load or unload compressor
TSHH11. Gauge, indicating temperature at outlet of compressor element
combined with shut-down switch
T1. Transformer
Y1. Loading solenoid valve
Y2. Solenoid valve, modulating control 1)
1X1. Terminal strip

1) Available as option

Figs. 12. Electrical diagrams, GA Standard Pack 50 Hz with star-delta starter

2920 1386 00 15
Instruction book

Motor overload relay (F21) Gp TSHH11


The relay prevents damage resulting from too high a motor
current. 1 5

1.4.2 Control panel (Fig. 13)


P1 S1/H1
Gp. Gauge indicating the working pressure
H1. Lamp, automatic operation 6
P1. Hourmeter indicating the total motor running time 2
S1. Push button to start the compressor
S3. Push button: S4
- to stop the compressor 30 seconds after 3 S3
switching over to unloaded running
- to stop the compressor immediately in case of
emergency 4
S4. Toggle switch to unload or load the compressor
TSHH11. Gauge/switch, indicating the temperature at the
outlet of the compressor element as well as the
shut-down temperature; the regulator then stops the
compressor
50394F
Pictographs Gp. Gauge indicating working pressure
1. Working pressure H1. Automatic operation lamp
2. Running hours P1. Hourmeter indicating total motor running time
3. Compressor unloaded S1. Start button
4. Routine stopping: unload compressor, wait 30 seconds, S3. Button to stop compressor after 30 seconds
then press stop button unloading or to stop it immediately (emergency)
5. Outlet temperature of compressor element S4. Switch to load or unload compressor
6. Compressor loaded TSHH11. Gauge, indicating temperature at outlet of
compressor element combined with shut-down
switch
1.5 Air dryer on GA Full-feature (Fig. 4a)
Pictographs
GA Full-feature are provided with a dryer which removes 1. Working pressure
moisture from compressed air. 2. Running hours
3. Unloaded operation
4. Unload compressor and wait 30 seconds before
1.5.1 Compressed air circuit stopping
5. Outlet temperature of compressor element
Compressed air enters heat exchanger (5) and is cooled by the 6. Loaded operation
outgoing, dried air. Moisture in the incoming air starts to
condense. The air then flows through heat exchanger (11) where Fig. 13. Control panel, GA Standard Pack
the refrigerant evaporates withdrawing heat from the air. This
cools the air to close to the evaporating temperature of the
refrigerant. More water in the air condenses. The cold air then
flows through moisture trap (MT) which separates condensate
from the air. The condensate is automatically drained through
outlet (Da). The cold, dried air then flows through heat
exchanger (5), where it is warmed up by the incoming air.

The refrigerant enters evaporator (11) where it withdraws heat


1.5.2 Refrigerant circuit from the compressed air by further evaporation. The heated
refrigerant leaves the evaporator and is sucked in by compressor
Compressor (M1) delivers high-pressure refrigerant gas which (M1).
flows through condenser (9) where the refrigerant condenses.
The liquid refrigerant flows through filter (6) to capillary tube By-pass valve (10) regulates the freon flow. Fan (8) is switched
(7). The refrigerant leaves the capillary tube at evaporating on or off by switch (S3) depending on the loading degree of
pressure. the refrigerant circuit.

16 2920 1386 00
Instruction book

2 Installation

2.1 Dimension drawings (Figs. 14)

Fig. 14a. Dimension drawing, GA Pack / Full-feature

2920 1386 00 17
Instruction book

Fig. 14b. Dimension drawing, GA Standard Pack

2.2 Installation proposal (Figs. 15)

Ref. Description/recommendation Ref. Description/recommendation

1 Install the compressor on a solid, level floor dp = pressure drop (recommended


suitable for taking the weight. maximum = 0.1 bar)
L = length of delivery pipe in m
2 Position of the compressed air outlet valve. d = inner diameter of the delivery pipe
in mm
3 The pressure drop over the delivery pipe can be P = absolute pressure at the compressor
calculated as follows: outlet in bar(a)
Qc = free air delivery of the compressor
L x 450 x Qc1.85 in l/s
________________________
dp =
d5 x P

18 2920 1386 00
Instruction book

Fig. 15a. Installation proposal, GA Pack / Full-feature

2920 1386 00 19
Instruction book

Fig. 15b. Installation proposal, GA Standard Pack

20 2920 1386 00
Instruction book

Ref. Description/recommendation Ref. Description/recommendation

It is recommended that the connection of the It is recommended to provide by-pass pipes and
compressor air delivery pipe is made on top of valves over the filters to isolate the filters during
the main air net pipe to minimize carry-over of maintenance without disturbing the compressor.
possible remainder of condensate.
9 The air receiver (optional) should be installed in
4 Ventilation: the inlet grids and ventilation fan a frost-free room on a solid, level floor.
should be installed in such a way that any
recirculation of cooling air to the compressor or For normal air consumption, the volume of the
dryer is avoided. The air velocity to the grids air net (receiver and piping) can be calculated as
must be limited to 5 m/s. The maximum follows:
allowable pressure drop over the cooling air ducts
is 30 Pa. If exceeding this value, a fan is needed 0.25 x Qc x P1 x To
_________________________________
at the outlet of the ducts. Consult Atlas Copco. V =
fmax x dP x T1
- For alternatives 1 and 3, the required
ventilation capacity to limit the compressor V = volume of air net in l
room temperature can be calculated as Qc = free air delivery of compressor in l/s
follows: P1 = compressor air inlet pressure in
bar absolute
Qv = 1.16 N / dT for GA Pack fmax = cycle frequency = 1 cycle/30 s
Qv = (1.16 N + 0.6) / dT for GA Full-feature dP = Punload - Pload in bar
T1 = compressor air inlet temperature in K
Qv = required ventilation capacity in m3/s To = air receiver temperature in K
N = nominal motor power of compressor
in kW 10-Fig. 15b For GA Standard Pack, a condensate trap is
dT = temperature increase in compressor available as option.
room
By-pass system for compressors with dryer (optional):
- For alternatives 2 and 4: the fan capacity
should match the compressor fan capacity at 10-Fig. 15a Dryer by-pass pipe.
a pressure head equal to the pressure drop
over the air ducts. 11-Fig. 15a Condensate trap.

5 The drain pipes to the drain collector must not


dip into the water of the drain collector. Atlas
Copco has oil/water separators (type OSD) to
separate the major part of oil from condensate to
ensure that the condensate meets the
requirements of the environmental codes.

6 Position of the control panel.

7 Position of the mains cable.

8 Filter, type DD, for general purpose filtration


(optional). The filter traps solid particles down
to 1 micron with a max. oil carry-over of 0.5 mg/
m3. A high-efficiency filter, type PD (optional),
may be installed downstream of a DD filter. This
filter traps solid particles down to 0.01 micron
with a max. oil carry-over of 0.01 mg/m3. If oil
vapour and odours are undesirable, a filter of the
QD type (optional) should be installed
downstream of the PD filter.

2920 1386 00 21
Instruction book

2.3 Electric cable size Compressor Voltage Fre- Cable


type quency section
Attention (V) (Hz) (AWG size)
- Local regulations remain applicable if they are stricter than
the values proposed below.
- The voltage drop must not exceed 5% of the nominal With direct-on-line starter
voltage. It may be necessary to use cables with a larger
section than those stated to comply with this requirement. GA5 200 60 AWG8
- The values below apply to Full-feature compressors GA5 220/230 60 AWG8
GA5 440/460 60 AWG12
Compressor Voltage Fre- Cable GA5 575 60 AWG12
type quency section
(V) (Hz) (mm²/AWG size) GA7 200 60 AWG6
GA7 220/230 60 AWG6
GA7 440/460 60 AWG10
With star-delta starter GA7 575 60 AWG10
GA5 200 50 6
GA5 230 50 6 GA10 200 60 AWG4
GA5 400 50 2.5 GA10 220/230 60 AWG4
GA5 500 50 2.5 GA10 440/460 60 AWG8
GA10 575 60 AWG8
GA7 200 50 10
GA7 230 50 10
GA7 400 50 4 Note: The size is valid for cable PVC 90°C at ambient
GA7 500 50 2.5 temperature 40°C according to EN60204

GA10 200 50 25
GA10 230 50 16 2.4 Electrical connections
GA10 400 50 6
GA10 500 50 6 General
1. Provide an isolating switch nearby the compressor.
With star-delta starter 2. Check the fuses and the setting of the overload relay. See
section 7.2.
GA5 200 60 6 3. If provided, check transformer (T1-Figs. 5 and 11) for
GA5 220/230 60 6 correct connection. Check the setting of drive motor
GA5 380 60 2.5 overload relay (F21) and that overload relay (F21) is set
GA5 440/460 60 2.5 for automatic resetting.

GA7 200 60 10 On GA Standard Pack with voltage transformer


GA7 220/230 60 10 1. Connect the power supply cables to terminals 1, 3 and 5 of
GA7 380 60 4 contactor K21 (see Figs. 12a and 11).
GA7 440/460 60 4 2. Connect the earth conductor to earth bolt (PE).

GA10 200 60 25 On GA Standard Pack without voltage transformer


GA10 220/230 60 16 1. Connect the power supply cables to terminals 1, 3 and 5 of
GA10 380 60 10 contactor K21 (see Figs. 12b and 11).
GA10 440/460 60 6 2. Connect the earth conductor to earth bolt (PE) and the
neutral conductor to terminal (N) of strip 1X1.
3. Check the connection of wire (2-Fig. 12b):
Note: The size is valid for cable PVC 70°C at ambient - either towards the neutral terminal (N) in case of a 3 x
temperature 40°C according to EN60204 400 V plus neutral mains
- or towards terminal (2) of fuse F2 in case of a 3 x 230 V
mains

On GA Pack
1. Connect the power supply to terminals 1, 3 and 5 of
contactor K21 (see Figs. 5 and 6).
2. Connect the earth conductor to the earthing terminal and
the neutral conductor to terminal (N) of strip 1X1.

22 2920 1386 00
Instruction book

On GA Full-feature
1. Connect the power supply to terminals 1, 3 and 5 of
contactor K21 (see Figs. 5 and 6).
2. Connect the earth conductor to the earthing terminal and
the neutral conductor to terminal (N) of strip 1X1.
3. The voltage supply to the dryer must be 230 V single-phase.
The voltage to the dryer is supplied over the contacts of
relay (K11), which close when the compressor is started.
For compressor supply voltages different from 3 x 400 V
plus neutral or 3 x 230 V, the power to the dryer is supplied
by a tranformer.

2.5 Pictographs (Fig. 16)

Read the warnings attentively and act accordingly.

1. Warning: voltage 6. Torques for steel (Fe) or brass (CuZn) bolts


2. Manual condensate drain 7. Consult Instruction book before greasing
3. Automatic condensate drain 8. Lightly oil gasket of oil filter, screw it on and tighten by
4. Warning: switch off voltage and depressurize hand (approx. half a turn)
compressor before repairing 9. Do not adjust switch if it is depressurized
5. Warning: before connecting compressor electrically,
consult Instruction book for motor rotation direction
Fig. 16. Pictographs (typical examples)

2920 1386 00 23
Instruction book

3 Operating instructions programmed in the electronic regulator (if terminals 30 and


34 are not bridged, the compressor is switched out of
automatic load/unload operation and remains running
unloaded).
3.1 Before initial start-up 3. For remote selecting between manual unload or
automatic operation, connect an unload/automatic
operation switch between terminals 30 and 34.
3.1.1 Safety

The operator must apply all relevant safety precautions, 3.1.6 Remote pressure sensing for GA Pack /
including those mentioned in this book. Full-feature

1. Bridge terminals 30 and 35 of strip (1X1-Fig. 6).


2. Connect a pressure switch between terminals 30 and 34 of
3.1.2 User manual strip (1X1): this results in loading and unloading of the
compressor at the closing and opening pressures of the
Read the "User manual for Elektronikon regulator for GA5 up external pressure switch respectively.
to GA75 compressors" to familiarize yourself with all regulator
functions.
3.2 Initial start-up

1. Following transport fixations, painted red, are provided:


3.1.3 Outdoor/altitude operation - two spacers (1-Fig. 17) underneath the compressor
element support: unscrew the bolts underneath the frame
If the compressor is installed outdoors or if the air inlet and remove the spacers
temperature can be below 0°C (32°F), precautions must be - support (2-Fig. 17) underneath the drive motor: unscrew
taken. In this case, and also if operating at high altitude, consult bolts (5) underneath the frame, loosen nut (3), remove
Atlas Copco. the support and retighten nut (3)
2. Check that the electrical connections correspond to the local
codes and that all wires are clamped tight to their terminals.
3.1.4 Remote compressor status indication for GA The installation must be earthed and protected against short
Pack / Full-feature circuits by fuses of the inert type in all phases. An isolating
switch must be installed near the compressor.
A relay box for remote compressor status indication is available 3. Fit air outlet valve (AV-Fig. 1). Close the valve. Connect
as option. It can be connected to the electronic control module the air net to the valve.
(see Fig. 6). 4. Connect the manual condensate drain valve (Dm-Fig. 1).
Close the valve. Connect the valve to a drain collector.
The following indications can be indicated by means of relays: See Figs. 15.
- Manual load/unload or automatic operation 5. Connect the automatic drain outlet (Da-Fig. 1) to a drain
- Warning condition collector. See Figs. 15.
- Shut-down condition 7. Check the oil level. The pointer of level gauge (Gl-Fig. 2)
should register in the green or orange range.
Attention 8. A label dealing in short with the operating instructions and
Stop the compressor and switch off the voltage before explaining the pictographs is delivered with the literature
connecting external equipment. Only voltage-free contacts are set. Affix it next to the control panel. Make yourself familiar
allowed. Have the modifications checked by Atlas Copco. with the instructions and pictographs explained, as well as
with those mentioned in section 2.6.
9. Provide labels, warning the operator that:
- the compressor may be restarted automatically after
3.1.5 Remote control for GA Pack / Full-feature voltage failure (GA Pack/Full-feature, see section 1.3.1)
- the compressor is automatically controlled and may be
1. To switch the compressor to remote control mode, bridge restarted (for GA Pack/Full-feature even after manually
terminals 2 and 4 of connector (2X4) located at the back stopping, see section 1.3.1)
side of the electronic module (E1-Fig. 1). - the compressor may be remotely controlled (see section
2. For remote starting and stopping, connect a start/stop 3.1.5)
switch between terminals 30 and 31 of terminal strip (1X1- 10. Switch on the voltage. Start the compressor and stop it
Fig. 6). immediately. Check the rotation direction of the motor (M1-
Bridge terminals 30 and 34 of strip (1X1): the outlet pressure Fig. 2): the correct rotation direction is indicated by an arrow
is still sensed by pressure transducer (PT20), resulting in provided on the fan housing. If the rotation direction is
loading and unloading of the compressor at the pressures wrong, switch off the voltage and reverse two incoming
electric lines.

24 2920 1386 00
Instruction book

3.4 For GA Pack / Full-feature


E AF
3.4.1 Starting (Fig. 8)

1. Switch on the voltage. Check that voltage on LED (2) lights


up. The message <<Compressor off>> appears.
2. Open air outlet valve (AV-Fig. 1).
3. Close condensate drain valve (Dm-Fig. 1).
4. Press start button (8). The compressor starts running and
automatic operation LED (1) lights up. Ten seconds 2) after
starting, the drive motor switches over from star to delta.
At the same time 2) the compressor starts running loaded.
The message on display (4) changes from <<Auto
unloaded>> to <<Auto loaded>>.

3.4.2 During operation

1. Check the oil level during unloaded operation: the pointer


of level gauge (Gl-Fig. 2) must register in the green range;
if not, press stop button (9-Fig. 8), wait until the compressor
has stopped, depressurize the oil system (by unscrewing oil
50428F

filler plug FC-Fig. 2 one turn) and wait a few minutes.


Remove the plug and add oil until the level reaches the filler
opening. Fit and tighten the plug.
2. When automatic operation LED (1-Fig. 8) is alight, the
FN 1 2 3 4 5 M1 regulator is automatically controlling the compressor, i.e.
loading, unloading, stopping of the motors and restarting.

3.4.3 Checking the display


AF. Air filter
E. Compressor element 1. Regularly check display (4-Fig. 8) for readings and
FN. Cooling fan messages. Normally, the main display (Fig. 9) is shown,
M1. Drive motor indicating the compressor outlet pressure, the status of the
1. Transport bolt and spacer, to be removed compressor and the abbreviations of the functions of the
2. Transport support, to be removed keys below the display.
3. Nut 2. Always check display (4-Fig. 8) and remedy the trouble if
4. Vibration damper alarm LED (3) is alight or blinks. Consult section 1.3.2.
5. Transport bolts, to be removed 3. The display (4-Fig. 8) will show a service message if one
of the monitored components is to be serviced; stop the
Fig. 17. Compressor element/transport fixations compressor, replace the component and reset the relevant
timer. 3)

11. Check the programmed settings. 1)


12. Start and run the compressor for a few minutes. Check that
the compressor operates normally.

3.3 Before starting

Check the oil level (Gl-Fig. 2). The pointer should register in
the upper field of the green range or in the orange range. If the
pointer registers in the red range (low range), depressurize the 1) Consult the User manual for the Elektronikon regulator.
oil system by unscrewing oil filler plug (FC) one turn. Remove 2) Programmable.
the plug and add oil until the level reaches the filler opening. 3) Using key <<Rset>>: see User manual for Elektronikon regulator,
section "Service submenu".
Fit and tighten the plug.

2920 1386 00 25
Instruction book

Warning Before carrying out any maintenance, repair or 3.4.5 Stopping (Fig. 8)
adjustment, stop the compressor, press emergency
stop button (S3-Fig. 8), switch off the voltage and 1. Press stop button (9). LED (1) goes out. The message
depressurize the compressor. <<Programmed stop>> appears. The compressor runs
unloaded for 30 seconds and then stops.
Notes 2. To stop the compressor in case of emergency, press button
- Whenever a warning, service request, sensor error or (S3). Alarm LED (3) blinks. After remedying the fault,
motor overload message is displayed, the free spaces unlock the button by pulling it out and press key <<Rset>>
on the display between function keys (5-Fig. 8) are filled (5) before restarting. The message <<All conditions are
with blinking indicators (**). OK>> appears. Press keys <<Menu>> and <<Main>>.
- When more than one message needs to be displayed (e.g. 3. Close air outlet valve (AV-Fig. 1) and switch off the voltage.
both warning and service), the messages will be 4. Open condensate drain valve (Dm-Fig. 1).
displayed one after the other for 3 seconds.

4. Regularly press key <<More>> (5-Fig. 8) 1) to call up 3.5 For GA Standard Pack
information about the actual compressor condition:
- the status of controlling the compressor (automatic or
manual, local or remote) 3.5.1 Starting (Fig. 13)
- the status of the compressor start/stop timer (on or off)
2) 1. Switch on the voltage.
- the maximum allowable unloading pressure 2. Open the air outlet valve.
- the outlet pressure 3. If installed, close the condensate drain valve. 5)
- the compressor element outlet temperature 4. Check that push button (S3) is unlocked (pulled out) and
- the dewpoint temperature 3) that toggle switch (S4) is moved to the left (unloaded)
- the status of the overload protection of the drive motor position.
(normal or not) 5. Press start button (S1). The compressor starts running and
- the total running and loading hours lamp (H1) lights up.
6. Move switch (S4) to the right to load the compressor.

3.5.2 During operation

1. Check the oil level during unloaded operation: the pointer


3.4.4 Manual control (Fig. 8) 4) of level gauge (Gl-Fig. 3) must register in the green range;
if not, move switch (S4) to the left, wait 30 seconds and
Normally, the compressor runs in automatic operation, i.e. the then press stop button (S3). Depressurize the oil system by
electronic regulator loads, unloads, stops and restarts the unscrewing oil filler plug (FC-Fig. 3) one turn and wait a
compressor automatically. LED (1) is then alight. few minutes. Remove the plug and add oil until the level
reaches the filler opening. Fit and tighten the plug. Pull
If required, the compressor can be unloaded manually. In this out button (S3).
case, the compressor is switched out of automatic operation: 2. When automatic operation lamp (H1) is alight, the regulator
the compressor remains running unloaded unless it is loaded is automatically controlling the compressor, i.e. loading,
again manually. unloading, stopping of the motor and restarting.

Manually unloading
Press the key <<Unld>> (unload) (5). LED (1) goes out. The
message <<Manual Unloaded>> appears on the display.

Manually loading 1) If the function <<More>> is not indicated on the bottom line of
Press the key <<Load>> (5). LED (1) lights up. The command display (4-Fig. 8), press key <<Menu>> (5) until function
<<Load>> does not force the compressor in loaded condition, <<Main>> appears above key (F1), then press the key <<Main>>.
but it will switch the compressor to automatic operation again: 2) The compressor is automatically started and stopped if these start/
the compressor will be loaded if the air net pressure drops below stop commands are programmed and activated; consult section
the programmed level. 1.3.1.
3) For Full-feature compressors.
4) If the <<Load>> or <<Unld>> (unload) function is not indicated
Manually starting
on the bottom line of display (4), press key <<Menu>> (5) until
In automatic operation, the regulator limits the number of motor the function <<Main>> appears above key (F1), then press the
starts. If the compressor is stopped manually, it must not be key <<Main>>.
restarted manually within 5 minutes after the last stop. 5) A condensate drain system is available as option.

26 2920 1386 00
Instruction book

3.5.3 Stopping

1. Move switch (S4) to the left to unload the compressor and


wait 30 seconds.
2. Press stop button (S3). After stopping, unlock the button
by pulling it out.
3. To stop the compressor in case of emergency, press button
(S3). Before restarting, unlock the button by pulling it out.
4. Close the air outlet valve and switch off the voltage.
5. If installed, open the condensate drain valve. 1)

3.6 Taking out of operation at end of


compressor service life

At the end of the service life of the compressor, proceed as


follows:

1. Stop the compressor and close the air outlet valve.


2. Switch off the voltage and disconnect the compressor from
the mains.
3. Depressurize the compressor by opening plug (FC-Fig. 3)
one turn and by opening valve (Dm-Fig. 1).
4. Shut off and depressurize the part of the air net which is
connected to the outlet valve. Disconnect the compressor
air outlet pipe from the air net.
5. Drain the oil and condensate circuits.
6. Disconnect the condensate piping from the condensate net.

1) A condensate drain system is available as option.

2920 1386 00 27
Instruction book

4 Maintenance - Close air outlet valve (AV-Fig. 1) and depressurize by


opening plug (FC-Fig. 3) one turn and by opening valve
Attention (Dm-Fig. 1).
1. Apply all relevant safety precautions, including those 4. The air outlet valve (AV-Fig. 1) can be locked during
mentioned in this book. maintenance or repair as follows:
2. Read section 2.5 to familiarize yourself with all warning - Close the valve.
labels and pictographs. - Remove the bolt fixing the handle.
3. Before carrying out any maintenance or repair on the - Lift the handle and turn it until the slot of the handle fits
compressor: over the blocking edge on the valve body.
- For GA Pack/Full-feature, press stop button (9-Fig. - Lock the handle using the special bolt and wrench
8), wait until the compressor has stopped (approx. 30 delivered loose with the compressor.
seconds), press emergency stop button (S3) and switch
off the voltage.
- For GA Standard Pack, move switch (S4-Fig. 13) to 4.1 Drive motor (M1-Fig. 2)
the left, wait 30 seconds, press stop button (S3) and
switch off the voltage. The motor bearings are greased for life.

Notes to maintenance schedule


1. More frequently when operating in a dusty atmosphere.
2. Use genuine Atlas Copco filters.
3. Recommended oil: Atlas Copco Roto-injectfluid. For the change interval in extreme conditions of temperature, humidity or
cooling air, consult Atlas Copco.
4. Consult the User Manual for Elektronikon regulator, section "Test submenu".
5. For GA Pack/Full-feature:
Consult the User Manual for Elektronikon regulator before modifying the temperature protection settings, section "Modify
settings submenu".
Decrease the shut-down warning level and shut-down level for the compressor element outlet temperature to the minimum.
Run the compressor: when reaching the setting, the unit must shut down. Attention: reset the shut-down level and warning
level to their original values.
For GA Standard Pack: consult Atlas Copco.
6. Any leak should be attended to immediately.
7. Damaged flexibles must be replaced immediately.
8. Replace the air filter element if damaged or heavily contaminated.

28 2920 1386 00
Instruction book

4.2 Preventive maintenance schedule for the compressor 1)


Attention The schedule comprises a summary of the maintenance
For overhauling or carrying out preventive maintenance, service instructions. Read the respective section before taking
kits are available. See section 4.7. Atlas Copco offers several maintenance measures. The "longer interval" checks must
types of Service contracts, relieving you of all preventive also include the "shorter interval" checks. When servicing,
maintenance work. For more details, consult your nearest Atlas replace all disengaged packings, e.g. gaskets, O-rings, washers.
Copco representative.

Period 2) Running See See note Operation


hours 2) section on pre-
vious page

Daily Before starting


" -- 3.3 -- Check oil level (Gl)

During operation
" -- 3.4/3.5/7.1 -- Check readings on display or gauges
" -- -- -- Check that condensate is discharged during loading (Da)
" -- 3.4/3.5 -- Check oil level (Gl)

After stopping
" -- 3.4/3.5 -- Drain condensate (Dm)

3-monthly -- 5.3 -- Operate safety valve (SV)


" -- -- 4 Carry out a LED/display test (Pack/Full-feature)
" -- -- 6 Check for possible leaks
" 1000 5.2 1 Inspect coolers (Ca/Co); clean if necessary
" 1000 -- 1 Inspect condensor of dryer (Full-feature); clean if necessary
" 1000 4.7 1/8 Remove air filter element (AF), replace if necessary
" -- -- -- Remove, dismantle and clean float valve of moisture trap (MT)
-- 1000 5.7 -- Check belt tension

Yearly -- 5.3 -- Have safety valve (SV) tested


" -- -- -- Have operation of electrical interlockings, motor breakers, etc. tested
" -- -- 5 Test temperature shut-down protection
" 4000 4.7/5.1 1 Replace air filter element (AF)
" 4000 4.4/4.5/4.7 2/3 If Atlas Copco Roto-injectfluid is used, change oil and oil filter (OF)

For 13 bar and 175 psi


" 500 4.4/4.5/4.7 2 If oil as specified in section 4.3.2 is used, change oil and oil filter

For 7.5-8-10 bar and 100-125-150 psi


" 1000 4.4/4.5/4.7 2 If oil as specified in section 4.3.2 is used, change oil and oil filter

" -- -- 7 Have all flexibles inspected


" -- -- -- Clean compressor

-- 4000 4.7 -- Have oil separator (OS) replaced; inspect valve (CV) for cleanness

-- 6000 5.7 -- Replace belts

1) Use only authorized parts. Any damage or malfunction caused by the use of unauthorized parts is not covered by
Warranty or Product Liability.
2) Whichever interval comes first. The local Sales Company may overrule the maintenance schedule, especially the
service intervals, depending on the environmental and working conditions of the compressor.

2920 1386 00 29
Instruction book

4.3 Oil specifications 4.5 Oil filter change (Fig. 2)

Attention 1. Stop the compressor and depressurize by unscrewing filler


Never mix oils of different brands or types. Use only non- plug (FC) one turn to permit any pressure in the system to
toxic oils. escape. Wait a few minutes.
4. Remove oil filter (OF-Fig. 18).
5. Clean the filter seat on the manifold. Oil the gasket of the
new element. Screw the element into place and tighten
4.3.1 Atlas Copco Roto-injectfluid firmly by hand.
6. Remove plug (FC) and fill with oil until the level reaches
It is strongly recommended to use Atlas Copco Roto-injectfluid. the filler opening.
This is special oil for screw compressors which keeps the 7. Tighten plug (FC).
compressor in excellent condition. Roto-injectfluid can be used 8. Reset the oil filter service warning. 1)
for compressors operating in ambient temperatures between
0°C and 40°C. See also section 4.7.
4.6 Storage after installation
Although Roto-injectfluid is recommended, mineral oil can be
used after taking following precautions: Run the compressor twice a week until warm. Load and unload
- the previously used oil should first be drained and the system the compressor a few times. If the compressor is stored without
flushed running from time to time, protective measures must be taken.
- the oil filter and oil separator should be replaced Consult Atlas Copco.
- the oil must meet the requirements as specified below

4.7 Service kits


4.3.2 Mineral oil Service kits are available offering the benefits of genuine Atlas
Copco parts while keeping the maintenance budget low. The
High-quality, mineral oil with oxidation inhibitors and anti-foam kits comprise all parts needed for servicing.
and anti-wear properties. The viscosity grade must correspond
to the ambient temperature and ISO 3448, as follows: Service kits Ordering number
For oil filter and air filter 2901 0559 00
Ambient Viscosity Viscosity For oil separator 2901 0523 00
temperature grade index
Atlas Copco Roto-injectfluid
Roto-injectfluid (see section 4.3) can be ordered in following
Consistently above 25°C (77°F) . ISO VG 68 Minimum 95 quantities:
Between 25°C (77°F) and
0°C (32°F) . . . . . . . . . . . . . . . . . . ISO VG 46 Minimum 95 Quantity Ordering number
5-litre can 2901 0245 01
20-litre can 2901 0522 00

4.4 Oil change (Fig. 2)

1. Run the compressor until warm. Stop the compressor and


depressurize by unscrewing filler plug (FC) one turn to
permit any pressure in the system to escape.
2. Drain the oil by removing drain plug (DP). Fit and tighten
plug (DP) after draining. Deliver the oil to the local oil
collection service.
3. Fill receiver (AR) with oil until the level reaches the filler
neck. Take care that no dirt drops into the system. Fit and
tighten plug (FC).
4. Run the compressor for a few minutes. Stop the compressor
and wait a few minutes to allow the oil to settle.
Depressurize the system. Fill the receiver with oil until the
level reaches the filler neck. Tighten plug (FC).
5. Reset the oil service warning. 1) 1) For GA Pack/Full-feature: using key <<Rset>>: see User manual
for Elektronikon regulator, section "Service submenu".

30 2920 1386 00
Instruction book

5 Adjustments and servicing 5.2 Coolers


procedures Keep the coolers clean to maintain the cooling efficiency.

5.1 Air filter (AF-Fig. 18) Remove any dirt from the coolers with a fibre brush. Never
use a wire brush or metal objects. Then clean by air jet in
1. Stop the compressor. Switch off the voltage. Remove the reverse direction of normal flow while covering all compressor
filter cover and the filter element. Discard the air filter parts under the coolers. If it is necessary to wash the coolers
element. with a cleansing agent, consult Atlas Copco.
2. Fit the new element and the cover.
3. For GA Pack/Full-feature, reset the air filter service warning
using key <<Rset>>. 1) 5.3 Safety valve (SV-Fig. 18)

Operate the safety valve, depending on the type of valve:


- by unscrewing the cap one or two turns and retightening it
- or by pulling the valve lifting lever

Testing
The valve can be tested on a separate compressed air line. If
the valve does not open at the set pressure stamped on the valve,
consult Atlas Copco.

Warning No adjustments are allowed. Never run the


compressor without safety valve.

AF OF SV 5.4 Safety devices of dryer on GA Full-


feature

The regulating and safety devices are factory-adjusted to obtain


optimum performance of the dryer. Do not alter the setting of
any of the devices.

5.5 Load/unload pressure switch


(PSR19-Fig. 19) on GA Standard Pack

The switch allows the operator to select the unloading pressure


and the pressure difference between the unloading and loading
pressures. The unloading and loading pressures are the opening
and closing pressures of the air pressure switch.

Adjustment can only be carried out when the pressure


switch is pressurized. Remove blocking device (1) before
adjusting knob (2).

The unloading pressure is controlled by adjusting knob (2).


Turn the knob clockwise to raise the unloading pressure, anti-
50443F
clockwise to lower it.

AR

AF. Air filter


AR. Air receiver/oil separator
OF. Oil filter
SV. Safety valve
1) See User manual for Elektronikon regulator, section "Service
Fig. 18. View on air receiver submenu".

2920 1386 00 31
Instruction book

5.6 Temperature shut-down switch on GA


Standard Pack
1
2 Switch (TSHH11-Fig. 13) has an adjusting screw in the centre
at the back of the housing of the switch.

The reset screw is located in the centre of the indicator scale


and is protected by a cap. To reset the switch after tripping,
unscrew the cap and turn the reset screw with a screwdriver
3 anti-clockwise.

50390F
5.7 Belt set exchange (Fig. 21)

The belts must be replaced as a set, even if one of them seems


worn. Use Atlas Copco belts only.

1. Blocking device, to be removed before turning knob 2 1. Remove panel (2-Fig. 1).
2. Adjusting knob 2. Loosen hose clip (1) an retract hose (2) from fan housing
3. Switch (3).
3. Untighten fixation bolts (4).
Fig. 19. Load/unload pressure switch (Standard Pack) 4. Screw locking nut (6) upwards. Screw bush (7) and threaded
rod (8) downwards; the compressor element will move
downwards loosening the belt tension.
5. Remove cover (9) from housing (3) by turning it anti-
clockwise.
The pressure difference between unloading and loading is 6. Unscrew the fixation bolt in the centre of the fan and remove
adjusted by means of the same knob. The adjustment range is the latter whereafter the belts can be removed without
given in Figs. 20. Push down the knob and turn it clockwise to disconnecting the fan housing from support (5).
reduce the pressure difference, anti-clockwise to increase it.

Fig. 20a. Switch MDR 53/16 Fig. 20b. Switch MDR 53/11

Example (Fig. 20b): for 8 bar(e) unloading pressure, the loading pressure is adjustable between 5 and 7.6 bar(e)

Figs. 20 Adjustment ranges for load/unload pressure switch (Standard Pack)

32 2920 1386 00
Instruction book

7. Install a new set of Atlas Copco belts.


8. Install and fix the fan. Mount inlet cover (9) on fan housing
(3).
4 9. Screw locking nut (6) against bush (7); by turning the nut
further, the compressor element is moved upwards
4 tensioning the belts. The belt tension is correct if the
7
deflection is between 5 and 6 mm when exerting a force of
25 N on the belt midway between both pulleys.
10. Mount hose (2) on fan housing (3) and tighten hose clip
2 (1).
11. Tighten fixation bolts (4) and run the compressor for about
15 minutes.
6 12. Stop the compressor, check the belt tension and, if necessary,
5 retension the belts (see steps 3 and 9).
1 13. Tighten fixation bolts (4) and screw locking nut (6)
downwards against its support.
8 14. Install panel (2-Fig. 1).

50444F

1. Hose clip
2. Hose
3. Fan housing
4. Fixation bolts
5. Compressor element support
6. Locking nut
7. Bush
8. Threaded rod
9. Cover

Fig. 21. Belt drive

2920 1386 00 33
Instruction book

6 Problem solving 4. Compressor air output or pressure below normal


a. Air consumption exceeds air output of compressor
Attention a. Check equipment connected
1. Apply all relevant safety precautions, including those b. Choked air inlet filter element (AF)
mentioned in this book. b. Replace filter element
2. Read section 2.6 to familiarize yourself with all warning c. Solenoid valve (Y1) malfunctioning
labels and pictographs. c. See 1a
3. Before carrying out any maintenance or repair on the d. Leak in control air flexibles
compressor: d. See 1c
- For GA Pack/Full-feature, press stop button (9-Fig. e. Inlet valve (IV) does not fully open
8), wait until the compressor has stopped (approx. 30 e. See 1b
seconds), press emergency stop button (S3) and switch f. Oil separator element (OS) clogged
off the voltage. f. Have element replaced
- For GA Standard Pack, move switch (S4-Fig. 13) to g. Air leakage
the left, wait 30 seconds, press stop button (S3) and g. See 1c
switch off the voltage. h. Safety valve (SV) leaking
- Close air outlet valve (AV-Fig. 1) and depressurize by h. Replace valve
opening plug (FC-Fig. 3) one turn and by opening valve i. Compressor element (E) out of order
(Dm-Fig. 1). i. Consult Atlas Copco
4. The air outlet valve (AV-Fig. 1) can be locked during
maintenance or repair as follows: 5. Excessive oil flow through air inlet filter after stopping
- Close the valve. a. Inlet valve (IV) stuck in open position
- Remove the bolt fixing the handle. a. Have valve checked. Replace filter
- Lift the handle and turn it until the slot of the handle fits
over the blocking edge on the valve body. 6. Safety valve (SV) blows after loading
- Lock the handle using the special bolt and wrench a. Inlet valve (IV) malfunctioning
delivered loose with the compressor. a. See 1b
5. Consult the User manual for Elektronikon regulator (section b. Minimum pressure valve (Vp) malfunctioning
"Status data submenu") if a service message or fault message b. See 1d
appears on display (4-Fig. 8) or when alarm LED (3-Fig. 8) c. Oil separator element (OS) clogged
is alight or blinks. c. See 4f
d. Safety valve (SV) out of order
d. See 4h
Mechanical faults and suggested remedies (Figs. 4) e. On GA Full-feature, dryer piping clogged because of
ice formation
1. Compressor starts running, but does not load after a e. Have refrigerant system checked by Atlas Copco
delay time
a. Solenoid valve (Y1) out of order 7. Element outlet 1) or air outlet temperature above normal
a. Replace valve a. Insufficient cooling air or cooling air temperature too
b. Inlet valve (IV) stuck in closed position high
b. Have valve checked a. Check for cooling air restriction or improve ventilation
c. Leak in control air flexibles of compressor room. Avoid recirculation of cooling air.
c. Replace leaking flexible If installed, check capacity of compressor room fan.
d. Minimum pressure valve (Vp) leaking (when net is b. Oil level too low
depressurized) b. Check and correct as necessary
d. Have valve checked c. Oil cooler (Co) clogged
c. Clean cooler
2. Compressor does not unload, safety valve blows d. By-pass valve (BV) malfunctioning
a. Solenoid valve (Y1) out of order d. Have valve tested
a. See 1a e. Air cooler (Ca) clogged
b. Inlet valve (IV) does not close e. Clean cooler
b. See 1b f. Compressor element (E) out of order
f. See 4i
3. Condensate is not discharged from condensate trap
during loading
a. Discharge flexible clogged
a. Check and correct as necessary
b. Float valve malfunctioning 1) For GA Pack/Full-feature, a warning message will appear on
b. Remove float valve assembly, clean and check display (4-Fig. 8).

34 2920 1386 00
Instruction book

8. High oil consumption 7 Principal data


a. Oil level (Gl) too high
a. Check for overfilling. Release pressure and drain oil to
correct level
b. Incorrect oil causing foam
7.1 Readings on display (Fig. 8) or gauges
b. Change to correct oil (Fig. 13) 1)
c. Oil separator element (OS) defective
c. Have element checked. Replace, if necessary. Ref.: Air outlet pressure
Reading: Modulates between programmed unloading and
loading pressures
Shown: On gauge Gp (Fig. 13) or main display (Fig. 9)

Ref.: Compressor element outlet temperature


Reading: Approx. 60°C above cooling air temperature
Shown: On gauge TSHH11 (Fig. 13) or when using key
<<More>> (5-Fig. 8)

On Full-feature also:

Ref.: Dewpoint temperature


Reading: Approx. 3°C at reference conditions
Shown: When using key <<More>> (5-Fig. 8)

1) For GA Pack and Full-feature, see section 3.4 and the User manual
for Elektronikon regulator, sections "Main display" and "More
function".

2920 1386 00 35
Instruction book

7.2 Settings of overload relay and fuses

Compressor Supply Frequency Max. setting Fuses Fuses Fuses


type voltage of relay F21 IEC CSA HRC UL K5
(V) (Hz) (A) (A) (A) (A)

With star-delta starter

GA5 200 50 14.3 35 - -


GA5 230 50 12.4 35 - -
GA5 400 50 7 20 - -
GA5 500 50 6 20 - -

GA7 200 50 20.3 63 - -


GA7 230 50 17.4 63 - -
GA7 400 50 10 25 - -
GA7 500 50 8 20 - -

GA10 200 50 29.4 63 - -


GA10 230 50 25.8 63 - -
GA10 400 50 14.9 35 - -
GA10 500 50 12 25 - -

With star-delta starter

GA5 200 60 14 35 - -
GA5 220/230 60 13 35 - -
GA5 380 60 7.4 20 - -
GA5 440/460 60 6.4 20 - -

GA7 200 60 20.6 63 - -


GA7 220/230 60 19 63 - -
GA7 380 60 11 25 - -
GA7 440/460 60 9 25 - -

GA10 200 60 30 63 - -
GA10 220/230 60 27 63 - -
GA10 380 60 15.7 63 - -
GA10 440/460 60 13.5 35 - -

With direct-on-line starter

GA5 200 60 24.6 - 40 40


GA5 220/230 60 22.3 - 40 40
GA5 440/460 60 11 - 25 25
GA5 575 60 8.5 - 20 20

GA7 200 60 35.6 - 60 60


GA7 220/230 60 33 - 60 60
GA7 440/460 60 16.4 - 30 30
GA7 575 60 12.5 - 25 25

GA10 200 60 52 - 80 80
GA10 220/230 60 47 - 80 80
GA10 440/460 60 23.4 - 45 45
GA10 575 60 18 - 40 40

36 2920 1386 00
Instruction book

7.3 Settings of fan control switch (GA Full-feature)

Cut-out pressure Switch-on pressure Unit

Dryer fan control switch (50 Hz) . . . . . . . . . . . . 7.9 9 bar(e)

Dryer fan control switch (60 Hz) . . . . . . . . . . . . 9.9 11 bar(e)

7.4 Compressor specifications

7.4.1 Reference conditions

Air inlet pressure (absolute) . . . . . . . . . . . . . . . . . . . . . . bar 1


Air inlet temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . °C 20
Relative humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . % 0
Working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) See nominal values below

7.4.2 Limitations

Maximum working pressure . . . . . . . . . . . . . . . . . . . . . . bar(e) See maximum values below


Minimum working pressure . . . . . . . . . . . . . . . . . . . . . . bar(e) 4
Maximum air inlet temperature . . . . . . . . . . . . . . . . . . . °C 40
Minimum air inlet temperature . . . . . . . . . . . . . . . . . . . . °C 0

7.4.3 GA5 Pack/Standard Pack 1)

Compressor type 7.5 bar 8 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi

Frequency . . . . . . . . . . . . . . . . Hz 50 50 50 50 60 60 60 60
Maximum (unloading)
pressure . . . . . . . . . . . . . . . . . . bar(e) 7.5 8 10 13 7.4 9.1 10.8 12.5
Nominal working pressure . . . bar(e) 7 8 9.5 12.5 6.9 8.6 10.3 12
Temperature of air leaving
outlet valve, approx. . . . . . . . . °C 29 29 29 29 29 29 29 29
Drive motor, LEROY
SOMER . . . . . . . . . . . . . . . . . LS132S LS132S LS132S LS132S LS132S LS132S LS132S LS132S
Motor shaft speed . . . . . . . . . . r/min 2920 2920 2920 2920 3515 3515 3515 3515
Power input, GA . . . . . . . . . . . kW 6.3 6.2 6.2 6.2 6.4 6.4 6.5 6.5
Oil capacity, GA . . . . . . . . . . . l 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
Mean sound pressure level 2) . dB 66 66 66 66 67 67 67 67

1) At reference conditions
2) According to PNEUROP PN8NTC2.2

2920 1386 00 37
Instruction book

7.4.4 GA5 Full-feature 1)

Compressor type 7.5 bar 8 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi

Frequency . . . . . . . . . . . . . . . . Hz 50 50 50 50 60 60 60 60
Maximum (unloading)
pressure . . . . . . . . . . . . . . . . . . bar(e) 7.25 7.75 9.75 12.75 7.15 8.85 10.55 12.25
Nominal working pressure . . . bar(e) 7 7.75 9.5 12.5 6.9 8.6 10.3 12
Temperature of air leaving
outlet valve, approx. . . . . . . . . °C 24 24 24 24 24 24 24 24
Drive motor, LEROY
SOMER . . . . . . . . . . . . . . . . . LS132S LS132S LS132S LS132S LS132S LS132S LS132S LS132S
Motor shaft speed . . . . . . . . . . r/min 2920 2920 2920 2920 3515 3515 3515 3515
Power input, GA . . . . . . . . . . . kW 6.4 6.1 6.3 6.3 6.5 6.5 6.6 6.6
Oil capacity, GA . . . . . . . . . . . l 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
Mean sound pressure level 2) . dB 66 66 66 66 67 67 67 67
Refrigerant type . . . . . . . . . . . R134a R134a R134a R134a R134a R134a R134a R134a
Refrigerant charge . . . . . . . . . kg 0.39 0.39 0.39 0.39 0.39 0.39 0.39 0.39
Pressure dewpoint,
approx. 3) . . . . . . . . . . . . . . . . °C 3 3 3 3 3 3 3 3

7.4.5 GA7 Pack/Standard Pack 1)

Compressor type 7.5 bar 8 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi

Frequency . . . . . . . . . . . . . . . . Hz 50 50 50 50 60 60 60 60
Maximum (unloading)
pressure . . . . . . . . . . . . . . . . . . bar(e) 7.5 8 10 13 7.4 9.1 10.8 12.5
Nominal working pressure . . . bar(e) 7 8 9.5 12.5 6.9 8.6 10.3 12
Temperature of air leaving
outlet valve, approx. . . . . . . . . °C 31 31 31 31 31 31 31 31
Drive motor, LEROY
SOMER . . . . . . . . . . . . . . . . . LS132M LS132M LS132M LS132M LS132M LS132M LS132M LS132M
Motor shaft speed . . . . . . . . . . r/min 2930 2930 2930 2930 3530 3530 3530 3530
Power input, GA . . . . . . . . . . . kW 8.7 8.8 8.7 8.7 8.9 8.9 8.9 8.8
Oil capacity, GA . . . . . . . . . . . l 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
Mean sound pressure level 2) . dB 68 68 68 68 69 69 69 69

1) At reference conditions
2) According to PNEUROP PN8NTC2.2
3) At 20°C / 100% relative humidity.

38 2920 1386 00
Instruction book

7.4.6 GA7 Full-feature 1)

Compressor type 7.5 bar 8 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi

Frequency . . . . . . . . . . . . . . . . Hz 50 50 50 50 60 60 60 60
Maximum (unloading)
pressure . . . . . . . . . . . . . . . . . . bar(e) 7.25 7.75 9.75 12.75 7.15 8.85 10.55 12.25
Nominal working pressure . . . bar(e) 7 7.75 9.5 12.5 6.9 8.6 10.3 12
Temperature of air leaving
outlet valve, approx. . . . . . . . . °C 26 26 26 26 26 26 26 26
Drive motor, LEROY
SOMER . . . . . . . . . . . . . . . . . LS132M LS132M LS132M LS132M LS132M LS132M LS132M LS132M
Motor shaft speed . . . . . . . . . . r/min 2930 2930 2930 2930 3530 3530 3530 3530
Power input, GA . . . . . . . . . . . kW 8.8 8.7 8.8 8.8 9.0 9.0 9.0 8.9
Oil capacity, GA . . . . . . . . . . . l 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
Mean sound pressure level 2) . dB 68 68 68 68 69 69 69 69
Refrigerant type . . . . . . . . . . . R134a R134a R134a R134a R134a R134a R134a R134a
Refrigerant charge . . . . . . . . . kg 0.39 0.39 0.39 0.39 0.39 0.39 0.39 0.39
Pressure dewpoint,
approx. 3) . . . . . . . . . . . . . . . . °C 3 3 3 3 3 3 3 3

7.4.7 GA10 Pack/Standard Pack 1)

Compressor type 7.5 bar 8 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi

Frequency . . . . . . . . . . . . . . . . Hz 50 50 50 50 60 60 60 60
Maximum (unloading)
pressure . . . . . . . . . . . . . . . . . . bar(e) 7.5 8 10 13 7.4 9.1 10.8 12.5
Nominal working pressure . . . bar(e) 7 8 9.5 12.5 6.9 8.6 10.3 12
Temperature of air leaving
outlet valve, approx. . . . . . . . . °C 33 33 33 33 33 33 33 33
Drive motor, LEROY
SOMER . . . . . . . . . . . . . . . . . LS132M LS132M LS132M LS132M LS132M LS132M LS132M LS132M
Motor shaft speed . . . . . . . . . . r/min 2940 2940 2940 2940 3560 3560 3560 3560
Power input, GA . . . . . . . . . . . kW 12.5 12.2 12.6 12.8 12.8 12.9 13.1 13.3
Oil capacity, GA . . . . . . . . . . . l 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
Mean sound pressure level 2) . dB 70 70 70 70 71 71 71 71

1) At reference conditions
2) According to PNEUROP PN8NTC2.2
3) At 20°C / 100% relative humidity.

2920 1386 00 39
Instruction book

7.4.8 GA10 Full-feature 1)

Compressor type 7.5 bar 8 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi

Frequency . . . . . . . . . . . . . . . . Hz 50 50 50 50 60 60 60 60
Maximum (unloading)
pressure . . . . . . . . . . . . . . . . . . bar(e) 7.25 7.75 9.75 12.75 7.15 8.85 10.55 12.25
Nominal working pressure . . . bar(e) 7 7.75 9.5 12.5 6.9 8.6 10.3 12
Temperature of air leaving
outlet valve, approx. . . . . . . . . °C 28 28 28 28 28 28 28 28
Drive motor, LEROY
SOMER . . . . . . . . . . . . . . . . . LS132M LS132M LS132M LS132M LS132M LS132M LS132M LS132M
Motor shaft speed . . . . . . . . . . r/min 2940 2940 2940 2940 3560 3560 3560 3560
Power input, GA . . . . . . . . . . . kW 12.7 12.2 12.8 13.0 12.9 13.0 13.2 13.4
Oil capacity, GA . . . . . . . . . . . l 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
Mean sound pressure level 2) . dB 70 70 70 70 71 71 71 71
Refrigerant type . . . . . . . . . . . R134a R134a R134a R134a R134a R134a R134a R134a
Refrigerant charge . . . . . . . . . kg 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4
Pressure dewpoint,
approx. 3) . . . . . . . . . . . . . . . . °C 3 3 3 3 3 3 3 3

7.5 Conversion list of SI units into US/British units

1 bar = 14.504 psi 1 l = 0.220 Imp gal (UK) 1 mbar = 0.401 in water column
1 g = 0.035 oz 1 l = 0.035 cu.ft 1 N = 0.225 lbf
1 kW = 1.341 hp (UK and US) 1 l/s = 2.117 cfm 1 Nm = 0.738 lbf.ft
1 l = 0.264 US gal 1 mm = 0.039 in x °C = (32 + 1.8 x) °F 4)

1) At reference conditions
2) According to PNEUROP PN8NTC2.2
3) At 20°C / 100% relative humidity.
4) A temperature difference of 1°C = a temperature difference of 1.8°F

40 2920 1386 00

You might also like